PERATION:
1. STEAM CONTROL VALVE SHALL MODULATE TO MANTAIN THE LEAVING HOT WATER TEMPERATURE AT SET POINT.
2, THE LEANG HOT WATER TEMPERATURE SHALL BE RESET INVERSELY WITH THE OUTDOOR TEMPERATURE AS SCHEDULED.
3. THE LEAD AND LAG PUMPS AND HEAT EXCHANGERS SHALL BE SEQUENTIAL BY THE OPERATOR CONTROLS AT THE PRE-DETERVINED
INTERVAL (USUALLY 7 DAYS). IN THE EVENT THE PUMP FALS TO START WITHIN 30 SECONDS, AN ALARM SHALL BE INTIATED AND THE
SECOND PUMP SHALL START AUTOMATICALLY.
‘VALVE SEQUENCE:
1, SUGGESTED VALVE SEQUENCE. DELETE THIS SEQUENCE FROM THIS ETAL IF SEQUENCE IS SHOWN ON CONTROLS
DRAWINGS OR SPECS.
2. V-1 (1/3) MODULATES TO MAINTAIN HW TEMPERATURE AT SETPOINT. WHEN V-1 HAS REACHED FULLY OPEN
POSITIONS, V-2 (2/3) STARTS TO MODULATE OPEN.
S.1F HX<2, V5 AND V4 ARE NOT REDUNDANT BACKUP, THEN THE STAGING ABOVE CONTINUES AS FOLLOWS: PROVIDE, ADDITIONAL MOTORIZED
ISOLATION VALVES AT THE THE HIS AND HR FOR EACH HX'S. WHEN V-2 HAS REACHED FULLY OPEN POSITION, THE ISOLATION VALVES AT
HX-2 HWS HWS AND HAR LINES FULLY OPEN, AFTER WHCH V-3 (1/3) STARTS TO MODULATE OPEN, WHEN V-3 HAS REACHED FULLY OPEN
POSITION. V-4 (2/3) STARTS TO MODULATE OPEN.
i= —_
L@-£
TRANSMITTER WITH SUN |
ae |
.
7 HI
CONTROL VALVES (NC)
SIZE VANES IN 1/3 - 2/3,
Sap) NCEE
LI
og
n 7
CONTROL VALVES (NC). SIZE VALVES IN 1/3
= 2/3 VALE. ARRANGEMENT
a owes
ik
Hs
TEMPERATURE
‘SENSOR (TYP)
PUMP ie
« cS TT
Hw
Y, ve
OA 10 S
wo
_ coo. wes) fe)
BOC (140F ) Hw, 82°C (180F) SIZE VALVES IN 1/3 - 2/3
(un) (wax) VANE ARRANGEMENT
TYP OSA RESET SCHEDULE
#) DUAL HEAT EXCHANGER CONTROLS (HEATING SYSTEM)
DETAIL TITLE: DUAL HEAT EXCHANGER CONTROLS (HEATING SYSTEM)
SCALE :NONE
DATE ISSUED #1
/01/2017 CAD DETAIL NO. : $D282113-10.0WG