Documente Academic
Documente Profesional
Documente Cultură
Document written by JY Pocthier, Power/ EM/ APOD, initial document: September 23 , 2009
th
Rev 4.0, dated April 13 , 2010
Schneider Electric
Energy Automation Asia Pacific
When installed on a live conductor for the first time (after hardware reset), Flite 11xSA
detects the electrical field and adjust to it. Once it has adjusted and is ready to detect faults,
Flite 11xSA flashes 7 times. The test may then start.
In this procedure, we make two faults: one using the IMAX principle (absolute current value)
and one using the di/dt principle (variation of load current within 30 ms).
B) Test procedure
1. Connect battery, set DIP switch 6 to ON (Flite 110SA only), and press the reset button
of Flite 11x SA until a long flash appears. Flite 11xSA is now set to show faults. Note:
Flite 110SA differentiates between permanent faults (1 flash every 3 seconds) &
transient faults (1 double flash every 12 seconds)
2. Clip Flite 11xSA clamps on both current injection cable and voltage injection + cable as
it is shown on the picture
3. Put the cable of the voltage injection case about 1 meter below Flite 11xSA to create
the same electrical field as when it is installed on a conductor
5. IMAX test
a. Set Flite 11xSA to IMAX=100A and di=OFF, then press reset blue push button
until a long flash occurs
b. Turn on the Voltage injection test set: inject 10kV continuously
c. Within 2mn, Flite 11xSA starts flashing (7 times) to tell it has adapted to MV level
d. Turn on the current injection test and inject 50A continuously
e. Simulate IMAX fault:
i. Increase the current to 120 Amps during a time greater than 30ms
ii. Within 70s, stop both current & voltage injection
iii. The flash must immediately start (one flash every 3 seconds)
f. Inject 10kV again continuously: after 70 seconds, flashing change to 1 double
flash every 12 seconds (indicating transient faults)
6. DI test
a. Set Flite 11xSA to IMAX=200A and di=30A, then press reset blue push button
until a long flash occurs
b. Turn on the Voltage injection test set: inject 10kV continuously
c. Within 2mn, Flite 11xSA starts flashing (7 times) to tell it has adapted to MV level
d. Turn on the current injection test and inject 30A continuously
e. Simulate DI fault:
i. Increase the current to 80 Amps within a time of less than 30ms and
during a time greater than 300 ms
ii. Within 70s, stop both current & voltage injection
iii. The flash must immediately start (one flash every 3 seconds)
f. Inject 10kV again continuously: after 70 seconds, flashing change to 1 double
flash every 12 seconds (indicating transient faults)
Note: it is essential to have the Flite 11xSA far from the current cable of the
loop
2m 2m
Flite
+cable 11xSA
Voltage
10 kV injection
Max 0.50m
case
-cable
Current
injection
2m
case
rd
Document written by JY Pocthier, Power/ EM/ APOD, initial document: September 23 , 2009
th
Rev 4.0, dated April 13 , 2010