KUWAIT OIL COMPANY (K.S.C)


NEW GATHERING CENTRE, GC-29 IN NORTH KUWAIT
JOB NO : JI-2027

THRUST BLOCK SIZING REPORT Rev. A


Date 22/03/2016

Native soil type : Medium Dense Sand/Gravel Calc. No./ Revision : SYS-152
Soil Bearing Capacity (kPa): 150
Safety Factor : 1.5 Author / Checker TM RL

SUPPORT ID FORCE (kN) REQUIRED THRUST AREA (m2) Comments


Anchor Node X Y Z XYZ X Y Z XYZ
1570 Thrust block at back of tee
1570 34.37 0 56.96 66.53 0.3437 0 0.5696 0.67 with minimum dimensions
1200mm/600mm/600mm
(X/Y/Z)

Dennis Southam Associates


consult@dsapl.com.au 1 of 1
PDF processed with CutePDF evaluation edition www.CutePDF.com
746/746

KUWAIT OIL COMPANY (K.S.C)


NEW GATHERING CENTRE, GC-29 IN NORTH KUWAIT
JOB NO : JI-2027

PUDDLE FLANGE THRUST BLOCK SIZING REPORT Rev. A


Date 23/03/2016

Native soil type : Medium Dense Sand/Gravel Calc. No./ Revision : SYS-152
Soil Bearing Capacity (kPa): 150
Concrete Shear Strength (Mpa): 0.34 Author / Checker TM RL
Safety Factor : 1.5

REQUIRED
REQUIRED PIPE OD PIPE AREA PIPE CIRC TOTAL
SUPPORT ID FORCE (kN) SHEAR Comments
THRUST AREA (m2) (mm) (m2) (m) AREA (m2) AREA (m)
Anchor Node LIM LIM
1828 Thrust block attached to puddle flange with
1828 61.42 0.6142 258.6 0.0525 0.81 0.67 0.36 minimum dimensions
850mm/850mm/900mm (H/W/L)

2043 Thrust block attached to puddle flange with


2043 29.29 0.2929 258.6 0.0525 0.81 0.35 0.17 minimum dimensions
600mm/600mm/450mm (H/W/L)