Documente Academic
Documente Profesional
Documente Cultură
ENGINEERING LABORATORY
Lab Manual
Dr.NGP.IT/EEE/LM/V 3.2
Release History
Ratification by
Table of Contents
Contents
10. OPEN CORCUIT AND SHORT CIRCUIT TEST ON SINGLE PHASE TRANSFORMER ...65
13. LOAD TEST ON THREE PHASE SQUIRREL CAGE INDUCTION MOTOR .89
15. SPEED CONTROL OF THREE PHASE SLIP RING INDUCTION MOTOR ...101
EXP.NO:- 1A
STUDY OF DC STARTERS
Date:-
AIM:
NECESSITY OF A STARTER:
When the motor is at rest the speed of the motor is zero, therefore, back emf E b is zero and
if a D.C motor is connected directly to the supply mains, a heavy current will flow through the
armature conductors because from the emf equation for armature circuit (E b=V-IaRa) armature
current Ia is given as V-Eb / Ra and armature resistance Ra is very small.
When running, of course, the applied voltage V is opposed by the induced back emf and
therefore a much smaller current flows.
II. Damage of the armature winding, either by heat developed in the windings or by the
mechanical forces set by the electromagnetic induction.
III. Damage to the rotating parts of the motor and load due to development of large
starting torque and quick acceleration and
Hence for the protection of the motor against the flow of excessive current during starting
period (say 5 to 10 seconds), it is necessary that a high resistance be connected in series with the
armature of the motor at the instant of starting.
Motor starters are generally manufactured in convenient sizes and styles for use as
auxiliaries with DC shunt and compound motors. Their primary function is to limit the current in the
armature circuit during starting or accelerating period. They are always rated on the basis of output
power and voltage of the motors with which they are employed. The simplest type of starter
consists of an additional resistance inserted in series with armature alone.
This starter is however; modified to include a few productive devices, such as no-volt
release, over-load release etc. There are two standard types of starters for DC shunt and compound
motors, the three point and four point starters; the four-point starter is employed when wide range
of speed by shunt field control is required. When no speed control is required, either type of starter
may be used.
Thus for a given load torque, the motor will accelerate quickly and take less time to reach
the lower operating speed from the starting instant. This will result in less heating of the armature
during starting. Thus, the rheostat, in series with the shunt field winding, should be at zero
resistance position at the time of starting of the dc shunt and compound motors.
The three-point starter with its electrical connections and productive devices is shown in
figure 1. It consists of a series starting resistance divided into several sections and connected to
brass arc by which the connection to shunt field is made through no-volt release and over-load
release. Since only three terminals (L, F&A) are available from the starter, it is called a three point
starter.
The last stud of the starting resistance is connected to terminal A to which one terminal of
the armature is connected. The positive supply line is connected to the line terminal L through main
switch from line terminal L supply is connected to the starter arm through over load release. A
spiral spring is placed over the lever to bring starter arm to the OFF position in case of failure of
supply.
A soft iron keeper is attached to the starter arm which is pulled by the holding coil or no-volt
release under normal running condition. The far end of the brass arc is connected to the terminal F
to which one terminal of the field is connected. The negative supply line is connected directly to the
remaining ends of armature and field winding of the DC shunt motor.
OPERATION:
When the motor is at rest, the starter arm is in the OFF position due to action of strong
spiral spring. For starting the motor, the DC supply is switched on by closing the main switch
keeping starter arm in OFF position. The starter arm is then turned clockwise to the first stud and
brass arc. As soon as it comes in contact with first stud, whole of the starting resistance R is
inserted in series with the armature, the field winding is directly connected across the supply
through the brass arc and the holding coil is also energized.
As the starter arm is turned further the starting resistance is cut off from the armature
circuit. When the starter arm reaches the ON position, it is held against the action of spiral spring
by the force of attraction between holding coil magnet and soft iron keeper attached to the starter
arms. The starter arm should not be held for an unduly long time in an intermediate position as it is
likely to burn out the starting resistor.
No-Volt release coil consists of an electro magnet connected in series with the shunt field
which holds the arm in the ON position. Now When the supply fails or gets disconnected, the
electromagnet demagnetizes and so as releases the starting arm A, which goes back to OFF position
due to the spring attached to it and gets disconnected from the supply mains.
The other important advantages of connecting NoVolt release in series with shunt field
winding is that it prevents the motor from running away from owing to an open shunt field because
open circuited shunt field will demagnetize the electro-magnet and release the starter arm A and,
thus the starter will go back to its OFF position and the supply will be disconnected.
This coil is provided for the protection of the motor against the flow of excessive current
due to over load. This coil is connected in series with motor so carries full load current. When the
motor is overloaded, it draws heavy current, which also flows through this coil and magnetizes it to
such an extent, that it pulls its armature upwards and so short circuits the no-volt release coil. The
no-volt release coil, being short circuited, demagnetizes and releases the starting arm, which goes
back to OFF position with the action of spring attached to it and the motor is automatically
disconnected from the supply mains. Thus the motor is disconnected from the supply and is
protected against over loading.
The starters for motors up to 15kW are provided with the over load release to disconnect
the motor from the supply mains in the event load. Larger motors are provided with separate
automatic circuit breakers.
In three-point starter no-volt release coil is connected in series with the shunt field and the
field rheostat and, therefore, the current flowing through the field is the same current that flows
through the holding coil current is no longer able to create sufficient electro-magnetic pull to
overcome the spring tension, the starter arm will back to the OFF position. It is thus undesirable
feature of the three-point starter that makes it unsuitable for use with speed controlled motors and
that has resulted on the wide spread application of four point starters.
A four-point starter with its internal wiring connected to a shunt motor is shown. From the
fig. 2 it is obvious that when the arm touches stud no.1, line current divides into three parts:
i). One part passes through starting resistance, armature and series field.
ii). Second part passes through the shunt field winding and.
iii). The third part through no-volt release coil and protective resistance.
Since in this arrangement, No-Volt Release coil circuit is independent of shunt field circuit,
so it will not be affected by the change of the current in the shunt field circuit. It means that the
electromagnetic pull exerted by the holding coil will always be sufficient and will prevent the spiral
spring from restoring the arm to the OFF position, no matter how the field rheostat is adjusted.
A motor is started with a four terminal starter in the same way as with three terminal
starters. Any desired speed, above normal, of the motor can be obtained by adjusting the field
rheostat which is in series with shunt field. It is necessary to ensure, before starting a DC motor that
the field circuit is closed, the rheostat in series with the shunt field winding is at zero resistance
position and starting resistance in series with the armature circuit is at maximum value.
For stopping the motor, the line switch should always be opened rather than throwing back
the starting arm. In shunt motors, the line switch can be opened without any appreciable arc, since
the motor develops a back emf nearly equal to applied line voltage and the net voltage across the
switch contact is small. The electro-magnet energy stored in the field does not appear at the switch
but is discharged gradually through the armature. On the other hand, if the starting arm is thrown
back the field circuit is broken at the last contact button. Owing to the inductive nature of the field,
this will cause a hot arc and burn the contact.
The arm is held in ON position by the holding coil. When the supply fails during running, or
the motor current falls to too low value, the pull of the holding coil is reduced to an extent that it
can no longer hold the arm against the spring action attached to it and the starter arm flies back to
the OFF position and thus the motor gets disconnected automatically from the supply mains. Over
load release is connected in series with the motor, so carries the total motor current. When the
input current to the motor becomes excessive, which also flows through the over load release coil,
the soft iron armature gets lifted to break the holding coil circuit. Thus the holding coil gets
demagnetized and the starter arm returns back to the OFF position under the action of the spring
attached to it and the motor gets disconnected automatically from the supply mains
For switching OFF DC series motor, the line switch should always be opened rather than
throwing back the starting arm, as in case of DC shunt and compound motors. If it is done, then
heavy sparking is caused at the stud no.1, because here the field circuit is broken and the entire
energy is stored in the magnetic field is dissipated in the form of heavy spark.
However, there is one significant difference. In case of a DC series motor, the flux does not
remain constant but varies with the current because the line current, field current and armature
current are the same. Thus the back emf at any given speed varies as the current varies between
the upper and lower limits.
INFERENCES:
RESULT:
EXP.NO:- 1B
STUDY OF AC STARTERS
Date:-
AIM:
Although there is no limitation on the size of the motor that may be started by this
method, it should be understood that objectionable line voltage drops will usually occur, especially
if large motors are started frequently. Whether or not normal voltage is employed will, therefore,
depend upon the following factors:
iv). the capacity of the power system and the rules governing such installations as
established by power supply companies. Squirrel cage motors of capacity up to 1.5 kW, double cage
motors and squirrel cage motors of large capacity having a large rotor resistance are started by this
method. This is the most economical method of starting induction motor.
As the name suggest, this method involves direct switching of poly phase squirrel
cage induction motor to the supply mains, as illustrated in Fig.1.
In this method of starting of cage motor the rate of temperature rise is high and the motor
may be damaged if the starting period is large, which is may be due to (i) excessive load (ii)
insufficient rotor resistance or (iii) excessive voltage drop in the supply lines. The starting period
usually lasts a few seconds because starting torque for induction motor is about twice the full load
torque.
In auto transformer starting method the reduced voltage is obtained by taking tapping at
suitable points from a three phase auto transformer, as shown in Fig.2. The auto transformer is
generally tapped at the 50, 60 and 80 percent points, so that adjustments at these voltages may be
made for proper starting torque requirements.
Since the contacts frequently break large values of current, arcing is sometime quenched
effectively by having them assembled to operate in an oil bath. Auto transformer starters may be
either manually or magnetically operated. The manual auto transformer starter is essentially a
multi pole double throw switch. It consists three sets of contacts starting, running (both stationary)
and the movable contacts (the contact attached to the operating handle).
R
3-PHASE
Y
ACSUPPLY
B
MAINSWITCH
AUTO
TRANSFORMER V
KV
KV
STATOR
ROTOR
The operating handle is spring loaded lever mounted on the outside of a steel cabinet to
stand vertically in the off position. When the operating handle is moved to the start position, the
movable contacts are moved against the starting contacts. This energizes the star connected auto
transformer and impresses reduced voltage (50 or 60 or 80 percent according to the setting on auto
transformer) across the motor.
After the motor has accelerated to about full speed, the operating handle is moved to the
run position. This instantly opens the starting contacts (or disconnects the auto transformer from
the line) and connects the motor directly to the line through the running contacts. A latch, fixed to
the mechanism, is made to drop into a notch so that the operator is prevented from throwing the
handle accidentally to the run position first, however, when the handle is quickly pushed from the
start to the run position, the latch is kicked up to make the lever free for its forward motion. The
operating handle is held in the run position by an electromagnet or under voltage coil until the stop
button is pressed. If the supply fails or supply voltage drops to low value, the electro-magnet will
release and trip the holding mechanism. Overload protection is provided by thermal overload
relays.
STAR-DELTA STARTER :
This method of starting of cage induction motors is based upon the principle that with 3
windings connected star, the voltage across the each winding is 1/3 i.e. 57.7% of the line to line
voltage whereas the same winding connected in delta will have full line to line voltage across each.
The star-delta starter connects the three stator windings in star across the rated supply
voltage at the starting instant. After the motor attains speed the same winding, through a change
over-switch, are reconnected in delta across the same supply voltage. An actual starter
incorporates under-voltage and over-voltage coils, as shown in the fig.3. The starter is also provided
with a mechanical inter- looking device to prevent the handle from being put in the Run position
first. Since the starting instant, the stator windings are connected in star, so voltage across each
phase winding is reduced to 1/3 of line voltage and therefore starting current per phase becomes
equal to Isc/3. Starting line current by connecting the stator winding in star at the starting instant is
equal to starting motor current per phase is equal to Isc/3.
Hence with star-delta switching, the starting torque is also reduced to one-third of starting
torque obtained with direct switching. This method of starting of cage motors is simple, chief,
effective and efficient since no power is lost in auxiliary components. This method is also suitable
for high inertia and long acceleration loads. This method needs a motor to be delta connected for
normal operation and all the six terminal of the three phase stator windings are to be brought out.
The reduction in voltage is fixed and starting torque is also low. So this method is limited to
application where high starting torque is not the essential requirement. This method is unsuitable
for line voltage exceeding 3000 V, because of excessive number of stator turns required for delta
connection. Such stators are employed for starting three phase squirrel cage induction motors of
rating between 4 and 20 kW.
INFERENCES:
RESULT:
CIRCUIT DIAGRAM
+ 25A +
A -
3 POINT
L F A STARTER
(0-20)A
MC
350
D
P
S
T + S1 S2
220V
(0-300)V
DC
SUPPLY
S MC V
W -
I
T Sh(+) A(+)
C
H
M #
Sh(-) A(-)
- 25A
Rated H.P:
Rated Voltage:
Rated Current:
Rated Speed:
EXP.NO:- 2
LOAD TEST ON DC SHUNT MOTOR
Date:-
AIM:
To conduct the load test on DC shunt motor and draw the performance characteristic
curves.
APPARATUS REQUIRED:
S. No EQUIPMENT TYPE RANGE QUANTITY
1 Ammeter MC (0-20) A 1
2 Voltmeter MC (0-300) V 1
3 Tachometer Digital - 1
PRECAUTIONS:
At the time of starting, the field circuit rheostat is in minimum resistance position.
There should be no load on the motor at the time of starting.
FORMULAE USED:
1. Torque (T) = (S1~S2) x R x 9.81 in Newton meter
where
S1, S2 - Spring balance readings in Kg
R - Radius of the brake drum in m
2. Input Power (Pi) = VLIL in Watts
where
VL- Line Voltage in Volts
IL Line Current in Amps
3. Output Power (Po) = 2NT/60 in Watts
where
N- Speed in RPM
T-Torque in Nm
Output power
4. Efficiency (%) = X 100
Input power
THEORY:
The word shunt means parallel. These motors are so named because they basically operate
with the field coils connected in parallel with the armature. The current supplied to the motor is
divided into two parts, one through the field winding and second through the armature i.e.,
Input line current, IL = Ia + Ish
VL is the line voltage in Volts
Rsh is the shunt field resistance in Ohms.
TABULATION:
Radius of the brake drum :
Line Line Input Output
Spring Balance Efficiency
Current Voltage Power Speed Torque Power
S. Reading Kg
IL
No VL Pi N rpm T N-m PO
Amps Watts S1 S2 S1~S2 Watts Percentage
Volts
1.
2.
3.
4.
5.
6.
GRAPH:
The performance characteristic curves are drawn as shown in Fig 2 and Fig 3.
a) Electrical characteristics
(i) Output power Vs Line Current
(ii) Output power Vs Speed
(iii) Output power Vs Torque
(iv) Output power Vs Efficiency
b) Mechanical Characteristics
(i) Torque Vs Speed
Speed in rpm (N)
0
0
Torque in N-m (T)
Where
Ia is the armature current in Amps
Ish is the shunt field current in Amps and is given by the expression
Ish = VL / Rsh
Where
MODEL CALCULATION:
INFERENCES:
RESULT:
CIRCUIT DIAGRAM
2 POINT
+ 25A +
A -
STARTER
L A
(0-20)A
D MC Se(+)
P
S + S1 S2
T (0-300)V Se(-)
220V MC V
S -
DC W
SUPPLY I A(+)
T
C
H
M #
A(-)
- 25A
NAME PLATE
FUSE RATING: 125% of rated current DETAILS
Rated H.P:
Rated Voltage:
Rated Current:
Rated Speed:
EXP.NO:- 3
LOAD TEST ON DC SERIES MOTOR
Date:-
AIM:
To conduct the load test on DC series motor and draw the performance characteristic
curves.
APPARATUS REQUIRED:
S. No EQUIPMENT TYPE RANGE QUANTITY
1 Ammeter MC (0-20) A 1
2 Voltmeter MC (0-300) V 1
3 Tachometer Digital - 1
PRECAUTIONS:
The dc series motor should always be started with some load. Otherwise the speed will
be enormous and fuse will blow out.
FORMULAE USED:
1. Torque (T) = (S1~S2) x R x 9.81 in Newton-meter
Where
S1, S2 - Spring Balance Readings in Kg
R - Radius of the brake drum in m
2. Input Power (Pi) = VL IL in Watts
Where
VL- Line Voltage in Volts
IL Line Current in Amps
3. Output Power (Po) = 2NT/60 in Watts
Where
N- Speed in RPM
T-Torque in Nm
Output power
4. Efficiency () = X 100 %
Input power
THEORY:
As the name implies, the field coils, consisting of few turns of thick wire, are connected in
series with the armature, as illustrated in Fig (3.1). The cross sectional area of the wire used for field
coils has to be fairly large to carry the armature current, but owing to the higher current, the
number of turns of wire in them need not be large.
In D.C series motor,
Armature Current (Ia) = Series field current
Series Field Current (Ise) = Line Current (IL)
Back EMF Developed (Eb) = V I (Ra + Rse)
Power drawn from supply mains P= VL IL
TABULATION:
Radius of the brake drum:
Input Output Efficiency
Line Line Speed Spring Balance
S. Current Power Reading Kg Torque Power
Voltage N
No IL Pi T N-m PO
VL Volts Percentag
Amps Watts RPM S1 S2 S1~S2 Watts e
GRAPH:
The performance characteristic curves are drawn as shown in Fig 2 and Fig 3.
a) Electrical Characteristics
(i) Output power Vs Armature Current
(ii) Output power Vs Speed
(iii) Output power Vs Torque
(iv) Output power Vs Efficiency
b) Mechanical Characteristics
(i) Torque Vs Speed
0
0
PROCEDURE:
1. Note down the Name plate details of the motor.
2. Connections are made as per the circuit diagram.
3. Ensure that 3/4th of the load is applied to the brake drum.
4. Supply is given by closing the DPST Switch and the motor is started.
5. At 3/4th of the load condition, tabulate the reading of Voltmeter, Ammeter, Spring balance
and Speed.
6. Then increase the load current in steps of 1/2 th, 3/4th, rated value and 125% of the rated
value.
7. Note down the corresponding ammeter, voltmeter, Spring balance readings and speed and
enter the values in the table.
8. The torque, input power, output power and percentage efficiency were calculated by using
the formulae and tabulated in the observation table.
MODEL CALCULATION:
INFERENCES:
RESULT:
SPEC
H.P
olts
Curre
Spee
CIRCUIT DIAGRAM
+ 25A
3 POINT
L F A STARTER 20A
+
(0-15)A
MC A
710 -
350
D D
P P
(0-300)V
S S
MC
T + + T
220V
LOAD
(0-2)A
DC S MC A V S
SUPPLY W W
- -
I I
T Sh(+) A(+) A(+) Sh(+) T
C C
H H
M # G
Sh(-) A(-) A(-) Sh(-)
- 25A 20A
Fig 4.1: Open Circuit and Load Characteristics of Self Excited DC Shunt Generator
AIM:
To conduct no load and load tests on self-excited DC shunt generator and obtain the
characteristics.
APPARATUS REQUIRED:
S. No EQUIPMENT TYPE RANGE QUANTITY
1 Ammeter MC (0-10) A 1
2 Ammeter MC (0-2) A 1
3 Voltmeter MC (0-300) V Each 1
350 /1.2 A 1
4 Rheostat Wire wound
710 /0.8 A 1
5 Loading Rheostat Resistive 5 kW / 230V 1
6 3 - Point Starter DC - 1
7 Tachometer Digital - 1
8 DPST switch - - 2
PRECAUTIONS:
At the time of starting,
The motor field rheostat should be kept at minimum resistance position.
The generator field rheostat should be kept at maximum resistance position.
FORMULAE USED:
Generated voltage (Eg) = VL + Ia Ra in Volts
where
VL- Load Voltage in Volts
Ia- Armature Current in Amps
Ra- Armature Resistance in Ohms
THEORY:
A DC generator whose field winding is excited by the current supplied by the generator itself
is called self-excited generator. In such machines the field coils are inter-connected with the
armature winding. The field coils may be connected either in series with the armature, in parallel
with the armature or partly in series or partly in parallel with the armature. Accordingly, the self-
excited generators may be classified as (i) series wound generators (ii) shunt wound generators and
(iii) compound wound generators.
Due to residual magnetism, some flux is always present in the poles of such machines.
When the armature is rotated, a small voltage is induced in the armature winding owing to residual
flux. This induced voltage causes a small current to flow in the field coils and thus increase in flux
per pole. The increase in flux causes increase in induced voltage which further increases the field
current.
+ 25A +
A -
(0 -2 0 )A
5 2
M C
D +
P
220V
DC
S
(0 -3 0 )V
M C
V
T -
SU PPLY S
A (+ )
M
A (-)
- 25A
TABULATION
OPEN CIRCUIT TEST:
Field Current Open Circuit Voltage
S. No
(If) Amps (Eo) Volts
10
PROCEDURE:
LOAD TEST:
1. Note down the Name plate details of motor.
2. Connections are made as per the circuit diagram.
3. Supply is given by closing the DPST Switch in the motor side.
4. Using the DC three-point starter, start the motor.
5. The field rheostat of motor is adjusted to run the motor at rated speed.
6. The generator field rheostat is adjusted for the rated voltage.
7. The DPST switch in the generator side is closed. Increase the resistive load in steps of 2
Amps and note down the corresponding load current and terminal voltage values.
8. Then the resistive load is gradually decreased and the DPST Switch on the generator side is
open. Then the supply is switched off.
9. The generated voltages Eg is calculated by using the formula as mentioned above and draw
the graph between Eg and If.
Average value of R a=
LOAD TEST:
Terminal
I a= I L + I f E g =Vt + IaRa
S.No IL Amps If Amps Voltage Ia Ra Volts
Amps Volts
(Vt) Volts
GRAPH:
a. Open Circuit Characteristics:
Field Current Vs Open Circuit Voltage
b. Load Characteristics:
Load Current Vs Terminal Voltage (External characteristic)
Load Current Vs Generated Voltage (Internal characteristic)
0
0
0
Fig 4.3: Open Circuit Characteristics Fig 4.4: Load Characteristics
MODEL CALCULATION
INFERENCES:
RESULT:
CIRCUIT DIAGRAM
+ 25A L F A
3 POINT
STARTER 20A
350 710 +
D (0-15)A
P
(0-300)V MC A
S -
MC
T + + D
220V P
(0-2)A
DC S MC A V S
SUPPLY W T
- -
LOAD
I S
T Sh(+) A(+) A(+) Sh(+)
C
H
M # G
Sh(-) A(-) A(-) Sh(-)
- 25A 20A
Fig 5.1: Open Circuit and Load Characteristics of Separately Excited DC Shunt Generator
AIM:
To conduct no load and load test on separately excited DC shunt generator and to obtain its
characteristics.
APPARATUS REQUIRED:
S. No EQUIPMENT TYPE RANGE QUANTITY
1 Ammeter MC (0-10) A 1
2 Ammeter MC (0-2) A 1
3 Voltmeter MC (0-300) V Each 1
350 / 1.2 A
4 Rheostat Wire wound Each 1
710 /0.8 A
5 Loading rheostat Resistive 5 kW / 230 V 1
6 DC three point starter - - 1
7 DPST switch - - 2
8 Tachometer Digital - 1
PRECAUTIONS:
At the time of Starting,
The motor field rheostat should be kept at minimum resistance position.
The generator field rheostat should be kept at maximum resistance position.
FORMULAE USED:
Generated Voltage (Eg) = VL + IaRa in Volts
Where,
VL Load Voltage in Volts
Ia - Armature Current in Amps
Ra - Armature Resistance in Ohms
THEORY:
In a separately excited DC generator the field coils are energized from an independent
source. Since exciting current is independent of load or armature current, so if a curve is drawn
between flux per pole and load current, keeping field current constant and neglecting armature
reaction, a straight line parallel to x-axis is obtained as indicated by curve I in Fig 5.3. But due to
armature reaction, the curve of actual flux is slightly drooping as represented by curve II in Fig 5.3.
CIRCUIT DIAGRAM
+ 25A +
A -
(0 -2 0 )A
5 2
M C
D +
P
220V
DC
S
(0 -3 0 )V
M C
V
T -
SU PPLY S
A (+ )
M
A (-)
- 25A
TABULATION:
OPEN CIRCUIT TEST:
Field Current Open Circuit Voltage
S. No.
(If) Amps (Eo) Volts
10
The second curve also gives to some other scale the emf generated in the armature and, therefore,
second curve represents internal or total characteristic of the separately excited DC generator. The terminal
voltage on load is the emf generated less voltage drop in the armature i.e. V=E-IaRa, so if a line OA
representing the armature resistance is drawn and its ordinates are deducted from curve II, curve III giving
relation between terminal voltage and load current, known as external characteristics is obtained. From
curve III, it is obvious that with the increase in load current, terminal voltage decreases slightly. This decrease
can easily be neutralized by increasing field current slightly and, therefore constant terminal voltage can be
maintained.
The separately excited DC generator has a decided advantage over the self-excited generators. It
operates in a stable condition with any field excitation. Thus a wide range of output voltage may be obtained.
The main disadvantage of a separately excited generator lies in the inconvenience and expense of providing
the separate excitation source. For this reason, the use of this type of generator is largely confined to
experimental and testing laboratories where such a source is available and a wide variation of output voltage
is desirable.
PROCEDURE:
LOAD TEST:
1. Note down the Name plate details of motor and Generator.
2. Connections are made as per the circuit diagram.
3. Supply is given by closing the DPST Switch.
4. Using the DC three-point starter, start the motor.
5. The field rheostat of motor is adjusted to run the motor at rated speed.
6. The generator field rheostat is adjusted up to rated voltage.
7. The DPST Switch in the generator side is closed. Increase the resistive load in steps of 2 Amps and
note down the corresponding load current and terminal voltage values.
8. Then the resistive load is gradually decreased and the DPST switch on the generator side is open.
Then the supply is switched off.
9. The generated voltages Eg is calculated by using the formula as mentioned above and enter the
values in the table.
LOAD TEST:
IL = Ia Terminal voltage Ia Ra E g =VL + IaRa
S. No
Amps (VL) Volts Volts Volts
1
2
3
4
5
6
GRAPH:
a) Open Circuit Characteristics:
i) Field Current Vs Open Circuit Voltage
b) Load Characteristics:
i) Load Current Vs Terminal Voltage (External Characteristics)
ii) Load Current Vs Generated Voltage (Internal Characteristics)
MODEL GRAPH:
INFERENCES:
RESULT:
CIRCUIT DIAGRAM
3 POINT
+ 25A
STARTER
L F A 10A +
A -
(0-10)A
MC
350 Se(-)
D + D
220V Se(+)
LOAD
P (0-300)V P
DC
SUPPLY
S MC V S
T - T
S S
Sh(+) A(+) A(+)
M#G
Sh(-) A(-) A(-)
- 25A 10A
MODEL GRAPH:
EXP.NO:- 6
LOAD CHARACTERISTICS OF DC SERIES GENERATOR
Date:-
AIM:
To conduct no load and load test on DC series generator and to obtain its characteristics.
APPARATUS REQUIRED:
S. No EQUIPMENT TYPE RANGE QUANTITY
1 Ammeter MC (0-10) A 1
3 Voltmeter MC (0-300) V 1
4 Rheostat Wire wound 350 / 1.2 A 1
5 Loading rheostat Resistive 5 kW / 230 V 1
6 DC three point starter - - 1
7 DPST switch - - 2
8 Tachometer Digital - 1
PRECAUTIONS:
At the time of Starting,
The motor field rheostat should be kept at minimum resistance position.
The generator field rheostat should be kept at maximum resistance position.
THEORY:
The field winding of a series generator is connected in series with the external circuit, called
the load. The field coils are composed of a few turns of large wire and the magnetic field strength
depends more on the current flow rather than the number of turns in the coil. Series generators
have very poor voltage regulation under changing load, since the greater the current through the
field coils to the external circuit, the greater the induced EMF and the greater the terminal or output
voltage.
Therefore, when the load is increased, the voltage increases; likewise, when the load is
decreased, the voltage decreases. The output voltage of a series wound generator may be
controlled by a rheostat in parallel with the field windings.
FORMULA USED:
% VR = (Vnl-Vfl)/Vfl * 100%
Eg = IaRa + IsRs + Vl
Note: Ia = Is = Il (series connection)
CIRCUIT DIAGRAM
+ 25A +
A -
(0 -2 0 )A
5 2
M C
D +
P
220V
DC
S
(0 -3 0 )V
M C
V
T -
SU PPLY S
A (+ )
M
A (-)
- 25A
10
LOAD TEST:
1. Note down the Name plate details of motor.
2. Connections are made as per the circuit diagram.
3. Supply is given by closing the DPST Switch.
4. Using the DC three-point starter, start the motor.
5. The field rheostat of motor is adjusted to run the motor at rated speed.
6. The generator field rheostat is adjusted for the rated voltage.
7. The DPST Switch in the generator side is closed. Increase the resistive load in steps of 2 Amps
and note down the corresponding load current and terminal voltage values.
8. Then the resistive load is gradually decreased and the DPST switch on the generator side is open.
Then the supply is switched off.
9. The generated voltages Eg is calculated by using the formula as mentioned above and enter the
values in the table.
MODEL CALCULATION:
Average value of R a=
INFERENCES:
RESULT:
CIRCUIT DIAGRAM:
3 POINT
STARTER
+ 5A +
A -
L F A
(0-5)A
MC
350 52
D
P
S
220V T + +
DC (0-2)A
SUPPLY S
(0-300)V
MC V A MC
W - -
I
T A(+)
Sh(+)
C
H +
M V
(0-300)V -
Sh(-) A(-) MC
- 5A
SPECIFICATIONS
Rated H.P:
Rated Voltage:
Rated Current:
FUSE RATING: 125% of rated current
Rated Speed:
EXP.NO:- 7
SPEED CONTROL OF DC SHUNT MOTOR
Date:-
AIM:
To control the speed of the given DC shunt motor by field and armature control methods
and also to draw their characteristics curves.
APPARATUS REQUIRED:
S.No. APPARATUS TYPE RANGE QUANTITY
1. Ammeter MC (0-25) A 1
2. Ammeter MC (0-2) A 1
3. Voltmeter MC (0-300) V 1
4. Rheostat Wire Wound 50 /5 A 1
5. Rheostat Wire Wound 360 /1.1 A 1
6. Tachometer Digital - 1
PRECAUTIONS:
The motor field rheostat should be kept at minimum resistance position at the time of
starting.
The motor armature rheostat should be kept at maximum resistance position at the time
of starting.
The motor should be in no load condition throughout the experiment.
The motor should run in anticlockwise direction.
THEORY:
The different ranges of speeds are required for different applications. A single motor can
be used for various work in different speeds. Smooth speed control is possible in DC shunt motor.
The speed of a DC motor can be expressed by the equation,
N=K (V-IaRa)/
Neglecting the small voltage drops I aRa, the speed is directly proportional to the voltage
across the armature and inversely proportional to the flux or filed current. Hence, the speed of the
DC motor is controlled by either voltage or field current.
TABULATION:
FIELD CONTROL METHOD:
Rated Speed:
Armature Voltage, Va = Armature Voltage, Va =
S.No. Field Current (IF) Field Current (IF)
Speed (N) (Rpm) Speed (N) (Rpm)
(Amps) (Amps)
PROCEDURE:
FIELD CONTROL METHOD (FLUX CONTROL METHOD):
1. Note down the name plate details of the motor.
2. Connections are made as per the Circuit diagram.
3. Using the three-point D.C starter, start the motor.
4. The armature rheostat is adjusted to run the motor at rated speed.
5. Keep the armature voltage constant at rated value.
6. Increase the speed in steps of 50 rpm above the rated speed and note down the
corresponding field current values in Table (1).
GRAPH:
The graphs are drawn for the following in the Fig (2) and Fig (3) for the following:
1. Armature voltage (Va) Vs Speed (N).
2. Field current (If) Vs Speed (N).
MODEL GRAPH:
INFERENCES:
RESULT:
CIRCUIT DIAGRAM
300V/10A 150V/20A
UPF UPF
P 15A CC CC
A M
PC
L
A M
PC
L
(0-10)A (0-20)A
C V C V
MI MI
D
P
S
230V
T
50Hz 1
LOAD
(0-300)V (0-150)V
AC
SUPPLY
S MI V V MI
W
I
T
C
H
LINK
EXP.NO:- 8
LOAD TEST ON SINGLE PHASE TRANSFORMER
Date:-
AIM:
To conduct the load test on the given single phase transformer and determine its
performance.
APPARATUS REQUIRED:
S.No. APPARATUS TYPE RANGE QUANTITY
(0-300)V 1
1. Voltmeter MI
(0-150 )V 1
(0-10)A 1
2. Ammeter MI
(0-20)A 1
300V/10A, 1
3. Wattmeter UPF
150V/20A , 1
4. Autotransformer 1 phase 230/(0-270)V/25A 1
PRECAUTIONS:
At the time of starting, the DPST switch on secondary side should be kept in open condition.
At the time of starting, there should be no load on the loading rheostat.
FORMULA:
1. Output power = Vs x Is x Cos in Watts
Where
Vs Secondary voltage in Volts
Is Secondary current in Amps
Cos - Power factor
2. Input Power = Wattmeter reading in Watts
3. Efficiency = (output power/Input power) X 100 %
4. Voltage Regulation = [(V no load - V load) / (V load)] X100 %
Where
V no load no load voltage in volts
V load load voltage in volts
THEORY:
When the secondary of the transformer is connected through a load, the transformer is said
to be loaded and the current flows through the secondary and the load.
The magnitude and phase of the secondary current with respect to the secondary voltage
will depend upon the characteristics of the load.
MODEL GRAPH:
The graph is drawn between
(I) Output power Vs Efficiency.
Efficiency () in %
PROCEDURE:
1. Note down the name plate details of the machine.
2. Connections are made as per the circuit diagram.
3. Supply is given by closing the DPST switch on the primary side and the DPST switch on the
secondary side is kept open.
4. Adjust the autotransformer to energize the transformer with rated primary voltage.
5. At no load condition, the input voltages, current and power are noted and enter the values
in the table.
6. Close the DPST switch on the secondary side.
7. Increase the load in steps of 2 Amps and note down the corresponding ammeter, voltmeter
and wattmeter readings in both primary and secondary sides and enter the values in the
Table.
8. Then the load is gradually decreased and the autotransformer is brought to the minimum
voltage position and the supply is switched off.
9. The output power, efficiency and regulation are calculated by using the formulae as
mentioned under calculation and enter the values in the table.
MODEL CALCULATION:
INFERENCES:
RESULT:
CIRCUIT DIAGRAM
300V /5A
LPF
P 5A CC
A M
PC
L
(0-2)A
C V
MI
D
P
S
230V
T
50H z 1
(0-300)V (0-150)V
AC
S U P PLY
S MI V MI V
W
I
T
C
H
LIN K
N 230/(0-270)V/25A 220/110V
2kV A 1
1 AU TO Tr
S TE P D O W N Tr NAME PLATE DETAILS
kVA rating :
Primary Voltage:
FUSE RATING: 125% of rated current
Secondary Voltage:
Fig 9.1: Open Circuit Test on Single Phase Transformer
Primary Current:
Secondary Current:
AIM:
To conduct Open Circuit and Short Circuit test on single phase transformer and obtain its
equivalent circuit.
APPARATUS REQUIRED:
S.NO APPARATUS TYPE RANGE QUANTITY
1 Voltmeter MI (0-300) V 1
2 Voltmeter MI (0-75) V 1
3 Ammeter MI (0-2) A, (0-10) A 1
4 Wattmeter LPF 300 V / 5A 1
5 Wattmeter UPF 150V / 10A 1
6 Autotransformer 1 (0-270) V / 10 A 1
7 Transformer 1 step down 220 V / 110 V, 2 KVA 1
PRECAUTIONS:
At the time of starting, the auto transformer should be in the minimum voltage position.
For OC test, the HV side of the transformer is in open circuit condition.
For SC test, the LV side of the transformer is short circuited.
FORMULAE USED:
OPEN CIRCUIT Test:
1. No load Power factor, Cos o = [ Woc / (Voc x Ioc ) ]
where
Woc No load losses
Voc No load voltage
Ioc No load current
2. Magnetizing component, Im = Ioc x Sin o
3. Working component, Iw = Ioc x Cos o
4. No load resistance, R0 = Voc / Iw in Ohms
5. No load reactance, X0 = Voc / Im in Ohms
SHORT CIRCUIT Test:
1. Primary winding resistance, R1 = Wsc / Isc2 in Ohms
where
Wsc - Short circuit power in Watts
Isc - Short circuit current in Amps
2. Primary winding impedance, Z1 = Vsc / Isc in Ohms
Where
Vsc = Short circuit voltage in Volts
3. Primary winding reactance, X1 = Z12 - R12 in Ohms
TABULATION:
OPEN CIRCUIT TEST
Multiplication Factor =
Voltage Current No Load Losses
S.NO.
VOC (Volts) I0C (Amps) WOC (Watts)
1
2
Power % Regulation
S.No. Factor
COS LAGGING LEADING
1
2
3
4
5
REGULATION:
CIRCUIT DIAGRAM
150V /10A
UPF
P 15A CC
A M
PC
L
(0-10)A
C V
MI
D
P
S
230V
T
50H z 1
AC
S
(0-75)V
MI V (0-20)A
MI
A
S U P P LY
W
I
T
C
H
LIN K
Secondary Voltage:
Primary Current:
Secondary Current :
Dr. N.G.P Institute of Technology Department of Electrical and Electronics Engineering
69
THEORY:
Open Circuit Test or No Load Test:
The purpose of this test is to determine the losses and no load current which is helpful in
finding Reactance (X0) and Resistance (R0). One winding of the transformer is left open and the
other is connected to the supply of normal voltage and frequency. The ammeter, voltmeter and
the wattmeters are connected to the primary side. With normal voltage applied to the primary
winding, flux is set up in the core, and hence normal iron losses occur which are recorded by
wattmeter. As the primary no load current is small, copper loss is negligibly small in primary and nil
in secondary. Hence the Wattmeter reading represents practically the core loss under no load
Condition. The reading in the voltmeter connected across the secondary gives the induced emf in
the secondary winding.
In this test, one winding, usually the low voltage winding is solidly short circuited by a thick
conductor or through an ammeter which may serve the purpose of indicating the rated load
current. Since the applied voltage is small percentage of the normal voltage the mutual flux
produced is also small. Hence core losses are very small with the result that the wattmeter reading
represents the full load copper loss.
PROCEDURE:
Open Circuit TEST:
1. Note down the Name plate details of the Transformer.
2. Connections are made as per circuit diagram.
3. Supply is given by closing the DPST Switch.
4. Vary the Autotransformer such that the voltmeter reads the rated primary voltage of the
transformer.
5. Note down the corresponding readings of the ammeter, voltmeter and wattmeter and the
values are tabulated.
Short Circuit TEST:
1. Connections are given as per circuit diagram.
2. Supply is given by closing the DPST Switch.
3. Vary the Autotransformer such that the ammeter reads the rated secondary current of the
transformer.
4. Note down the corresponding readings of the ammeter, voltmeter and wattmeter and the
values are tabulated.
MODEL GRAPH
Fig (4)
Fig 9.3: Output Power Vs Efficiency Fig 9.4: Percentage Regulation Vs Power Factor
I1 R1 X1 R2 X2 I2
I0
X0 L
V1 O
R0
A
D
MODEL CALCULATION
INFERENCES:
RESULT:
CIRCUIT DIAGRAM
Rated Power
Rated Current
Rated Voltage
Rated Speed
Fig: 10.1 Regulation of Three Phase Alternator by using EMF and MMF Method
AIM:
To predetermine the percentage regulation of the given alternator by EMF (Synchronous
impedance Method) and MMF (Ampere Turns Method) method, by conducting Open Circuit
and Short circuit test.
APPARATUS REQUIRED:
Where,
Rdc=Resistance of dc supply
TABULATION:
10
EMF Method
Open circuit voltage for lagging p.f. Eph = (Vphcos + IaRa)2 + (Vphsin + IaXs)2
Open circuit voltage for leading p.f. Eph = (Vphcos + IaRa)2 + (Vphsin IaXs)2
Open circuit voltage for unity p.f. Eph = (Vph+ IaRa)2 + (IaXs)2
Where,
THEORY:
The regulation of a 3-phase alternator may be predetermined by conducting the Open
Circuit (OC) and the Short Circuit (SC) test. The methods employed for determination of
regulation are EMF or synchronous impedance method, MMF or Ampere Turns method and the
ZPF or Potier triangle method. In this experiment, the EMF and MMF methods are used. The OC
and SC graphs are plotted from the two tests. The synchronous impedance is found from the
OC test. The regulation is then determined at different power factors by calculations using
vector diagrams. The EMF method is also called pessimistic method as the value of regulation
obtained is much more than the actual value. The MMF method is also called optimistic method
as the value of regulation obtained is much less than the actual value. In the MMF method the
armature leakage reactance is treated as an additional armature reaction. In both methods the
OC and SC test data are utilized.
PROCEDURE:
Note down the name plate details of the motor and alternator.
Connections are made as per the circuit diagram.
Switch ON the supply by closing the DPST switch.
Using the Three-point starter, start the motor to run at the rated speed by adjusting the
motor field rheostat.
Conduct Open Circuit test by varying the potential divider for various values of field
current and tabulate the corresponding Open Circuit Voltage readings.
Conduct Short Circuit test by closing the TPST switch and adjust the potential divider to
set the rated armature current and tabulate the corresponding field current.
The Stator resistance per phase is determined by connecting any one phase stator
winding of the alternator as per the circuit diagram using MC voltmeter and ammeter of
suitable ranges.
MODEL GRAPH:
OPEN AND SHORT CIRCUIT CHARACTERISTICS
Fig10.4 Voltage Regulation Graph for both EMF and MMF Method
MODEL CALCULATION:
INFERENCES:
RESULT:
CIRCUIT DIAGRAM
RATED POWER
RATED CURRENT
RATED VOLTAGE
RATED SPEED
AIM:
To obtain V and inverted V curves of the given Synchronous motor at no load and at half load
conditions.
APPARATUS REQUIRED:
S.NO. Name of the Apparatus Type Range Quantity
1 Ammeter MC (0 2)A 1
2 Ammeter MI (0 5) A 1
3 Voltmeter MC (0 300) V 1
4 Voltmeter MI (0 600) V 1
5 Rheostat Wire wound 710 / 0.8 A 1
6 Wattmeter UPF 300 V/10A 2
7 Autotransformer 3-Phase (0-470)V 1
8 Tachometer Digital --- 1
9 TPST switch -- -- 1
10 Power factor meter UPF 300 V/10A 1
PRECAUTION:
The Rheostat should be in the maximum position.
The motor should be started without any load.
Initially TPST switch is kept in open position.
FORMULAE USED:
Input Power = K (W1+ W2) Watts
Power factor, cos = K (W1 + W2)
Vac Iac
Where,
K = Wattmeter constant
W1 = Reading of Wattmeter 1
W2 = Reading of Wattmeter 2
Vac = Alternator Voltage
TABULATION:
NO LOAD:
Excitation Current Armature
S.NO. Input Voltage Vin (V) Power Factor Cos
If (A) Current Ia (A)
HALF LOAD
THEORY:
It has been stated, when the field current (i.e., excitation) of a Synchronous motor is
reduced, a lagging armature current Ia is produced which exceeds the minimum current at
unity power or at normal excitation. Similarly, when the motor is over excited the armature
current also exceeds the current required at normal excitation to develop the necessary at any
given load.
By applying a given constant load to the shaft of a synchronous motor and varying the
field current, from under excitation to over excitation. Recording the armature current at each
step, the curves of synchronous motor are obtained. The AC armature current is plotted against
the DC field current. For no load, half load, full load values respectively. The curves show that a
slightly increased field current is required to produce normal excitation as the load is increased.
PROCEDURE:
1. The connections are made as per the circuit diagram.
2. By closing the TPST switch, 415 V, 50 Hz, 3 supply is given to the Auto transformer.
3. Now the Auto transformer is slowly adjusted and the motor is started.
4. Now the field of the synchronous motor is exited from the separate DC power supply
5. The load on the brake drum is adjusted for a constant value.
6. For this constant load output, by varying the rheostat connected to the field winding,
the field current is varied
7. The corresponding armature current and the input voltage is noted and tabulated. The
field current is varied in such a way that the armature current should not exceed its
maximum value.
8. Graph between Field Current Vs Armature current and Field current Vs cosare drawn.
MODEL GRAPH:
INFERENCES:
RESULT:
CIRCUIT DIAGRAM
Fig: 12.1 Load Test on Three Phase Squirrel Cage Induction Motor
AIM:
To conduct load test on given squirrel cage induction motor and to draw the following
characteristic curves.
Torque Vs Power output
Power Factor Vs Power Output
Line Current Vs Power Output
Efficiency Vs Power Output
Slip Vs Power Output
Torque Vs Speed
APPARATURS REQUIRED:
TABULATION:
Speed of Motor
Load Voltage VL
Load Current IL
Output Power
r reading reading S in Kg
Torque T Nm
Input Power
Efficiency
in Watts
N rpm
Watts
Watts
Cos
S.NO.
Amps
Slip S
Volts W1 W2 S1 S2 S1-S2
kg kg kg
MODEL GRAPH:
Fig: 12.1 Mechanical and Performance characteristics of Three Phase Induction Motor
T = S x R x 9.81 Nm
Where,
T= Torque in N-m
S = spring balance in kgs
R = Radius of the brake drum in m
9.81 = Constant (To convert kg to Nm)
Pout = (2x 3.14 x N xT)/60
Where,
Pout = output power in watts.
N = Speed in rpm
T = Torque in Nm
% Efficiency = (Pout/Pin) *100
Where,
Pout = Output Power in Watts
Pin = Input Power in Watts
Cos = Pin/3x VL x IL
Where,
Cos = Power Factor of Machine
Pin = w1+w2 Input Power in Watts
VL = Line Voltage in Volts
IL = Line Current in Amperes
THEORY:
The squirrel cage rotor is made up of stamping which are keyed directly to the shaft. The
great majority of present Induction motors are manufactured with squirrel cage rotor, a
common practice to employ winding of cast aluminum. In this type of rotor, it may be noted
made parallel to the shaft but they are skewed to serve the following purposes.
To make the rotor run quietly by reducing the magnetic hum.
To reduce the locking tendency of the rotor.
The ordinary squirrel cage motor has the excellent running characteristics, but the starting
torque is very poor. On the other hand wound rotor induction motor has good starting torque.
But it is unsuitable for many types of services, because the starting rheostat has to be
manipulated while the motor accelerates and the extra cost of the external switch is also
another objection. It has been the aim of designing engineers to combine in one-machine two
characteristics
i. Good starting torque
Ii. Excellent running performance.
To realize it is necessary to have high resistance for the rotor phase during starting period,
and the rotor resistance must be low to obtain excellent running performance.
MODEL CALCULATION:
PROCEDURE:
1. The connections are made as per the circuit diagram.
2. By closing the TPST switch, 415 V, 50 Hz, 3 supply is given to the Auto transformer.
3. The motor is started using the direct on line (DOL) starter.
4. At no load, the readings of voltmeter, ammeter, spring balance readings s1 and s2 and
speed are noted and tabulated.
5. Then the load on the brake drum is increased gradually up to the rated value of load
current and for each value of load, the readings of voltmeter, ammeter, spring balance
s1 and s2 and speed are noted and tabulated.
6. By using the given formula. % slip, Torque, input power, Output power, Efficiency and
power factor are calculated and required graphs are drawn.
INFERENCES:
RESULT:
CIRCUIT DIAGRAM
EXP.NO:- 13
LOAD TEST ON SINGLE PHASE INDUCTION MOTOR
Date:-
AIM:
To conduct load test on capacitor start single phase induction motor and to draw the
following characteristic curves.
Torque Vs Power Output
Speed Vs Power Output
Line Current Vs Power Output
Torque Vs Power Output
Efficiency Vs Power Output
Slip Vs Power Output
Torque Vs Speed
APPARATUS REQUIRED:
S.NO. Name of the Apparatus Type Range Quantity
1 Ammeter MI (0 15) A 1
2 Voltmeter MI (0 300) V 1
3 Wattmeter UPF 300 V/15A 2
4 Tachometer Digital --- 1
5 Auto transformer 1 (0-270)V/25A 1
PRECAUTION:
There wont be any load at the time of starting of induction motor.
FORMULA USED:
Synchronous Speed Ns = 120f/p rpm
Where,
f = Frequency in Hertz
p = Number of poles
S= S1 ~ S2
Where,
S1, S2 = Spring Balance Readings in kg
T = S x R x 9.81 Nm
Where,
T= Torque in Nm
S = spring balance in Kgs
R = Radius of the brake drum in m
Pout = ( 2x 3.14 x N xT)/60
96
TABULATION:
Speed of Motor N
Load Voltage VL Spring balance
Load Current IL
Output Power
Torque T Nm
Input Power
Wattmeter
reading S in Kg
Efficiency
W1 Watts
reading
Watts
Watts
Cos
S.NO.
Amps
Volts
rpm
S1 S2 S1-S2
kg kg kg
1
MODEL GRAPH:
Fig: 13.2 Mechanical and Performance characteristics of Three Phase Induction Motor
97
Where,
Pout = Output Power in Watts.
N = Speed in RPM
T = Torque in Nm
% Efficiency = (Pout/Pin)*100
Where,
Pout = Output Power in Watts
Pin = Input Power in Watts
Cos = Pin/ VL x IL
Where,
Cos = Power factor of machine
Pin = W1+W2 Input power in Watts
VL = Line Voltage in Volts
IL = Line Current in Amperes
THEORY:
The single phase squirrel cage rotor is made up of stamping which are keyed directly to
the shaft. The great majority of present Induction motors are manufactured with squirrel cage
rotor, a common practice to employ winding of cast aluminum. In this type of rotor, it may be
noted rotor made parallel to the shaft but they are skewed to serve the following purposes.
To make the rotor run quietly by reducing the magnetic hum.
To reduce the locking tendency of the rotor.
The ordinary squirrel cage motor has the excellent running characteristics, but the starting
torque is very poor. On the other hand, wound rotor induction motor has good starting torque.
But it is unsuitable for many types of services, because the starting rheostat has to be
manipulated while the motor accelerates and the extra cost of the external switch is also
another objection. It has been the aim of designing engineers to combine in one-machine two
characteristics
Good starting torque
Excellent running performance.
To realize it is necessary to have high resistance for the rotor phase during starting period,
and the rotor resistance must be low to obtain excellent running performance.
98
MODEL CALCULATION:
99
PROCEDURE:
The connections are made as per the circuit diagram.
By closing the DPST switch, 230 V, 50 Hz, 1Phase supply is given to the Auto
transformer.
At no load, the readings of voltmeter, ammeter, spring balance readings s 1 and s2 and
speed are noted and tabulated.
Then the load on the brake drum is increased gradually up to the rated value of load
current and for each value of load, the readings of voltmeter, ammeter, spring balance
s1 and s2 and speed are noted and tabulated.
By using the given formula. Torque, input power, output power, efficiency and power
factor are calculated and required graphs are drawn.
INFERENCES:
RESULT:
100
CIRCUIT DIAGRAM
RATED POWER
RATED CURRENT
AIM:
To conduct the load test on three phase slip ring induction motor and draw its
performance characteristics.
APPARATUS REQUIRED:
PRECAUTIONS
1. TPST switch is kept open initially.
2. There must be no load when starting the load.
THEORY
1. When we apply mechanical load to the shaft of the motor, it will begin to slow down
and the rotating flux will cut the rotor conductors at a higher and higher rate. The induced
voltage and resulting current in rotor Conductors will increase progressively, producing greater
and greater torque.
2. The motor and mechanical load will soon reach a state of equilibrium when the motor
torque is exactly equal to the load torque. When this state is reached, the speed will cease to
drop anymore and the motor will run at the new speed at a constant rate.
3. The drop in speed of the induction motor on increased load is small. It is because the
rotor impedance is low and a small decrease in speed produces a large rotor current. The
increased rotor current produces a higher torque to meet the increased load on the motor. This is
why induction motors are considered to be constant-speed machines. However, because they
never actually turn at synchronous speed, they are sometimes called asynchronous machines.
104
TABULATION
MODEL GRAPH
Fig: 14.2 Speed characteristics of Three Phase Slip Ring Induction Motor
4. Note that change in load on the induction motor is met through the adjustment of slip. When
load on the motor increases, the slip increases slightly (i.e., motor speed decreases slightly). This
results in greater relative speed between the rotating flux and rotor conductors. Consequently,
rotor current is increased, producing a higher torque to meet the increased load. Reverse
happens should the load on the motor decrease.
5. With increasing load, the increased load currents I'2 are in such a direction so as to decrease
the stator flux (Lenzs law), thereby decreasing the counter e.m.f. in the stator windings. The
decreased counter e.m.f. allows motor stator current (I1) to increase, thereby increasing the
power input to the motor. It may be noted that action of the induction motor in adjusting its
stator or primary current with changes of current in the rotor or secondary is very much similar to
the changes occurring in transformer with changes in load.
SLIP RING ROTOR OR WOUND ROTOR:
In this type of construction, rotor winding is exactly similar to the stator. The rotor carries
a three phase star or delta connected, distributed winding, wound for same number of poles as
that of stator. The rotor construction is laminated and slotted. The slots contain the rotor
winding. The three ends of three phase winding, available after connecting the winding in star or
delta, are permanently connected to the slip rings. The slip rings are mounted on the same shaft.
We have seen that slip slip rings are used to connect external stationary circuit to the internal
rotating circuit. So in this type of rotor, the external resistances can be added with the help of
brushes and slip ring arrangement, in series with each phase of the rotor winding.
PROCEDURE:
1. Connections are given as per circuit diagram.
2. 3- induction motor is started with TPST switch. Now the motor is started with the help
of rotor resistance starter. Where the rotor resistance starter is begins from maximum
resistance to minimum resistance.
3. If the pointer of one of the wattmeter readings reverses, interchange the current coil
terminals and take the reading as negative.
4. The no load readings are taken.
5. The motor is loaded step by step till we get the rated current and the readings of the
voltmeter, ammeter, wattmeters, spring balance are noted.
6. After note down the reading load is brought to its initial position.
7. Now switch off the AC supply which is given to the motor.
8. From the tabulated reading, the parameters are calculated using the formulae.
9. The performance characteristics are drawn from the calculated and tabulated readings by
the power output in X-axis and the remaining parameter in Y-axis
INFERENCES:
RESULT:
CIRCUIT DIAGRAM
4 POINT
+ 25A +
A -
STARTER
L1 L2 F A
(0-20)A
MC
350
Se(+)
D
P
S
Se(-)
T + S1 S2
220V
(0-300)V
DC
SUPPLY
S MC V
W -
I
T Sh(+) A(+)
C
H
M #
Sh(-) A(-)
- 25A
4 P O IN T
+
STARTER
25A L1 L2 F A
S e(+) S e(-)
+
A -
(0-20)A
MC
350
D
P
S
T + S1 S2
220V
(0-300)V
DC
S U P P LY
S MC V
W -
I
T S h(+) A (+)
C
H
M #
S h(-) A (-)
- 25A
AIM:
To conduct the load test on DC compound motor and draw the characteristic curves.
APPARATUS REQUIRED:
2 Voltmeter (0-300) V MC 1
4 Tachometer - Digital 1
5 SPST switch - - 1
PRECAUTIONS:
At the time of starting, the motor field rheostat should be in minimum resistance
position.
There should be no load on the motor at the time of starting.
FORMULAE USED:
1. Torque (T) = (S1-S2) x R x 9.81 in Newton-meter
Where,
S1, S2 - spring balance readings in Kg
R - Radius of the brake drum in m
2. Input power (Pi) = VLIL in Watts
Where,
VL- Line voltage in Volts
IL Line current in Amps
3. Output power (Po) = 2NT/60 in Watts
Where,
N- Speed in rpm
T-Torque in Nm
Output power
4. Efficiency ()= X 100 in %
Input power
TABULATION:
CUMULATIVE COMPOUND MOTOR:
Radius of the brake drum :
Armatu Load Input Spring Balance Output
Load Torque
S. re Voltage Power Speed Reading Kg Power Efficiency
Current T
No. Current (VL W N rpm P0 %
IL Amps S1 S2 S1~S2 N-m
Ia Amps Volts Watts Watts
THEORY:
A DC Compound motor has both shunt and series field coils. Compound motors are of two
types namely cumulative compound and differential compound motors.
Cumulative Compound motor: Cumulative compound motor is one in which the field
windings are connected in such a way that the direction of flow of current is same in both of the
field windings. In this type of motor, the flux due to series field winding strengthens the flux due
to the shunt field winding.
Differential Compound Motor: Differential compound motor is one in which the field
windings are connected in such a way that the direction of flow of current is opposite to each
other in the two field windings. In this type of motor, the flux due to series field winding weakens
the flux due to shunt field winding.
PROCEDURE:
1. Note down the name plate details of the motor.
2. Connections are made as per the circuit diagram.
3. Supply is given by closing the DPST switch and the motor is started using DC 3-point starter.
4. The field rheostat is adjusted to run the motor at rated speed.
5. At no load condition, the input voltage, current, spring balance readings and speed are
noted and enter the value in the table.
6. Increase the load current in steps of 1/4th,1/2 th, 3/4 th, full load and 1 th of the load.
7. Note down the corresponding readings of the voltmeter, ammeter, spring balance readings
and speed and enter the values.
8. Change the series field winding terminals and repeat the above procedure for differential
compound motor in table.
MODEL GRAPH:
MODEL CALCULATION:
INFERENCES:
RESULT:
EXP.NO:- 16
LOAD TEST ON THREE PHASE ALTERNATOR
Date:-
AIM:
To Study Load Test on Three Phase Alternator.
THEORY:
The most commonly used machine for generation of electrical power for commercial
purpose is the synchronous generator or alternator. An alternator works as a generator when its
rotor carrying the field system is rotated by a prime-mover which in this case is DC shunt motor.
The terminal voltage of an alternator changes with load.
Alternators are by far the most important source of electric energy. Alternators generate
an AC voltage whose frequency depends entirely upon the speed of rotation. The generated
voltage value depends upon the speed, the dc field excitation and the power factor of the load.
As the DC field excitation of an alternator is increased, its speed being held constant, the
magnetic flux, and hence, the output voltage, will also increase in direct proportion to the
current. However, with progressive increases in DC field current, the flux will eventually reach a
high enough value to saturate the iron in the alternator. Saturation in the iron means that there
will be a smaller increase in flux for a given increase in DC field current. Because the generated
voltage is directly related to the magnetic flux intensity, it can be used as a measure of the degree
of saturation.
When an alternator delivering full rated output voltage is suddenly subjected to a short-
circuit, very large currents will initially flow. However, these large short-circuit currents drop off
rapidly to safe values if the short-circuit is maintained. The output voltage of an alternator
depends essentially upon the total flux in the air-gap. At no load this flux is established and
determined exclusively by the DC field excitation.
Under load, however, the air-gap flux is determined by the ampere-turns of the rotor and the
ampere-turns of the stator. The latter may aid or oppose the MMF (magneto motive force) of the
rotor depending upon the power factor of the load. Leading power factors assist the rotor, and
lagging power factors oppose it. Load test of an alternator provides the information about the
efficiency and regulation. It is performed by driving the alternator at its rated speed and increase
the field excitation till the armature voltage reaches to its rated value. Increase the load on
alternator terminals during this process alternator armature current will increase, terminal
voltage will vary according to the type of the load. By observing the input and output of an
alternator at each load we can calculate the corresponding efficiency and regulation.
1. Close DPST (double pole single throw) switch connected to the DC shunt motor and apply
voltage in steps till desired speed of the alternator is attained.
13) Cut off the supply through DPST (double pole single throw) of the for DC shunt motor after
INFERENCES:
RESULT:
AIM:
V Curves and Inverted V curves of Three Phase Synchronous Motor
THEORY:
Electromagnetic devices draw a magnetizing current from the AC source, in order to
establish the working flux. This magnetizing current lags the applied voltage by almost 900. A
synchronous motor is a double-excited machine, its armature winding is energized from an AC
source and its field winding from DC source. When synchronous motor is working at constant
applied voltage, the resultant air gap flux demanded by applied voltage remains constant. This
resultant air gap flux is established by both AAC in armature winding and DC in the field winding.
If the field current is sufficient enough to set up the air-gap flux, as demanded by constant
applied voltage then magnetizing current or lagging reactive VA required from the AC source is
zero and therefore motor operates at unity power factor. This field current, which causes unity
power factor operation of the synchronous motor, is called normal excitation or normal field
current. If the current less than the normal excitation, i.e the motor is under excited, then the
deficiency in flux must be made up by the armature winding m.m.f.
In order to do the needful, the armature winding draws a magnetizing current or lagging
reactive VA from the AC source and as a result of it, the motor operates at a lagging power factor.
In case the field current is made more than its normal excitation, i.e the motor is over-excited,
operates at leading power factor. Fig (1) shows the variation of armature current and power
factor with field current at no load, half load and full load conditions.
1. The machine under consideration salient pole synchronous motor. The short circuited
aluminum damper bars are put in the rotor to make it self-starting. When 3 phase supply
is applied to the stator of motor, motor will act like induction machine and it will attain
speed slightly less than synchronous speed. This is achieved by switching on the 3 phase
supply with TPST (Triple Pole Single Throw) for synchronous motor.
2. With the help of 3 phase auto-transformer the voltage to be applied to the stator of
synchronous motor is varied smoothly.
3. When motor attends speed near to synchronous speed (generally at rated voltage), turn
field supply on of motor with help of DPST (Double Pole Single Throw) switch and apply
rated voltage in steps. Here onwards the speed of synchronous machine will be constant
as synchronous speed.
Rheostat
Dr.N.G.P Institute of Technology Department of Electrical and Electronics Engineering
124
6. To keep air gap flux constant in synchronous motor reactive power is needed. It is met
by AC supply of synchronous motor depending on its field excitation. Plot the variations
of stator current drawn by the synchronous motor with its field current.
7. Its graph follows shape of V, hence the name V curves. This characteristic of
synchronous machine. Variation of power factor with field current of motor in exactly
reverse fashion, which is called as inverted V curves. The point of least armature current
drawn from stator of Synchronous motor will correspond to unity power factor and both
graphs will have same field current reading.
8. Store this data by clicking Start Storing Data.
9. Go on repeating this procedure till all load are connected and data is stored.
10. Now display the data by clicking Show data.
Where,
Vfa = Field Voltage of Alternator
Ifa = Field Current of Alternator
Vt = Terminal Voltage
Vs = Supply Voltage
Ial = Alternator Current
11. These V curves can be performed on various loads and no load conditions on the
synchronous motors.
12. While switching motor off, in stepwise manner reduce the stator supply to zero, and
switch off TPST (Triple Pole Single Throw) switch. Then in steps cut down field supply for
synchronous motor.
13. Now select one of the graph from available graphs and use Generate graph to plot the
graph.
INFERENCES:
RESULT:
Kd =
Where,
Kd= Distributed Factor
(SPP) m = Number of slots / pole / phase
= slot angel
Distribution factor is always less than unity.
5. What are the tests data required for predetermining the voltage regulation of an
alternator by MMF method?
For determining the voltage regulation by MMF method, we need the following test results
i) Open circuit test
ii) Short circuit test
10. How are the armature windings in alternators different from those used in DC
machines?
Armature of the DC machine is rotor. The output current taken from DC machine is direct
current. The winding may be either lap or wave winding. Armature winding is placed in the
rotor of DC machine. But in AC machine, armature winding is placed in stator. It may be a
short pitched double layer distributed winding. For high power rating machine. It is a start
connected 3 phase winding.
11. List the two types of rotors of synchronous generator. State its features.
Types of rotors of synchronous generator are
i) Salient pole (or) projected pole rotor
ii) Non salient pole (or) smooth cylindrical pole rotor
Salient pole rotor has large diameter and short axial length, it is suitable for low and medium
speed generator.
Smooth cylindrical has small diameter and very long axial length. It is suitable only for high
speed generators.
12. What is the necessity for short chording the armature winding of synchronous
machines?
Short pitching eliminates high frequency harmonics which distort the sinusoidal nature of
emf. Hence waveform of an induced emf is more sinusoidal due to short pitching.
= . Tsy
Tsy=
15. Write down the equation for frequency of emf induced in an alternator.
16. What are the methods by which zero p.f lagging curve can be obtained?
1. Open circuit characteristic (OCC)
2. Short circuit test (SC)
3. Zero power factor test (ZPF)
17. What are squirrel cage windings of alternators? How and why are they used?
Squirrel cage winding is also called as Damper winding. It consisting of squirrel cage bars is
place in the rotor pole face to damp out the hunting effect.
18. state why an alternator with low value of SCR has lower limit of stability.
A lower value of SCR means a greater change in field current to maintain constant terminal
voltage and a lower value of steady state stability limit lesser the SCR, lesser in the size,
weight and cost of the machine.
19. What is the necessity for short chording the armature winding of synchronous
machines?
Short pitching eliminates high frequency harmonics which distort the sinusoidal nature of
emf. Hence waveform of an induced emf is more sinusoidal due to short pitching.
17. What is the other name for EMF and MMF method?
The other name for EMF method is called as Synchronous impedance method and MMF
method is called as Ampere turn method.
EMF method Pessimistic method
MMF method Optimistic method
It is a transformer with one winding only, part of this being common to both primary
and secondary. In this transformer the primary and secondary are not electrically isolated
from each other.
The synchronous reactance of an alternator is due to both leakage flux as well as armature
reaction
8. In which fault the positive sequence component of voltage at fault point is zero?
3-Phase fault
9. If Ia1 is the positive sequence current of an alternative and Z 1, Z2 & Z0 are the sequence
impedances of the alternator, the voltage drop produced in L-G fault will be equal to
Ia1 (Z1+Z2+Z0)
10.Which statement is correct for positive, negative and zero sequence impedances Z1 greater
than Z2 greater than Z0
The magnitude of armature current varies with excitation. If graph of armature current
drawn by the motor against field current is plotted then we get V curves.
If the power factor is plotted against field current then the shape of the graph looks like an
inverted V and are called as Inverted v curves.
The value of excitation for which back emf is equal to the applied voltage is known as
100% excitation or when the power factor of the synchronous motor is unity.
Eb=V
When the excitation is changed, the power factor changes. The excitation for which the
power factor of the motor is unity is called critical excitation.
When the excitation is adjusted in such a way that the magnitude of induced emf is less than
the applied voltage the excitation is called under excitation (lagging power factor)
When the excitation is adjusted in such a way that the magnitude of induced emf is greater
than the applied voltage the excitation is called over excitation (leading power factor).
When synchronous motor is over excited it takes leading power factor current. This
characteristic is similar to a normal capacitor which always takes leading power factor
current.
6. What is hunting?
When synchronous motor is on no load, the stator and rotor pole axis coincide with each
other. When motor is loaded, the rotor pole axis falls back with respect to stator.
If the load connected to motor is suddenly changed by a large amount , the rotor tries to
take its new equilibrium position. But due to inertia of rotor, it cannot achieve equilibrium
instantaneously while achieving new position, it passes beyond its final position
9. A synchronous motor starts as usual but fails to develop its full torque. What could be due
to?
3. DC exciter starting
The V curves of synchronous motor reveals the fact that its power factor is
controllable by means of its excitation.
1. What is the function of slip rings and brush assembly in three phase induction motor?
Slip rings are used to connect external stationary circuit to the internal
rotating circuit. Hence in induction motor, the external resistances can be
added with the help of brushes and slip ring arrangement in series with each
phase of rotor winding.
2. List the difference between squirrel cage rotor and slip ring rotor
Slip of the induction motor is defined as the difference between the synchronous speed
and actual speed of rotor expressed as a fraction of the synchronous speed.
4. How the direction of rotation of three phase induction motor can be reversed?
5. Under what condition, the slip in an induction motor is zero, one, negative and greater than
one.
Zero: when N = Ns, S=0 which is not possible for an induction motor.
One: when N = 0, S=1. At start motor is at rest and hence its speed N is zero.
Negative: When the rotor is running at a speed above synchronous speed, slip is
negative.
Greater than one: When the motor is rotated in opposite direction to that of rotating
field, slip is greater than 1. When slip is greater than one, the machine works in
breaking mode.
The resultant of three alternating fluxes separated from each other by 120 degree
has constant amplitude of 1.5 m, where m is maximum amplitude of an individual
flux due to any phase.
The resultant always keeps on rotating with certain speed in space, and the speed is
given by Ns = 120f / P
When run faster than its synchronous speed, an induction motor runs as a generator called
as induction generator. Slip is negative.
When rotor starts rotating it tries to catch the speed of rotating magnetic field. If it
catches the speed of rotating magnetic field, the relative motion between rotor and RMF will
vanish. In fact the relative motion is the main cause for the individual emf in the rotor. So
induced emf will vanish and hence there cannot be rotor current and rotor flux which is
essential to produce the torque on the rotor. Eventually motor will stop. The induction motor
never rotates at synchronous speed.
4. Worn bearings due to which the armature may be touching field laminae, thus
introducing excessive friction.
2. What happens if single phasing occurs when the motor is running? And when it is
stationary?
If already running and carrying half load or less, the motor will continue running as a
single phase motor on the remaining single phase supply, without damage because half
loads do not blow normal fuses.
If motor is very heavily loaded, then it will stop under single phasing and since it can
neither restart nor blow out the remaining fuses, the burn out prompt.
A stationary motor will not start with one line broken. In fact due to heavy standstill
current, it is likely to burn out quickly unless immediately disconnected.
5. What are the different methods of speed control of three phase induction motor?
1. Control from stator side:
i) By changing the supply voltage
Induction motor particularly the squirrel cage type, sometimes exhibit a tendency to run
stably at speeds as low as one seventh of their synchronous speed. This phenomenon is
known as crawling.
The rotor of a squirrel cage induction motor sometimes refuses to start at all, particularly
when the voltage is low. This happens when the number of stator teeth is equal to the
number of rotor teeth and is due to the magnetic locking between the stator and rotor teeth.
That is why this phenomenon is also called as teeth locking.
9. What is jogging?
Jogging means inching a motor ie, make it to move a little at a time by constant starting and
stopping.
3. Over heating
1. Stator losses
3. Mechanical losses
The no load losses are the constant losses which include core loss and friction and
windage loss.
3. In which type of induction motor can resistance be introduced in the rotor circuit?
In slip ring induction motor the resistance can be introduced in the rotor circuit.
4. The squirrel cage rotor is also known as short circuited rotor. Why?
In squirrel cage rotor, the copper bars are placed in the slots. These bars are short
circuited at each end with the help of conducting copper ring called end ring. The
entire rotor resistance is very small. Hence this rotor is also called as short circuited
rotor.
6. Define operating torque, starting torque and breakdown torque. Which of these is the
largest?
If loaded beyond this torque the motor will decelerate and come to standstill.
Breakdown torque is the largest among these for normal induction motor.
7. Why do induction motor runs at low power factor when lightly loaded?
At no load an induction motor draws large magnetizing current to create flux in the air gap.
This current has very low power factor of the order 0.2 lag. The power is mainly drawn to
provide for core loss. As the motor is loaded, it draws a load component of current with
much higher power factor.
Therefore the power factor of the net current drawn from main increases with load. It rises
to 0.8 - 0.85 at full load. At light load the power factor will be slightly more than that at no
load.
Maximum power output condition corresponds to matching of the load resistance in the
circuit model to the circuit impedance as seen by the load resistance. This condition
corresponds to much larger than the normal operating slip and hence larger current than
the full load value. As copper loss is proportional to square of motor current, the motor
efficiency under condition of maximum power output is well below 50% which is
unacceptable for a power device. Acceptable efficiencies are about 85% or higher.
Since the induction motor runs always at a speed lesser than the synchronous speed, it
is called asynchronous motor.
10. Why is the efficiency of a three phase induction motor less than that of a transformer?
In Induction motor, there are mechanical losses due to the rotation of the rotor. Hence
the efficiency of an induction motor is less than that of the transformer.
LOAD TEST ON SINGLE PHASE CAPACITOR START INDUCTION MOTOR & SPEED CONTROL OF
THREE PHASE SLIP RING INDUCTION MOTOR
The rating of the single phase machine is from 1/8 to hp range. They are widely used
for fans, washing machines, refrigerators, blowers, centrifugal pumps etc.
2. How will you change the direction of rotation of a split phase induction motor?
The direction of rotation of a split phase induction motor can be changed by changing
the direction of current either in the starting winding or in the running winding.
The current through the running winding lags behind the supply voltage by a very large
angle. Hence the power factor is low in single phase induction motor.
The copper shading coil is used to produce rotating magnetic field moving from the
unshaded to shaded portion of the pole. Hence the motor produces a starting torque.
6. Why are centrifugal switches provided on many single phase inductions motor?
The centrifugal switches are provided on many single phase induction motors, because
when the motor is running at 75% of the synchronous speed, the centrifugal switch
connected in the auxiliary winding operates and disconnect the auxiliary winding from the
supply.
7. What could be the reasons if a split phase motor runs too slow?
2. Overload
8. What could be the reasons if a split phase motor fails to start and hums loudly?
Universal motor is a series motor of rating less than 1Kw which is designed to operate on
both dc and ac supply. They are widely used for food mixers, vaccum cleaners, hair driers,
electric shavers, portable drills, sewing machines etc.
10. A single phase induction motor is not self-starting. Why?
When a single phase supply is connected across a single phase winding, a pulsating
magnetic field is produced. The force experienced by the upper conductors of the rotor
will be downward and the force experienced by the lower conductors will be directed
upward. The two sets of force will cancel and the rotor will experience no torque. Hence the
rotor will not rotate.
Capacitor is used to improve the power factor of the motor. Due to the capacitor connected
in series with the auxiliary winding, the capacitive circuit draws a leading current which
increases the split phase angle between the two current I m and Ist.
According to this theory, any alternating quantity can be resolved into two rotating
components which rotates in opposite directions and each having magnitude as half of the
maximum magnitude of the alternating quantity.
3. What are the classifications of single phase induction motor based on the method of
starting?
4. What design features are incorporated in a split phase motor to make it starting?
The split phase motor is provided with windings, main winding and auxiliary winding.
These two windings are excited from the same voltage. The currents in the two windings
can be made out of phase by adjustment of the impedance of the auxiliary winding in
relation to the main winding. As a result, the mmf of main winding and mmf of auxiliary
winding constitute an unbalanced field set with 900 electrical space phase relationship.
The two symmetrical components now being unequal the forward rotating field is made
stronger than the backward rotating field, which results in the net production of starting
torque. Thus the two windings with phase difference make the split phase motor self-
starting.
5. What is the advantage of a capacitor start motor over a resistance split phase motor?
In case of capacitor start, it is possible to have the phase angle between the two currents.
Therefore, this type of motor has high starting torque as compared to resistance split phase
motor and used for heavy loads such as compressors, conveyors, pumps, certain machine
tools, refrigerators and air conditioning equipment.
2. To limit the initial in rush of current during starting conditions, which would otherwise
produce larger line voltage drop affecting equipments connected to the same line.
10. What is the difference between the dc motors and single phase induction motor?
An important difference between the two is that the dc motors are self-starting while
single phase induction motors are not self-starting.