Documente Academic
Documente Profesional
Documente Cultură
0
15.10.01
ISSUED AS STANDARD
BDG
SC
STANDARD PIPING DESIGN BASIS
SML
FORMAT No. : 0060-F-
CONTENTS
2.3
ANNEXURE-F
ANNEXURE-H
ANNEXURE-G
CLEARANCES.
INSULATED PIPING.
FIELD PAINT SYSTEM
PAINTING UNDER INSULATION FOR
FORMAT No. : 0060-F-
2.1.1 For equipment layout Petroleum Rules 1995, OISD Std.118 will be followed.
2.1.3 Pipe-rack
The width of the rack shall be 6m, 8m, or 10m for single bay and 12m, 16m, or
20m for double bay having 4 tiers maximum. The spacing between pipe-rack
portals shall be taken as 6m in general. However it can be increased to 8m, in
which case an intermediate member shall be provided for supporting of small bore
express or implied agreement of the Borrower that it shall not be reproduced, copied, transferred or used for a purpose other than the one for which it is given.
line.
Towers and vertical vessels shall be arranged in a row with common center line,
decided by the largest vessels, placing O.D. of the equipment minimum 4m away
from the pipe-rack. A minimum clearance of 3m shall be allowed between tower
shells, but in any case adjacent towers shall be checked so that platforms do not
overlap (minimum 100mm horizontal gap shall be provided between platform of
adjacent towers) and that a minimum 900mm is left between tower plinths.
To handle heavy items (like relieve valves, blinds etc.) a davit or monorail is
required. The davit shall be on the side of the vessel/ column away from the rack.
The area at grade shall be kept clear for a dropout.
The horizontal vessels shall be laid perpendicular to pipe-rack and dished end
shall be placed minimum 4m away from the pipe-rack. The clearance between
horizontal vessel shells shall be minimum 2m or 900mm clear aisle whichever is
higher.
2.1.6 Pumps
Whenever practicable pumps shall be arranged in row with the center line of the
discharge on a common line, 3000mm away from the centerline of the rack
column. In general pumps shall be kept in open. Pumps shall be located outside
the pipe rack with motor towards the center of the rack and motor cable entry shall
be on the same side.
Pumps which are susceptible to fire and pumps for which specific notes are given
in P&ID shall be housed accordingly.
Clearance between two adjacent pumps shall be such that clear 900mm aisle is
available.
FORMAT No. : 0060-F-
All pumps with motor rating >= 55 KW are to be provided with monorail under
pipe-rack/ shed.
2.1.7 Exchangers
For heat exchangers on grade lying back to back, minimum clear gap of 15m shall
be provided.
2.1.8 Furnaces
Furnaces shall be located upwind or side wind of process units to blow any
combustible leaks away from the open flame. They shall be located minimum 90m
away from tanks and 30m away from control room. Distances for equipment
handling hydrocarbon from the furnace shall be strictly as per OISD norms.
Vessels/ reactors/ columns directly connected to the furnace (If required as per
P&ID) are exception. Stack height shall be minimum 6m above working platform in
the vicinity of 25m radius. In case of wall fired furnaces min. 2m wide platform with
escape route at each end is necessary.
Drop-out area tube bundle length +1.5m shall be provided for tube bundle
removal. Monorail with chain pulley shall be provided for all heat exchangers,
except on grade & open to sky.
2.1.9.3 Layout & Access Requirements for Platforms Ladders and Stairs
a. Dual access (i.e. one staircase and one ladder) shall be provided for
structure having length upto 22.65m (75ft). For large elevated structure, if
any part of platform has more than 22.65m (75ft) of travel, it shall have
staircase on both sides. Landing height of staircase should not be more
than 4m.
2.1.9.4 Clearances
Access platforms / ladders shall be provided along the column for valves
and instruments. Minimum width of platform shall be 750mm clear.
For upto two no. safety valves on column top platforms, davit is adequate,
for more than two no. safety valves, monorail with chain-pulley block shall
be provided. Load capacity for davit & monorail shall be minimum 0.5T.
Liquid-vapour phase relief valves shall discharge into the flare header at
an angle 450 in the direction of header flow, to minimize the effect of
kinetic energy and to avoid accumulation of liquid.
Relief valve discharge piping shall be taken to safe location as per
following.
a) Steam lines with conditioned listed below fall in the scope of IBR.
FORMAT No. : 0060-F-
All materials used in lines falling under IBR must be accompanied with IBR
Inspection Cerficate.
express or implied agreement of the Borrower that it shall not be reproduced, copied, transferred or used for a purpose other than the one for which it is given.
Line traps shall be thermodynamic type upto Class 600# & bimetallic for piping
Class 900# & above.
Number of
Size of Lead Line
connections
2
3 1
4-6 1
7-12 2
Upto 4 1
6 to 16 2
18 to 24 3
A steam jacketed pipe consist of a product line which passes through the center of
a larger diameter steam line.
The nominal size of the inner pipe (CORE) and outer pipe (JACKET) in inches
shall be as per table below unless otherwise mentioned in project piping material
specification (PMS) or P&ID.
Utility stations shall have three connections [one for LP steam (SL), one for Plant
Air (AP) and one for Service Water (WS) each of 1] unless otherwise specified in
P&ID.
The approach of utility station shall be considered 15m all around the station
location.
2.2.9 For piping Class 900# & above, hydrostatic vents/ drains, pressure connections &
orifice tap-offs shall be with double block valves with blind flange.
2.3 Offsite & Yard Piping
FORMAT No. : 0060-F-
In general, the pipes shall be laid at grade level on sleepers of concrete 300mm to
500mm high from grade level.
Flare header shall be supported on shoe of height ranging from 100mm to 300mm.
express or implied agreement of the Borrower that it shall not be reproduced, copied, transferred or used for a purpose other than the one for which it is given.
Pipe supporting shall preferably follow the basic span as given in Annexure-A.
Depending on the pipe size as a rule guides shall be provided on straight run of
pipes at intervals as specified in Annexure-C, unless specifically becomes non-
viable due to flexibility problems.
Pipe support design shall be such that deflection in piping system due to sustained
loads does not exceed 15mm in any case.
Following lines shall be considered critical and shall mandatorily require formal
analysis.
All process lines to and from fired heaters and steam generators.
All pump lines and air coolers (6 & above and analysis temp> 65 0C &
less than 600C)
2.6.1 Pipe
a) Wall Thickness
Design
Material Class Size
Condition
Class
Upto 24
150 condition
Above 24 Line condition
Upto 16 Class
condition
300
Lines
C.S. & LTCS, Above 16
condition
Low Alloy upto Class
1 Cr-1/2 Mo, Upto 12
600 condition
2 Cr-1 Mo, 5
Cr- Mo, 9 Cr- Above 12 Line condition
1Mo Class
900 & Upto 8
condition
1500
Above 8 Line condition
Class
Upto 4
2500 condition
Above 4 Line condition
S.S. Class
Upto 12
150,300 condition
Above 12 Line condition
Class
Upto 6
600 condition
Above 6 Line condition
900,1500 Class
Upto 4
condition
Above 4 Line condition
FORMAT No. : 0060-F-
Class
Upto 2
2500 condition
Above 2 Line condition
Class
Upto 6
150 condition
Higher Alloys Above 6 Line condition
300-
All sizes Line condition
2500
express or implied agreement of the Borrower that it shall not be reproduced, copied, transferred or used for a purpose other than the one for which it is given.
In addition to the requirement covered in Para A & B given below, ratio of selected
pipe thickness (excluding mill tolerance and corrosion allowance) to pipe O.D.
shall not be less than 1/150.
b) Pipe Size
Pipe size shall normally be 0.5, 0.75, 1.0, 1.5, 2.0, 3, 4, 6, 8, 10,
12, 14, 16, 18, 20, 24, 26, 30, 36, 40, 44, 48, 52, 56, 60, 64,
72, 78, and 80.
c) Pipe Type
2.6.2 Fittings
c) For branch connection above 600# rating equal tee / unequal tee shall be
used for all sizes. Unequal tee may be replaced by weldolet upto branch
size of 8.
d) Mittres shall be used in Category D service above 6. For all other 150#,
300# classes mitres may be used after checking line condition for sizes
above 36 only.
b) Flanges
2.6. 4 Gaskets
express or implied agreement of the Borrower that it shall not be reproduced, copied, transferred or used for a purpose other than the one for which it is given. FORMAT No. : 0060-F-
Rating
Temperature (0C)
Type
Remarks
FORMAT No. : 0060-F-
Spiral SS304/ SS
150# Upto 3710C Specific requirement
316L+ CAF
Spiral SS316+
Above 4000C Specific requirement
Grafoil
express or implied agreement of the Borrower that it shall not be reproduced, copied, transferred or used for a purpose other than the one for which it is given.
Spiral SS304+
-
CAF
Upto 5000C
Spiral
For NACE classes
SS316L+CAF
Spiral SS304+
300# & 600# 5010C to 5400C -
Grafoil
Spiral SS316+
5410C to 7000C -
Grafoil
Spiral SS304H+
Above 7000C -
Grafoil
2.6.5 Valves
As a rule, all hydrogen, oxygen, NACE and any other lethal service shall have
100% radiography on weld joints. Castings used in these services shall have
100% radiography. For high pressure application i.e. 600 lb upward 100%
radiography on weld joints shall be employed. In 100% radiography classes any
fillet welds employed shall have 100% MP in CS/ AS classes and 100% DP in SS
classes. Cat. D service does not require radiography. Classes in 150# for normal
hydrocarbon service shall be subjected to 10% radiography and fillet welds shall
express or implied agreement of the Borrower that it shall not be reproduced, copied, transferred or used for a purpose other than the one for which it is given.
2.6.7 Strainers:
A Temporary Strainers :
B Permanent Strainers:
The insulation of piping, equipments and vessels shall be carried out with the
following insulating materials and the thickness of insulation shall be chosen from
the tables enclosed.
Resin bonded pipe sections of glass wool may be used upto 350 0C.
Density shall not be less than 80 Kg/m3
b) Calcium Silicate
FORMAT No. : 0060-F-
Cellular glass foamed are fused into unicellular foam can be used upto
temperature of 1250C.The testing of samples shall be as per ASTM C552.
Insulation for cold insulation (IC) for operating temperatures below 100C and dual
temperature (cold/hot) service where upper temperature limit is 120 0C shall be as
given below:
a) Polyurethane Foam
Preformed pipe sections and radial lags (for higher diameter pipe) of
polyurethane foam of shelf extinguishing type in accordance with ASTM
C591 TYPE-II Grade 2 shall be used as cold insulation material.
High density polyurethane foam block of bulk density more than 300
Kg/m3 shall be used for supports in cold lines.
Adhesive for bonding sections shall be Foster Fire Resistive Adhesive 81-
33 or blown bitumen type 85/25 shall be used.
Vapour seal like Forster Fire Retardant Mastic 60-30 or equal shall be
used.
Filler material shall be PUF dust or mineral wool mixed with specified
adhesive shall be placed lightly so as to fill irregular voids and at flashing
of insulation shall be Foster Foam Seal Sealer 30-45. Glass cloth to be
used for vapour barrier reinforcement, shall be open weave 10 mesh
having glass fibre thickness of 5 mils. Aluminium sheets shall be used for
cladding of vapour barriers.
The insulation thickness and type of insulation (Ih, It, Ic, Is, Ie and acoustics) to be
applied on equipments and vessels shall be as per equipment data sheet. In
absence of insulation thickness on equipment data sheet, insulation thickness as
specified in the enclosed tables shall be followed.
0.56 mm
0.56 mm (24SWG) (24SWG)
For grade piping in Galvanized steel as Galvanized steel
offsites per IS 277 Class I or as per IS 277
equivalent. Class I or
equivalent
2.7.5.1 Aluminium Foil to protect stainless surfaces in temp.below 00C shall be 0.1 mm
(42 SWG) thick per ASTM B209 alloy 3003 H16 or IS-737 designation 31000 (old
NS3) condition H3.
FORMAT No. : 0060-F-
2.7.5.2 Bands/Wires for securing insulation shall be of ASTM B209 Alloy 3003 H16 or IS-
737 designation 31000 (old NS3) condition H3 or 18/8 Stainless steel. For
securing aluminium foil on stainless steel surface 24 SWG thick x 20mm wide
aluminium bands shall be used.
For securing fibrous material on spheres, stainless steel bands of 25mm wide x
0.8mm thick shall be used.
For securing rigid insulation on pipe upto 16 O.D., annealed galvanized steel wire
of 16 SWG shall be used. Galvanizing coating shall have 600 g/m2 of surface area.
For securing rigid insulation on pipe 18 O.D. and above, galvanized steel band
20mm wide x24 SWG shall be used. Galvanizing shall be 600 g/m2 of surface
area.
For securing rigid insulation on vertical & horizontal vessels, galvanized steel band
20mm wide x 24 SWG shall be used. Galvanizing shall be 600 g/m 2 of surface
area.
2.7.5.3 For securing cladding on insulation on piping, aluminium band 12mm (min) x24
SWG thick shall be used.
For securing cladding on insulation for vertical storage tanks stainless steel band
25mm wide x 24 SWG shall be used.
For securing cladding on insulation for spheres stainless steel band 25mm wide x
24 SWG shall be used.
2.7.5.4 Rivets used for securement of metal jacket shall be expanding aluminium POP
blind eye type, 9.5mm long x 5mm diameter.
2.7.6 Application
Support skirts of vertical vessels and columns shall be insulated both from inside
and outside to a minimum distance of 600mm from bottom tangent line. The
insulation must terminate at minimum 300mm above support concrete or steel
work.
The following items under hot insulation shall not be insulated unless otherwise
specifically asked.
FORMAT No. : 0060-F-
Vapour barrier shall be applied on all the vessels and equipments in cold services
and also for services upto 1250C
2.8 Painting
Painting work shall require to satisfy the Civil Defence requirements of the area
where the plant is being setup. All other colour coding shall be as per the table of
Colour Coding scheme for pipes, equipments, machinery and structures (refer
Annexure-E).
All surfaces to be painted shall be blast cleaned either by Air blasting or water
blasting using sand / steel grit to finish SA 2.5 as per SIS-055900/ISO-8501-1.
Only repair painting of shop primed piping shall be done with mechanical tools to
surface finish ST-3 as per SIS-0559 00/ISO-8501-1.
2.8.5 No surface shall be coated in rain, wind or in environment where injurious airborne
element exists, where surface temperature is below 5 F above due point, where
relative humidity is greater than 90 % and temperature is below 40 F.
2.8.6.1 Inorganic Zinc Silicate (F-9) of 65-76 micron DFT Universal shop primer and repair
paint at site upto design temp of 400 C for all surface except stainless and higher
alloy piping. For surface above 400 C, heat resistant synthetic alluminium paint
(F12) shall be used.
Annexure D
express or implied agreement of the Borrower that it shall not be reproduced, copied, transferred or used for a purpose other than the one for which it is given.
Ends
Unless otherwise specified, the ends shall be to the following standard :
Face Finish
This shall be to MSS-SP-6/ASME B46.1 / ASME B16.5. the interpretation shall be :
Pipes
- Double seam is allowed for sizes 36 and larger.
- Galvanized Pipes shall be only Hot Dip galv. To ASTM A53.
Fittings
FORMAT No. : 0060-F-
- Al welded fittings shall be double welded. Inside weld projection shall not
exceed 1.6mm, and the welds shall be ground smooth at least 25mm
from the ends.
- All welded fittings shall be normalized for CS, normalized & tempered for
AS; and 100% radiographed by X-ray for all welds made by fitting
manufacturer as well as for welds on the parent material.
- Bevel ends of all BW fittings shall undergo 100% MP/DP test.
Flanges
- For Ring joint Flanges, Blinds and Spacers, the hardness shall be as
follows :
express or implied agreement of the Borrower that it shall not be reproduced, copied, transferred or used for a purpose other than the one for which it is given.
Valves
- Valves of Class 900 & above shall be pressure-seal type. Threaded and
seal welded or welded bonnet may be employed upto sizes 1-1/2.
- Forgings are acceptable in place of Castings but not vice-versa.
Dimensions
- Face-to Face/End-to-End dimension shall be as per ANSI N16.10. in case
the same is not covered under B16.10, the dimension shall be as per BS
2080/Manufacturers Std.
- Valve under cryogenic service (temp. below 45 C) shall be as per BS-
6364 and shall be procured from prequalified vendor.
Operation
- Generally the valves are handwheel or lever operated. However, suitable
gear operator in enclosed gear box shall be provided for valves as follows
:
Gate 150 12
300 12
600 12
900 6
1500 3
2500 3
Globe/Y-Globe/ 900 6
Stop-Check 1500 3
2500 3
Ball/Plug 150 6
300 6
600 4
FORMAT No. : 0060-F-
900 3
1500 3
Butterfly 150 10
300 6
- Hand wheel diameter shall not exceed 750mm and lever length shall not
exceed 500mm on each side. Effort to operate shall not exceed 35 kgf at
handwheel periphery.
By Pass
- A globe type valve (size as per ASME/ANSI B16.34) shall be provided as
express or implied agreement of the Borrower that it shall not be reproduced, copied, transferred or used for a purpose other than the one for which it is given.
Class Size
150 26 & above
300 16 & above
600 6 & above
900 4 & above
1500 4 & above
2500 3 & above
Ball/Plug/Butterfly Valves
- The ball of Ball valves shall not protrude outside the end flanges.
- Ball valves shall be floating ball type/trunion mounted type as per
following :
Class Floating Ball Trunion Mounted
express or implied agreement of the Borrower that it shall not be reproduced, copied, transferred or used for a purpose other than the one for which it is given.
Strainer
- All 2 & higher sized Y type strainers shall be provided with 3/4 threaded
tap and solid threaded plug as drain connection. For less than 2, this
shall be size.
- For fabricated strainers, all BW joints shall be fully radiographed and fillet
welds shall be 100% DP/MP checked.
- All the strainers shall be hydrostatically tested at twice the design
pressure.
Expansion Joints
- The applicable codes are ASME B31.3 and EJMA (Expansion Joint
Manufacturers Association).
- Bellows shall be formed from solution annealed sheet conforming to the
latest ASTM spec. any longitudinal weld shall be 100% radiographed.
- The out of roundness shall be limited to 3mm. This is the max. deviation
between the max. & min. diamter.
- The actual circumference of the welding end shall be maintained to
3mm of the theoretical circumference.
- Bellows should be designed for 10,000 cycles (ANSI B31.3) minimum.
Gaskets
- Non-metallic ring gaskets as per ASME/ANSI B16.21 shall match flanges
to ASME/ANSI B16.5 upto 24, and ASME/ANSI B16.47 or AWWA for
sizes 24 unless otherwise specified.
- Spiral wound gasket as per ASME B16.20 shall match flanges to
ASME/ANSI B16.5 upto 24, and ASME B16.47 series B for sizes 24,
unless otherwise specified.
FORMAT No. : 0060-F-
- Inner and outer rings shall be considered for spiral wound gaskets based
on undermention philosophy :
OUTER ring :
(i) C.S. outer ring irrespective of temp./spiral strip material
(except subzero temperatures).
INNER ring :
(i) Material of inner ring to be C.S. for C.S. classes & same as
that of spiral strip material for other than C.S. classes.
(ii) 26 & above for all classes.
express or implied agreement of the Borrower that it shall not be reproduced, copied, transferred or used for a purpose other than the one for which it is given.
- RTJ Gaskets :
(i) To be used for Class 900# and above in line with OISD
recommendation.
(ii) Gasket material to be as follows :
CS Classes = soft iron
Upto 5% Cr = 5% Cr alloy steel
SS = Same as class material
Impact Tests
- Welded Pipes and Fittings used below ASME Temp. 29 C shall be
impact tested as per requirement of ASME B31.3.