SHEET : 1 OF: 10

TEST REPORT FOR MOTOR PROTECTION RELAY PAGE :

2. Name plate details :

TESTED BY WITNESSED BY
SHEET : 2 OF: 10
TEST REPORT FOR MOTOR PROTECTION RELAY PAGE :

3. General Inspection : OK
4. Service Settings:
1 1000 26 0006
2 0200 27 0002
3 0005 28 0015 (Stall (t))
4 1111 29 0010 (Ist (t))
5 0005 30 1111
6 3333 31 05.00 (I2 (t))

TESTED BY WITNESSED BY
SHEET : 3 OF: 10
TEST REPORT FOR MOTOR PROTECTION RELAY PAGE :

7 OFF 32 00.10 (E/F (t))


8 OFF 33 OFF
9 OFF 34 1111
10 00.99 (Thermal) 35 1111
11 02.40 (Isc) 36 0001 (Thermal (T))
12 03.84 (Stall) 37 0001 (Isc (T))
13 00.84 (I2) 38 0001 (Stall (T))
14 1111 39 0001 (I2 (T))
15 0520 40 0001 (Reverse Ph seq(T))
16 06.0 (Ist (Prolong)) 41 0001 (E/F (T))
17 OFF 42 0001 (Prolong T)
TESTED BY WITNESSED BY
SHEET : 4 OF: 10
TEST REPORT FOR MOTOR PROTECTION RELAY PAGE :

18 1111 43 0001 (Loss of load T)


19 0003 44 OFF
20 0002 45 0010
21 0008 (E/F (mA)) 46 0051
22 0060 (Thermal) 47 0000
23 00.67 48 1111
24 06.00 49 OFF
25 OFF 50 0000

5. Secondary injection test:


TESTED BY WITNESSED BY
SHEET : 5 OF: 10
TEST REPORT FOR MOTOR PROTECTION RELAY PAGE :

5.1 Measurement:

Phase Ref Applied Sec Amps(A) Measured current at relay(A)


R 5 201
Y 5 202
B 5 201

5.2 Thermal:

Ref Set Current (A) Injecting Current(A) K2 Set Time(S) Operating Time(S)

TESTED BY WITNESSED BY
SHEET : 6 OF: 10
TEST REPORT FOR MOTOR PROTECTION RELAY PAGE :

RY 4.9 29.4 6 1.0 2.198


YB 4.9 29.4 6 1.0 2.186

5.3 Short Circuit (Isc):

Ref Set Current (A) Operating Current (A) Set time(S) Operated time(S)
RY 11.76 11.76 Inst 0.071
YB 11.76 11.76 Inst 0.078

5.4 Stall Current (Ist):

TESTED BY WITNESSED BY
SHEET : 7 OF: 10
TEST REPORT FOR MOTOR PROTECTION RELAY PAGE :

Ref Set Current (A) Operating Current (A) Set time(S) Operated time(S)
RYB 17.05 18.81 15.0 16.01

5.5 NPS Fault:

Ref Set Current (A) Operating Current (A) Set time(S) NPS Current (%)
RY 4.2 7.27 5.0 4.972
YB 4.2 7.27 5.0 4.928

5.6 Prolong Start:

TESTED BY WITNESSED BY
SHEET : 8 OF: 10
TEST REPORT FOR MOTOR PROTECTION RELAY PAGE :

Ref Set Current (A) Operating Current (A) Set time(S) Operated time(S)
RYB 29.4 29.4 10 10.18

5.7 Earth Fault:

Operating Current
Ref Set Current (mA) Set time(S) Operated time(S)
(mA)
RE 520 530 0.10 0.108
YE 520 534 0.10 0.148

TESTED BY WITNESSED BY
SHEET : 9 OF: 10
TEST REPORT FOR MOTOR PROTECTION RELAY PAGE :

BE 520 528 0.10 0.156

6. Functional checks : (Whether Operational Checks OK / Not OK / Not Applicable)

1 Wiring checks OK
2 Correct operation of appropriate indication/aux.relay OK
3 Correct operation of alarm contacts OK
4 Correct circuit breaker tripping contacts OK
5 Relay cover properly fixing OK

TESTED BY WITNESSED BY
SHEET : 10 OF: 10
TEST REPORT FOR MOTOR PROTECTION RELAY PAGE :

6 Correct operating reset switch OK

7. Comments : Nil.

8. Remarks : Relay Found Healthy.

TESTED BY WITNESSED BY