The document provides a test report for current transformers used in a 50/75 MVA, 132/33 kV power transformer. It details testing of 8 current transformer cores across 3 phases, including measurement of terminal markings, polarity, accuracy limiting factor, secondary resistance, knee point voltage, and accuracy class in accordance with standard IEC 60044-1. All tests were performed by Salman Sadiq Shuvo of ENERGYPAC ENGINEERING LTD on October 6, 2017.
The document provides a test report for current transformers used in a 50/75 MVA, 132/33 kV power transformer. It details testing of 8 current transformer cores across 3 phases, including measurement of terminal markings, polarity, accuracy limiting factor, secondary resistance, knee point voltage, and accuracy class in accordance with standard IEC 60044-1. All tests were performed by Salman Sadiq Shuvo of ENERGYPAC ENGINEERING LTD on October 6, 2017.
The document provides a test report for current transformers used in a 50/75 MVA, 132/33 kV power transformer. It details testing of 8 current transformer cores across 3 phases, including measurement of terminal markings, polarity, accuracy limiting factor, secondary resistance, knee point voltage, and accuracy class in accordance with standard IEC 60044-1. All tests were performed by Salman Sadiq Shuvo of ENERGYPAC ENGINEERING LTD on October 6, 2017.
Transformer Serial No.:50/75 MVA-16 Current Ratio: Core 1 & 2: 400/5 & 328/5A (HVBCT) Standard: IEC: 60044-1
Phase: R Rated frequency: 50Hz
01.Verification of terminal markings------------------------Found Okay 02.Polarity Test--------------------------------------------Found Okay
03. Accuracy limiting Factor ------------------------------ Found Okay
TEST DATA (Core-1, PROTECTION, CLASS: 5P20)
Ratio: 400/5 A, Connection : Primary P1 – P2, Secondary 1S1 –1S2 Burden & Power Factor Secondary Resistance at ambient 381.6 mΩ Temperature (34°C)
30 VA & 0.8 Lag Knee Point Voltage (Vk) 116.5 V
Accuracy limiting Factor (ALF) 18.72
TEST DATA (Core-2, PROTECTION, CLASS: 5P20)
Ratio: 400/5 A, Connection : Primary P1 – P2, Secondary 2S1 –2S2 Burden & Power Factor Secondary Resistance at ambient 308.6 mΩ Temperature (34°C)
30 VA & 0.8 Lag Knee Point Voltage (Vk) 116.1 V
Accuracy limiting Factor (ALF) 19.19
Date of Test :06.10.2017
Tests Performed by ………………………….. Salman Sadiq Shuvo Senior Engr., Testing& Commissioning, EEL. ENERGYPAC ENGINEERING LTD. TEST REPORT OF BUSHING TYPE CURRENT TRANSFORMER FOR 50/75 MVA, 132/33 kV TRANSFORMER
Client Name: Power Grid Company Bangladesh (PGCB)
Transformer Serial No.:50/75 MVA-16 Current Ratio: Core 1 ,2 & 3: 400/5 , 400/5A & 328/5 (HVBCT) Standard: IEC: 60044-1
Phase: B Rated frequency: 50Hz
01.Verification of terminal markings------------------------Found Okay 02.Polarity Test--------------------------------------------Found Okay
Ratio: 400/5 A, Connection : Primary P1 – P2, Secondary 1S1 –1S2 Burden & Power Factor Secondary Resistance at ambient 281.1 mΩ Temperature (34°C)
30 VA & 0.8 Lag Knee Point Voltage (Vk) 122.3 V
Accuracy limiting Factor (ALF) 20.35
TEST DATA (Core-2, PROTECTION, CLASS: 5P20)
Ratio: 400/5 A, Connection : Primary P1 – P2, Secondary 2S1 –2S2 Burden & Power Factor Secondary Resistance at ambient 439.2 mΩ Temperature (34°C)
30 VA & 0.8 Lag Knee Point Voltage (Vk) 119.1 V
Accuracy limiting Factor (ALF) 18.38
TEST DATA (Core-3, METERING (WTI) , CLASS: 0.5 )
Ratio: 328/5 A, Connection : Primary P1 – P2, Secondary 3S1 –3S2 Burden & Power Factor Secondary Resistance at ambient 229.2 mΩ Temperature (34°C)
30 VA & 0.8 Lag Knee Point Voltage (Vk) 16.49 V
Accuracy limiting Factor (ALF) 4.74
Date of Test :06.10.2017
Tests Performed by ………………………….. Salman Sadiq Shuvo Senior Engr., Testing& Commissioning, EEL. ENERGYPAC ENGINEERING LTD. TEST REPORT OF BUSHING TYPE CURRENT TRANSFORMER FOR 50/75 MVA, 132/33 kV TRANSFORMER Client Name: Power Grid Company Bangladesh (PGCB) Transformer Serial No.:50/75 MVA-16 Current Ratio: Core 1 & 2: 400/5 & 328/5A (HVBCT) Standard: IEC: 60044-1
Phase: Y Rated frequency: 50Hz
01.Verification of terminal markings------------------------Found Okay 02.Polarity Test--------------------------------------------Found Okay 03. Accuracy limiting Factor ------------------------------ Found Okay
TEST DATA (Core-1, PROTECTION, CLASS: 5P20)
Ratio: 400/5 A, Connection : Primary P1 – P2, Secondary 1S1 –1S2 Burden & Power Factor Secondary Resistance at ambient 302.3 mΩ Temperature (34°C)
30 VA & 0.8 Lag Knee Point Voltage (Vk) 116.5 V
Accuracy limiting Factor (ALF) 19.61
TEST DATA (Core-2, PROTECTION, CLASS: 5P20)
Ratio: 400/5 A, Connection : Primary P1 – P2, Secondary 2S1 –2S2 Burden & Power Factor Secondary Resistance at ambient 401 mΩ Temperature (34°C)
30 VA & 0.8 Lag Knee Point Voltage (Vk) 118.6 V
Accuracy limiting Factor (ALF) 18.38
Date of Test :06.10.2017
Tests Performed by ………………………….. Salman Sadiq Shuvo Senior Engr., Testing& Commissioning, EEL. ENERGYPAC ENGINEERING LTD. TEST REPORT OF BUSHING TYPE CURRENT TRANSFORMER FOR 50/75 MVA, 132/33 kV TRANSFORMER Client Name: Power Grid Company Bangladesh (PGCB) Transformer Serial No.:50/75 MVA-16 Current Ratio: Core 1,2 & 3,4 : 1600/2.89, 1600/5 A & 1312/5 (LVBCT) Standard: IEC: 60044-1
Phase: R Rated frequency: 50Hz
01.Verification of terminal markings------------------------Found Okay 02.Polarity Test--------------------------------------------Found Okay 03. Accuracy limiting Factor ------------------------------ Found Okay
TEST DATA (Core-1, PROTECTION, CLASS: 5P20)
Ratio: 1600/2.89 A, Connection : Primary P1 – P2, Secondary 1S1 –1S2 Burden & Power Factor Secondary Resistance at ambient 900 mΩ Temperature (34°C)
30 VA & 0.8 Lag Knee Point Voltage (Vk) 232.8 V
Accuracy limiting Factor (ALF) 24.51
TEST DATA (Core-2, PROTECTION, CLASS: 5P20)
Ratio: 1600/5 A, Connection : Primary P1 – P2, Secondary 2S1 –2S2 Burden & Power Factor Secondary Resistance at ambient 588.6 mΩ Temperature (34°C)
30 VA & 0.8 Lag Knee Point Voltage (Vk) 134.1 V
Accuracy limiting Factor (ALF) 19.92
Date of Test :06.10.2017
Tests Performed by ………………………….. Salman Sadiq Shuvo Senior Engr., Testing& Commissioning, EEL. ENERGYPAC ENGINEERING LTD. TEST REPORT OF BUSHING TYPE CURRENT TRANSFORMER FOR 50/75 MVA, 132/33 kV TRANSFORMER Client Name: Power Grid Company Bangladesh (PGCB) Transformer Serial No.:50/75 MVA-16 Current Ratio: Core 1,2 : 1600/2.89, 1600/5 A Standard: IEC: 60044-1
Phase: Y Rated frequency: 50Hz
01.Verification of terminal markings------------------------Found Okay 02.Polarity Test--------------------------------------------Found Okay 03. Accuracy limiting Factor ------------------------------ Found Okay
TEST DATA (Core-1, PROTECTION, CLASS: 5P20)
Ratio: 1600/2.89 A, Connection : Primary P1 – P2, Secondary 1S1 –1S2 Burden & Power Factor Secondary Resistance at ambient 996.6 mΩ Temperature (34°C)
30 VA & 0.8 Lag Knee Point Voltage (Vk) 239.2 V
Accuracy limiting Factor (ALF) 24.62
TEST DATA (Core-2, PROTECTION, CLASS: 5P20)
Ratio: 1600/5 A, Connection : Primary P1 – P2, Secondary 2S1 –2S2 Burden & Power Factor Secondary Resistance at ambient 587.3 mΩ Temperature (34°C)
30 VA & 0.8 Lag Knee Point Voltage (Vk) 132.6 V
Accuracy limiting Factor (ALF) 19.90
Date of Test :06.10.2017
Tests Performed by ………………………….. Salman Sadiq Shuvo Senior Engr., Testing& Commissioning, EEL. ENERGYPAC ENGINEERING LTD. TEST REPORT OF BUSHING TYPE CURRENT TRANSFORMER FOR 50/75 MVA, 132/33 kV TRANSFORMER Client Name: Power Grid Company Bangladesh (PGCB) Transformer Serial No.:50/75 MVA-16 Current Ratio: Core 1,2,3 & 4:1600/2.89,1600/5,1312/5 & 1312/5 A (LVBCT) Standard: IEC: 60044-1
Phase: B Rated frequency: 50Hz
01.Verification of terminal markings------------------------Found Okay 02.Polarity Test--------------------------------------------Found Okay 03. Accuracy limiting Factor ------------------------------ Found Okay
TEST DATA (Core-1, PROTECTION, CLASS: 5P20)
Ratio: 1600/2.89 A, Connection : Primary P1 – P2, Secondary 1S1 –1S2 Burden & Power Factor Secondary Resistance at ambient 961 mΩ Temperature (34°C)
30 VA & 0.8 Lag Knee Point Voltage (Vk) 234.1 V
Accuracy limiting Factor (ALF) 24.78
TEST DATA (Core-2, PROTECTION, CLASS: 5P20)
Ratio: 1600/5 A, Connection : Primary P1 – P2, Secondary 2S1 –2S2 Burden & Power Factor Secondary Resistance at ambient 611.1 mΩ Temperature (34°C)
30 VA & 0.8 Lag Knee Point Voltage (Vk) 136.8 V
Accuracy limiting Factor (ALF) 19.97
TEST DATA (Core-4, METERING (WTI) , CLASS: 0.5 )
Ratio: 1312/5 A, Connection : Primary P1 – P2, Secondary 4S1 –4S2 Burden & Power Factor Secondary Resistance at ambient 440 mΩ Temperature (34°C) Knee Point Voltage (Vk) 60.93 V 30 VA & 0.8 Lag Accuracy limiting Factor (ALF) 14.97
Date of Test :06.10.2017
Tests Performed by ………………………….. Salman Sadiq Shuvo Senior Engr., Testing& Commissioning, EEL. ENERGYPAC ENGINEERING LTD. TEST REPORT OF BUSHING TYPE CURRENT TRANSFORMER FOR 50/75 MVA, 132/33 kV TRANSFORMER
Client Name: Power Grid Company Bangladesh (PGCB)
Transformer Serial No.:50/75 MVA-16 Current Ratio: Core 1 & 2: 1600/5 & 1600/5 A (LVBCT) Standard: IEC: 60044-1
Phase: N Rated frequency: 50Hz
01.Verification of terminal markings------------------------Found Okay
03. Accuracy limiting Factor ------------------------------ Found Okay
TEST DATA (Core-1, PROTECTION, CLASS: 5P20)
Ratio: 1600/5 A, Connection : Primary P1 – P2, Secondary 1S1 –1S2 Burden & Power Factor Secondary Resistance at ambient 662 mΩ Temperature (34°C)
30 VA & 0.8 Lag Knee Point Voltage (Vk) 124.1 V
Accuracy limiting Factor (ALF) 17.43
TEST DATA (Core-2, PROTECTION, CLASS: 5P20)
Ratio: 1600/5 A, Connection : Primary P1 – P2, Secondary 2S1 –2S2 Burden & Power Factor Secondary Resistance at ambient 593.9 mΩ Temperature (34°C) Knee Point Voltage (Vk) 122.3 V 30 VA & 0.8 Lag Accuracy limiting Factor (ALF) 17.96
Date of Test :06.10.2017
Tests Performed by ………………………….. Salman Sadiq Shuvo Senior Engr., Testing& Commissioning, EEL.