ENERGYPAC ENGINEERING LTD.

TEST REPORT OF BUSHING TYPE CURRENT TRANSFORMER


FOR 50/75 MVA, 132/33 kV TRANSFORMER

Client Name: Power Grid Company Bangladesh (PGCB)


Transformer Serial No.:50/75 MVA-16
Current Ratio: Core 1 & 2: 400/5 & 328/5A (HVBCT)
Standard: IEC: 60044-1

Phase: R Rated frequency: 50Hz


01.Verification of terminal markings------------------------Found Okay
02.Polarity Test--------------------------------------------Found Okay

03. Accuracy limiting Factor ------------------------------ Found Okay

TEST DATA (Core-1, PROTECTION, CLASS: 5P20)


Ratio: 400/5 A, Connection : Primary P1 – P2, Secondary 1S1 –1S2
Burden & Power
Factor Secondary Resistance at ambient 381.6 mΩ
Temperature (34°C)

30 VA & 0.8 Lag Knee Point Voltage (Vk) 116.5 V


Accuracy limiting Factor (ALF) 18.72

TEST DATA (Core-2, PROTECTION, CLASS: 5P20)


Ratio: 400/5 A, Connection : Primary P1 – P2, Secondary 2S1 –2S2
Burden & Power
Factor Secondary Resistance at ambient 308.6 mΩ
Temperature (34°C)

30 VA & 0.8 Lag Knee Point Voltage (Vk) 116.1 V


Accuracy limiting Factor (ALF) 19.19

Date of Test :06.10.2017


Tests Performed by
…………………………..
Salman Sadiq Shuvo
Senior Engr., Testing& Commissioning, EEL.
ENERGYPAC ENGINEERING LTD.
TEST REPORT OF BUSHING TYPE CURRENT TRANSFORMER
FOR 50/75 MVA, 132/33 kV TRANSFORMER

Client Name: Power Grid Company Bangladesh (PGCB)


Transformer Serial No.:50/75 MVA-16
Current Ratio: Core 1 ,2 & 3: 400/5 , 400/5A & 328/5 (HVBCT)
Standard: IEC: 60044-1

Phase: B Rated frequency: 50Hz


01.Verification of terminal markings------------------------Found Okay
02.Polarity Test--------------------------------------------Found Okay

03. Accuracy limiting Factor -------------------------------Found Okay

TEST DATA (Core-1, PROTECTION, CLASS: 5P20)


Ratio: 400/5 A, Connection : Primary P1 – P2, Secondary 1S1 –1S2
Burden & Power
Factor Secondary Resistance at ambient 281.1 mΩ
Temperature (34°C)

30 VA & 0.8 Lag Knee Point Voltage (Vk) 122.3 V


Accuracy limiting Factor (ALF) 20.35

TEST DATA (Core-2, PROTECTION, CLASS: 5P20)


Ratio: 400/5 A, Connection : Primary P1 – P2, Secondary 2S1 –2S2
Burden & Power
Factor Secondary Resistance at ambient 439.2 mΩ
Temperature (34°C)

30 VA & 0.8 Lag Knee Point Voltage (Vk) 119.1 V


Accuracy limiting Factor (ALF) 18.38

TEST DATA (Core-3, METERING (WTI) , CLASS: 0.5 )


Ratio: 328/5 A, Connection : Primary P1 – P2, Secondary 3S1 –3S2
Burden & Power
Factor Secondary Resistance at ambient 229.2 mΩ
Temperature (34°C)

30 VA & 0.8 Lag Knee Point Voltage (Vk) 16.49 V


Accuracy limiting Factor (ALF) 4.74

Date of Test :06.10.2017


Tests Performed by
…………………………..
Salman Sadiq Shuvo
Senior Engr., Testing& Commissioning, EEL.
ENERGYPAC ENGINEERING LTD.
TEST REPORT OF BUSHING TYPE CURRENT TRANSFORMER
FOR 50/75 MVA, 132/33 kV TRANSFORMER
Client Name: Power Grid Company Bangladesh (PGCB)
Transformer Serial No.:50/75 MVA-16
Current Ratio: Core 1 & 2: 400/5 & 328/5A (HVBCT)
Standard: IEC: 60044-1

Phase: Y Rated frequency: 50Hz


01.Verification of terminal markings------------------------Found Okay
02.Polarity Test--------------------------------------------Found Okay
03. Accuracy limiting Factor ------------------------------ Found Okay

TEST DATA (Core-1, PROTECTION, CLASS: 5P20)


Ratio: 400/5 A, Connection : Primary P1 – P2, Secondary 1S1 –1S2
Burden & Power
Factor Secondary Resistance at ambient 302.3 mΩ
Temperature (34°C)

30 VA & 0.8 Lag Knee Point Voltage (Vk) 116.5 V


Accuracy limiting Factor (ALF) 19.61

TEST DATA (Core-2, PROTECTION, CLASS: 5P20)


Ratio: 400/5 A, Connection : Primary P1 – P2, Secondary 2S1 –2S2
Burden & Power
Factor Secondary Resistance at ambient 401 mΩ
Temperature (34°C)

30 VA & 0.8 Lag Knee Point Voltage (Vk) 118.6 V


Accuracy limiting Factor (ALF) 18.38

Date of Test :06.10.2017


Tests Performed by
…………………………..
Salman Sadiq Shuvo
Senior Engr., Testing& Commissioning, EEL.
ENERGYPAC ENGINEERING LTD.
TEST REPORT OF BUSHING TYPE CURRENT TRANSFORMER
FOR 50/75 MVA, 132/33 kV TRANSFORMER
Client Name: Power Grid Company Bangladesh (PGCB)
Transformer Serial No.:50/75 MVA-16
Current Ratio: Core 1,2 & 3,4 : 1600/2.89, 1600/5 A & 1312/5 (LVBCT)
Standard: IEC: 60044-1

Phase: R Rated frequency: 50Hz


01.Verification of terminal markings------------------------Found Okay
02.Polarity Test--------------------------------------------Found Okay
03. Accuracy limiting Factor ------------------------------ Found Okay

TEST DATA (Core-1, PROTECTION, CLASS: 5P20)


Ratio: 1600/2.89 A, Connection : Primary P1 – P2, Secondary 1S1 –1S2
Burden & Power
Factor Secondary Resistance at ambient 900 mΩ
Temperature (34°C)

30 VA & 0.8 Lag Knee Point Voltage (Vk) 232.8 V


Accuracy limiting Factor (ALF) 24.51

TEST DATA (Core-2, PROTECTION, CLASS: 5P20)


Ratio: 1600/5 A, Connection : Primary P1 – P2, Secondary 2S1 –2S2
Burden & Power
Factor Secondary Resistance at ambient 588.6 mΩ
Temperature (34°C)

30 VA & 0.8 Lag Knee Point Voltage (Vk) 134.1 V


Accuracy limiting Factor (ALF) 19.92

Date of Test :06.10.2017


Tests Performed by
…………………………..
Salman Sadiq Shuvo
Senior Engr., Testing& Commissioning, EEL.
ENERGYPAC ENGINEERING LTD.
TEST REPORT OF BUSHING TYPE CURRENT TRANSFORMER
FOR 50/75 MVA, 132/33 kV TRANSFORMER
Client Name: Power Grid Company Bangladesh (PGCB)
Transformer Serial No.:50/75 MVA-16
Current Ratio: Core 1,2 : 1600/2.89, 1600/5 A
Standard: IEC: 60044-1

Phase: Y Rated frequency: 50Hz


01.Verification of terminal markings------------------------Found Okay
02.Polarity Test--------------------------------------------Found Okay
03. Accuracy limiting Factor ------------------------------ Found Okay

TEST DATA (Core-1, PROTECTION, CLASS: 5P20)


Ratio: 1600/2.89 A, Connection : Primary P1 – P2, Secondary 1S1 –1S2
Burden & Power
Factor Secondary Resistance at ambient 996.6 mΩ
Temperature (34°C)

30 VA & 0.8 Lag Knee Point Voltage (Vk) 239.2 V


Accuracy limiting Factor (ALF) 24.62

TEST DATA (Core-2, PROTECTION, CLASS: 5P20)


Ratio: 1600/5 A, Connection : Primary P1 – P2, Secondary 2S1 –2S2
Burden & Power
Factor Secondary Resistance at ambient 587.3 mΩ
Temperature (34°C)

30 VA & 0.8 Lag Knee Point Voltage (Vk) 132.6 V


Accuracy limiting Factor (ALF) 19.90

Date of Test :06.10.2017


Tests Performed by
…………………………..
Salman Sadiq Shuvo
Senior Engr., Testing& Commissioning, EEL.
ENERGYPAC ENGINEERING LTD.
TEST REPORT OF BUSHING TYPE CURRENT TRANSFORMER
FOR 50/75 MVA, 132/33 kV TRANSFORMER
Client Name: Power Grid Company Bangladesh (PGCB)
Transformer Serial No.:50/75 MVA-16
Current Ratio: Core 1,2,3 & 4:1600/2.89,1600/5,1312/5 & 1312/5 A
(LVBCT)
Standard: IEC: 60044-1

Phase: B Rated frequency: 50Hz


01.Verification of terminal markings------------------------Found Okay
02.Polarity Test--------------------------------------------Found Okay
03. Accuracy limiting Factor ------------------------------ Found Okay

TEST DATA (Core-1, PROTECTION, CLASS: 5P20)


Ratio: 1600/2.89 A, Connection : Primary P1 – P2, Secondary 1S1 –1S2
Burden & Power
Factor Secondary Resistance at ambient 961 mΩ
Temperature (34°C)

30 VA & 0.8 Lag Knee Point Voltage (Vk) 234.1 V


Accuracy limiting Factor (ALF) 24.78

TEST DATA (Core-2, PROTECTION, CLASS: 5P20)


Ratio: 1600/5 A, Connection : Primary P1 – P2, Secondary 2S1 –2S2
Burden & Power
Factor Secondary Resistance at ambient 611.1 mΩ
Temperature (34°C)

30 VA & 0.8 Lag Knee Point Voltage (Vk) 136.8 V


Accuracy limiting Factor (ALF) 19.97

TEST DATA (Core-4, METERING (WTI) , CLASS: 0.5 )


Ratio: 1312/5 A, Connection : Primary P1 – P2, Secondary 4S1 –4S2
Burden & Power
Factor Secondary Resistance at ambient 440 mΩ
Temperature (34°C)
Knee Point Voltage (Vk) 60.93 V
30 VA & 0.8 Lag
Accuracy limiting Factor (ALF) 14.97

Date of Test :06.10.2017


Tests Performed by
…………………………..
Salman Sadiq Shuvo
Senior Engr., Testing& Commissioning, EEL.
ENERGYPAC ENGINEERING LTD.
TEST REPORT OF BUSHING TYPE CURRENT TRANSFORMER
FOR 50/75 MVA, 132/33 kV TRANSFORMER

Client Name: Power Grid Company Bangladesh (PGCB)


Transformer Serial No.:50/75 MVA-16
Current Ratio: Core 1 & 2: 1600/5 & 1600/5 A (LVBCT)
Standard: IEC: 60044-1

Phase: N Rated frequency: 50Hz


01.Verification of terminal markings------------------------Found Okay

02.Polarity Test--------------------------------------------Found Okay


03. Accuracy limiting Factor ------------------------------ Found Okay

TEST DATA (Core-1, PROTECTION, CLASS: 5P20)


Ratio: 1600/5 A, Connection : Primary P1 – P2, Secondary 1S1 –1S2
Burden & Power
Factor Secondary Resistance at ambient 662 mΩ
Temperature (34°C)

30 VA & 0.8 Lag Knee Point Voltage (Vk) 124.1 V


Accuracy limiting Factor (ALF) 17.43

TEST DATA (Core-2, PROTECTION, CLASS: 5P20)


Ratio: 1600/5 A, Connection : Primary P1 – P2, Secondary 2S1 –2S2
Burden & Power
Factor Secondary Resistance at ambient 593.9 mΩ
Temperature (34°C)
Knee Point Voltage (Vk) 122.3 V
30 VA & 0.8 Lag
Accuracy limiting Factor (ALF) 17.96

Date of Test :06.10.2017


Tests Performed by
…………………………..
Salman Sadiq Shuvo
Senior Engr., Testing& Commissioning, EEL.