DP-SG projects approved signal list - Smart Remote Monitoring (SRM) Project 2000 SS

Zone: xxxxx
Substations: xxxxx Substation To Control Centers -Signal List for Typical one transformer substations
Station: xxxxx
KV Level Bayname B3 Text Element Name Alarm text for DCC (Element Signal Description Info Sig
SI. No Project Scope
(B2) (B3 Name) (LBS Toward) (SND use only) Text) Type

1 xxxxx LBS Load Break Switch Load Break Switch Status Status DPI Spare (reserved for DA upgrade)

2 11 LBS1 xxxxx LBS Load Break Switch Load Break Switch Command Control DC Spare (reserved for DA upgrade)

3 xxxxx Iso ETH Earth Switch Status LBS1 ETH STATUS Status DPI Spare (reserved for DA upgrade)

4 xxxxx EFIBTLW EFI Battery Low EFI Low Battery Alarm AIStat SPI Required
11 EFI
5 xxxxx EFIOPTD EFI Operated EFI Operated Status SPI Required

6 xxxxx LBS Load Break Switch Load Break Switch Status Status DPI Spare (reserved for DA upgrade)

11 LBS2
7 xxxxx LBS Load Break Switch Load Break Switch Command Control Spare (reserved for DA upgrade)

8 xxxxx Iso ETH Earth Switch Status LBS1 ETH STATUS Status DPI Spare (reserved for DA upgrade)

9 CB Circuit Breaker Transformer Switch Status Status DPI Required

10 Iso ETH Earth Switch Status Trafo LBS Earth Status Status DPI Spare (reserved for DA upgrade)

11 TROVLDTR Overload trip Transformer Tripping Alarm AlStat SPI Required

11 TR1 LD1
12 TRFHITMP High Temperature TRF High Temperature Alarm AlStat SPI Required

13 TRMDI100 Transformer MDI 100% Transformer MDI Trip 100% AlStat SPI Required

14 TRMDI80 Transformer MDI 80% Transformer MDI Alarm 80% AlStat SPI Required

15 DoorOpen Substation Door Open Door Open/Close AIStat SPI Required

16 SuperMod RMU Selector Switch Local/Remote Switch AIStat SPI Spare (reserved for DA upgrade)

17 Test Point Test Point Dummy Control Control DPI Required, Based on RTU availability

18 Test Point Test Point Dummy Status Status DC Required, Based on RTU availability

RTU High Temperature


19 DSHITemp RTU Panel High Temperature AIStat SPI Required
Alarm

Required (Voltage shall be measured


20 DSACFAIL AC Supply Fail RTU AC Supply Fail AIStat SPI from the auxiliary supply or through
voltage sensor provided by the bidder)
COMMON

COMMON

21 DBatCHAl Battery Charger Alarm RTU Battery Charger Alarm AIStat SPI Required

22 RMUGASL Gas Pressure Low RMU Gas Pressure Low AIStat SPI Required

23 RTUMaAL RTU Major Alarm RTU Major Alarm AIStat SPI Required

24 RTUMinAL RTU Minor Alarm RTU Minor Alarm AIStat SPI Required

25 RTU-MCB RTU MCB Trip RTU CTRL MCBTRP AIStat SPI Required

26 RTU-MCB RTU MCB Control RTU MCB CTRL Control DPI Spare (reserved for DA upgrade)

27 EARTTFTA Earth Wire Theft Alarm Earth Theft Alarm AIStat SPI Spare (reserved for DA upgrade)

28 PDCablTR PD for Cable Termination Partial Disch Cable Trmintn AIStat SPI Spare (reserved for DA upgrade)

29 FIREAL Fire Alarm Smoke Detector Indication AIStat SPI Spare (reserved for DA upgrade)

30 I Balanced Current Transformer Load Current MvMoment Analog (MN) Required

31 TEMP Temperature LV Panel Temperature MvMoment Analog (MN) Required


0.4 LVDB LVDB
LV Feeder Fuse
32 LVFSBLWN LV Feeder Fuse Blown/MCCB Trip AIStat SPI Spare (reserved for DA upgrade)
Blown/MCCB Trip
LV Power Fail/Under Volt
33 ACBTRIP ACB Tripped AIStat SPI Spare (reserved for DA upgrade)
Relay
Notes:
- The above signal list is the common signal configuration given for a typical one transformer substation. some signals could be removed/added depends on field signals availability within the specified I/O spares.
- For Substations with two transformers, additional signals for second transformer and LVDB2 shall be included.
- For Substations with three transformers , additional signals for transformer2 , transformer3 , LBS3, LVDB2 and LVDB3 shall be included.
Date 1 of 1 Rev-00