Description Highlights
The ExBin-P-... pressure switch generation from 5...5000 Pa (acc. to ►For all types of gases, mists, vapours and dust for use in zone 1, 2, 21 and 22
type) is a revolution for differential pressure switches in HVAC systems,
►Power supply 24 VAC/DC
in chemical, pharmaceutical, industrial and offshore /onshore plants, for
use in hazardous areas zone 1, 2 (gas) and zone 21, 22 (dust). ►Potential free switching contact output
Highest protection class (ATEX) and IP66 protection, small dimensions, ►Adjustable switching threshold, hysteresis and start-up bypass time
universal functions and technical data guarantee safe operation even ►Adjustable switch activation delay (acc. to type)
under difficult environmental conditions.
►Integrated Ex-e terminal box
All pressure switches are programmable on site without any additional
tools. The switching points are scalable within the maximum ranges. The ►No addional Ex-i module required
integrated display is for parametrisation and an actual value indication ►No intrinsically safe wiring/installation between panel and sensor required
at working mode (can be switched off as needed). ►No intrinsically safe wiring/installation and no space in the panel required
...Bin-P-...-2 sensors are equipped with an additional switching output
►Optional second switching output (acc. to type)
(2-stage), which can be parametrised independently.
...Bin-P-...-OCT and ...-OVA offshore versions are equipped with stain- ►Display with backlight, can be switched off
less steel tubing Ø 6 mm. ►Password locking
►Down to −20 °C ambient temperature applicable
►Compact design and small dimension
►Robust aluminium housing (optional with seawater resistant coating) or in stainless steel
►IP66 protection
►Offshore versions with pressure tube connection for clamping ring Ø 6 mm
ExBin-P_en
V02 – 7-Apr-2017
Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail info-de@schischek.com
www.schischek.com 1/6
ExBin-P... ExBin-P...-2
Special options ...-CT ...-OCT ...-VA ...-OVA E X P L O S I O N P R O O F
www.schischek.com 2/6
ExBin-P... ExBin-P...-2
Special options ...-CT ...-OCT ...-VA ...-OVA E X P L O S I O N P R O O F
At different relay and supply voltages (24 VAC/DC) Push button for
! the cable installation must be considered ! Fig.
level selection
(see “Information for Installation”) ! ...Bin-P-2
(o
N
Password input
(G
h1
h2
PE
- IN
-C
The default / delivery setup is 0000. In this configuration the password input is not
SW
SW
SW
activated. To activate the password protection (menu 15) change the 4 digits into your
AUB
ExBin-P_en
V02 – 7-Apr-2017
Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail info-de@schischek.com
www.schischek.com 3/6
ExBin-P... ExBin-P...-2
Special options ...-CT ...-OCT ...-VA ...-OVA E X P L O S I O N P R O O F
Dimensions [mm ]
Aluminium housing ...Bin-P...-OCT
Ø 4,5
117
138
157,5
166
170
~ 180
213
Ø 4,5 68 Ø 4,5
55
80
107 66
123.3
181.7
182.7
~ 194
~ 226
21.5
59
102
69 ~ 61
81.3 70
126.3
Menu Function ENTER Indication Select ENTER Next indication Select ENTER Next menu
Menu 1 Preset
Select application
FAN, FILT, PRO
Menu 2 Unit sensor
Select physical unit
Pa, mbar, inH2O
Menu 3 set 1
Select switching point 1
enter setpoint
Menu 4 set 2 (optional) *
Select switching point 2
enter setpoint
Menu 5 hysteresis **
Select hysteresis
enter hysteresis
Menu 6 mode **
Select switching properties
(break contact, make contact) Up, Down, Mid * nc, no
Menu 7 no function – menu skip
www.schischek.com 4/6
ExBin-P... ExBin-P...-2
Special options ...-CT ...-OCT ...-VA ...-OVA E X P L O S I O N P R O O F
Continue Parametrisation
Menu Function ENTER Indication Select ENTER Next indication Select ENTER Next menu
Menu 8 no function – menu skip
Menu 12 time
Select bypass (AUB) time
enter seconds for AUB
Menu 13 display setting
Select display
on, off
Menu 14 Zero point compensation
Sensor’s calibration for
its installation position
Menu 15 security
Select password protection
enter password
Menu 16 save
Select: save data, discard, (operation mode after “save”)
back to menu, factory setting Yes, no, menu, dset (default setting)
∆p ∆p
− + + −
setpoint 1 setpoint 2 setpoint 1 setpoint 2
normal normal
state state
green green
output output
switch 1 red switch 1 red
Hysteresis Hysteresis
Hysteresis normal normal Hysteresis
state state
green green
output output
switch 2 switch 2
(optional) red (optional) red
ExBin-P_en
V02 – 7-Apr-2017
Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail info-de@schischek.com
www.schischek.com 5/6
ExBin-P... ExBin-P...-2
Special options ...-CT ...-OCT ...-VA ...-OVA E X P L O S I O N P R O O F
„UP range“ – „Normally Closed“ (nc) „UP range“ – „Normally Open“ (no)
Normal range above setpoint – switch is closed Normal range above setpoint – switch is open
The switch opens The switch closes
when the set value when the set value
is underrun. is underrun.
output output
switch 1 red switch 1 red
Hysteresis Hysteresis
Hysteresis normal Hysteresis normal
state state
green green
output output
switch 2 switch 2
(optional) red (optional) red
„Down range“ – „Normally Closed“ (nc) „Down range“ – „Normally Open“ (no)
Normal range below setpoint – switch is closed Normal range below setpoint – switch is open
The switch opens The switch closes
when the set value when the set value
is underrun. is underrun.
output output
switch 1 red switch 1 red
Hysteresis Hysteresis
normal Hysteresis normal Hysteresis
state state
green green
output output
switch 2 switch 2
(optional) red (optional) red
„Mid range“ – „Normally Closed“ (nc) „Mid range“ – „Normally Open“ (no)
Normal range between setpoints – switch is closed Normal range between setpoints – switch is open
output output
switch 1 red switch 1 red
Hysteresis Hysteresis
normal Hysteresis normal Hysteresis
state state
green green
output output
switch 2 red switch 2 red
ExBin-P_en
V02 – 7-Apr-2017
Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail info-de@schischek.com
www.schischek.com 6/6