Sunteți pe pagina 1din 32

ECE 333

Renewable Energy Systems


Lecture 13: Per Unit, Power Flow

Prof. Tom Overbye


Dept. of Electrical and Computer Engineering
University of Illinois at Urbana-Champaign
overbye@illinois.edu
Announcements

• First exam average: 74.1


• Per unit and power flow is only covered in lecture; not
in the book
• No quiz on March 12
• HW 6 is posted on the website and is due on Thursday
March 19. HW 6 must be turned in and will count the
same as a quiz. There will be no quiz on March 19.
• Start Reading Chapter 4 (The Solar Resource)

1
Wind Speed Doubling and Wind
Turbine Generator (WTG) Output
• Just about everyone missed problem 3.d, asking about
what happens to the output of a WTG if the wind speed
doubles; the answer was "It Depends"
– Power in wind goes up by 8, but not usually the power output
Image shows power
output for GE 1.5
and 1.6 MW WTGs;
cut-in speed is 3.5
m/s, while cut-out is
25 m/s

Image: http://site.ge-energy.com/prod_serv/products/wind_turbines/en/downloads/GEA14954C15-MW-Broch.pdf
2
Wind Power and the Power Flow

• The most common power system analysis tool is the


power flow (also known sometimes as the load
flow)
– power flow determines how the power flows in a network
– also used to determine all bus voltages and all currents
– because of constant power models, power flow is a
nonlinear analysis technique
– power flow is a steady-state analysis tool
– it can be used as a tool for planning the location of new
generation, including wind

3
Simplified Power System Modeling

• Balanced three phase systems can be analyzed using


per phase analysis
• A “per unit” normalization is simplify the analysis of
systems with different voltage levels.
• To provide an introduction to power flow analysis we
need models for the different system devices:
– Transformers and Transmission lines, generators and loads
• Transformers and transmission lines are modeled as a
series impedances

4
Load Models

• Ultimate goal is to supply loads with electricity at


constant frequency and voltage
• Electrical characteristics of individual loads matter,
but usually they can only be estimated
– actual loads are constantly changing, consisting of a large
number of individual devices
– only limited network observability of load characteristics
• Aggregate models are typically used for analysis
• Two common models
– constant power: Si = Pi + jQi
– constant impedance: Si = |V|2 / Zi
5
Generator Models

• Engineering models depend upon application


• Generators are usually synchronous machines
• For generators we will use two different models:
– a steady-state model, treating the generator as a constant
power source operating at a fixed voltage; this model will be
used for power flow and economic analysis
– This model works fairly well for type 3 and type 4 wind
turbines
– Other models include treating as constant real power with a
fixed power factor.

6
Per Unit Calculations

• A key problem in analyzing power systems is the


large number of transformers.
– It would be very difficult to continually have to refer
impedances to the different sides of the transformers
• This problem is avoided by a normalization of all
variables.
• This normalization is known as per unit analysis.
actual quantity
quantity in per unit 
base value of quantity

7
Per Unit Conversion Procedure, 1f

1. Pick a 1f VA base for the entire system, SB


2. Pick a voltage base for each different voltage level,
VB. Voltage bases are related by transformer turns
ratios. Voltages are line to neutral.
3. Calculate the impedance base, ZB= (VB)2/SB
4. Calculate the current base, IB = VB/ZB
5. Convert actual values to per unit
Note, per unit conversion on affects magnitudes, not
the angles. Also, per unit quantities no longer have
units (i.e., a voltage is 1.0 p.u., not 1 p.u. volts)
8
Per Unit Solution Procedure

1. Convert to per unit (p.u.) (many problems are


already in per unit)
2. Solve
3. Convert back to actual as necessary

9
Per Unit Example

Solve for the current, load voltage and load power


in the circuit shown below using per unit analysis
with an SB of 100 MVA, and voltage bases of
8 kV, 80 kV and 16 kV.

Original Circuit
10
Per Unit Example, cont’d

8kV 2
Z BLeft   0.64
100 MVA
80kV 2
Middle
ZB   64
100MVA
2
16kV
Z BRight   2.56
100 MVA

Same circuit, with


values expressed
in per unit.
11
Per Unit Example, cont’d

1.00
I   0.22  30.8 p.u. (not amps)
3.91  j 2.327
VL  1.00  0.22  30.8  
    p.u.
2
VL
SL  
VL I L*  0.189 p.u.
Z
SG  1.00  0.2230.8  30.8p.u.
12
Per Unit Example, cont’d

To convert back to actual values just multiply the


per unit values by their per unit base

VL Actual
 0.859  30.8 16 kV  13.7  30.8 kV
S LActual  0.1890 100 MVA  18.90 MVA
SGActual  0.2230.8 100 MVA  22.030.8 MVA
100 MVA
I Middle
B   1250 Amps
80 kV
Middle  0.22  30.8 Amps  275  30.8
I Actual
13
Three Phase Per Unit

Procedure is very similar to 1f except we use a 3f


VA base, and use line to line voltage bases
1. Pick a 3f VA base for the entire system, S B3f
2. Pick a voltage base for each different voltage
level, VB. Voltages are line to line.
3. Calculate the impedance base
VB2, LL ( 3 VB , LN ) 2 VB2, LN
ZB   
S B3f 3S 1Bf S 1Bf
Exactly the same impedance bases as with single phase!
14
Three Phase Per Unit, cont'd

4. Calculate the current base, IB

3f S B3f 3 S 1Bf S 1Bf 1f


IB     IB
3 VB , LL 3 3 VB , LN VB , LN

Exactly the same current bases as with single phase!


5. Convert actual values to per unit

15
Three Phase Per Unit Example

Solve for the current, load voltage and load power


in the previous circuit, assuming a 3f power base of
300 MVA, and line to line voltage bases of 13.8 kV,
138 kV and 27.6 kV (square root of 3 larger than the 1f
example voltages). Also assume the generator is Y-
connected so its line to line voltage is 13.8 kV.
Convert to per unit
as before. Note the
system is exactly the
same!
16
3f Per Unit Example, cont'd

1.00
I   0.22  30.8 p.u. (not amps)
3.91  j 2.327
VL  1.00  0.22  30.8  
    p.u.
2
VL
SL   *
VL I L  0.189 p.u.
Z
SG  1.00  0.2230.8  30.8p.u.

Again, analysis is exactly the same!

17
3f Per Unit Example, cont'd
Differences appear when we convert back to actual values
V LActual  0.859  30.8 27.6 kV  23.8  30.8 kV
S LActual  0.1890 300 MVA  56.70 MVA
SGActual  0.2230.8 300 MVA  66.030.8 MVA
300 MVA
Middle
IB   1250 Amps (same current!)
3 138 kV
Middle  0.22  30.8  Amps  275  30.8
I Actual

18
3f Per Unit Example 2
•Assume a 3f load of 100+j50 MVA with VLL of 69
kV is connected to a source through the below
network:

What is the supply current and complex power?


Answer: I=467 amps, S = 103.3 + j76.0 MVA
19
Power Flow Analysis

• We now have the necessary models to start to


develop the power system analysis tools
• The most common power system analysis tool is the
power flow (also known sometimes as the load flow)
– power flow determines how the power flows in a network
– also used to determine all bus voltages and all currents
– because of constant power models, power flow is a
nonlinear analysis technique
– power flow is a steady-state analysis tool

20
Linear Power System Elements
Resistors, inductors, capacitors, independent
voltage sources and current sources are linear
circuit elements
1
V = R I V = j L I V = I
j C
Such systems may be analyzed by superposition

21
Nonlinear Power System Elements

•Constant power loads and generator injections are


nonlinear and hence systems with these elements can
not be analyzed by superposition

Nonlinear problems can be very difficult to solve,


and usually require an iterative approach
22
Nonlinear Systems May Have
Multiple Solutions or No Solution
•Example 1: x2 - 2 = 0 has solutions x = 1.414…
•Example 2: x2 + 2 = 0 has no real solution
f(x) = x2 - 2 f(x) = x2 + 2

two solutions where f(x) = 0 no solution f(x) = 0


23
Multiple Solution Example 3

• The dc system shown below has two solutions:

where the 18 watt


load is a resistive
load
The equation we're solving is
2 What is the
 9 volts 
I RLoad  
2
 RLoad  18 watts maximum
 1 +R Load  PLoad?
One solution is R Load  2
Other solution is R Load  0.5
24
Adding New Generation

• Adding (siting) large amounts of new generation, such as


for a wind farm, often require changes to the transmission
system
– Developers try to site where existing capacity is available
• Getting new right-of-ways for transmission lines can be
quite difficult (i.e., not in my backyard [NIMBY]) even
when the transmission is associated with "green" energy
• High voltage (e.g., 345 kV) overhead transmission lines
can cost $2 million per mile, whereas burying the
conductors can increase costs by a factor of 10
– AC lines cannot be buried for long distances because of the
high capacitance associated with underground lines 25
Adding New Generation and
Transmission
• Power flow studies are done to determine how much
new transmission is required, and which would be the
best right-of-ways
– Often there is no single best answer
• Example: Ameren Illinois Rivers Project

Project Website: http://www.ilriverstransmission.com/maps


26
Ameren Illinois Rivers Project:
Sidney to Rising 345 kV Line
• One portion of project is adding a new 28 mile 345 kV
transmission line in Champaign County
– Estimated in-service Nov 2016, cost $66 million

27
Bus Admittance Matrix or Ybus

• First step in solving the power flow is to create what is


known as the bus admittance matrix, often call the Ybus.
• The Ybus gives the relationships between all the bus
current injections, I, and all the bus voltages, V,
I = Ybus V
• The Ybus is developed by applying KCL at each bus in
the system to relate the bus current injections, the bus
voltages, and the branch impedances and admittances

28
Ybus Example

Determine the bus admittance matrix for the network


shown below, assuming the current injection at each
bus i is Ii = IGi - IDi where IGi is the current injection into
the bus from the generator and IDi is the current flowing
into the load

29
Ybus Example, cont’d
By KCL at bus 1 we have
I1 IG1  I D1
V1  V2 V1  V3
I1  I12  I13  
ZA ZB
1
I1  (V1  V2 )YA  (V1  V3 )YB (with Yj  )
Zj
 (YA  YB )V1  YA V2  YB V3
Similarly
I 2  I 21  I 23  I 24
 YA V1  (YA  YC  YD )V2  YC V3  YD V4 30
Ybus Example, cont’d
We can get similar relationships for buses 3 and 4
The results can then be expressed in matrix form
I  Ybus V
 I1  YA  YB YA YB 0  V1 
 I   Y YA  YC  YD YC YD  V2 
  
2 A  
 I 3   YB YC YB  YC 0  V3 
I   0 YD YD  V4 
 4  0

For a system with n buses, Ybus is an n by n


symmetric matrix (i.e., one where Aij = Aji)
31

S-ar putea să vă placă și