Sunteți pe pagina 1din 6

IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, VOL. 47, NO.

5, OCTOBER 1998 1265

A Novel Transmission-Line
Voltage Measuring Method
David W. P. Thomas, Member, IEEE, Richard Eric Batty, Christos Christopoulos, Member, IEEE, and Anding Wang

Abstract— A novel transmission-line monitoring method for


estimating the transient voltage from the transient current alone
is presented. This is based on the properties of traveling waves
instigated on high-voltage transmission lines as a result of a fault,
switching operation, or a lightning strike. The method is unique
in that superimposed voltage transients can be deduced without
employing measurements taken from voltage transducers. It is
demonstrated that full advantage can be made of the broad
bandwidth of the current transducers to improve fault location
and enable high-speed traveling wave protection to be applied on
power systems. Fig. 1. Incident and reflected voltage waves at a load.
Index Terms— Impedance measurement, power systems,
transmission-line protection, traveling waves. be predefined, however, as this depends on the local loads
and connected transmission lines which will be constantly
I. INTRODUCTION changing on an active power system. A technique is therefore
required for initially estimating the busbar impedance so that

M OST protection, measurement, and control schemes


employ two transducers on each phase to measure
voltage and current. The voltage transducers are usually the ca-
(1) can be used.
The method proposed is based on the properties of traveling
waves on transmission lines. The traveling wave voltage
pacitor voltage transformer type, which is essentially a circuit amplitude on a transmission line is related to the traveling
tuned to the power frequency with a very poor bandwidth. The wave current amplitude and the line surge impedance only.
application of modern techniques for power system protection
For a single phase line the traveling wave voltage is given
and control have been limited by the poor bandwidth available by [1]
from the voltage transformers. The benefits of this scheme
are that it will provide a backup for the conventional voltage (2)
transducers and also improve the bandwidth of the measured
where is the line surge impedance, is the traveling wave
transient voltages enabling high-speed traveling wave-type
current, and the sign depends on the direction of propagation
protection to be employed on power systems. The principle is,
of the transient with respect to the direction of positive current.
however, general enough to find application in other areas of
In general, however, the transmission-line voltages and
electrical engineering which involve significant transmission-
currents will be the result of many propagating waves and
line propagation such as microwave engineering.
so the total superimposed voltage will not be as given by (2).
For a traveling wave incident at a busbar, as shown in Fig. 1,
II. PRINCIPLE OF THE METHOD the resulting total voltage at the busbar will be the sum of
If the busbar impedance to ground and the current the incident and reflected wave voltage amplitudes and ,
to ground at the busbar are known, then the voltage at the respectively, which gives
busbar will be given by
(1) (3)
In principle then, it is possible to estimate the busbar voltage The transmission line current at the busbar will be the sum
from the measured busbar current to ground and the known of the incident and reflected currents and , respectively,
busbar impedance. The busbar impedance to ground cannot giving
Manuscript received May 18, 1998; revised November 30, 1998. This work
was supported in part by the U.K. Engineering and Physical Sciences Research
(4)
Council.
D. W. P. Thomas, R. E. Batty, and C. Christopoulos are with the Electrical Thus, in general the ratio on a transmission line is not
and Electronic Engineering Department, The University of Nottingham, equal to the line surge impedance. However, if we consider a
Nottingham NG7 2RD, U.K. general busbar with many connected transmission lines, then if
A. Wang is with the Department of Electrical Engineering, Xian Jiatong
Universiy, Xian, Shaanxi, 710049 China. a transient is instigated on line 1 (possibly due to a fault), the
Publisher Item Identifier S 0018-9456(98)09802-7. initial transient traveling waves at the busbar will be as shown
0018–9456/98$10.00  1998 IEEE

Authorized licensed use limited to: UNIVERSIDAD TUCUMAN. Downloaded on June 09,2010 at 12:42:00 UTC from IEEE Xplore. Restrictions apply.
1266 IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, VOL. 47, NO. 5, OCTOBER 1998

modal current are given by

(6)
(7)

where and are the matrix vectors of the phase


voltages, respectively, and and are the modal voltage
Fig. 2. The direction of propagation of the incident, reflected, and transmit- and current transformation matrices, respectively. For a three-
ted voltage waves at a busbar due to a fault on line 1. phase system and are 3 3 matrices giving three
modes of propagation, two aerial modes propagating at close
in Fig. 2. Fig. 2 shows that initially there will be two transient to the velocity of light, and one ground or common mode
traveling waves on line 1, due to the incident and reflected which usually propagates at a much reduced velocity [1].
waves, and only one transient traveling wave on all the other With suitable choice of and it can then be shown [1]
lines due to transmission of the transient onto these lines. that the modal voltages and currents propagate as independent
The transient voltage (an incremental voltage superimposed modes and they have the relationship
on the power system voltage) can then be estimated from (2)
(8)
using the line currents on all the transmission lines except
the one where the transient originated. Provided there are where the sign depends on the direction of propagation of
at least three connecting transmission lines, the correct line the transients with respect to the defined positive current and
voltage can then be identified. This in itself could be used is the modal surge impedance matrix which is a diagonal
as a directional protection scheme as the faulted line can be matrix.
immediately identified as the line current on the faulted line Then each modal current must also satisfy Kirchoff’s current
which will be different from that on the healthy lines, and this law given by (5) which gives
protection principle is described in publication [2].
Clearly, after a short time all the transmission lines will (9)
contain more than one transient traveling wave, due to reflec-
tions from remote terminations. Nevertheless, there is a short
window in which the busbar voltage and current to ground For a three-phase power transmission system it is the modal
is known and the busbar transient impedance can be found. voltages which are estimated for each line at the busbar using
With this estimated impedance it should be possible to derive (8), and then the busbar modal impedance is estimated using
the busbar voltage from (1) for a period (typically one power the busbar current found from (9).
cycle) that will enable protection and control equipment based On power systems it is common to make the approximation
on superimposed quantities to be employed. that the three phases are fully balanced and the transmission
The total busbar current to ground (due to loads or sources) lines are fully transposed so that all mutual inductances and
can either be measured directly using a current transformer capacitances are the same. For this case the voltage and current
(CT) or it can be found from the transmission line currents transformation matrices are identical , and in this
and applying Kirchhoff’s current law work we have used

(5) (10)

The proposed scheme is then as follows.


1) First estimate the busbar voltage and current to ground III. LOAD PARAMETER ESTIMATION
using (2) and (5). Over the short duration considered in this study it is believed
2) From the estimated voltage and current, estimate the that the modal impedance of a load can be characterized to
busbar impedance to ground. a reasonable approximation by a resistance and inductance
3) Once the busbar impedance is established, continue to in series. The estimation of the modal resistance and
obtain estimates of the busbar voltage using (1). inductance can take several forms and each was investigated
If there is not a significant local load at the busbar, then for accuracy, speed, and computational efficiency. The basic
a remote load on a healthy short transmission line may be equation is
used provided there is another longer healthy line from which
the busbar voltage can be found. This will be described more (11)
fully in a later publication.
On multiconductor transmission lines the traveling-wave where and are the known voltages and currents, respec-
transients propagate as independent modes [1] where each tively.
modal voltage is related to its modal current through the Equation (11) can be solved directly using numerical meth-
modal surge impedance. The transients are first transformed ods for estimating the derivative However, numerical
into modal quantities [1] where the modal voltage and differentiation tends to enhance noise and reduces the accuracy

Authorized licensed use limited to: UNIVERSIDAD TUCUMAN. Downloaded on June 09,2010 at 12:42:00 UTC from IEEE Xplore. Restrictions apply.
THOMAS et al.: TRANSMISSION-LINE VOLTAGE MEASURING 1267

Fig. 3. System simulated of a phase-to-ground fault 50 km from the busbar


on line 4 (all distances in kilometers).

(a)

(a)

(b)
Fig. 5. (a) The resistance estimate and (b) inductance estimate of the local
impedance using the fault transient given in Fig. 4.

original formulation given in (11) this then has the form

(b)
(14)
Fig. 4. (a) Mode 1 and (b) mode 2 incremental voltages compared with the
modal currents on each of the transmission lines at the busbar (I2 = line 2, where
I3 = line 3 and I4 = line 4) multiplied by the line modal surge impedance Z.
(15)
of the estimates. Another form involves numerical integration
and
over a time interval to

(12)
(16)
Numerical integration tends to average out noise, but care
has to be taken to optimize the integration interval so that
only a reasonable data set is used.
The data can also be transformed in to the frequency domain All these methods were investigated over a range of system
so that the following expression is solved for and : conditions and load types. It was found that the integral form
(13) given in (12) gave the most reliable results, requiring about
a millisecond, at a 25 kHz sample rate, of voltage data (25
where and are the Fourier transforms of the samples). This voltage data can be provided by applying (2)
time domain voltage and current transients and , to a healthy line of at least 150 km in length. The differential
respectively, with being the frequency. The advantage form of (11) also gave reasonable results but was a little
of the frequency domain is that numerical integration or too susceptible to noise. The frequency domain method given
differentiation are not required and efficient Fourier transforms in (13) proved the least useful as the transients tend to be
exist in the form of the fast Fourier transform. This method dominated by the power frequency (50 Hz), particularly when
may, however, require an excessively large data set. a fault at voltage zero has occurred. The data required for
The method of least squares can be employed to improve accurate Fourier transforms was then of the order of 20 ms
the estimation accuracy over a certain window length. For the which would not be practical.

Authorized licensed use limited to: UNIVERSIDAD TUCUMAN. Downloaded on June 09,2010 at 12:42:00 UTC from IEEE Xplore. Restrictions apply.
1268 IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, VOL. 47, NO. 5, OCTOBER 1998

the correct voltage. For lines of length 40–50 km this means


that only about 0.3 ms of data is available.

B. Load Parameter Estimates


The estimate of the load impedance has been tried on many
load types and for many variations of the main methods
described in Section III. It has been found that the integral
method as given by (12) and an integral period of 0.8 ms
(20 time steps) give rapid and accurate results, and these are
presented here. Fig. 5 shows the inductance and resistance
Fig. 6. Estimated and actual mode 1 voltage. estimates of a local load using (12) over the initial 2 ms of
the transient event. The integral period used was 0.8 ms and
IV. RESULTS the voltage estimate is reliable for 2 ms for this example, so
that after about 1.2 ms the inductance and resistance estimates
Since the principle aim of the project is to provide a method become unreliable. It follows that a rapid and accurate estimate
for estimating transient voltages on power systems, the work can be made of the local impedance using a data window
was carried out on simulated power system transient data using of 1 ms. The loads are likely to be an impedance attached
the EMTP package [3]. Several ehv power system configura- via a step-down transformer. However, it has been found that
tions were studied and a variety of transient conditions were the transformer load combination can be represented by a
also considered. The example system used is shown in Fig. 3 equivalent series inductance and resistance so that only these
where the busbar studied is attached to three transmission equivalent values need to be estimated to give reliable results.
lines and the local impedance has a short circuit capacity of
35 GVA (inductance 0.0147H, resistance for
C. Voltage Estimate Using the Load Impedance
aerial modes). The three-phase transients were decomposed
into modal transients to simplify the calculations and the Once the load impedance has been estimated, the busbar
ground or common mode was ignored as its propagation voltage is then simply given by (11) by using the measured
velocity and surge impedance is vary variable. A sampling busbar current to ground found from (9). Fig. 6 shows the
rate of 25 kHz was considered as it was felt that this was a actual mode 1 voltage compared with the estimated mode 1
practical value and also meant that the EMTP was simulating voltage. Fig. 7 shows the error between the estimated voltage
transients within its range of validity (less than 100 kHz). mode 1 transients compared with the actual voltage transients
The frequency range considered should also be well below for the example in Fig. 6. Similar results are found for the
the cutoff frequency of linetraps [4]. mode 2 transients. It can be seen that the incremental voltages
The immediate objective was to be able to reproduce the are now reproduced accurately over a period of a full power
transient voltage over about one power cycle to an accuracy cycle which should be sufficient for ultra-high-speed power
of about 5% (this was thought to be equivalent to the normal system protection.
noise in the power system voltage). The utility of the voltage
estimate was demonstrated by incorporating it into a traveling D. Remote Loads
wave protection scheme where it was shown to perform
If there is no local load at the relay busbar then there
extremely well.
will not be a current to ground with which to estimate the
transient voltages. For this situation the nearest remote load
A. Initial Estimation of the Voltage that is connected by a healthy line may be used. A second
longer healthy line has to be used to provide the voltage data
As described in Section II, the initial estimate of the voltage
for the remote impedance estimate. It should then be possible
is made by applying (8) to the superimposed currents sampled
to estimate the voltage and current at the remote load and
on all the connecting transmission lines at the busbar. This
from this the remote load impedance. Once the remote load
approach has been validated on many transmission line con-
impedance is known then the busbar voltage will be given by
figurations. The equation is a straightforward scaling of the
the line current in the transmission line connecting the busbar
modal currents and is therefore limited only by the current
to the remote load and the impedance of the combination of
measurements. Typical results are shown in Fig. 4 which
the remote load and connecting transmission line.
shows the modes 1 and 2 voltage estimates on each of the
transmission lines given in Fig. 3 compared with the actual
busbar voltage. Note that after a period, equal to the round E. Application to a Traveling Wave Protection Scheme
trip propagation time of the transmission line, the estimated To demonstrate the utility of the estimated voltage, this and
voltages deviate from the true busbar voltage (this is at 2.16 ms the measured current were applied to a traveling wave scheme.
for line 2 and 2.83 ms for line 3). Thus the limitation is that The traveling wave scheme chosen was that proposed by
as soon as there is a reflected wave from the remote end of the Crossley and McLaren [5] as it is one of the more demanding
healthy lines then the line current will not be proportional to schemes. It was found that this voltage estimation scheme
the line surge impedance and the estimation will cease to give preforms very well with the traveling wave protection which

Authorized licensed use limited to: UNIVERSIDAD TUCUMAN. Downloaded on June 09,2010 at 12:42:00 UTC from IEEE Xplore. Restrictions apply.
THOMAS et al.: TRANSMISSION-LINE VOLTAGE MEASURING 1269

Fig. 7. The percentage error in the estimated voltage given in Fig. 5.

Fig. 8. The S1 and S2 parameters for the transients given in Fig. 4.


Fig. 9. The cross-correlation function of signal S1 with S2 as shown in
Fig. 8.
then responded correctly to the faults. Results are shown for
the transients given in the previous figures. round-trip transient propagation time between the busbar and
Fig. 8 shows the relaying quantities and which are the fault.
defined as [5] The transients were caused by a fault 50 km from the relay
location on line 4. Fig. 9 shows the deduced cross-correlation
(17)
function as used in the Crossley and McLaren scheme. The
(18) first peak in the cross-correlation at 4 10 s indicates the
location of the fault and this gives a clear indication of a fault
where represents the transients incident at the busbar and
location 59 km from the relay which is within the expected
represents the transients propagating away from the busbar.
error margin (12 km).
An amplitude greater than indicates that there is a
forward fault and is the basis of many traveling wave schemes
[6], [7]. In the Crossley and McLaren scheme a sample of V. CONCLUSIONS
the reflected signal is also cross-correlated with the signal A technique for estimating the voltage transients has been
The peak in the cross-correlation function indicates the developed that can provide about one cycle of transient voltage

Authorized licensed use limited to: UNIVERSIDAD TUCUMAN. Downloaded on June 09,2010 at 12:42:00 UTC from IEEE Xplore. Restrictions apply.
1270 IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, VOL. 47, NO. 5, OCTOBER 1998

with a bandwidth of a few kilohertz using just the information David W. P. Thomas (M’95) was born in Padstow, U.K., on May 5, 1959. He
available from the transient current. The scheme is thought to received the B.Sc. degree in physics from the Imperial College of Science and
Technology, the M.Phil. degree in space physics from Sheffield University,
be ideal for traveling wave relaying schemes which in the past and the Ph.D. degree in electrical engineering from Nottingham University,
have not found wide application due to the poor bandwidth of in 1981, 1987, and 1990, respectively.
capacitor-voltage transformers. Results presented demonstrate In 1990 he joined the Department of Electrical and Electronic Engineering
at the University of Nottingham as a Lecturer. His research interests include
its utility for the traveling wave protection scheme as proposed electromagnetic compatibility, electrostatic precipitation, and the protection
by Crossley and McLaren. and simulation of power networks.
This scheme uses the fact that initially the line transient
current is related to the transient voltage by the line surge
impedance. An estimate of the busbar impedance can then be
found from the initial transients, which is then used to estimate Richard Eric Batty was born in Scunthorp, U.K.,
the transient voltage over a period of about one power cycle. on June 21, 1970. He received the M.Eng. degree
The power system must, however, contain at least two lines of in electrical engineering at the University on New-
castle upon Tyne in 1993.
150-km length. This is not expected to be a severe restriction In 1993 he joined the School of Electrical and
as the scheme is intended for application in traveling wave Electronic Engineering of the University of Notting-
relaying schemes which are applied to the longer lines. ham and spent three years as a Research Assistant
studying novel traveling wave protection schemes.
In 1997 he joined BICC Cables Supertension and
ACKNOWLEDGMENT Subsea Cables Ltd., U.K., where he is now an
Engineer.
The authors wish to thank the University of Nottingham
for the facilities made available during the preparation of this
paper.

REFERENCES Christos Christopoulos (M’94) was born in Patras, Greece, in 1946. He


received a diploma in electrical and mechanical engineering from the National
[1] D. E. Hedmen, “Propagation on overhead transmission lines, Part Technical University of Athens in 1969 and the M.Sc. and D.Phil. degrees
1—Theory of modal analysis,” IEEE Trans. Power Aparatus Syst., vol. from the University of Sussex in 1970 and 1975, respectively.
84, p. 489, 1965. In 1974, he joined the Arc Research Project at the University of Liverpool
[2] E. R. Batty, D. W. P. Thomas, and C. Christopoulos, “A novel unit and spent two years working on vacuum arcs and breakdown while on
protection scheme based on superimposed currents” in Proc. 6th Int. attachment to the UKAEA Culham Laboratories. In 1976 he joined the
Conf. Developments in Power System Protection, no. 434, pp. 83–86. University of Durham as a Senior Demonstrator in Electrical Engineering
[3] W. Scott-Meyer, EMTP Rule Book. Portland, OR: Bonneville Power Science. In 1978 he joined the School of Electrical and Electronic Engineering
Admin. where he is now a Professor of Electrical Engineering. His research interests
[4] R. K. Aggrawal, A. T. Johns, and Z. Q. Bo, “Non-unit protection tech- include electrical discharges and plasmas, electromagnetic compatibility,
nique for EHV transmission systems based on fault-generated noise,” electromagnetics, and the protection and simulation of power networks.
Proc. Inst. Elec. Eng. Gener. Transm. Distrib., vol. 141, no. 2, pp.
133–140, Mar. 1994.
[5] P. A. Crossley and P. G. McLaren, “Distance protection based on
traveling waves,” IEEE Trans. Power Aparatus Syst., vol. PAS-102, pp.
2271–2982, Sept. 1983.
[6] A. T. Johns and E. P. Walker, “Co-operative research into the engineer- Anding Wang was born in China on November 4, 1958. He received the
ing and design of a new digital directional comparison scheme,” Proc. B.Sc., M.Sc., and Ph.D. degrees in electrical engineering from Xi’an Jiaotong
Inst. Elec. Eng., vol. 135, pp. 2971–2982, 1983. University in 1982, 1984, and 1988, respectively.
[7] C. Christopoulos, D. W. P. Thomas, and A. Wright, “Scheme based on He joined Xi’an Jiaotong University as a Teaching Assistant in 1984, where
traveling-waves for the protection of major transmission lines,” Proc. he is now an Associate Professor. His research interests include the protection
Inst. Elec. Eng., vol. 135, pt. C, pp. 63–73, 1988. and simulation of power networks.

Authorized licensed use limited to: UNIVERSIDAD TUCUMAN. Downloaded on June 09,2010 at 12:42:00 UTC from IEEE Xplore. Restrictions apply.

S-ar putea să vă placă și