Purpose Calibration Procedure for Differential Pressure Transmitters (FOUNDATION FieldBus Application)
Safety and Standard PPE is required that includes protection against H2S Gas.
Environmental
Requirements
References ILD, P&ID, Operation/maintenance manual, and instrument datasheet.
2. Ensure all the materials needed for the calibration are within reach (e.g HHC475, meters, pressure
source, pressure gauge, Digital multi-meter, power supply module 24Vdc, etc)
3. Record and put down the following (can easily be sourced from transmitter nameplate or hook-up
the HHC475):
o Transmitter make and model
o Transmitter calibration range
o Transmitter range
o Transmitter MWP(Maximum Working Pressure)
4. Connect all the equipment needed for the calibration exercise in the appropriate manner. To
ensure you don’t make any mistake, you should draw a connection diagram for all equipment
involved paying particular attention to polarity of transmitter and power source! Then connect
them according to the connection diagram shown below:
5. Using the calibrator with its hand pump and tubes connected; exercise the pressure transmitter
sensor by applying 50% of the calibration range for at least 5 mins to check for leaks. Observe
transmitter display and HHC475 for pressure drop, if clear, proceed to next step.
6. Apply the test points in increasing and decreasing manner with minimum interval of five (5)
seconds per test point to obtain the stabilized reading. Apply 0, 25, 50, 75, 100% (increasing and
decreasing) accordingly and check for STD vs. UUT reading correctness. Record readings obtained
as AS FOUND reading. If the transmitter is found still accurate, no need to do adjustments. If
transmitter needs to be adjusted or ZEROED, follow next steps.
A message is displayed: There could be a data mismatch; changes made with 475 may not be
recorded in the HOST system database. Ensure all safety precaution and work procedure has
been followed.
A warning is displayed: Process control could be affected; changing the mode and or block
parameter of this device could adversely affect the control of your process.
Select NEXT
Pressure calibration complete.
The calibration lowest point and pressure value will be displayed.
Select FINISH and click NEXT
A message is displayed: Pressure calibration finish
Select FINISH
Note: Change the BLOCK MODE-TARGET from OOS
Go back to block mode (Configuration menu)
Select block mode –target and change OOS
A warning is displayed: Process control could be affected; changing the mode and or block
parameter of this device could adversely affect the control of your process