Sunteți pe pagina 1din 49

distance.

adt:
. .
Test Object - Device Settings
. . .
Substation/Bay:
Substation: Substation Substation address: Location
Bay: bay Bay address: bay address
. . .
Device:
Name/description: Multilin G60 Manufacturer: GE
Device type: Generator Protection Device address:
Serial/model number: AALC17000517
Additional info 1: information
Additional info 2: information
. . .
Nominal Values:
f nom: 50.00 Hz Number of phases: 3
V nom (secondary): 110.0 V V primary: 11.00 kV
I nom (secondary): 1.000 A I primary: 2.000 kA
. . .
Residual Voltage/Current Factors:
VLN / VN: 1.732 IN / I nom: 1.000
. . .
Limits:
V max: 10.00 kV I max: 50.00 A
. . .
Debounce/Deglitch Filters:
Debounce time: 3.000 ms Deglitch time: 0.000 s
. . .
Overload Detection:
Suppression time: 50.00 ms

Test Object - Custom Settings


.
GE Multilin G60 \ Relay Parameter Section \ Device Definition
Description Name Value
Order Code Order Code
Version Version

.
GE Multilin G60 \ Relay Parameter Section \ System Setup \ AC Inputs \ Current \ CT F1
Description Name Value
Phase CT Primary Phase CT Primary 2000 A
Phase CT Secondary Phase CT Secondary 1A
Ground CT Primary Ground CT Primary 1 A
Ground CT Secondary Ground CT Secondary 1A

.
GE Multilin G60 \ Relay Parameter Section \ System Setup \ AC Inputs \ Current \ CT F5
Description Name Value
Phase CT Primary Phase CT Primary 1 A
Phase CT Secondary Phase CT Secondary 1A
Ground CT Primary Ground CT Primary 1 A
Ground CT Secondary Ground CT Secondary 1A
.
GE Multilin G60 \ Relay Parameter Section \ System Setup \ AC Inputs \ Current \ CT M1
Description Name Value
Phase CT Primary Phase CT Primary 2000 A
Phase CT Secondary Phase CT Secondary 1A
Ground CT Primary Ground CT Primary 500 A
Ground CT Secondary Ground CT Secondary 1A

.
GE Multilin G60 \ Relay Parameter Section \ System Setup \ AC Inputs \ Current \ CT M5
Description Name Value
Phase CT Primary Phase CT Primary 1 A
Phase CT Secondary Phase CT Secondary 1A
Ground CT Primary Ground CT Primary 1 A
Ground CT Secondary Ground CT Secondary 1A

.
GE Multilin G60 \ Relay Parameter Section \ System Setup \ AC Inputs \ Voltage \ VT F5
Description Name Value
Phase VT Connection Phase VT Connection Wye
Phase VT Secondary Phase VT Secondary 63.5 V
Phase VT Ratio Phase VT Ratio 100.00 :1
Auxiliary VT Connection Auxiliary VT Connection Vag
Auxiliary VT Secondary Auxiliary VT Secondary 95.5 V
Auxiliary VT Ratio Auxiliary VT Ratio 110.00 :1

.
GE Multilin G60 \ Relay Parameter Section \ System Setup \ AC Inputs \ Voltage \ VT M5
Description Name Value
Phase VT Connection Phase VT Connection Wye
Phase VT Secondary Phase VT Secondary 95.5 V
Phase VT Ratio Phase VT Ratio 110.00 :1
Auxiliary VT Connection Auxiliary VT Connection Vag
Auxiliary VT Secondary Auxiliary VT Secondary 110.0 V
Auxiliary VT Ratio Auxiliary VT Ratio 57.73 :1

.
GE Multilin G60 \ Relay Parameter Section \ System Setup \ Power System
Description Name Value
Nominal Frequency Nominal Frequency 50 Hz
Phase Rotation Phase Rotation ABC
Reverse Phase Rotation Reverse Phase Rotation OFF
Frequency And Phase Reference Frequency And Phase TERM (SRC 2)
Reference
Frequency Tracking Function Frequency Tracking Function Enabled

.
GE Multilin G60 \ Relay Parameter Section \ System Setup \ Signal Sources \ Source 1
Description Name Value
Name Name NEUT
Phase CT Phase CT M1
Ground CT Ground CT M1
Phase VT Phase VT F5
Auxiliary VT Auxilliary VT None

.
GE Multilin G60 \ Relay Parameter Section \ System Setup \ Signal Sources \ Source 2
Description Name Value
Name Name TERM
Phase CT Phase CT F1
Ground CT Ground CT None
Phase VT Phase VT F5
Auxiliary VT Auxilliary VT M5

.
GE Multilin G60 \ Relay Parameter Section \ System Setup \ Signal Sources \ Source 3
Description Name Value
Name Name SYN G
Phase CT Phase CT None
Ground CT Ground CT None
Phase VT Phase VT M5
Auxiliary VT Auxilliary VT None

.
GE Multilin G60 \ Relay Parameter Section \ System Setup \ Signal Sources \ Source 4
Description Name Value
Name Name SYN B
Phase CT Phase CT None
Ground CT Ground CT None
Phase VT Phase VT None
Auxiliary VT Auxilliary VT F5

.
GE Multilin G60 \ Relay Parameter Section \ System Setup \ Breakers
Description Name Value
Breaker 1 Function Breaker 1 Function Disabled
Breaker 1 Push Button Control Breaker 1 Push Button Control Disabled
Breaker 1 Name Breaker 1 Name Bkr 1
Breaker 1 Mode Breaker 1 Mode 3-Pole
Breaker 1 Open Breaker 1 Open OFF
Breaker 1 Block Open Breaker 1 Block Open OFF
Breaker 1 Close Breaker 1 Close OFF
Breaker 1 Block Close Breaker 1 Block Close OFF
Breaker 1 Phase A/3-Pole Closed Breaker 1 Phase A/3-Pole OFF
Closed
Breaker 1 Phase A/3-Pole Opened Breaker 1 Phase A/3-Pole OFF
Opened
Breaker 1 Phase B Closed Breaker 1 Phase B Closed OFF
Breaker 1 Phase B Opened Breaker 1 Phase B Opened OFF
Breaker 1 Phase C Closed Breaker 1 Phase C Closed OFF
Breaker 1 Phase C Opened Breaker 1 Phase C Opened OFF
Breaker 1 Toperate Breaker 1 Toperate 70 ms
Breaker 1 External Alarm Breaker 1 External Alarm OFF
Breaker 1 Alarm Delay Breaker 1 Alarm Delay 0.000 s
Breaker 1 Manual Close Recal Time Breaker 1 Manual Close Recal 0.000 s
Time
Breaker 1 Out Of Service Breaker 1 Out Of Service OFF
Breaker 1 Events Breaker 1 Events Disabled
Breaker 2 Function Breaker 2 Function Disabled
Breaker 2 Push Button Control Breaker 2 Push Button Control Disabled
Breaker 2 Name Breaker 2 Name Bkr 2
Breaker 2 Mode Breaker 2 Mode 3-Pole
Breaker 2 Open Breaker 2 Open OFF
Breaker 2 Block Open Breaker 2 Block Open OFF
Breaker 2 Close Breaker 2 Close OFF
Breaker 2 Block Close Breaker 2 Block Close OFF
Breaker 2 Phase A/3-Pole Closed Breaker 2 Phase A/3-Pole OFF
Closed
Breaker 2 Phase A/3-Pole Opened Breaker 2 Phase A/3-Pole OFF
Opened
Breaker 2 Phase B Closed Breaker 2 Phase B Closed OFF
Breaker 2 Phase B Opened Breaker 2 Phase B Opened OFF
Breaker 2 Phase C Closed Breaker 2 Phase C Closed OFF
Breaker 2 Phase C Opened Breaker 2 Phase C Opened OFF
Breaker 2 Toperate Breaker 2 Toperate 70 ms
Breaker 2 External Alarm Breaker 2 External Alarm OFF
Breaker 2 Alarm Delay Breaker 2 Alarm Delay 0.000 s
Breaker 2 Manual Close Recal Time Breaker 2 Manual Close Recal 0.000 s
Time
Breaker 2 Out Of Service Breaker 2 Out Of Service OFF
Breaker 2 Events Breaker 2 Events Disabled
Breaker 3 Function Breaker 3 Function Disabled
Breaker 3 Push Button Control Breaker 3 Push Button Control Disabled
Breaker 3 Name Breaker 3 Name Bkr 3
Breaker 3 Mode Breaker 3 Mode 3-Pole
Breaker 3 Open Breaker 3 Open OFF
Breaker 3 Block Open Breaker 3 Block Open OFF
Breaker 3 Close Breaker 3 Close OFF
Breaker 3 Block Close Breaker 3 Block Close OFF
Breaker 3 Phase A/3-Pole Closed Breaker 3 Phase A/3-Pole OFF
Closed
Breaker 3 Phase A/3-Pole Opened Breaker 3 Phase A/3-Pole OFF
Opened
Breaker 3 Phase B Closed Breaker 3 Phase B Closed OFF
Breaker 3 Phase B Opened Breaker 3 Phase B Opened OFF
Breaker 3 Phase C Closed Breaker 3 Phase C Closed OFF
Breaker 3 Phase C Opened Breaker 3 Phase C Opened OFF
Breaker 3 Toperate Breaker 3 Toperate 70 ms
Breaker 3 External Alarm Breaker 3 External Alarm OFF
Breaker 3 Alarm Delay Breaker 3 Alarm Delay 0.000 s
Breaker 3 Manual Close Recal Time Breaker 3 Manual Close Recal 0.000 s
Time
Breaker 3 Out Of Service Breaker 3 Out Of Service OFF
Breaker 3 Events Breaker 3 Events Disabled
Breaker 4 Function Breaker 4 Function Disabled
Breaker 4 Push Button Control Breaker 4 Push Button Control Disabled
Breaker 4 Name Breaker 4 Name Bkr 4
Breaker 4 Mode Breaker 4 Mode 3-Pole
Breaker 4 Open Breaker 4 Open OFF
Breaker 4 Block Open Breaker 4 Block Open OFF
Breaker 4 Close Breaker 4 Close OFF
Breaker 4 Block Close Breaker 4 Block Close OFF
Breaker 4 Phase A/3-Pole Closed Breaker 4 Phase A/3-Pole OFF
Closed
Breaker 4 Phase A/3-Pole Opened Breaker 4 Phase A/3-Pole OFF
Opened
Breaker 4 Phase B Closed Breaker 4 Phase B Closed OFF
Breaker 4 Phase B Opened Breaker 4 Phase B Opened OFF
Breaker 4 Phase C Closed Breaker 4 Phase C Closed OFF
Breaker 4 Phase C Opened Breaker 4 Phase C Opened OFF
Breaker 4 Toperate Breaker 4 Toperate 70 ms
Breaker 4 External Alarm Breaker 4 External Alarm OFF
Breaker 4 Alarm Delay Breaker 4 Alarm Delay 0.000 s
Breaker 4 Manual Close Recal Time Breaker 4 Manual Close Recal 0.000 s
Time
Breaker 4 Out Of Service Breaker 4 Out Of Service OFF
Breaker 4 Events Breaker 4 Events Disabled

.
GE Multilin G60 \ Relay Parameter Section \ System Setup \ Switches
Description Name Value
Switch 1 Function Switch 1 Function Disabled
Switch 1 Name Switch 1 Name SW 1
Switch 1 Mode Switch 1 Mode 3-Pole
Switch 1 Open Switch 1 Open OFF
Switch 1 Block Open Switch 1 Block Open OFF
Switch 1 Close Switch 1 Close OFF
Switch 1 Block Close Switch 1 Block Close OFF
Switch 1 Phase A/3 Pole Closed Switch 1 Phase A/3 Pole OFF
Closed
Switch 1 Phase A/3 Pole Opened Switch 1 Phase A/3 Pole OFF
Opened
Switch 1 Phase B Closed Switch 1 Phase B Closed OFF
Switch 1 Phase B Opened Switch 1 Phase B Opened OFF
Switch 1 Phase C Closed Switch 1 Phase C Closed OFF
Switch 1 Phase C Opened Switch 1 Phase C Opened OFF
Switch 1 Toperate Switch 1 Toperate 70 ms
Switch 1 Alarm Delay Switch 1 Alarm Delay 0.000 s
Switch 1 Events Switch 1 Events Disabled
Switch 2 Function Switch 2 Function Disabled
Switch 2 Name Switch 2 Name SW 2
Switch 2 Mode Switch 2 Mode 3-Pole
Switch 2 Open Switch 2 Open OFF
Switch 2 Block Open Switch 2 Block Open OFF
Switch 2 Close Switch 2 Close OFF
Switch 2 Block Close Switch 2 Block Close OFF
Switch 2 Phase A/3 Pole Closed Switch 2 Phase A/3 Pole OFF
Closed
Switch 2 Phase A/3 Pole Opened Switch 2 Phase A/3 Pole OFF
Opened
Switch 2 Phase B Closed Switch 2 Phase B Closed OFF
Switch 2 Phase B Opened Switch 2 Phase B Opened OFF
Switch 2 Phase C Closed Switch 2 Phase C Closed OFF
Switch 2 Phase C Opened Switch 2 Phase C Opened OFF
Switch 2 Toperate Switch 2 Toperate 70 ms
Switch 2 Alarm Delay Switch 2 Alarm Delay 0.000 s
Switch 2 Events Switch 2 Events Disabled
Switch 3 Function Switch 3 Function Disabled
Switch 3 Name Switch 3 Name SW 3
Switch 3 Mode Switch 3 Mode 3-Pole
Switch 3 Open Switch 3 Open OFF
Switch 3 Block Open Switch 3 Block Open OFF
Switch 3 Close Switch 3 Close OFF
Switch 3 Block Close Switch 3 Block Close OFF
Switch 3 Phase A/3 Pole Closed Switch 3 Phase A/3 Pole OFF
Closed
Switch 3 Phase A/3 Pole Opened Switch 3 Phase A/3 Pole OFF
Opened
Switch 3 Phase B Closed Switch 3 Phase B Closed OFF
Switch 3 Phase B Opened Switch 3 Phase B Opened OFF
Switch 3 Phase C Closed Switch 3 Phase C Closed OFF
Switch 3 Phase C Opened Switch 3 Phase C Opened OFF
Switch 3 Toperate Switch 3 Toperate 70 ms
Switch 3 Alarm Delay Switch 3 Alarm Delay 0.000 s
Switch 3 Events Switch 3 Events Disabled
Switch 4 Function Switch 4 Function Disabled
Switch 4 Name Switch 4 Name SW 4
Switch 4 Mode Switch 4 Mode 3-Pole
Switch 4 Open Switch 4 Open OFF
Switch 4 Block Open Switch 4 Block Open OFF
Switch 4 Close Switch 4 Close OFF
Switch 4 Block Close Switch 4 Block Close OFF
Switch 4 Phase A/3 Pole Closed Switch 4 Phase A/3 Pole OFF
Closed
Switch 4 Phase A/3 Pole Opened Switch 4 Phase A/3 Pole OFF
Opened
Switch 4 Phase B Closed Switch 4 Phase B Closed OFF
Switch 4 Phase B Opened Switch 4 Phase B Opened OFF
Switch 4 Phase C Closed Switch 4 Phase C Closed OFF
Switch 4 Phase C Opened Switch 4 Phase C Opened OFF
Switch 4 Toperate Switch 4 Toperate 70 ms
Switch 4 Alarm Delay Switch 4 Alarm Delay 0.000 s
Switch 4 Events Switch 4 Events Disabled
Switch 5 Function Switch 5 Function Disabled
Switch 5 Name Switch 5 Name SW 5
Switch 5 Mode Switch 5 Mode 3-Pole
Switch 5 Open Switch 5 Open OFF
Switch 5 Block Open Switch 5 Block Open OFF
Switch 5 Close Switch 5 Close OFF
Switch 5 Block Close Switch 5 Block Close OFF
Switch 5 Phase A/3 Pole Closed Switch 5 Phase A/3 Pole OFF
Closed
Switch 5 Phase A/3 Pole Opened Switch 5 Phase A/3 Pole OFF
Opened
Switch 5 Phase B Closed Switch 5 Phase B Closed OFF
Switch 5 Phase B Opened Switch 5 Phase B Opened OFF
Switch 5 Phase C Closed Switch 5 Phase C Closed OFF
Switch 5 Phase C Opened Switch 5 Phase C Opened OFF
Switch 5 Toperate Switch 5 Toperate 70 ms
Switch 5 Alarm Delay Switch 5 Alarm Delay 0.000 s
Switch 5 Events Switch 5 Events Disabled
Switch 6 Function Switch 6 Function Disabled
Switch 6 Name Switch 6 Name SW 6
Switch 6 Mode Switch 6 Mode 3-Pole
Switch 6 Open Switch 6 Open OFF
Switch 6 Block Open Switch 6 Block Open OFF
Switch 6 Close Switch 6 Close OFF
Switch 6 Block Close Switch 6 Block Close OFF
Switch 6 Phase A/3 Pole Closed Switch 6 Phase A/3 Pole OFF
Closed
Switch 6 Phase A/3 Pole Opened Switch 6 Phase A/3 Pole OFF
Opened
Switch 6 Phase B Closed Switch 6 Phase B Closed OFF
Switch 6 Phase B Opened Switch 6 Phase B Opened OFF
Switch 6 Phase C Closed Switch 6 Phase C Closed OFF
Switch 6 Phase C Opened Switch 6 Phase C Opened OFF
Switch 6 Toperate Switch 6 Toperate 70 ms
Switch 6 Alarm Delay Switch 6 Alarm Delay 0.000 s
Switch 6 Events Switch 6 Events Disabled
Switch 7 Function Switch 7 Function Disabled
Switch 7 Name Switch 7 Name SW 7
Switch 7 Mode Switch 7 Mode 3-Pole
Switch 7 Open Switch 7 Open OFF
Switch 7 Block Open Switch 7 Block Open OFF
Switch 7 Close Switch 7 Close OFF
Switch 7 Block Close Switch 7 Block Close OFF
Switch 7 Phase A/3 Pole Closed Switch 7 Phase A/3 Pole OFF
Closed
Switch 7 Phase A/3 Pole Opened Switch 7 Phase A/3 Pole OFF
Opened
Switch 7 Phase B Closed Switch 7 Phase B Closed OFF
Switch 7 Phase B Opened Switch 7 Phase B Opened OFF
Switch 7 Phase C Closed Switch 7 Phase C Closed OFF
Switch 7 Phase C Opened Switch 7 Phase C Opened OFF
Switch 7 Toperate Switch 7 Toperate 70 ms
Switch 7 Alarm Delay Switch 7 Alarm Delay 0.000 s
Switch 7 Events Switch 7 Events Disabled
Switch 8 Function Switch 8 Function Disabled
Switch 8 Name Switch 8 Name SW 8
Switch 8 Mode Switch 8 Mode 3-Pole
Switch 8 Open Switch 8 Open OFF
Switch 8 Block Open Switch 8 Block Open OFF
Switch 8 Close Switch 8 Close OFF
Switch 8 Block Close Switch 8 Block Close OFF
Switch 8 Phase A/3 Pole Closed Switch 8 Phase A/3 Pole OFF
Closed
Switch 8 Phase A/3 Pole Opened Switch 8 Phase A/3 Pole OFF
Opened
Switch 8 Phase B Closed Switch 8 Phase B Closed OFF
Switch 8 Phase B Opened Switch 8 Phase B Opened OFF
Switch 8 Phase C Closed Switch 8 Phase C Closed OFF
Switch 8 Phase C Opened Switch 8 Phase C Opened OFF
Switch 8 Toperate Switch 8 Toperate 70 ms
Switch 8 Alarm Delay Switch 8 Alarm Delay 0.000 s
Switch 8 Events Switch 8 Events Disabled
Switch 9 Function Switch 9 Function Disabled
Switch 9 Name Switch 9 Name SW 9
Switch 9 Mode Switch 9 Mode 3-Pole
Switch 9 Open Switch 9 Open OFF
Switch 9 Block Open Switch 9 Block Open OFF
Switch 9 Close Switch 9 Close OFF
Switch 9 Block Close Switch 9 Block Close OFF
Switch 9 Phase A/3 Pole Closed Switch 9 Phase A/3 Pole OFF
Closed
Switch 9 Phase A/3 Pole Opened Switch 9 Phase A/3 Pole OFF
Opened
Switch 9 Phase B Closed Switch 9 Phase B Closed OFF
Switch 9 Phase B Opened Switch 9 Phase B Opened OFF
Switch 9 Phase C Closed Switch 9 Phase C Closed OFF
Switch 9 Phase C Opened Switch 9 Phase C Opened OFF
Switch 9 Toperate Switch 9 Toperate 70 ms
Switch 9 Alarm Delay Switch 9 Alarm Delay 0.000 s
Switch 9 Events Switch 9 Events Disabled
Switch 10 Function Switch 10 Function Disabled
Switch 10 Name Switch 10 Name SW 10
Switch 10 Mode Switch 10 Mode 3-Pole
Switch 10 Open Switch 10 Open OFF
Switch 10 Block Open Switch 10 Block Open OFF
Switch 10 Close Switch 10 Close OFF
Switch 10 Block Close Switch 10 Block Close OFF
Switch 10 Phase A/3 Pole Closed Switch 10 Phase A/3 Pole OFF
Closed
Switch 10 Phase A/3 Pole Opened Switch 10 Phase A/3 Pole OFF
Opened
Switch 10 Phase B Closed Switch 10 Phase B Closed OFF
Switch 10 Phase B Opened Switch 10 Phase B Opened OFF
Switch 10 Phase C Closed Switch 10 Phase C Closed OFF
Switch 10 Phase C Opened Switch 10 Phase C Opened OFF
Switch 10 Toperate Switch 10 Toperate 70 ms
Switch 10 Alarm Delay Switch 10 Alarm Delay 0.000 s
Switch 10 Events Switch 10 Events Disabled
Switch 11 Function Switch 11 Function Disabled
Switch 11 Name Switch 11 Name SW 11
Switch 11 Mode Switch 11 Mode 3-Pole
Switch 11 Open Switch 11 Open OFF
Switch 11 Block Open Switch 11 Block Open OFF
Switch 11 Close Switch 11 Close OFF
Switch 11 Block Close Switch 11 Block Close OFF
Switch 11 Phase A/3 Pole Closed Switch 11 Phase A/3 Pole OFF
Closed
Switch 11 Phase A/3 Pole Opened Switch 11 Phase A/3 Pole OFF
Opened
Switch 11 Phase B Closed Switch 11 Phase B Closed OFF
Switch 11 Phase B Opened Switch 11 Phase B Opened OFF
Switch 11 Phase C Closed Switch 11 Phase C Closed OFF
Switch 11 Phase C Opened Switch 11 Phase C Opened OFF
Switch 11 Toperate Switch 11 Toperate 70 ms
Switch 11 Alarm Delay Switch 11 Alarm Delay 0.000 s
Switch 11 Events Switch 11 Events Disabled
Switch 12 Function Switch 12 Function Disabled
Switch 12 Name Switch 12 Name SW 12
Switch 12 Mode Switch 12 Mode 3-Pole
Switch 12 Open Switch 12 Open OFF
Switch 12 Block Open Switch 12 Block Open OFF
Switch 12 Close Switch 12 Close OFF
Switch 12 Block Close Switch 12 Block Close OFF
Switch 12 Phase A/3 Pole Closed Switch 12 Phase A/3 Pole OFF
Closed
Switch 12 Phase A/3 Pole Opened Switch 12 Phase A/3 Pole OFF
Opened
Switch 12 Phase B Closed Switch 12 Phase B Closed OFF
Switch 12 Phase B Opened Switch 12 Phase B Opened OFF
Switch 12 Phase C Closed Switch 12 Phase C Closed OFF
Switch 12 Phase C Opened Switch 12 Phase C Opened OFF
Switch 12 Toperate Switch 12 Toperate 70 ms
Switch 12 Alarm Delay Switch 12 Alarm Delay 0.000 s
Switch 12 Events Switch 12 Events Disabled
Switch 13 Function Switch 13 Function Disabled
Switch 13 Name Switch 13 Name SW 13
Switch 13 Mode Switch 13 Mode 3-Pole
Switch 13 Open Switch 13 Open OFF
Switch 13 Block Open Switch 13 Block Open OFF
Switch 13 Close Switch 13 Close OFF
Switch 13 Block Close Switch 13 Block Close OFF
Switch 13 Phase A/3 Pole Closed Switch 13 Phase A/3 Pole OFF
Closed
Switch 13 Phase A/3 Pole Opened Switch 13 Phase A/3 Pole OFF
Opened
Switch 13 Phase B Closed Switch 13 Phase B Closed OFF
Switch 13 Phase B Opened Switch 13 Phase B Opened OFF
Switch 13 Phase C Closed Switch 13 Phase C Closed OFF
Switch 13 Phase C Opened Switch 13 Phase C Opened OFF
Switch 13 Toperate Switch 13 Toperate 70 ms
Switch 13 Alarm Delay Switch 13 Alarm Delay 0.000 s
Switch 13 Events Switch 13 Events Disabled
Switch 14 Function Switch 14 Function Disabled
Switch 14 Name Switch 14 Name SW 14
Switch 14 Mode Switch 14 Mode 3-Pole
Switch 14 Open Switch 14 Open OFF
Switch 14 Block Open Switch 14 Block Open OFF
Switch 14 Close Switch 14 Close OFF
Switch 14 Block Close Switch 14 Block Close OFF
Switch 14 Phase A/3 Pole Closed Switch 14 Phase A/3 Pole OFF
Closed
Switch 14 Phase A/3 Pole Opened Switch 14 Phase A/3 Pole OFF
Opened
Switch 14 Phase B Closed Switch 14 Phase B Closed OFF
Switch 14 Phase B Opened Switch 14 Phase B Opened OFF
Switch 14 Phase C Closed Switch 14 Phase C Closed OFF
Switch 14 Phase C Opened Switch 14 Phase C Opened OFF
Switch 14 Toperate Switch 14 Toperate 70 ms
Switch 14 Alarm Delay Switch 14 Alarm Delay 0.000 s
Switch 14 Events Switch 14 Events Disabled
Switch 15 Function Switch 15 Function Disabled
Switch 15 Name Switch 15 Name SW 15
Switch 15 Mode Switch 15 Mode 3-Pole
Switch 15 Open Switch 15 Open OFF
Switch 15 Block Open Switch 15 Block Open OFF
Switch 15 Close Switch 15 Close OFF
Switch 15 Block Close Switch 15 Block Close OFF
Switch 15 Phase A/3 Pole Closed Switch 15 Phase A/3 Pole OFF
Closed
Switch 15 Phase A/3 Pole Opened Switch 15 Phase A/3 Pole OFF
Opened
Switch 15 Phase B Closed Switch 15 Phase B Closed OFF
Switch 15 Phase B Opened Switch 15 Phase B Opened OFF
Switch 15 Phase C Closed Switch 15 Phase C Closed OFF
Switch 15 Phase C Opened Switch 15 Phase C Opened OFF
Switch 15 Toperate Switch 15 Toperate 70 ms
Switch 15 Alarm Delay Switch 15 Alarm Delay 0.000 s
Switch 15 Events Switch 15 Events Disabled
Switch 16 Function Switch 16 Function Disabled
Switch 16 Name Switch 16 Name SW 16
Switch 16 Mode Switch 16 Mode 3-Pole
Switch 16 Open Switch 16 Open OFF
Switch 16 Block Open Switch 16 Block Open OFF
Switch 16 Close Switch 16 Close OFF
Switch 16 Block Close Switch 16 Block Close OFF
Switch 16 Phase A/3 Pole Closed Switch 16 Phase A/3 Pole OFF
Closed
Switch 16 Phase A/3 Pole Opened Switch 16 Phase A/3 Pole OFF
Opened
Switch 16 Phase B Closed Switch 16 Phase B Closed OFF
Switch 16 Phase B Opened Switch 16 Phase B Opened OFF
Switch 16 Phase C Closed Switch 16 Phase C Closed OFF
Switch 16 Phase C Opened Switch 16 Phase C Opened OFF
Switch 16 Toperate Switch 16 Toperate 70 ms
Switch 16 Alarm Delay Switch 16 Alarm Delay 0.000 s
Switch 16 Events Switch 16 Events Disabled

.
GE Multilin G60 \ Relay Parameter Section \ System Setup \ FlexCurves \ FlexCurve A
Description Name Value
0.00 x PKP 0 ms
0.05 x PKP 0 ms
0.10 x PKP 0 ms
0.15 x PKP 0 ms
0.20 x PKP 0 ms
0.25 x PKP 0 ms
0.30 x PKP 0 ms
0.35 x PKP 0 ms
0.40 x PKP 0 ms
0.45 x PKP 0 ms
0.48 x PKP 0 ms
0.50 x PKP 0 ms
0.52 x PKP 0 ms
0.54 x PKP 0 ms
0.56 x PKP 0 ms
0.58 x PKP 0 ms
0.60 x PKP 0 ms
0.62 x PKP 0 ms
0.64 x PKP 0 ms
0.66 x PKP 0 ms
0.68 x PKP 0 ms
0.70 x PKP 0 ms
0.72 x PKP 0 ms
0.74 x PKP 0 ms
0.76 x PKP 0 ms
0.78 x PKP 0 ms
0.80 x PKP 0 ms
0.82 x PKP 0 ms
0.84 x PKP 0 ms
0.86 x PKP 0 ms
0.88 x PKP 0 ms
0.90 x PKP 0 ms
0.91 x PKP 0 ms
0.92 x PKP 0 ms
0.93 x PKP 0 ms
0.94 x PKP 0 ms
0.95 x PKP 0 ms
0.96 x PKP 0 ms
0.97 x PKP 0 ms
0.98 x PKP 0 ms
1.03 x PKP 0 ms
1.05 x PKP 0 ms
1.10 x PKP 0 ms
1.20 x PKP 0 ms
1.30 x PKP 0 ms
1.40 x PKP 0 ms
1.50 x PKP 0 ms
1.60 x PKP 0 ms
1.70 x PKP 0 ms
1.80 x PKP 0 ms
1.90 x PKP 0 ms
2.00 x PKP 0 ms
2.10 x PKP 0 ms
2.20 x PKP 0 ms
2.30 x PKP 0 ms
2.40 x PKP 0 ms
2.50 x PKP 0 ms
2.60 x PKP 0 ms
2.70 x PKP 0 ms
2.80 x PKP 0 ms
2.90 x PKP 0 ms
3.00 x PKP 0 ms
3.10 x PKP 0 ms
3.20 x PKP 0 ms
3.30 x PKP 0 ms
3.40 x PKP 0 ms
3.50 x PKP 0 ms
3.60 x PKP 0 ms
3.70 x PKP 0 ms
3.80 x PKP 0 ms
3.90 x PKP 0 ms
4.00 x PKP 0 ms
4.10 x PKP 0 ms
4.20 x PKP 0 ms
4.30 x PKP 0 ms
4.40 x PKP 0 ms
4.50 x PKP 0 ms
4.60 x PKP 0 ms
4.70 x PKP 0 ms
4.80 x PKP 0 ms
4.90 x PKP 0 ms
5.00 x PKP 0 ms
5.10 x PKP 0 ms
5.20 x PKP 0 ms
5.30 x PKP 0 ms
5.40 x PKP 0 ms
5.50 x PKP 0 ms
5.60 x PKP 0 ms
5.70 x PKP 0 ms
5.80 x PKP 0 ms
5.90 x PKP 0 ms
6.00 x PKP 0 ms
6.50 x PKP 0 ms
7.00 x PKP 0 ms
7.50 x PKP 0 ms
8.00 x PKP 0 ms
8.50 x PKP 0 ms
9.00 x PKP 0 ms
9.50 x PKP 0 ms
10.00 x PKP 0 ms
10.50 x PKP 0 ms
11.00 x PKP 0 ms
11.50 x PKP 0 ms
12.00 x PKP 0 ms
12.50 x PKP 0 ms
13.00 x PKP 0 ms
13.50 x PKP 0 ms
14.00 x PKP 0 ms
14.50 x PKP 0 ms
15.00 x PKP 0 ms
15.50 x PKP 0 ms
16.00 x PKP 0 ms
16.50 x PKP 0 ms
17.00 x PKP 0 ms
17.50 x PKP 0 ms
18.00 x PKP 0 ms
18.50 x PKP 0 ms
19.00 x PKP 0 ms
19.50 x PKP 0 ms
20.00 x PKP 0 ms

.
GE Multilin G60 \ Relay Parameter Section \ System Setup \ FlexCurves \ FlexCurve B
Description Name Value
0.00 x PKP 0 ms
0.05 x PKP 0 ms
0.10 x PKP 0 ms
0.15 x PKP 0 ms
0.20 x PKP 0 ms
0.25 x PKP 0 ms
0.30 x PKP 0 ms
0.35 x PKP 0 ms
0.40 x PKP 0 ms
0.45 x PKP 0 ms
0.48 x PKP 0 ms
0.50 x PKP 0 ms
0.52 x PKP 0 ms
0.54 x PKP 0 ms
0.56 x PKP 0 ms
0.58 x PKP 0 ms
0.60 x PKP 0 ms
0.62 x PKP 0 ms
0.64 x PKP 0 ms
0.66 x PKP 0 ms
0.68 x PKP 0 ms
0.70 x PKP 0 ms
0.72 x PKP 0 ms
0.74 x PKP 0 ms
0.76 x PKP 0 ms
0.78 x PKP 0 ms
0.80 x PKP 0 ms
0.82 x PKP 0 ms
0.84 x PKP 0 ms
0.86 x PKP 0 ms
0.88 x PKP 0 ms
0.90 x PKP 0 ms
0.91 x PKP 0 ms
0.92 x PKP 0 ms
0.93 x PKP 0 ms
0.94 x PKP 0 ms
0.95 x PKP 0 ms
0.96 x PKP 0 ms
0.97 x PKP 0 ms
0.98 x PKP 0 ms
1.03 x PKP 0 ms
1.05 x PKP 0 ms
1.10 x PKP 0 ms
1.20 x PKP 0 ms
1.30 x PKP 0 ms
1.40 x PKP 0 ms
1.50 x PKP 0 ms
1.60 x PKP 0 ms
1.70 x PKP 0 ms
1.80 x PKP 0 ms
1.90 x PKP 0 ms
2.00 x PKP 0 ms
2.10 x PKP 0 ms
2.20 x PKP 0 ms
2.30 x PKP 0 ms
2.40 x PKP 0 ms
2.50 x PKP 0 ms
2.60 x PKP 0 ms
2.70 x PKP 0 ms
2.80 x PKP 0 ms
2.90 x PKP 0 ms
3.00 x PKP 0 ms
3.10 x PKP 0 ms
3.20 x PKP 0 ms
3.30 x PKP 0 ms
3.40 x PKP 0 ms
3.50 x PKP 0 ms
3.60 x PKP 0 ms
3.70 x PKP 0 ms
3.80 x PKP 0 ms
3.90 x PKP 0 ms
4.00 x PKP 0 ms
4.10 x PKP 0 ms
4.20 x PKP 0 ms
4.30 x PKP 0 ms
4.40 x PKP 0 ms
4.50 x PKP 0 ms
4.60 x PKP 0 ms
4.70 x PKP 0 ms
4.80 x PKP 0 ms
4.90 x PKP 0 ms
5.00 x PKP 0 ms
5.10 x PKP 0 ms
5.20 x PKP 0 ms
5.30 x PKP 0 ms
5.40 x PKP 0 ms
5.50 x PKP 0 ms
5.60 x PKP 0 ms
5.70 x PKP 0 ms
5.80 x PKP 0 ms
5.90 x PKP 0 ms
6.00 x PKP 0 ms
6.50 x PKP 0 ms
7.00 x PKP 0 ms
7.50 x PKP 0 ms
8.00 x PKP 0 ms
8.50 x PKP 0 ms
9.00 x PKP 0 ms
9.50 x PKP 0 ms
10.00 x PKP 0 ms
10.50 x PKP 0 ms
11.00 x PKP 0 ms
11.50 x PKP 0 ms
12.00 x PKP 0 ms
12.50 x PKP 0 ms
13.00 x PKP 0 ms
13.50 x PKP 0 ms
14.00 x PKP 0 ms
14.50 x PKP 0 ms
15.00 x PKP 0 ms
15.50 x PKP 0 ms
16.00 x PKP 0 ms
16.50 x PKP 0 ms
17.00 x PKP 0 ms
17.50 x PKP 0 ms
18.00 x PKP 0 ms
18.50 x PKP 0 ms
19.00 x PKP 0 ms
19.50 x PKP 0 ms
20.00 x PKP 0 ms

.
GE Multilin G60 \ Relay Parameter Section \ System Setup \ FlexCurves \ FlexCurve C
Description Name Value
0.00 x PKP 0 ms
0.05 x PKP 0 ms
0.10 x PKP 0 ms
0.15 x PKP 0 ms
0.20 x PKP 0 ms
0.25 x PKP 0 ms
0.30 x PKP 0 ms
0.35 x PKP 0 ms
0.40 x PKP 0 ms
0.45 x PKP 0 ms
0.48 x PKP 0 ms
0.50 x PKP 0 ms
0.52 x PKP 0 ms
0.54 x PKP 0 ms
0.56 x PKP 0 ms
0.58 x PKP 0 ms
0.60 x PKP 0 ms
0.62 x PKP 0 ms
0.64 x PKP 0 ms
0.66 x PKP 0 ms
0.68 x PKP 0 ms
0.70 x PKP 0 ms
0.72 x PKP 0 ms
0.74 x PKP 0 ms
0.76 x PKP 0 ms
0.78 x PKP 0 ms
0.80 x PKP 0 ms
0.82 x PKP 0 ms
0.84 x PKP 0 ms
0.86 x PKP 0 ms
0.88 x PKP 0 ms
0.90 x PKP 0 ms
0.91 x PKP 0 ms
0.92 x PKP 0 ms
0.93 x PKP 0 ms
0.94 x PKP 0 ms
0.95 x PKP 0 ms
0.96 x PKP 0 ms
0.97 x PKP 0 ms
0.98 x PKP 0 ms
1.03 x PKP 0 ms
1.05 x PKP 0 ms
1.10 x PKP 0 ms
1.20 x PKP 0 ms
1.30 x PKP 0 ms
1.40 x PKP 0 ms
1.50 x PKP 0 ms
1.60 x PKP 0 ms
1.70 x PKP 0 ms
1.80 x PKP 0 ms
1.90 x PKP 0 ms
2.00 x PKP 0 ms
2.10 x PKP 0 ms
2.20 x PKP 0 ms
2.30 x PKP 0 ms
2.40 x PKP 0 ms
2.50 x PKP 0 ms
2.60 x PKP 0 ms
2.70 x PKP 0 ms
2.80 x PKP 0 ms
2.90 x PKP 0 ms
3.00 x PKP 0 ms
3.10 x PKP 0 ms
3.20 x PKP 0 ms
3.30 x PKP 0 ms
3.40 x PKP 0 ms
3.50 x PKP 0 ms
3.60 x PKP 0 ms
3.70 x PKP 0 ms
3.80 x PKP 0 ms
3.90 x PKP 0 ms
4.00 x PKP 0 ms
4.10 x PKP 0 ms
4.20 x PKP 0 ms
4.30 x PKP 0 ms
4.40 x PKP 0 ms
4.50 x PKP 0 ms
4.60 x PKP 0 ms
4.70 x PKP 0 ms
4.80 x PKP 0 ms
4.90 x PKP 0 ms
5.00 x PKP 0 ms
5.10 x PKP 0 ms
5.20 x PKP 0 ms
5.30 x PKP 0 ms
5.40 x PKP 0 ms
5.50 x PKP 0 ms
5.60 x PKP 0 ms
5.70 x PKP 0 ms
5.80 x PKP 0 ms
5.90 x PKP 0 ms
6.00 x PKP 0 ms
6.50 x PKP 0 ms
7.00 x PKP 0 ms
7.50 x PKP 0 ms
8.00 x PKP 0 ms
8.50 x PKP 0 ms
9.00 x PKP 0 ms
9.50 x PKP 0 ms
10.00 x PKP 0 ms
10.50 x PKP 0 ms
11.00 x PKP 0 ms
11.50 x PKP 0 ms
12.00 x PKP 0 ms
12.50 x PKP 0 ms
13.00 x PKP 0 ms
13.50 x PKP 0 ms
14.00 x PKP 0 ms
14.50 x PKP 0 ms
15.00 x PKP 0 ms
15.50 x PKP 0 ms
16.00 x PKP 0 ms
16.50 x PKP 0 ms
17.00 x PKP 0 ms
17.50 x PKP 0 ms
18.00 x PKP 0 ms
18.50 x PKP 0 ms
19.00 x PKP 0 ms
19.50 x PKP 0 ms
20.00 x PKP 0 ms

.
GE Multilin G60 \ Relay Parameter Section \ System Setup \ FlexCurves \ FlexCurve D
Description Name Value
0.00 x PKP 0 ms
0.05 x PKP 0 ms
0.10 x PKP 0 ms
0.15 x PKP 0 ms
0.20 x PKP 0 ms
0.25 x PKP 0 ms
0.30 x PKP 0 ms
0.35 x PKP 0 ms
0.40 x PKP 0 ms
0.45 x PKP 0 ms
0.48 x PKP 0 ms
0.50 x PKP 0 ms
0.52 x PKP 0 ms
0.54 x PKP 0 ms
0.56 x PKP 0 ms
0.58 x PKP 0 ms
0.60 x PKP 0 ms
0.62 x PKP 0 ms
0.64 x PKP 0 ms
0.66 x PKP 0 ms
0.68 x PKP 0 ms
0.70 x PKP 0 ms
0.72 x PKP 0 ms
0.74 x PKP 0 ms
0.76 x PKP 0 ms
0.78 x PKP 0 ms
0.80 x PKP 0 ms
0.82 x PKP 0 ms
0.84 x PKP 0 ms
0.86 x PKP 0 ms
0.88 x PKP 0 ms
0.90 x PKP 0 ms
0.91 x PKP 0 ms
0.92 x PKP 0 ms
0.93 x PKP 0 ms
0.94 x PKP 0 ms
0.95 x PKP 0 ms
0.96 x PKP 0 ms
0.97 x PKP 0 ms
0.98 x PKP 0 ms
1.03 x PKP 0 ms
1.05 x PKP 0 ms
1.10 x PKP 0 ms
1.20 x PKP 0 ms
1.30 x PKP 0 ms
1.40 x PKP 0 ms
1.50 x PKP 0 ms
1.60 x PKP 0 ms
1.70 x PKP 0 ms
1.80 x PKP 0 ms
1.90 x PKP 0 ms
2.00 x PKP 0 ms
2.10 x PKP 0 ms
2.20 x PKP 0 ms
2.30 x PKP 0 ms
2.40 x PKP 0 ms
2.50 x PKP 0 ms
2.60 x PKP 0 ms
2.70 x PKP 0 ms
2.80 x PKP 0 ms
2.90 x PKP 0 ms
3.00 x PKP 0 ms
3.10 x PKP 0 ms
3.20 x PKP 0 ms
3.30 x PKP 0 ms
3.40 x PKP 0 ms
3.50 x PKP 0 ms
3.60 x PKP 0 ms
3.70 x PKP 0 ms
3.80 x PKP 0 ms
3.90 x PKP 0 ms
4.00 x PKP 0 ms
4.10 x PKP 0 ms
4.20 x PKP 0 ms
4.30 x PKP 0 ms
4.40 x PKP 0 ms
4.50 x PKP 0 ms
4.60 x PKP 0 ms
4.70 x PKP 0 ms
4.80 x PKP 0 ms
4.90 x PKP 0 ms
5.00 x PKP 0 ms
5.10 x PKP 0 ms
5.20 x PKP 0 ms
5.30 x PKP 0 ms
5.40 x PKP 0 ms
5.50 x PKP 0 ms
5.60 x PKP 0 ms
5.70 x PKP 0 ms
5.80 x PKP 0 ms
5.90 x PKP 0 ms
6.00 x PKP 0 ms
6.50 x PKP 0 ms
7.00 x PKP 0 ms
7.50 x PKP 0 ms
8.00 x PKP 0 ms
8.50 x PKP 0 ms
9.00 x PKP 0 ms
9.50 x PKP 0 ms
10.00 x PKP 0 ms
10.50 x PKP 0 ms
11.00 x PKP 0 ms
11.50 x PKP 0 ms
12.00 x PKP 0 ms
12.50 x PKP 0 ms
13.00 x PKP 0 ms
13.50 x PKP 0 ms
14.00 x PKP 0 ms
14.50 x PKP 0 ms
15.00 x PKP 0 ms
15.50 x PKP 0 ms
16.00 x PKP 0 ms
16.50 x PKP 0 ms
17.00 x PKP 0 ms
17.50 x PKP 0 ms
18.00 x PKP 0 ms
18.50 x PKP 0 ms
19.00 x PKP 0 ms
19.50 x PKP 0 ms
20.00 x PKP 0 ms

.
GE Multilin G60 \ Relay Parameter Section \ Grouped Elements \ Group1 \ Distance \
Distance
Description Name Value
Source Source SRC 1 (SRC 1)
Memory Duration (cy) Memory Duration (cy) 8 cy
Force Self-Polar Force Self-Polar OFF
Force Mem-Polar Force Mem-Polar OFF

.
GE Multilin G60 \ Relay Parameter Section \ Grouped Elements \ Group1 \ Distance \
Phase Distance \ Phase Distance Z1
Description Name Value
Function Function Enabled
Direction Direction Forward
Shape Shape Mho
Xfmr Vol Connection Xfmr Vol Connection None
Xfmr Curr Connection Xfmr Curr Connection None
Reach Reach 9.68 Ohm
RCA RCA 85 °
Rev Reach Rev Reach 2.00 Ohm
Rev Reach RCA Rev Reach RCA 85 °
Comp Limit Comp Limit 90 °
DIR RCA DIR RCA 85 °
DIR Comp Limit DIR Comp Limit 90 °
Quad Right Blinder Quad Right Blinder 10.00 Ohm
Quad Right Blinder RCA Quad Right Blinder RCA 85.00 °
Quad Left Blinder Quad Left Blinder 10.00 Ohm
Quad Left Blinder RCA Quad Left Blinder RCA 85.00 °
Supervision Supervision 0.200 pu
Volt Level Volt Level 0.000 pu
Delay Delay 0.500 s
Block Block VT FAILURE On
(VO11)
Target Target Latched
Events Events Enabled

.
GE Multilin G60 \ Relay Parameter Section \ Grouped Elements \ Group1 \ Distance \
Phase Distance \ Phase Distance Z2
Description Name Value
Function Function Enabled
Direction Direction Reverse
Shape Shape Mho
Xfmr Vol Connection Xfmr Vol Connection None
Xfmr Curr Connection Xfmr Curr Connection None
Reach Reach 27.67 Ohm
RCA RCA 85 °
Rev Reach Rev Reach 2.00 Ohm
Rev Reach RCA Rev Reach RCA 85 °
Comp Limit Comp Limit 90 °
DIR RCA DIR RCA 85 °
DIR Comp Limit DIR Comp Limit 90 °
Quad Right Blinder Quad Right Blinder 10.00 Ohm
Quad Right Blinder RCA Quad Right Blinder RCA 85.00 °
Quad Left Blinder Quad Left Blinder 10.00 Ohm
Quad Left Blinder RCA Quad Left Blinder RCA 85.00 °
Supervision Supervision 0.200 pu
Volt Level Volt Level 0.000 pu
Delay Delay 0.250 s
Block Block VT FAILURE On
(VO11)
Target Target Latched
Events Events Enabled

.
GE Multilin G60 \ Relay Parameter Section \ Grouped Elements \ Group1 \ Distance \
Phase Distance \ Phase Distance Z3
Description Name Value
Function Function Disabled
Direction Direction Forward
Shape Shape Mho
Xfmr Vol Connection Xfmr Vol Connection None
Xfmr Curr Connection Xfmr Curr Connection None
Reach Reach 2.00 Ohm
RCA RCA 85 °
Rev Reach Rev Reach 2.00 Ohm
Rev Reach RCA Rev Reach RCA 85 °
Comp Limit Comp Limit 90 °
DIR RCA DIR RCA 85 °
DIR Comp Limit DIR Comp Limit 90 °
Quad Right Blinder Quad Right Blinder 10.00 Ohm
Quad Right Blinder RCA Quad Right Blinder RCA 85.00 °
Quad Left Blinder Quad Left Blinder 10.00 Ohm
Quad Left Blinder RCA Quad Left Blinder RCA 85.00 °
Supervision Supervision 0.200 pu
Volt Level Volt Level 0.000 pu
Delay Delay 0.000 s
Block Block OFF
Target Target Self-reset
Events Events Disabled

.
GE Multilin G60 \ Relay Parameter Section \ Grouped Elements \ Group1 \ Power Swing
Detect
Description Name Value
Function Function Enabled
Source Source TERM (SRC 2)
Shape Shape Mho Shape
Mode Mode Two Step
Supv Supv 0.400 pu
I2 Supv Enable I2 Supv Enable OFF
I2 Supv I2 Supv 0.200 pu
Fwd Reach Fwd Reach 12.10 Ohm
Quad Fwd Mid Quad Fwd Mid 60.00 Ohm
Quad Fwd Out Quad Fwd Out 70.00 Ohm
Fwd Rca Fwd Rca 85.0 °
Rev Reach Rev Reach 46.11 Ohm
Quad Rev Mid Quad Rev Mid 60.00 Ohm
Quad Rev Out Quad Rev Out 70.00 Ohm
Rev Rca Rev Rca 90 °
Outer Limit Angle Outer Limit Angle 120 °
Middle Limit Angle Middle Limit Angle 90 °
Inner Limit Angle Inner Limit Angle 60 °
Outer Rgt Bld Outer Rgt Bld 100.00 Ohm
Outer Lft Bld Outer Lft Bld 100.00 Ohm
Middle Rgt Bld Middle Rgt Bld 100.00 Ohm
Middle Lft Bld Middle Lft Bld 100.00 Ohm
Inner Rgt Bld Inner Rgt Bld 100.00 Ohm
Inner Lft Bld Inner Lft Bld 100.00 Ohm
Delay 1 Pickup Delay 1 Pickup 0.017 s
Delay 1 Reset Delay 1 Reset 0.020 s
Delay 2 Pickup Delay 2 Pickup 0.018 s
Delay 3 Pickup Delay 3 Pickup 0.033 s
Delay 4 Pickup Delay 4 Pickup 0.017 s
Seal-In Delay Seal-In Delay 0.400 s
Trip Mode Trip Mode Delayed
Block Block VT FAILURE On
(VO11)
Target Target Latched
Event Event Enabled

.
GE Multilin G60 \ Relay Parameter Section \ Grouped Elements \ Group1 \ Stator
Differential
Description Name Value
Function Function Enabled
Line End Source Line End Source TERM (SRC 2)
Neutral End Source Neutral End Source NEUT (SRC 1)
Pickup Pickup 0.080 pu
Slope 1 Slope 1 10 %
Break 1 Break 1 1.20 pu
Slope 2 Slope 2 80 %
Break 2 Break 2 3.00 pu
Block Block OFF
Target Targets Latched
Events Events Enabled

.
GE Multilin G60 \ Relay Parameter Section \ Grouped Elements \ Group1 \ Phase Current \
Phase TOC \ Phase TOC 1
Description Name Value
Function Function Enabled
Signal Source Signal Source TERM (SRC 2)
Input Input Phasor
Pickup Pickup 1.080 pu
Curve Curve IEC Curve C
TD Multiplier TD Multiplier 0.05
Reset Reset Instantaneous
Voltage Restraint Voltage Restraint Enabled
Block A Block A VT FAILURE On
(VO11)
Block B Block B VT FAILURE On
(VO11)
Block C Block C VT FAILURE On
(VO11)
Target Target Latched
Events Events Enabled

.
GE Multilin G60 \ Relay Parameter Section \ Grouped Elements \ Group1 \ Phase Current \
Phase IOC \ Phase IOC 1
Description Name Value
Function Function Disabled
Source Source SRC 1 (SRC 1)
Pickup Pickup 1.000 pu
Delay Delay 0.00 s
Reset Delay Reset Delay 0.00 s
Block A Block A OFF
Block B Block B OFF
Block C Block C OFF
Target Target Self-reset
Events Events Disabled

.
GE Multilin G60 \ Relay Parameter Section \ Grouped Elements \ Group1 \ Phase Current \
Phase IOC \ Phase IOC 2
Description Name Value
Function Function Enabled
Source Source TERM (SRC 2)
Pickup Pickup 0.144 pu
Delay Delay 0.00 s
Reset Delay Reset Delay 0.00 s
Block A Block A OFF
Block B Block B OFF
Block C Block C OFF
Target Target Disabled
Events Events Disabled

.
GE Multilin G60 \ Relay Parameter Section \ Grouped Elements \ Group1 \ Phase Current \
Phase Directional \ Phase DIR1
Description Name Value
Function Function Disabled
Source Source SRC 1 (SRC 1)
Block Block OFF
ECA ECA 30 °
Pol V Threshold Pol V Threshold 0.700 pu
Block when V Men Exp Block when V Men Exp Yes
Target Target Self-reset
Events Events Disabled

.
GE Multilin G60 \ Relay Parameter Section \ Grouped Elements \ Group1 \ Neutral
Current \ Neutral TOC \ Neutral TOC 1
Description Name Value
Function Function Disabled
Source Source SRC 1 (SRC 1)
Input Input Phasor
Pickup Pickup 1.000 pu
Curve Curve IEEE Mod Inv
TD Multiplier TD Multiplier 1.00
Reset Reset Instantaneous
Block Block OFF
Target Target Self-reset
Events Events Disabled

.
GE Multilin G60 \ Relay Parameter Section \ Grouped Elements \ Group1 \ Neutral
Current \ Neutral IOC \ Neutral IOC 1
Description Name Value
Function Function Disabled
Source Source SRC 1 (SRC 1)
Pickup Pickup 1.000 pu
Delay Delay 0.00 s
Reset Delay Reset Delay 0.00 s
Block Block OFF
Target Target Self-reset
Events Events Disabled

.
GE Multilin G60 \ Relay Parameter Section \ Grouped Elements \ Group1 \ Neutral
Current \ Neutral Directional OC \ Neutral DIR OC1
Description Name Value
Function Function Enabled
Source Source NEUT (SRC 1)
Polarizing Polarizing Voltage
Polarizing Volt Polarizing Volt Calculated V0
Op Current Op Current Measured IG
POS SEQ Restraint POS SEQ Restraint 0.000
Offset Offset 0.00 Ohm
Forward ECA Forward ECA -45 °
Forward Limit Angle Forward Limit Angle 90 °
Forward Pickup Forward Pickup 30.000 pu
Reverse Limit Angle Reverse Limit Angle 90 °
Reverse Pickup Reverse Pickup 0.050 pu
Block Block VT FAILURE On
(VO11)
Target Target Latched
Events Events Enabled

.
GE Multilin G60 \ Relay Parameter Section \ Grouped Elements \ Group1 \ Neutral
Current \ Neutral Directional OC \ Neutral DIR OC2
Description Name Value
Function Function Disabled
Source Source SRC 1 (SRC 1)
Polarizing Polarizing Voltage
Polarizing Volt Polarizing Volt Calculated V0
Op Current Op Current Calculated 3I0
POS SEQ Restraint POS SEQ Restraint 0.063
Offset Offset 0.00 Ohm
Forward ECA Forward ECA 75 °
Forward Limit Angle Forward Limit Angle 90 °
Forward Pickup Forward Pickup 0.050 pu
Reverse Limit Angle Reverse Limit Angle 90 °
Reverse Pickup Reverse Pickup 0.050 pu
Block Block OFF
Target Target Self-reset
Events Events Disabled

.
GE Multilin G60 \ Relay Parameter Section \ Grouped Elements \ Group1 \ Ground
Current \ Ground TOC \ Ground TOC 1
Description Name Value
Function Function Enabled
Source Source NEUT (SRC 1)
Input Input Phasor
Pickup Pickup 1.000 pu
Curve Curve Definite Time
TD Multiplier TD Multiplier 0.10
Reset Reset Instantaneous
Block Block OFF
Target Target Latched
Events Events Enabled

.
GE Multilin G60 \ Relay Parameter Section \ Grouped Elements \ Group1 \ Ground
Current \ Ground IOC \ Ground IOC 1
Description Name Value
Function Function Disabled
Source Source SRC 1 (SRC 1)
Pickup Pickup 1.000 pu
Delay Delay 0.00 s
Reset Delay Reset Delay 0.00 s
Block Block OFF
Target Target Self-reset
Events Events Disabled

.
GE Multilin G60 \ Relay Parameter Section \ Grouped Elements \ Group1 \ Ground
Current \ Restricted Ground Fault \ RGF1
Description Name Value
Function Function Enabled
Source Source TERM (SRC 2)
Pickup Pickup 0.050 pu
Slope Slope 45 %
Delay Pickup Delay 0.01 s
Reset Delay Reset Delay 0.01 s
Block Block OFF
Target Target Latched
Events Events Enabled

.
GE Multilin G60 \ Relay Parameter Section \ Grouped Elements \ Group1 \ Ground
Current \ Restricted Ground Fault \ RGF2
Description Name Value
Function Function Disabled
Source Source SRC 1 (SRC 1)
Pickup Pickup 0.080 pu
Slope Slope 40 %
Delay Pickup Delay 0.00 s
Reset Delay Reset Delay 0.00 s
Block Block OFF
Target Target Self-reset
Events Events Disabled
.
GE Multilin G60 \ Relay Parameter Section \ Grouped Elements \ Group1 \ Ground
Current \ Restricted Ground Fault \ RGF3
Description Name Value
Function Function Disabled
Source Source SRC 1 (SRC 1)
Pickup Pickup 0.080 pu
Slope Slope 40 %
Delay Pickup Delay 0.00 s
Reset Delay Reset Delay 0.00 s
Block Block OFF
Target Target Self-reset
Events Events Disabled

.
GE Multilin G60 \ Relay Parameter Section \ Grouped Elements \ Group1 \ Ground
Current \ Restricted Ground Fault \ RGF4
Description Name Value
Function Function Disabled
Source Source SRC 1 (SRC 1)
Pickup Pickup 1.000 pu
Slope Slope 40 %
Delay Pickup Delay 0.00 s
Reset Delay Reset Delay 0.00 s
Block Block OFF
Target Target Self-reset
Events Events Disabled

.
GE Multilin G60 \ Relay Parameter Section \ Grouped Elements \ Group1 \ Ground
Current \ Restricted Ground Fault \ RGF5
Description Name Value
Function Function Disabled
Source Source SRC 1 (SRC 1)
Pickup Pickup 1.000 pu
Slope Slope 40 %
Delay Pickup Delay 0.00 s
Reset Delay Reset Delay 0.00 s
Block Block OFF
Target Target Self-reset
Events Events Disabled

.
GE Multilin G60 \ Relay Parameter Section \ Grouped Elements \ Group1 \ Ground
Current \ Restricted Ground Fault \ RGF6
Description Name Value
Function Function Disabled
Source Source SRC 1 (SRC 1)
Pickup Pickup 1.000 pu
Slope Slope 40 %
Delay Pickup Delay 0.00 s
Reset Delay Reset Delay 0.00 s
Block Block OFF
Target Target Self-reset
Events Events Disabled

.
GE Multilin G60 \ Relay Parameter Section \ Grouped Elements \ Group1 \ Generator
Unbalance
Description Name Value
Function Function Enabled
Source Source NEUT (SRC 1)
Inom Inom 0.722 pu
Stage 1 Pickup Stage 1 Pickup 7 %
Stage 1 K-Value Stage 1 K-Value 18.00
Stage 1 Tmin Stage 1 Tmin 0.100 s
Stage 1 Tmax Stage 1 Tmax 300.0 s
Stage 1 K-Reset Stage 1 K-Reset 240.0 s
Stage 2 Pickup Stage 2 Pickup 4.00 %
Stage 2 Pickup Delay Stage 2 Pickup Delay 2.0 s
Block Block OFF
Targets Target Latched
Events Events Enabled

.
GE Multilin G60 \ Relay Parameter Section \ Grouped Elements \ Group1 \ Split Phase
Description Name Value
Function Function Disabled
Source Source SRC 1 (SRC 1)
Load Source Load Source SRC 1 (SRC 1)
PHA Pickup PHA Pickup 0.200 pu
PHA Offset PHA Offset 0.000 pu
PHA Slope PHA Slope 0.0 %
PHB Pickup PHB Pickup 0.200 pu
PHB Offset PHB Offset 0.000 pu
PHB Slope PHB Slope 0.0 %
PHC Pickup PHC Pickup 0.200 pu
PHC Offset PHC Offset 0.000 pu
PHC Slope PHC Slope 0.0 %
Min Load Min Load 0.00 pu
Mode Mode Over
Delay Delay 0.000 s
Block Block OFF
Targets Target Self-reset
Events Events Disabled

.
GE Multilin G60 \ Relay Parameter Section \ Grouped Elements \ Group1 \ Negative
Sequence Current \ Negative Sequence Directional OC \ Negative Seq DIR OC1
Description Name Value
Function Function Disabled
Source Source SRC 1 (SRC 1)
Offset Offset 0.00 Ohm
Type Type Neg Sequence
POS SEQ Restraint POS SEQ Restraint 0.063
Forward ECA Forward ECA 75 °
Forward Limit Angle Forward Limit Angle 90 °
Forward Pickup Forward Pickup 0.050 pu
Reverse Limit Angle Reverse Limit Angle 90 °
Reverse Pickup Reverse Pickup 0.050 pu
Block Block OFF
Target Target Self-reset
Events Events Disabled

.
GE Multilin G60 \ Relay Parameter Section \ Grouped Elements \ Group1 \ Negative
Sequence Current \ Negative Sequence Directional OC \ Negative Seq DIR OC2
Description Name Value
Function Function Disabled
Source Source SRC 1 (SRC 1)
Offset Offset 0.00 Ohm
Type Type Neg Sequence
POS SEQ Restraint POS SEQ Restraint 0.063
Forward ECA Forward ECA 75 °
Forward Limit Angle Forward Limit Angle 90 °
Forward Pickup Forward Pickup 0.050 pu
Reverse Limit Angle Reverse Limit Angle 90 °
Reverse Pickup Reverse Pickup 0.050 pu
Block Block OFF
Target Target Self-reset
Events Events Disabled

.
GE Multilin G60 \ Relay Parameter Section \ Grouped Elements \ Group1 \ Breaker
Failure \ BF 1
Description Name Value
Function Function Disabled
Mode Mode 3-Pole
Source Source SRC 1 (SRC 1)
Current Supervision Current Supervision Yes
Use Seal-In Use Seal-In Yes
Three Pole Initiate Three Pole Initiate OFF
Block Block OFF
Phase Current Supv Pickup Phase Current Supv Pickup 1.050 pu
Neutral Current Supv Pickup Neutral Current Supv Pickup 1.050 pu
Use Timer 1 Use Timer 1 Yes
Timer 1 Pickup Delay Timer 1 Pickup Delay 0.000 s
Use Timer 2 Use Timer 2 Yes
Timer 2 Pickup Delay Timer 2 Pickup Delay 0.000 s
Use Timer 3 Use Timer 3 Yes
Timer 3 Pickup Delay Timer 3 Pickup Delay 0.000 s
Breaker Pos1 Phase A/3P Breaker Pos1 Phase A/3P OFF
Breaker Pos2 Phase A/3P Breaker Pos2 Phase A/3P OFF
Breaker Test On Breaker Test On OFF
Phase Current HiSet Pickup Phase Current HiSet Pickup 1.050 pu
Neutral Current HiSet Pickup Neutral Current HiSet Pickup 1.050 pu
Phase Current LoSet Pickup Phase Current LoSet Pickup 1.050 pu
Neutral Current LoSet Pickup Neutral Current LoSet Pickup 1.050 pu
LoSet Time Delay LoSet Time Delay 0.000 s
Trip Dropout delay Trip Dropout Delay 0.000 s
Target Target Self-reset
Events Events Disabled
Phase A Initiate Phase A Initiate OFF
Phase B Initiate Phase B Initiate OFF
Phase C Initiate Phase C Initiate OFF
Breaker Pos1 Phase B Breaker Pos1 Phase B OFF
Breaker Pos1 Phase C Breaker Pos1 Phase C OFF
Breaker Pos2 Phase B Breaker Pos2 Phase B OFF
Breaker Pos2 Phase C Breaker Pos2 Phase C OFF

.
GE Multilin G60 \ Relay Parameter Section \ Grouped Elements \ Group1 \ Breaker
Failure \ BF 2
Description Name Value
Function Function Disabled
Mode Mode 3-Pole
Source Source SRC 1 (SRC 1)
Current Supervision Current Supervision Yes
Use Seal-In Use Seal-In Yes
Three Pole Initiate Three Pole Initiate OFF
Block Block OFF
Phase Current Supv Pickup Phase Current Supv Pickup 1.050 pu
Neutral Current Supv Pickup Neutral Current Supv Pickup 1.050 pu
Use Timer 1 Use Timer 1 Yes
Timer 1 Pickup Delay Timer 1 Pickup Delay 0.000 s
Use Timer 2 Use Timer 2 Yes
Timer 2 Pickup Delay Timer 2 Pickup Delay 0.000 s
Use Timer 3 Use Timer 3 Yes
Timer 3 Pickup Delay Timer 3 Pickup Delay 0.000 s
Breaker Pos1 Phase A/3P Breaker Pos1 Phase A/3P OFF
Breaker Pos2 Phase A/3P Breaker Pos2 Phase A/3P OFF
Breaker Test On Breaker Test On OFF
Phase Current HiSet Pickup Phase Current HiSet Pickup 1.050 pu
Neutral Current HiSet Pickup Neutral Current HiSet Pickup 1.050 pu
Phase Current LoSet Pickup Phase Current LoSet Pickup 1.050 pu
Neutral Current LoSet Pickup Neutral Current LoSet Pickup 1.050 pu
LoSet Time Delay LoSet Time Delay 0.000 s
Trip Dropout delay Trip Dropout Delay 0.000 s
Target Target Self-reset
Events Events Disabled
Phase A Initiate Phase A Initiate OFF
Phase B Initiate Phase B Initiate OFF
Phase C Initiate Phase C Initiate OFF
Breaker Pos1 Phase B Breaker Pos1 Phase B OFF
Breaker Pos1 Phase C Breaker Pos1 Phase C OFF
Breaker Pos2 Phase B Breaker Pos2 Phase B OFF
Breaker Pos2 Phase C Breaker Pos2 Phase C OFF

.
GE Multilin G60 \ Relay Parameter Section \ Grouped Elements \ Group1 \ Breaker
Failure \ BF 3
Description Name Value
Function Function Disabled
Mode Mode 3-Pole
Source Source SRC 1 (SRC 1)
Current Supervision Current Supervision Yes
Use Seal-In Use Seal-In Yes
Three Pole Initiate Three Pole Initiate OFF
Block Block OFF
Phase Current Supv Pickup Phase Current Supv Pickup 1.050 pu
Neutral Current Supv Pickup Neutral Current Supv Pickup 1.050 pu
Use Timer 1 Use Timer 1 Yes
Timer 1 Pickup Delay Timer 1 Pickup Delay 0.000 s
Use Timer 2 Use Timer 2 Yes
Timer 2 Pickup Delay Timer 2 Pickup Delay 0.000 s
Use Timer 3 Use Timer 3 Yes
Timer 3 Pickup Delay Timer 3 Pickup Delay 0.000 s
Breaker Pos1 Phase A/3P Breaker Pos1 Phase A/3P OFF
Breaker Pos2 Phase A/3P Breaker Pos2 Phase A/3P OFF
Breaker Test On Breaker Test On OFF
Phase Current HiSet Pickup Phase Current HiSet Pickup 1.050 pu
Neutral Current HiSet Pickup Neutral Current HiSet Pickup 1.050 pu
Phase Current LoSet Pickup Phase Current LoSet Pickup 1.050 pu
Neutral Current LoSet Pickup Neutral Current LoSet Pickup 1.050 pu
LoSet Time Delay LoSet Time Delay 0.000 s
Trip Dropout delay Trip Dropout Delay 0.000 s
Target Target Self-reset
Events Events Disabled
Phase A Initiate Phase A Initiate OFF
Phase B Initiate Phase B Initiate OFF
Phase C Initiate Phase C Initiate OFF
Breaker Pos1 Phase B Breaker Pos1 Phase B OFF
Breaker Pos1 Phase C Breaker Pos1 Phase C OFF
Breaker Pos2 Phase B Breaker Pos2 Phase B OFF
Breaker Pos2 Phase C Breaker Pos2 Phase C OFF

.
GE Multilin G60 \ Relay Parameter Section \ Grouped Elements \ Group1 \ Breaker
Failure \ BF 4
Description Name Value
Function Function Disabled
Mode Mode 3-Pole
Source Source SRC 1 (SRC 1)
Current Supervision Current Supervision Yes
Use Seal-In Use Seal-In Yes
Three Pole Initiate Three Pole Initiate OFF
Block Block OFF
Phase Current Supv Pickup Phase Current Supv Pickup 1.050 pu
Neutral Current Supv Pickup Neutral Current Supv Pickup 1.050 pu
Use Timer 1 Use Timer 1 Yes
Timer 1 Pickup Delay Timer 1 Pickup Delay 0.000 s
Use Timer 2 Use Timer 2 Yes
Timer 2 Pickup Delay Timer 2 Pickup Delay 0.000 s
Use Timer 3 Use Timer 3 Yes
Timer 3 Pickup Delay Timer 3 Pickup Delay 0.000 s
Breaker Pos1 Phase A/3P Breaker Pos1 Phase A/3P OFF
Breaker Pos2 Phase A/3P Breaker Pos2 Phase A/3P OFF
Breaker Test On Breaker Test On OFF
Phase Current HiSet Pickup Phase Current HiSet Pickup 1.050 pu
Neutral Current HiSet Pickup Neutral Current HiSet Pickup 1.050 pu
Phase Current LoSet Pickup Phase Current LoSet Pickup 1.050 pu
Neutral Current LoSet Pickup Neutral Current LoSet Pickup 1.050 pu
LoSet Time Delay LoSet Time Delay 0.000 s
Trip Dropout delay Trip Dropout Delay 0.000 s
Target Target Self-reset
Events Events Disabled
Phase A Initiate Phase A Initiate OFF
Phase B Initiate Phase B Initiate OFF
Phase C Initiate Phase C Initiate OFF
Breaker Pos1 Phase B Breaker Pos1 Phase B OFF
Breaker Pos1 Phase C Breaker Pos1 Phase C OFF
Breaker Pos2 Phase B Breaker Pos2 Phase B OFF
Breaker Pos2 Phase C Breaker Pos2 Phase C OFF

.
GE Multilin G60 \ Relay Parameter Section \ Grouped Elements \ Group1 \ Voltage
Elements \ Phase UV \ Phase UV 1
Description Name Value
Function Function Enabled
Signal Source Signal Source TERM (SRC 2)
Mode Mode Phase to Ground
Pickup Pickup 0.900 pu
Curve Curve Definite Time
Delay Delay 10.00 s
Minimum Voltage Minimum Voltage 0.100 pu
Block Block 27P&81U BL On
(VO13)
Target Target Latched
Events Events Enabled

.
GE Multilin G60 \ Relay Parameter Section \ Grouped Elements \ Group1 \ Voltage
Elements \ Phase UV \ Phase UV 2
Description Name Value
Function Function Disabled
Signal Source Signal Source SRC 1 (SRC 1)
Mode Mode Phase to Ground
Pickup Pickup 1.000 pu
Curve Curve Definite Time
Delay Delay 1.00 s
Minimum Voltage Minimum Voltage 0.100 pu
Block Block OFF
Target Target Self-reset
Events Events Disabled

.
GE Multilin G60 \ Relay Parameter Section \ Grouped Elements \ Group1 \ Voltage
Elements \ Phase UV \ Phase UV 3
Description Name Value
Function Function Disabled
Signal Source Signal Source SRC 1 (SRC 1)
Mode Mode Phase to Ground
Pickup Pickup 1.000 pu
Curve Curve Definite Time
Delay Delay 1.00 s
Minimum Voltage Minimum Voltage 0.100 pu
Block Block OFF
Target Target Self-reset
Events Events Disabled

.
GE Multilin G60 \ Relay Parameter Section \ Grouped Elements \ Group1 \ Voltage
Elements \ Phase OV \ Phase OV 1
Description Name Value
Function Function Enabled
Source Source TERM (SRC 2)
Pickup Pickup 1.100 pu
Delay Delay 10.00 s
Reset Delay Reset Delay 0.50 s
Block Block OFF
Target Target Latched
Events Events Enabled

.
GE Multilin G60 \ Relay Parameter Section \ Grouped Elements \ Group1 \ Voltage
Elements \ Phase OV \ Phase OV 2
Description Name Value
Function Function Enabled
Source Source TERM (SRC 2)
Pickup Pickup 1.200 pu
Delay Delay 0.50 s
Reset Delay Reset Delay 0.50 s
Block Block OFF
Target Target Latched
Events Events Enabled

.
GE Multilin G60 \ Relay Parameter Section \ Grouped Elements \ Group1 \ Voltage
Elements \ Phase OV \ Phase OV 3
Description Name Value
Function Function Disabled
Source Source SRC 1 (SRC 1)
Pickup Pickup 1.000 pu
Delay Delay 1.00 s
Reset Delay Reset Delay 1.00 s
Block Block OFF
Target Target Self-reset
Events Events Disabled

.
GE Multilin G60 \ Relay Parameter Section \ Grouped Elements \ Group1 \ Voltage
Elements \ Neutral OV \ Neutral OV 1
Description Name Value
Function Function Enabled
Source Source TERM (SRC 2)
Pickup Pickup 0.150 pu
Curve Curve Definite Time
Pickup Delay Pickup Delay 0.70 s
Reset Delay Reset Delay 1.00 s
Block Block VT FAILURE On
(VO11)
Target Target Latched
Events Events Enabled

.
GE Multilin G60 \ Relay Parameter Section \ Grouped Elements \ Group1 \ Voltage
Elements \ Neutral OV \ Neutral OV 2
Description Name Value
Function Function Disabled
Source Source SRC 1 (SRC 1)
Pickup Pickup 0.300 pu
Curve Curve Definite Time
Pickup Delay Pickup Delay 1.00 s
Reset Delay Reset Delay 1.00 s
Block Block OFF
Target Target Self-reset
Events Events Disabled

.
GE Multilin G60 \ Relay Parameter Section \ Grouped Elements \ Group1 \ Voltage
Elements \ Neutral OV \ Neutral OV 3
Description Name Value
Function Function Disabled
Source Source SRC 1 (SRC 1)
Pickup Pickup 0.300 pu
Curve Curve Definite Time
Pickup Delay Pickup Delay 1.00 s
Reset Delay Reset Delay 1.00 s
Block Block OFF
Target Target Self-reset
Events Events Disabled

.
GE Multilin G60 \ Relay Parameter Section \ Grouped Elements \ Group1 \ Voltage
Elements \ Negative Sequence OV \ Neg Seq OV1
Description Name Value
Function Function Disabled
Source Source SRC 1 (SRC 1)
Pickup Pickup 0.300 pu
Pickup Delay Pickup Delay 0.50 s
Reset Delay Reset Delay 0.50 s
Block Block OFF
Target Target Self-reset
Events Events Disabled

.
GE Multilin G60 \ Relay Parameter Section \ Grouped Elements \ Group1 \ Voltage
Elements \ Negative Sequence OV \ Neg Seq OV2
Description Name Value
Function Function Disabled
Source Source SRC 1 (SRC 1)
Pickup Pickup 0.300 pu
Pickup Delay Pickup Delay 0.50 s
Reset Delay Reset Delay 0.50 s
Block Block OFF
Target Target Self-reset
Events Events Disabled

.
GE Multilin G60 \ Relay Parameter Section \ Grouped Elements \ Group1 \ Voltage
Elements \ Negative Sequence OV \ Neg Seq OV3
Description Name Value
Function Function Disabled
Source Source SRC 1 (SRC 1)
Pickup Pickup 0.300 pu
Pickup Delay Pickup Delay 0.50 s
Reset Delay Reset Delay 0.50 s
Block Block OFF
Target Target Self-reset
Events Events Disabled
.
GE Multilin G60 \ Relay Parameter Section \ Grouped Elements \ Group1 \ Voltage
Elements \ Auxiliary UV \ Auxiliary UV 1
Description Name Value
Function Function Disabled
Source Source SRC 1 (SRC 1)
Pickup Pickup 0.700 pu
Curve Curve Definite Time
Delay Delay 1.00 s
Minimum Voltage Minimum Voltage 0.100 pu
Block Block OFF
Target Target Self-reset
Events Events Disabled

.
GE Multilin G60 \ Relay Parameter Section \ Grouped Elements \ Group1 \ Voltage
Elements \ Auxiliary UV \ Auxiliary UV 2
Description Name Value
Function Function Disabled
Source Source SRC 1 (SRC 1)
Pickup Pickup 0.700 pu
Curve Curve Definite Time
Delay Delay 1.00 s
Minimum Voltage Minimum Voltage 0.100 pu
Block Block OFF
Target Target Self-reset
Events Events Disabled

.
GE Multilin G60 \ Relay Parameter Section \ Grouped Elements \ Group1 \ Voltage
Elements \ Auxiliary OV \ Auxiliary OV 1
Description Name Value
Function Function Enabled
Source Source TERM (SRC 2)
Pickup Pickup 0.150 pu
Pickup Delay Pickup Delay 0.50 s
Reset Delay Reset Delay 1.00 s
Block Block OFF
Target Target Latched
Events Events Enabled

.
GE Multilin G60 \ Relay Parameter Section \ Grouped Elements \ Group1 \ Voltage
Elements \ Auxiliary OV \ Auxiliary OV 2
Description Name Value
Function Function Disabled
Source Source SRC 1 (SRC 1)
Pickup Pickup 0.300 pu
Pickup Delay Pickup Delay 1.00 s
Reset Delay Reset Delay 1.00 s
Block Block OFF
Target Target Self-reset
Events Events Disabled

.
GE Multilin G60 \ Relay Parameter Section \ Grouped Elements \ Group1 \ Voltage
Elements \ Volts Per Hertz \ Volts Per Hertz 1
Description Name Value
Function Function Enabled
Source Source TERM (SRC 2)
VHZ Voltage Mode VHZ Voltage Mode Phase to Ground
Pickup Pickup 1.10 pu
Curve Curve Inverse A
TD Multiplier TD Multiplier 2.00
T Reset T Reset 600.0 s
Block Block OFF
Target Target Latched
Events Events Enabled

.
GE Multilin G60 \ Relay Parameter Section \ Grouped Elements \ Group1 \ Voltage
Elements \ Volts Per Hertz \ Volts Per Hertz 2
Description Name Value
Function Function Enabled
Source Source TERM (SRC 2)
VHZ Voltage Mode VHZ Voltage Mode Phase to Ground
Pickup Pickup 1.20 pu
Curve Curve Definite Time
TD Multiplier TD Multiplier 1.00
T Reset T Reset 600.0 s
Block Block OFF
Target Target Latched
Events Events Enabled

.
GE Multilin G60 \ Relay Parameter Section \ Grouped Elements \ Group1 \ Loss of
Excitation
Description Name Value
Function Function Enabled
Source Source TERM (SRC 2)
Center 1 Center 1 55.53 Ohm
Radius 1 Radius 1 44.00 Ohm
UV Supervision Enable 1 UV Supervision Enable 1 Enabled
Pickup Delay 1 Pickup Delay 1 0.050 s
Center 2 Center 2 103.71 Ohm
Radius 2 Radius 2 92.18 Ohm
UV Supervision Enable 2 UV Supervision Enable 2 Disabled
Pickup Delay 2 Pickup Delay 2 0.500 s
UV Supervision UV Supervision 0.700 pu
Block Block VT FAILURE On
(VO11)
Target Target Latched
Events Events Enabled

.
GE Multilin G60 \ Relay Parameter Section \ Grouped Elements \ Group1 \ Accidental
Energization
Description Name Value
Function Function Enabled
Source Source TERM (SRC 2)
Accidental Energization Arming Mode Accidental Energization Arming UV and Offline
Mode
Accidental Energization OC Pickup Accidental Energization OC 0.500 pu
Pickup
Accidental Energization UV Pickup Accidental Energization UV 0.700 pu
Pickup
Accidental Energization Offline Accidental Energization Offline 52GC Off(H6a)
Block Block OFF
Target Target Self-reset
Events Events Enabled

.
GE Multilin G60 \ Relay Parameter Section \ Grouped Elements \ Group1 \ Stator Ground \
Stator Ground Source
Description Name Value
Source Source NEUT (SRC 1)
.
GE Multilin G60 \ Relay Parameter Section \ Grouped Elements \ Group1 \ Stator Ground \
100% Stator Ground
Description Name Value
Function Function Disabled
Stage 1 Pickup Stage 1 Pickup 0.150 pu
Stage 1 Pickup Delay Stage 1 Pickup Delay 1.00 s
Stage 1 Supv Stage 1 Supv 0.0057 pu
Stage 2 Pickup Stage 2 Pickup 0.150 pu
Stage 2 Pickup Delay Stage 2 Pickup Delay 0.00 s
Stage 2 Supv Stage 2 Supv 0.0045 pu
Block Block OFF
Target Target Self-reset
Event Event Disabled

.
GE Multilin G60 \ Relay Parameter Section \ Grouped Elements \ Group1 \ Stator Ground \
3rd Harmonic Ntrl UV
Description Name Value
Function Function Disabled
Pickup Pickup 0.3000 pu
Delay Delay 0.00 s
Max Power Max Power 0.200 pu
Min Power Min Power 0.200 pu
Volt Supervision Volt Supervision 0.500 pu
Block Block OFF
Target Target Self-reset
Events Events Disabled

.
GE Multilin G60 \ Relay Parameter Section \ Grouped Elements \ Group1 \ Stator Ground \
Subharmonic Stator Ground
Description Name Value
Function Function Disabled
SH Stator GND Stage 1 Pickup SH Stator GND Stage 1 Pickup 10 kOhm
SH Stator GND Stage 1 Pickup Delay SH Stator GND Stage 1 Pickup 10.0 s
Delay
SH Stator GND Stage 2 Pickup SH Stator GND Stage 2 Pickup 3 kOhm
SH Stator GND Stage 2 Pickup Delay SH Stator GND Stage 2 Pickup 1.0 s
Delay
SH CT Angle Compensation SH CT Angle Compensation 0.00 °
SH Stator Ground OC Pickup SH Stator Ground OC Pickup 0.010 pu
SH Stator Ground OC Delay SH Stator Ground OC Delay 1.00 s
SH Stator Ground Voltage Supervision SH Stator Ground Voltage 0.000 pu
Supervision
SH Stator Ground Current Supervision SH Stator Ground Current 0.000 pu
Supervision
Block Block OFF
Target Target Self-reset
Events Events Disabled

.
GE Multilin G60 \ Relay Parameter Section \ Grouped Elements \ Group1 \ Power \
Sensitive Directional Power \ Sensitive Directional Power \ Sens Dir Power1
Description Name Value
UnderPower 1 Function Function Enabled
Signal Source Signal Source TERM (SRC 2)
Sensitive Directional Power RCA Sensitive Directional Power 180 deg
RCA
Sensitive Directional Power Calibration Sensitive Directional Power 0.20 deg
Calibration
Stage 1 SMIN Stage 1 SMIN 0.005 pu
Stage 1 Delay Stage 1 Delay 0.50 s
Stage 2 SMIN Stage 2 SMIN 0.009 pu
Stage 2 Delay Stage 2 Delay 3.00 s
UnderPower 2 Block Block VT FAILURE On
(VO11)
UnderPower 2 Target Target Self-reset
UnderPower 2 Events Events Enabled

.
GE Multilin G60 \ Relay Parameter Section \ Grouped Elements \ Group1 \ Power \
Sensitive Directional Power \ Sensitive Directional Power \ Sens Dir Power2
Description Name Value
UnderPower 2 Function Function Disabled
Signal Source Signal Source SRC 1 (SRC 1)
Sensitive Directional Power RCA Sensitive Directional Power 0 deg
RCA
Sensitive Directional Power Calibration Sensitive Directional Power 0.00 deg
Calibration
Stage 1 SMIN Stage 1 SMIN 0.100 pu
Stage 1 Delay Stage 1 Delay 0.50 s
Stage 2 SMIN Stage 2 SMIN 0.100 pu
Stage 2 Delay Stage 2 Delay 20.00 s
UnderPower 2 Block Block OFF
UnderPower 2 Target Target Self-reset
UnderPower 2 Events Events Disabled

.
GE Multilin G60 \ Relay Parameter Section \ Control Elements \ Underfrequency \
Underfrequency 1
Description Name Value
Function Function Enabled
Block Block 27P&81U BL On
(VO13)
Signal Source Source TERM (SRC 2)
Min Volt/Amp Min Volt/Amp 0.15 pu
Pickup Pickup 48.50 Hz
Delay Pickup Delay 5.000 s
Reset Delay Reset Delay 0.500 s
Target Target Latched
Events Events Enabled

.
GE Multilin G60 \ Relay Parameter Section \ Control Elements \ Underfrequency \
Underfrequency 2
Description Name Value
Function Function Enabled
Block Block 27P&81U BL On
(VO13)
Signal Source Source TERM (SRC 2)
Min Volt/Amp Min Volt/Amp 0.15 pu
Pickup Pickup 47.00 Hz
Delay Pickup Delay 0.500 s
Reset Delay Reset Delay 0.500 s
Target Target Latched
Events Events Enabled

.
GE Multilin G60 \ Relay Parameter Section \ Control Elements \ Underfrequency \
Underfrequency 3
Description Name Value
Function Function Disabled
Block Block OFF
Signal Source Source SRC 1 (SRC 1)
Min Volt/Amp Min Volt/Amp 0.10 pu
Pickup Pickup 59.50 Hz
Delay Pickup Delay 2.000 s
Reset Delay Reset Delay 2.000 s
Target Target Self-reset
Events Events Disabled

.
GE Multilin G60 \ Relay Parameter Section \ Control Elements \ Underfrequency \
Underfrequency 4
Description Name Value
Function Function Disabled
Block Block OFF
Signal Source Source SRC 1 (SRC 1)
Min Volt/Amp Min Volt/Amp 0.10 pu
Pickup Pickup 59.50 Hz
Delay Pickup Delay 2.000 s
Reset Delay Reset Delay 2.000 s
Target Target Self-reset
Events Events Disabled

.
GE Multilin G60 \ Relay Parameter Section \ Control Elements \ Underfrequency \
Underfrequency 5
Description Name Value
Function Function Disabled
Block Block OFF
Signal Source Source SRC 1 (SRC 1)
Min Volt/Amp Min Volt/Amp 0.10 pu
Pickup Pickup 59.50 Hz
Delay Pickup Delay 2.000 s
Reset Delay Reset Delay 2.000 s
Target Target Self-reset
Events Events Disabled

.
GE Multilin G60 \ Relay Parameter Section \ Control Elements \ Underfrequency \
Underfrequency 6
Description Name Value
Function Function Disabled
Block Block OFF
Signal Source Source SRC 1 (SRC 1)
Min Volt/Amp Min Volt/Amp 0.10 pu
Pickup Pickup 59.50 Hz
Delay Pickup Delay 2.000 s
Reset Delay Reset Delay 2.000 s
Target Target Self-reset
Events Events Disabled

.
GE Multilin G60 \ Relay Parameter Section \ Control Elements \ Overfrequency \
Overfrequency 1
Description Name Value
Function Function Enabled
Block Block OFF
Signal Source Source TERM (SRC 2)
Min Volt/Amp Min Volt/Amp 0.10 pu
Pickup Pickup 51.500 Hz
Delay Pickup Delay 10.00 s
Reset Delay Reset Delay 0.50 s
Target Target Latched
Events Events Enabled

.
GE Multilin G60 \ Relay Parameter Section \ Control Elements \ Overfrequency \
Overfrequency 2
Description Name Value
Function Function Enabled
Block Block OFF
Signal Source Source TERM (SRC 2)
Min Volt/Amp Min Volt/Amp 0.10 pu
Pickup Pickup 53.000 Hz
Delay Pickup Delay 1.00 s
Reset Delay Reset Delay 0.50 s
Target Target Latched
Events Events Enabled

.
GE Multilin G60 \ Relay Parameter Section \ Control Elements \ Overfrequency \
Overfrequency 3
Description Name Value
Function Function Disabled
Block Block OFF
Signal Source Source SRC 1 (SRC 1)
Min Volt/Amp Min Volt/Amp 0.10 pu
Pickup Pickup 60.500 Hz
Delay Pickup Delay 0.50 s
Reset Delay Reset Delay 0.50 s
Target Target Self-reset
Events Events Disabled

.
GE Multilin G60 \ Relay Parameter Section \ Control Elements \ Overfrequency \
Overfrequency 4
Description Name Value
Function Function Disabled
Block Block OFF
Signal Source Source SRC 1 (SRC 1)
Min Volt/Amp Min Volt/Amp 0.10 pu
Pickup Pickup 60.500 Hz
Delay Pickup Delay 0.50 s
Reset Delay Reset Delay 0.50 s
Target Target Self-reset
Events Events Disabled

.
GE Multilin G60 \ Relay Parameter Section \ Control Elements \ Synchrocheck \
Synchrocheck1
Description Name Value
Function Function Enabled
Block Block SYN BLOCKED On
(VO31)
V1 Source V1 Source SYN B (SRC 4)
V2 Source V2 Source SYN G (SRC 3)
Max Volt Diff Max Volt Diff 550 V
Max Angle Diff Max Angle Diff 5 °
Max Freq Diff Max Freq Diff 0.05 Hz
Freq Hysteresis Freq Hysteresis 0.06 Hz
Dead Source Select Dead Source Select DV1 and LV2
Dead V1 Max Volt Dead V1 Max Volt 0.30 pu
Dead V2 Max Volt Dead V2 Max Volt 0.30 pu
Live V1 Min Volt Live V1 Min Volt 0.70 pu
Live V2 Min Volt Live V2 Min Volt 0.70 pu
Target Target Self-reset
Events Events Enabled

.
GE Multilin G60 \ Relay Parameter Section \ Control Elements \ Synchrocheck \
Synchrocheck2
Description Name Value
Function Function Disabled
Block Block OFF
V1 Source V1 Source SRC 1 (SRC 1)
V2 Source V2 Source SRC 2 (SRC 2)
Max Volt Diff Max Volt Diff 10000 V
Max Angle Diff Max Angle Diff 30 °
Max Freq Diff Max Freq Diff 1.00 Hz
Freq Hysteresis Freq Hysteresis 0.06 Hz
Dead Source Select Dead Source Select LV1 and DV2
Dead V1 Max Volt Dead V1 Max Volt 0.30 pu
Dead V2 Max Volt Dead V2 Max Volt 0.30 pu
Live V1 Min Volt Live V1 Min Volt 0.70 pu
Live V2 Min Volt Live V2 Min Volt 0.70 pu
Target Target Self-reset
Events Events Disabled

.
GE Multilin G60 \ Relay Parameter Section \ Control Elements \ Synchrocheck \
Synchrocheck3
Description Name Value
Function Function Disabled
Block Block OFF
V1 Source V1 Source SRC 1 (SRC 1)
V2 Source V2 Source SRC 2 (SRC 2)
Max Volt Diff Max Volt Diff 10000 V
Max Angle Diff Max Angle Diff 30 °
Max Freq Diff Max Freq Diff 1.00 Hz
Freq Hysteresis Freq Hysteresis 0.06 Hz
Dead Source Select Dead Source Select LV1 and DV2
Dead V1 Max Volt Dead V1 Max Volt 0.30 pu
Dead V2 Max Volt Dead V2 Max Volt 0.30 pu
Live V1 Min Volt Live V1 Min Volt 0.70 pu
Live V2 Min Volt Live V2 Min Volt 0.70 pu
Target Target Self-reset
Events Events Disabled

.
GE Multilin G60 \ Relay Parameter Section \ Control Elements \ Synchrocheck \
Synchrocheck4
Description Name Value
Function Function Disabled
Block Block OFF
V1 Source V1 Source SRC 1 (SRC 1)
V2 Source V2 Source SRC 2 (SRC 2)
Max Volt Diff Max Volt Diff 10000 V
Max Angle Diff Max Angle Diff 30 °
Max Freq Diff Max Freq Diff 1.00 Hz
Freq Hysteresis Freq Hysteresis 0.06 Hz
Dead Source Select Dead Source Select LV1 and DV2
Dead V1 Max Volt Dead V1 Max Volt 0.30 pu
Dead V2 Max Volt Dead V2 Max Volt 0.30 pu
Live V1 Min Volt Live V1 Min Volt 0.70 pu
Live V2 Min Volt Live V2 Min Volt 0.70 pu
Target Target Self-reset
Events Events Disabled

.
GE Multilin G60 \ Relay Parameter Section \ Control Elements \ Monitoring Elements \
Breaker Flashover \ Breaker Flashover 1
Description Name Value
Function Function Disabled
Side 1 Side 1 SRC 1 (SRC 1)
Side 2 Side 2 None
Status Closed A Status Closed A OFF
Status Closed B Status Closed B OFF
Status Closed C Status Closed C OFF
V Pickup V Pickup 0.850 pu
Diff V Pickup Diff V Pickup 1000 V
Amp Pickup Amp Pickup 0.600 pu
Pickup Delay Pickup Delay 0.100 s
Supv A Supv A OFF
Supv B Supv B OFF
Supv C Supv C OFF
Block Block OFF
Target Target Self-reset
Events Events Disabled

.
GE Multilin G60 \ Relay Parameter Section \ Control Elements \ Monitoring Elements \
Breaker Flashover \ Breaker Flashover 2
Description Name Value
Function Function Disabled
Side 1 Side 1 SRC 1 (SRC 1)
Side 2 Side 2 None
Status Closed A Status Closed A OFF
Status Closed B Status Closed B OFF
Status Closed C Status Closed C OFF
V Pickup V Pickup 0.850 pu
Diff V Pickup Diff V Pickup 1000 V
Amp Pickup Amp Pickup 0.600 pu
Pickup Delay Pickup Delay 0.100 s
Supv A Supv A OFF
Supv B Supv B OFF
Supv C Supv C OFF
Block Block OFF
Target Target Self-reset
Events Events Disabled

.
GE Multilin G60 \ Relay Parameter Section \ Control Elements \ Monitoring Elements \ CT
Failure Detector \ CT Failure Detector 1
Description Name Value
Function Function Disabled
Logic Block Logic Block OFF
3I_0 Input 1 Source 3I_0 Input 1 Source SRC 1 (SRC 1)
3I_0 Input 1 Pickup 3I_0 Input 1 Pickup 0.2 pu
3I_0 Input 2 Source 3I_0 Input 2 Source SRC 2 (SRC 2)
3I_0 Input 2 Pickup 3I_0 Input 2 Pickup 0.2 pu
3V_0 Input Source 3V_0 Input Source SRC 1 (SRC 1)
3V_0 Input Pickup 3V_0 Input Pickup 0.2 pu
Pickup Delay Pickup Delay 1.000 s
Target Target Self-reset
Events Events Disabled

.
GE Multilin G60 \ Relay Parameter Section \ Control Elements \ Monitoring Elements \ CT
Failure Detector \ CT Failure Detector 2
Description Name Value
Function Function Disabled
Logic Block Logic Block OFF
3I_0 Input 1 Source 3I_0 Input 1 Source SRC 1 (SRC 1)
3I_0 Input 1 Pickup 3I_0 Input 1 Pickup 0.2 pu
3I_0 Input 2 Source 3I_0 Input 2 Source SRC 2 (SRC 2)
3I_0 Input 2 Pickup 3I_0 Input 2 Pickup 0.2 pu
3V_0 Input Source 3V_0 Input Source SRC 1 (SRC 1)
3V_0 Input Pickup 3V_0 Input Pickup 0.2 pu
Pickup Delay Pickup Delay 1.000 s
Target Target Self-reset
Events Events Disabled

.
GE Multilin G60 \ Relay Parameter Section \ Control Elements \ Monitoring Elements \ CT
Failure Detector \ CT Failure Detector 3
Description Name Value
Function Function Disabled
Logic Block Logic Block OFF
3I_0 Input 1 Source 3I_0 Input 1 Source SRC 1 (SRC 1)
3I_0 Input 1 Pickup 3I_0 Input 1 Pickup 0.2 pu
3I_0 Input 2 Source 3I_0 Input 2 Source SRC 2 (SRC 2)
3I_0 Input 2 Pickup 3I_0 Input 2 Pickup 0.2 pu
3V_0 Input Source 3V_0 Input Source SRC 1 (SRC 1)
3V_0 Input Pickup 3V_0 Input Pickup 0.2 pu
Pickup Delay Pickup Delay 1.000 s
Target Target Self-reset
Events Events Disabled

.
GE Multilin G60 \ Relay Parameter Section \ Control Elements \ Monitoring Elements \ CT
Failure Detector \ CT Failure Detector 4
Description Name Value
Function Function Disabled
Logic Block Logic Block OFF
3I_0 Input 1 Source 3I_0 Input 1 Source zzz (SRC 1)
3I_0 Input 1 Pickup 3I_0 Input 1 Pickup 0.2 pu
3I_0 Input 2 Source 3I_0 Input 2 Source SRC 2 (SRC 2)
3I_0 Input 2 Pickup 3I_0 Input 2 Pickup 0.2 pu
3V_0 Input Source 3V_0 Input Source zzz (SRC 1)
3V_0 Input Pickup 3V_0 Input Pickup 0.2 pu
Pickup Delay Pickup Delay 1.000 s
Target Target Self-reset
Events Events Disabled

.
GE Multilin G60 \ Relay Parameter Section \ Control Elements \ Monitoring Elements \ VT
Fuse Failure \ VT Fuse Failure 1
Description Name Value
Function Function Disabled
Alarm Delay Alarm Delay 1.000 s
Neutral Wire Open Detection Neutral Wire Open Detection Disabled
3rd Harmonic Pickup 3rd Harmonic Pickup 0.100 pu

.
GE Multilin G60 \ Relay Parameter Section \ Control Elements \ Monitoring Elements \ VT
Fuse Failure \ VT Fuse Failure 2
Description Name Value
Function Function Enabled
Alarm Delay Alarm Delay 1.000 s
Neutral Wire Open Detection Neutral Wire Open Detection Disabled
3rd Harmonic Pickup 3rd Harmonic Pickup 0.100 pu

.
GE Multilin G60 \ Relay Parameter Section \ Control Elements \ Monitoring Elements \ VT
Fuse Failure \ VT Fuse Failure 3
Description Name Value
Function Function Disabled
Alarm Delay Alarm Delay 1.000 s
Neutral Wire Open Detection Neutral Wire Open Detection Disabled
3rd Harmonic Pickup 3rd Harmonic Pickup 0.100 pu
.
GE Multilin G60 \ Relay Parameter Section \ Control Elements \ Monitoring Elements \ VT
Fuse Failure \ VT Fuse Failure 4
Description Name Value
Function Function Disabled
Alarm Delay Alarm Delay 1.000 s
Neutral Wire Open Detection Neutral Wire Open Detection Disabled
3rd Harmonic Pickup 3rd Harmonic Pickup 0.100 pu

.
GE Multilin G60 \ Relay Parameter Section \ Control Elements \ Monitoring Elements \
Thermal Overload \ Thermal Protection 1
Description Name Value
Function Function Disabled
Source Source SRC 1 (SRC 1)
Base Current Base Current 0.80 pu
k Factor k Factor 1.10
Trip Time Constant Trip Time Constant 45 min
Reset Time Constant Reset Time Constant 45 min
Minimum Reset Time Minimum Reset Time 20 min
Reset Reset OFF
Block Block OFF
Target Target Self-reset
Events Events Disabled

.
GE Multilin G60 \ Relay Parameter Section \ Control Elements \ Monitoring Elements \
Thermal Overload \ Thermal Protection 2
Description Name Value
Function Function Disabled
Source Source SRC 1 (SRC 1)
Base Current Base Current 0.80 pu
k Factor k Factor 1.10
Trip Time Constant Trip Time Constant 45 min
Reset Time Constant Reset Time Constant 45 min
Minimum Reset Time Minimum Reset Time 20 min
Reset Reset OFF
Block Block OFF
Target Target Self-reset
Events Events Disabled

.
GE Multilin G60 \ Relay Parameter Section \ Control Elements \ Frequency Rate of Change
\ Freq Rate 1
Description Name Value
Function Function Disabled
Source Source SRC 1 (SRC 1)
Trend Trend Increasing
Pickup Pickup 0.50 Hz/s
OV Supv OV Supv 0.70 pu
OC Supv OC Supv 0.20 pu
Min Min 45.00 Hz
Max Max 65.00 Hz
Pickup Delay Pickup Delay 0.000 s
Reset Delay Reset Delay 0.000 s
Block Block OFF
Target Target Self-reset
Events Events Disabled

.
GE Multilin G60 \ Relay Parameter Section \ Control Elements \ Frequency Rate of Change
\ Freq Rate 2
Description Name Value
Function Function Disabled
Source Source SRC 1 (SRC 1)
Trend Trend Increasing
Pickup Pickup 0.50 Hz/s
OV Supv OV Supv 0.70 pu
OC Supv OC Supv 0.20 pu
Min Min 45.00 Hz
Max Max 65.00 Hz
Pickup Delay Pickup Delay 0.000 s
Reset Delay Reset Delay 0.000 s
Block Block OFF
Target Target Self-reset
Events Events Disabled

.
GE Multilin G60 \ Relay Parameter Section \ Control Elements \ Frequency Rate of Change
\ Freq Rate 3
Description Name Value
Function Function Disabled
Source Source SRC 1 (SRC 1)
Trend Trend Increasing
Pickup Pickup 0.50 Hz/s
OV Supv OV Supv 0.70 pu
OC Supv OC Supv 0.20 pu
Min Min 45.00 Hz
Max Max 65.00 Hz
Pickup Delay Pickup Delay 0.000 s
Reset Delay Reset Delay 0.000 s
Block Block OFF
Target Target Self-reset
Events Events Disabled

.
GE Multilin G60 \ Relay Parameter Section \ Control Elements \ Frequency Rate of Change
\ Freq Rate 4
Description Name Value
Function Function Disabled
Source Source SRC 1 (SRC 1)
Trend Trend Increasing
Pickup Pickup 0.50 Hz/s
OV Supv OV Supv 0.70 pu
OC Supv OC Supv 0.20 pu
Min Min 45.00 Hz
Max Max 65.00 Hz
Pickup Delay Pickup Delay 0.000 s
Reset Delay Reset Delay 0.000 s
Block Block OFF
Target Target Self-reset
Events Events Disabled

.
GE Multilin G60 \ Relay Parameter Section \ Control Elements \ Frequency OOB
Accumulation
Description Name Value
Freq OOB Accumulator Source Freq OOB Accumulator Source NEUT (SRC 1)
Freq OOB Accumulator Min V A Freq OOB Accumulator Min V A 0.10 pu
Freq OOB Accumulator Block Freq OOB Accumulator Block OFF
Freq OOB Accumulator Target Freq OOB Accumulator Target Self-reset
Freq OOB Accumulator Events Freq OOB Accumulator Events Disabled
Freq OOB Accumulator 1 Function Freq OOB Accumulator 1 Disabled
Function
Freq OOB Accumulator 1 Upper Freq Freq OOB Accumulator 1 Upper 60.00 Hz
Freq
Freq OOB Accumulator 1 Lower Freq Freq OOB Accumulator 1 60.00 Hz
Lower Freq
Freq OOB Accumulator 1 Time Limit Freq OOB Accumulator 1 Time 200 s
Limit
Freq OOB Accumulator 1 Time Preset Freq OOB Accumulator 1 Time 0 s
Preset
Freq OOB Accumulator 2 Function Freq OOB Accumulator 2 Disabled
Function
Freq OOB Accumulator 2 Upper Freq Freq OOB Accumulator 2 Upper 60.00 Hz
Freq
Freq OOB Accumulator 2 Lower Freq Freq OOB Accumulator 2 60.00 Hz
Lower Freq
Freq OOB Accumulator 2 Time Limit Freq OOB Accumulator 2 Time 200 s
Limit
Freq OOB Accumulator 2 Time Preset Freq OOB Accumulator 2 Time 0 s
Preset
Freq OOB Accumulator 3 Function Freq OOB Accumulator 3 Disabled
Function
Freq OOB Accumulator 3 Upper Freq Freq OOB Accumulator 3 Upper 60.00 Hz
Freq
Freq OOB Accumulator 3 Lower Freq Freq OOB Accumulator 3 60.00 Hz
Lower Freq
Freq OOB Accumulator 3 Time Limit Freq OOB Accumulator 3 Time 200 s
Limit
Freq OOB Accumulator 3 Time Preset Freq OOB Accumulator 3 Time 0 s
Preset
Freq OOB Accumulator 4 Function Freq OOB Accumulator 4 Disabled
Function
Freq OOB Accumulator 4 Upper Freq Freq OOB Accumulator 4 Upper 60.00 Hz
Freq
Freq OOB Accumulator 4 Lower Freq Freq OOB Accumulator 4 60.00 Hz
Lower Freq
Freq OOB Accumulator 4 Time Limit Freq OOB Accumulator 4 Time 200 s
Limit
Freq OOB Accumulator 4 Time Preset Freq OOB Accumulator 4 Time 0 s
Preset
Freq OOB Accumulator 5 Function Freq OOB Accumulator 5 Disabled
Function
Freq OOB Accumulator 5 Upper Freq Freq OOB Accumulator 5 Upper 60.00 Hz
Freq
Freq OOB Accumulator 5 Lower Freq Freq OOB Accumulator 5 60.00 Hz
Lower Freq
Freq OOB Accumulator 5 Time Limit Freq OOB Accumulator 5 Time 200 s
Limit
Freq OOB Accumulator 5 Time Preset Freq OOB Accumulator 5 Time 0 s
Preset
Freq OOB Accumulator 6 Function Freq OOB Accumulator 6 Disabled
Function
Freq OOB Accumulator 6 Upper Freq Freq OOB Accumulator 6 Upper 60.00 Hz
Freq
Freq OOB Accumulator 6 Lower Freq Freq OOB Accumulator 6 60.00 Hz
Lower Freq
Freq OOB Accumulator 6 Time Limit Freq OOB Accumulator 6 Time 200 s
Limit
Freq OOB Accumulator 6 Time Preset Freq OOB Accumulator 6 Time 0 s
Preset
Freq OOB Accumulator 7 Function Freq OOB Accumulator 7 Disabled
Function
Freq OOB Accumulator 7 Upper Freq Freq OOB Accumulator 7 Upper 60.00 Hz
Freq
Freq OOB Accumulator 7 Lower Freq Freq OOB Accumulator 7 60.00 Hz
Lower Freq
Freq OOB Accumulator 7 Time Limit Freq OOB Accumulator 7 Time 200 s
Limit
Freq OOB Accumulator 7 Time Preset Freq OOB Accumulator 7 Time 0 s
Preset

.
GE Multilin G60 \ Additional Information \ General - General Information
Description Name Value
Manufacturer Manufacturer GE
Device Model Device Model Multilin G60
Serial Number Serial Number serial no.
Device Address Device Address device address
Device type Device type Generator Protection
Manufacturer HW code Hardware revision
Software revision Software revision
Substation Substation Substation
Substation Address Substation Address Substation address
Feeder Feeder feeder
Feeder Address Feeder Address feeder address
Bay Bay bay
Bay address Bay address bay address
Protected object name Protected object name Protected object name
Description Description information
Location Location Location

.
GE Multilin G60 \ Additional Information \ Relay Information \ Stator Differential
Description Name Value
Operating Time Operating Time 20.00 ms
Abs. Timing Tolerance Abs. Timing Tolerance 15.00 ms
Rel. Timing Tolerance Rel. Timing Tolerance 3.00 %
Abs. Current Tolerance Abs. Current Tolerance 50.00 mA
Rel. Current Tolerance Rel. Current Tolerance 3.00 %

.
GE Multilin G60 \ Additional Information \ Relay Information \ Phase Distance
Description Name Value
Relative Impedance Tol. Z Tol. rel. 5.00 %
Absolute Impedance Tol. Z Tol. abs. 20.00 mOhm
Relative Timing Tol. Time Tol. rel. 3.00 %
Absolute Timing Tol. Time Tol. abs. 5.00 ms
Angle Accuracy Angle Accuracy 2.00 °
Min. operating Time Min. operating Time 30.00 ms
Current supervision pick-up/drop-off ratio Current supervision pick- 0.97
up/drop-off ratio

.
GE Multilin G60 \ Additional Information \ Relay Information \ Loss of Excitation
Description Name Value
Relative Impedance Tol. Z Tol. rel. 3.00 %
Absolute Impedance Tol. Z Tol. abs. 20.00 mOhm
Relative Timing Tol. Time Tol. rel. 3.00 %
Absolute Timing Tol. Time Tol. abs. 20.00 ms
Angle Accuracy Angle Accuracy 2.00 °
Min. operating Time <50ms Min. operating Time 50.00 ms

.
GE Multilin G60 \ Additional Information \ Relay Information \
Phase\Neutral\Ground\NegSeq OC
Description Name Value
Abs. current tolerance (Maximum of TOC and IOC) Abs. current tolerance 10.00 mA
Rel. current tolerance (Maximum of TOC and IOC) Rel. current tolerance 1.50 %
Abs. timing tolerance (Maximum of TOC and IOC) Abs. timing tolerance 10.00 ms
Rel. timing tolerance (Maximum of TOC and IOC) Rel. timing tolerance 3.50 %
Dropout level Dropout level 0.97
Min. operate time Min. operate time 25.00 ms
Angle accuracy Angle accuracy 2.00 °

.
GE Multilin G60 \ Additional Information \ Relay Information \ Power
Description Name Value
Operating Time 50.00 ms
Abs. t-Tolerance 5.00 ms
Rel. t-Tolerance 3.00 %
Rel S-Tolerance 5.000 %

.
GE Multilin G60 \ Additional Information \ Relay Information \ Voltage
Description Name Value
Undervoltage Drop-off / Pickup 102.00 %
Ratio
Overvoltage Drop-off / Pickup 97.00 %
Ratio
Rel. V-Tolerance 2.00 %
Rel. t-Tolerance 3.50 %
Abs. t-Tolerance 20.00 ms
Operating Time 30.00 ms

.
GE Multilin G60 \ Additional Information \ Relay Information \ Frequency
Description Name Value
Dropout Hysteresis 0.03 Hz
Pickup Accuracy 0.001 Hz
Rel. t-Tolerance 3.00 %
Abs. t-Tolerance 0.75 cy
Operating Time 4.00 cy
Test method time tolerance 0.50 cy

.
GE Multilin G60 \ Additional Information \ Relay Information \ Thermal Overload
Description Name Value
Abs. current tolerance (Maximum of TOC and IOC) Abs. current tolerance 10.00 mA
Rel. current tolerance (Maximum of TOC and IOC) Rel. current tolerance 1.50 %
Abs. timing tolerance (Maximum of TOC and IOC) Abs. timing tolerance (cold 100.00 ms
curve)
Abs. timing tolerance (Maximum of TOC and IOC) Abs. timing tolerance (hot 500.00 ms
curve)
Rel. timing tolerance (Maximum of TOC and IOC) Rel. timing tolerance 2.00 %
Min. operate time Min. operate time 25.00 ms

.
GE Multilin G60 \ Additional Information \ Relay Information \ VoltPerHertz
Description Name Value
Drop-off / Pickup Ratio 97.00 %
Level accuracy 0.02 pu
for values greater than 1.1 × pickup Rel. t-Tolerance 3.00 %
for values greater than 1.1 × pickup Abs. t-Tolerance 15.00 cy
Operating Time 30.00 ms

.
GE Multilin G60 \ Additional Information \ Relay Information \ Accidental Energization
Description Name Value
Level accuracy I> 0.50 %
Drop-off / Pickup Ratio I> 97.00 %
Level accuracy U< 0.50 %
Drop-off / Pickup Ratio U< 102.00 %
Operating Time 30.00 ms
.
GE Multilin G60 \ Additional Information \ Circuit Breaker Data
Description Name Value
52a/b Percentage 20.00 %
Abs. t-Tolerance 0.00 ms
Rel. t-Tolerance 5.00 %
CB Trip Time 50.00 ms
CB Close Time 100.00 ms

.
GE Multilin G60 \ Additional Information \ Trip/Alarm Output
Description Name Value
Stator Differential Stator Differential true
Phase Distance Z1 Phase Distance Z1 false
Phase Distance Z2 Phase Distance Z2 false
Phase Distance Z3 Phase Distance Z3 false
Thermal Overload 1 Thermal Overload 1 false
Thermal Overload 2 Thermal Overload 2 false
Phase TOC1 Phase TOC1 true
Phase IOC1 Phase IOC1 true
Phase IOC2 Phase IOC2 false
Neutral TOC1 Neutral TOC1 false
Neutral IOC1 Neutral IOC1 false
Ground TOC1 Ground TOC1 false
Ground IOC1 Ground IOC1 false
Neg Seq DIR OC1 FWD Neg Seq DIR OC1 FWD false
Neg Seq DIR OC1 REV Neg Seq DIR OC1 REV false
Neg Seq DIR OC2 FWD Neg Seq DIR OC2 FWD false
Neg Seq DIR OC2 REV Neg Seq DIR OC2 REV false
Generator Unbalance STG1 GEN UNBAL STG1 false
Generator Unbalance STG2 GEN UNBAL STG2 false
Generator Unbalance STG2 Alarm GEN UNBAL STG2 Alarm false
Phase UV 1 Phase UV 1 false
Phase UV 2 Phase UV 2 false
Phase UV 3 Phase UV 3 false
Phase OV 1 Phase OV 1 false
Phase OV 2 Phase OV 2 false
Phase OV 3 Phase OV 3 false
Neutral OV 1 Neutral OV 1 false
Neutral OV 2 Neutral OV 2 false
Neutral OV 3 Neutral OV 3 false
Neg Seq OV 1 Neg Seq OV 1 false
Neg Seq OV 2 Neg Seq OV 2 false
Neg Seq OV 3 Neg Seq OV 3 false
Auxiliary UV1 Auxiliary UV1 false
Auxiliary UV2 Auxiliary UV2 false
Auxiliary OV1 Auxiliary OV1 false
Auxiliary OV2 Auxiliary OV2 false
Volts Per Hertz Alarm Volts Per Hertz Alarm false
Volts Per Hertz 1 Volts Per Hertz 1 false
Volts Per Hertz 2 Volts Per Hertz 2 false
Loss of Excitation Loss of Excitation false
Accidental Energization Accidental Energization false
Sens Dir Power 1 Sens Dir Power 1 false
Sens Dir Power 2 Sens Dir Power 2 false
Underfrequency 1 Underfrequency 1 false
Underfrequency 2 Underfrequency 2 false
Underfrequency 3 Underfrequency 3 false
Underfrequency 4 Underfrequency 4 false
Underfrequency 5 Underfrequency 5 false
Underfrequency 6 Underfrequency 6 false
Overfrequency 1 Overfrequency 1 false
Overfrequency 2 Overfrequency 2 false
Overfrequency 3 Overfrequency 3 false
Overfrequency 4 Overfrequency 4 false
.
GE Multilin G60 \ Additional Information \ Test Information \ Phase Undervoltage
Description Name Value
> PHASE UV1 MINIMUM VOLTAGE ! Phase UV1 Relative Test 0.95 x Pickup
Voltage
> PHASE UV2 MINIMUM VOLTAGE ! Phase UV2 Relative Test 0.95 x Pickup
Voltage
> PHASE UV3 MINIMUM VOLTAGE ! Phase UV3 Relative Test 0.95 x Pickup
Voltage

.
GE Multilin G60 \ Additional Information \ Test Information \ Test Tolerance
Description Name Value
Test Tolerance Test Tolerance 4.00 %

Test Object - Other RIO Functions


.
CB Configuration
Description Name Value
CB trip time CB trip time 50.00 ms
CB close time CB close time 100.00 ms
Times for 52a, 52b in percent of CB time 52a, 52b % of CB 20.00 %

Test Object - Distance Settings


. . . .
System parameters:
Line length: 5.000 Ω Line angle: 85.00 °
PT connection: at line CT starpoint: Dir. line
Impedance correction no
1A/I nom:
Impedances in primary no
values:
. . . .
Tolerances:
Tol. T rel.: 3.000 %
Tol. T abs. +: 5.000 ms Tol. T abs. -: 5.000 ms
Tol. Z rel.: 5.000 % Tol. Z abs.: 20.00 mΩ
. . . .
Grounding factor:
kL mag.: 0.000000 kL angle: 0.000000°
Separate arc resistance: no

Zone Settings:
Label Type Fault loop Trip time Tol.T rel Tol.T abs+ Tol.T abs- Tol.Z rel. Tol.Z abs
Z1 All Tripping All 500.0 ms 3.000 % 100.0 ms 100.0 ms 5.000 % 20.00 mΩ
Z2 All Tripping All 250.0 ms 3.000 % 100.0 ms 100.0 ms 5.000 % 20.00 mΩ
X/Ω

-5

-10

-15

-20

-25

-30

-20 -15 -10 -5 0 5 10 15 20


R/Ω

Linked XRIO References


Reference Name Unit Value XRIO Path
RIO.DEVICE.NOMINALVALUES.INOM In 1.00 A RIO/Device/Nominal Values/In
RIO.DEVICE.NOMINALVALUES.VNOM V_nom 110.00 V RIO/Device/Nominal Values/V nom

Comment

. .
Test Module
Name: OMICRON Advanced Distance Version: 3.01
Test Start: 03-Jan-2018 11:29:21 Test End: 03-Jan-2018 11:30:01
User Name: Manager:
Company:

Test Settings
.
Test model:
Test model: constant test voltage VTest 40.00 V
Allow reduction of no kS = kL: no
ITest/VTest:
ZS mag.: 0.000 Ω ZS angle: 0.00 °
kS mag.: 1.000 kS angle: 0.00 °
.
Fault Inception:
Mode: random
DC-offset: no
.
Times:
Prefault: 1.000 s Max. fault: 6.000 s
Postfault: 500.0 ms Time reference: fault inception

.
Other:
Extended zones: not active Switch off at zero crossing: yes
Load current enabled: no Load current:: n/a

.
Search Settings:
Search res. rel.: 1.000 % Search res. abs.: 50.00 mΩ
Ignore nominal no
characteristics:
Search interval: 200.0 mΩ

.
Auxiliary Binary Outputs:
Name Fault inception Slope Trip Delay time Slope
Delay time
Ext. zones active n/a Open n/a Open

Test Results
Shot Test: Fault Type L1-L2-L3
|Z| Phi % % of t nom t act. Dev. VTest Result
4.783 Ω -40.00 ° n/a 250.0 ms 271.2 ms 8.48 % 40.00 V Passed
11.31 Ω -45.00 ° n/a 250.0 ms 281.4 ms 12.56 % 40.00 V Passed
19.53 Ω -55.01 ° n/a 250.0 ms 283.9 ms 13.56 % 40.00 V Passed
22.48 Ω -74.18 ° n/a 250.0 ms 281.2 ms 12.48 % 40.00 V Passed
22.76 Ω -103.34 ° n/a 250.0 ms 280.2 ms 12.08 % 40.00 V Passed
18.30 Ω -123.17 ° n/a 250.0 ms 275.4 ms 10.16 % 40.00 V Passed
11.31 Ω -135.00 ° n/a 250.0 ms 270.7 ms 8.28 % 40.00 V Passed
5.843 Ω -130.00 ° n/a 250.0 ms 269.9 ms 7.96 % 40.00 V Passed
8.000 Ω 80.00 ° n/a 500.0 ms 534.2 ms 6.84 % 40.00 V Passed
6.812 Ω 60.00 ° n/a 500.0 ms 532.8 ms 6.56 % 40.00 V Passed
4.000 Ω 50.00 ° n/a 500.0 ms 525.5 ms 5.1 % 40.00 V Passed
3.231 Ω 120.00 ° n/a 500.0 ms 525.8 ms 5.16 % 40.00 V Passed
5.676 Ω 120.00 ° n/a 500.0 ms 533.2 ms 6.64 % 40.00 V Passed
7.521 Ω 100.00 ° n/a 500.0 ms 535.8 ms 7.16 % 40.00 V Passed
X/Ω

-5

-10

-15

-20

-25

-30

-20 -15 -10 -5 0 5 10 15 20


R/Ω

Shot Details:
.
Parameters:
Fault Type: L1-L2-L3
| Z |: 7.521 Ω Phi: 100.00 °
R: -1.306 Ω X: 7.406 Ω
%: n/a % of:
VTest 40.00 V

.
Results:
t act.: 535.8 ms Assessment: Passed
t nom: 500.0 ms Dev.: 7.16 %
t min: 400.0 ms t max: 600.0 ms

. .
Fault Quantities (natural): Fault Quantities (symmetrical):
VL1: 40.00 V 0.00 ° V0: 0.000 V n/a
VL2: 40.00 V -120.00 ° V1: 40.00 V 0.00 °
VL3: 40.00 V 120.00 ° V2: 0.000 V n/a
IL1: 5.319 A -100.00 ° I0: 0.000 A n/a
IL2: 5.319 A -220.00 ° I1: 5.319 A -100.00 °
IL3: 5.319 A 20.00 ° I2: 0.000 A n/a
VFault: 40.00 V 0.00 °
IFault: 5.319 A -100.00 °

Fault Trip
V/V
50
40
30
20
10
0
-10 -0.9 -0.8 -0.7 -0.6 -0.5 -0.4 -0.3 -0.2 -0.1 -0.0 0.1 0.2 0.3 0.4
t/s
-20
-30
-40
-50
-60
VL1 VL2 VL3

I/A

-2 -0.9 -0.8 -0.7 -0.6 -0.5 -0.4 -0.3 -0.2 -0.1 -0.0 0.1 0.2 0.3 0.4
t/s

-4

-6

-8
IL1 IL2 IL3

Trip
Start

-0.9 -0.8 -0.7 -0.6 -0.5 -0.4 -0.3 -0.2 -0.1 -0.0 0.1 0.2 0.3 0.4
t/s

.
Cursor Data
Time Signal Value
Cursor 1 0.000 s <none> n/a
Cursor 2 535.8 ms <none> n/a
C2 - C1 535.8 ms n/a

.
Test State:
Test passed