One Way Slab Design Sheet

L 12 ft Shorter Dimension of the Slab


Lb/La > 2
Cs 20 Coefficient for One way Slab
thickness
Fc 3 Ksi
Fy 60 Ksi
Slab S.S OEC BEC Cantilever
(L/20) L/24 L/28 L/10

hf 7.2 in (L*12)/Cs
Say hf 7 in hf taken for design
b 12 in

(A) Mud + Tile 65 Psf (Take 60 to 65 Psf)


(hf * 130)/12 Psf
(B) Slab Weight 87.5 Psf (hf * 150)/12 Psf

(C) L.L 80 Psf May be taken 60, 80, 1000

Un-Restrained End
-10 -11 -11 -11
(D) Wu 0.311 Psf
C+ 8 +11 +16 +16

C- 10
M+ 5.598 K-ft
M- 4.4784 K-ft
Rho+ 0.00356 Use 880 P -24 -9 -9 -14
Rho- 0.0046 Use 880 P
Rho min 0.0033 +14 +14
As+ 0.29904 in 2
-16 -16
As- 0.3864 in2
Integral End More Than 2 SPANS
As min 0.2772 in2 For Beam
Provide for -24 -10 -11 -11 -11 -11 -11
As+ 4#4
2.5 in2 +14 +16 +16
As- 4#4 -16
2.5 in2
Beem Design Sheet for Negative Movements (Assuming One Way Distribution)

L 20 (ft) (Beem Length between Supports)


Beam S.S OEC BEC Cantilever
(L/10) L/18.5 L/21 L/8
Cs 18.5 (Coefficient for Beem thickness)
fc 3 (ksi)
fy 60 (ksi)
Tf 0.8
hf 6 (Thickness of Slab)
h min 10.38 (Beem depth)
Say h 24 (Assume depth based on span length)
b 12

Slab wt-1 75 psf


mud + tile-2 65 psf
Beem wt-3 0.3 Kip / ft
Slab Span 10 ft
L.L 100 psf
F.D.L /ft = WuDL 1.68 Kip / ft
F.L.L / ft = WuLL 1.6 (multiply L.L by Slab Span)
Wu 3.28 Kip / ft (WuDL+WuLL)
C 10 (Moments Coefficient)

M neg 1576.13 Kip-in


Rho max = use 880 P
Rho Required 0.00713 = 0.002 from 200/fy = 40 ksi
Rho min = 0.0033 from 200/fy = 60 ksi
As req 1.80 in2 (Rho req * b * d)
As min 0.8316 in2 (0.0033 * b * d)
Provide As 4#6
A (provided) 2.64 in2
Beem Design Sheet for Positive Movements (Assuming one way Distribution)

C 11 (Moment Co-efficient)
Wu 3.2836 K/ft
L 20
Mu + 119.40 Kip-ft
fc 3 Ksi
d 21 in
Effective width Calculation
hf 6
b 12
(i) (L/4) 60
(ii) Beem Spacing 120 (10' Spacing)
(iii) 12 + 16 hf 108
Select beffect 60 (Minimum of (i) (ii) and (iii)

Design Strength 1239.3 Kip-ft

Note: Since design Strength is more than the factored moment


Mu so beem will act as R.T.B
Rho max use 880 P
Rho Required 0.00118 = 0.002 from 200/fy = 40 ksi
As Req 1.4868 in2 Rho min = 0.0033 from 200/fy = 60 ksi
As min 0.8316 in2
As max 13.2307164 in2

Note: As Req is not greater than As max so ok


Provide As 4#6
As Provided 1.76