Sunteți pe pagina 1din 1

Engine~~fnnJ FLUID HANDLING/MAINTENANCE

Small Drip Legs


Cause Big Problems
Correct sizing eliminates water hammer,
pipe erosion, and long startup times

THOMAS J. GRUBKA, Senior Application Engineer, Armstrong International, Inc., Three Rivers, MI

t first glance it would seem that creat- Piping, "Suitable drains or drips shall be pro-

A ing a drip leg is simply a matter of con-


necting piping or equipment to a cor-
rectly sized steam trap. But, an analysis of the
vided wherever necessary to drain the con-
densate from all sections of the piping and
equipment where it may collect. ... " Taking a
few simple precautions when laying out steam
varying conditions inside a steam system
reveals that the location and sizing of drip legs lines minimizes the number of collection
are much more complex than first meets the points.
eye. • Ensure that steam mains are well support-
Condensate moves in a combination of ed. This is one of the most important, but
ways, depending on the type of system under often overlooked, precautions. A pocket of
consideration. At startup, low pressure and a condensate can be trapped in a section of
relatively high load create a gravity flow con- main that is sagging due to insufficient sup-
dition. High condensate loads, combined with port (Fig. 1).
moderate steam velocities, cause condensate • Use eccentric fittings to provide a contin-
to flow along the perimeter of piping. Under uous path along the bottom of distribution
high-velocity, low-load conditions, conden- piping (Fig. 2).
sate actually becomes entrained in steam. • Pitch steam mains down, in the direction
Drip legs must be located and designed to of flow, not less than 1 in. for every 20 ft of
remove condensate from steam lines through- run.
out the operation cycle, regardless of conden- • Always trap each drip leg with a separate
sate flow conditions. trap. Even the slight pressure drop found
Many problems mistakenly thought of as between two adjacent drip legs is enough to
inevitable in the operation of a "typical" short circuit the system.
steam system are avoidable. Occurrences such • Properly insulate piping to minimize the
as water hammer, steam leaks resulting from amount of condensate generated in a distrib-
pipe erosion, short equipment life, reduced ution line.
heat transfer, and long startup times are often Along with these general precautions, there
reduced or eliminated by the proper place- are several specific recommendations that
ment and sizing of drip legs. should be followed for the proper placement
of drip legs. Drip legs should be located at
Drip Leg Location about 300-ft intervals along steam mains, and
According to Section I, Paragraph 118 (a) never at intervals greater that 500ft. In addi-
of the American Standard Code for Pressure tion, drip legs should be placed at risers,

Fig. 1. Condensate collects


in low areas that are created Sag In Steam Supply Main
by the sagging ofpoorly sup-
ported piping.

-/

/
Water Pocket

S-ar putea să vă placă și