Sunteți pe pagina 1din 6

RE928X

RE927X RE928X
RE927X

Honeywell DSC
Vista 20P or 15P SIM Card PowerSeries SIM Card
Tech Support Line: (715)808-0164
DATA OUT 7 A/Rx A/Rx
Yellow CLK YEL Yellow CLK
B/Tx B/Tx
Green
RE928X-01-00 / RE928X-01-01 DATA IN 6 DATA
GND
GRN Green DATA
GND
Flexible Bus CDMA Communicator AUX + 5 Red +12V AUX - BLK Black
+12V
Black Red
Features AUX - 4 AUX + RED

• Connects panels to CDMA Network


• Compatible with:
o Honeywell Vista® 15P and 20P
o DSC PowerSeries
o CADDX NX
o UTC Concord 4
o Napco GEM P816
o Future: Napco GEM P801, GEM P1632, GEM P3200, GEM P9600
• Enables:
o Alarm Reporting
o Interactive Control Functions
o Z-Wave Communicator included

Key Instructions
• The same unit works for Vista, Power Series, CADDX NX, UTC Concord 4 &
Napco GEM P816.
• Selectable switch determines panel compatibility.
• DO NOT MOUNT INSIDE METAL CAN – there are radios on the boards that
need to be in free-air to communicate.
• Communicator must be connected to a 12V power supply with battery
backup, such as the control panel's aux power output.
• The communicator should be mounted in a location that will optimize
cellular signal strength. Mount as high in the building as possible.
• RE928X communicates with the Vista 15P/20P via AUI device 2. Enable
AUI 2 in the Vista.

Wiring Instructions
NOTE: Some programming must be done PRIOR to connection
Maximum cable lengths shown in the table below, this assumes the
communicator is the only device attached to the cable. If multiple devices
share the same cable, the maximum cable length must be derated accordingly.

Wire Size (AWG) Maximum cable length to Control Panel

18 350

22 130

24 75

RE928X-01-00_RE928X-01-01_Flexible Bus CDMA Communicator Page 1 of 11 11-Nov-16 RE928X-01-00_RE928X-01-01_Flexible Bus CDMA Communicator Page 2 of 11 11-Nov-16
Tech Support: (715)808-0164 Tech Support: (715)808-0164
www.ResolutionProducts.com www.ResolutionProducts.com
Vista 20P and Vista 15P Programming: DSC Power Series Programming:
Compatible Honeywell Panels:
Vista 20P (version 4.0 or later) (controls partition 1 only)
Compatible DSC Panels:
Vista 15P (version 4.0 or later)
PC580 (Power 432) PC5020 (Power 864)
PC1555 (Power 632) PC1616
1) Refer to server setup instructions and set up the account on the Dealer Portal.
PC1555MX (Power 632) PC1832
2) Be sure to add a contact that uses the system MASTER CODE to the account before PC5010 (Power 832) PC1864
connecting the module. This will ensure the module can properly communicate PC5015 (Power 832)
with and configure required system settings.
3) Disarm the system (all partitions). 1) Refer to server setup instructions and set up the account on the Dealer Portal.
4) The RE928X automatically communicates with the Vista using AUI device 2. 2) Be sure to add a contact that uses the system MASTER CODE to the account before
The panel is probably defaulted to this. If not, enable AUI 2 in the *189 field. If a connecting the module. This will ensure the module can properly communicate
device is already using AUI 2, that device must be moved to another AUI address (AUI with and configure required system settings.
1, for Vista 15P, AUI 1, 3 or 4 for Vista 20P 3) Using the system’s Installer Code:
5) If Vista system has a *91 field that supports RIS, then RIS will need to be disabled. a) Disable the Communicator ([380]:[1])
Refer to panel programming instructions for details. If RIS is not supported no
action is required. b) Disable the Telephone Line Monitor ([015]:[7])
6) Vista 15p and 20p panel versions 10.21 and later have the keypad lockout feature c) Delete Telephone Numbers (programming section 301-303)
enabled by default. It is recommended that this feature be disabled to prevent d) Verify Alt Comm ([351]:[5]) is enabled
possible keypad lockout conditions if the system master code in the IGM is not
synchronized with the master code in the Vista panel. Use programming option e) Verify T-Link is Disabled ([382]:[5])
*188 to disable keypad lockout. f) Verify Master Code Not Changeable is Disabled ([015]:[6])
NOTE: If it is required to have the keypad lockout feature enabled, it is critical that the system g) Verify Access Code Required for *1, *2, *3 menus is disabled ([022]:[1])
master code be set up as a contact for this account before connecting the module to the panel
(see Step 2 above). Also all changes to the system master code must be done at the user portal h) Verify that keypad lockout is either zero(disabled) or higher than 6 ([012])
or dealer portal, not at the keypad. Failing to do this may result in a keypad lockout condition. i) If you have removed any bus devices, perform a Module Supervision Reset ([902])
7) Power down the Vista system.
4) Verify Alarm report codes are setup properly for zones that are being used, 1-64
8) Set RE928X panel selector switch to Honeywell: DSC CDX HW UTC (programming section 320-349). System will report as Burg(130) if programmed as
9) Connect the Vista and RE928X as shown in the Wiring Instructions above. FF.
10) Apply power to the Vista 15P/20P system. It will automatically program.
5) If using Aux input (PGM2) verify Aux input report codes are setup properly
a) Be sure ALL partitions are disarmed. (programming section 329:4). System will report as Fire (110) if programmed as FF.
b) First, the Vista control panel will be busy for 50-60 seconds after powerup.
6) To enable reporting of the Period Test Transmission, program the “periodic Test
c) Then, the module will enable the following settings automatically: Transmission” ([348]:[4]) and the “Periodic Test Transmission with Trouble”
IP/GSM device (*29) = 1 (enabled) ([348]:[3]) reporting codes to “02”

Communicate to IP/GSM device first (*55) = 1 (IP/GSM first) 7) All other reports are hardcoded in the gateway and cannot be changed regardless
Opening Report (*65) = 1 (enabled) of what is entered in the programmed location.
Closing reports (*66) = 1, 1 (stay closing & away closing reports enabled)
8) Format and account number have no effect on reporting.
Alarm cancel report (*68) = 1 (enabled)
9) Disarm the system (all partitions)
AC Power restoral report (*73) = 1 (enabled)
Low Battery restoral report (*74) = 1 (enabled) 10) Power down the DSC system.
Phone Monitor (*92) = 0 (disabled) 11) Set RE928X panel selector switch to DSC: DSC CDX HW UTC
12) Connect the DSC Panel and RE928X as shown in the Wiring Instructions above.
11) Finally, the keypad(s) should display "DISARMED Ready to Arm".
13) Apply power to the DSC system.
12) Installation is complete.
14) The DSC control panel will begin automatic configuration. This can take up to 2
minutes.
15) Installation complete.

RE928X-01-00_RE928X-01-01_Flexible Bus CDMA Communicator Page 3 of 11 11-Nov-16 RE928X-01-00_RE928X-01-01_Flexible Bus CDMA Communicator Page 4 of 11 11-Nov-16
Tech Support: (715)808-0164 Tech Support: (715)808-0164
www.ResolutionProducts.com www.ResolutionProducts.com
Reporting Codes for DSC panels: Concord Programming
The following table shows all events reported when connected to a DSC Panel. Compatible with Concord 4.
Event Report Code 1) Refer to server setup instructions and set up the account on the Dealer Portal.
AC Fail/Restore 301 2) Be sure to add a contact that uses the system MASTER CODE to the account before
Panel Low Battery/Low Battery Restore 302 connecting the module. This will ensure the module can properly communicate with and
configure required system settings.
Opening/Closing Report 400
3) Using the System’s Installers Code:
Cancel Report 406 a. Turn off ACCESS CODE LOCK (0003).
Zone Alarm See below b. Delete phone numbers for CS1-CS3 (01000 – 01020).
Keypad fire panic 110 c. Turn on OPENING REPORTS for partition 1 (06100).
Keypad aux panic 100 d. Turn on CLOSING REPORTS for partition 1 (06101).
Keypad police panic 120 4) If there is an automation or wireless reporting device (i.e. automation module, cell
Duress 121 backup module) already connected to the panel, remove the device and delete from the
panel. Concord 4 only supports 1 automation bus device.
Periodic Test Transmission 602
5) Disarm the System (all partitions).
Periodic Test with Trouble Transmission 608 6) Power down the Concord System.
7) Set the RE928X selector switch to UTC: DSC CDX HW UTC
Automatic Contact ID is not supported. Manually programmed reporting codes are only 8) Connect the Concord panel and the RE928X as shown in the Wiring Instructions above.
supported for alarms on zones 1-64 ([320] – [324]) and for alarms on the PGM2/Aux 9) Apply power to the Concord System.
input ([329]:[4]). The PGM2/Aux input is reported as zone number 99. 10) If this is the first time the module is powered with the panel:
a. Do not press any keys on the keypad for the first 2 minutes after power up.
If Report Codes have not been manually programmed for zone alarms, zone alarm b. After 2 minutes, initiate a bus scan (8+installer code+01)
reporting codes default to: c. Do not press any keys on the keypad for 1 minute after you have
• Any zone alarm (zones 1-64): Code 1130 (Burglary) performed the bus scan.
• PGM2/Aux input (zone 99, likely a 2-wire Smoke): Code 1110 (Fire) 11) If the CS or Platform LED is still blinking refer to “Trouble Shooting the Panel
Connection”.
Be sure to verify that all codes are being properly reported to the central station after 12) It is normal for the keypad to display “Enter Light Key” a few times after connecting
you have installed the communicator module or modified any reporting program the module to the panel. If the keypad continues to display “Enter Light Key”, verify you
settings in the DSC installer programming menu. have the correct system master code setup in the account.
13) Installation is complete.
Caddx NX Programming:
Compatible with all NX series panels IMPORTANT: Be sure to turn Off ACCESS CODE LOCK before adding the module!
1) Refer to server setup instructions and setup account on the Dealer Portal.
2) Be sure to add a contact that uses the system MASTER CODE to the Napco GEM Programming
Compatible Napco Panels:
account before connecting the module. This will ensure the module can
GEM P816
properly communicate with and configure required system settings. GEM P801 (coming soon)
3) Disarm the system (all partitions). GEM P1632 (coming soon)
4) Power down the NX system. GEM P3200 (coming soon)
5) Set the RE928X panel selector switch to CDX: DSC CDX HW UTC GEM P9600 (coming soon)
6) Connect the NX panel and the RE928X as shown in the Wiring Instructions
1) Refer to server setup instructions and set up the account on the Dealer Portal.
above.
2) Be sure to add a contact that uses the system DEALER CODE to the account before
7) Apply power to the NX system. During this process, the communicator will connecting the module. This will ensure the module can properly communicate with
program the following settings: and configure required system settings.
Enable Opening and Closing reports 3) Disarm the system.
Set Telephone Line Cut delay to 0 (no TLM) 4) Use the system DEALER CODE to enter programming.
8) Installation complete. a) Add an additional keypad.
Important: Do not attempt to enter program mode until the CS and Platform b) Program zone reporting codes.
LEDs have stopped flashing. i) Version 29 and older uses locations 0358-0373.
ii) Version 30 and newer uses locations 0720-0735.
Additional Notes for NX installations: ** Note: The RE928X uses the left digit of the data entry to generate
reporting codes for each zone.
1. Some NX panels limit the number of non-keypad devices they support. Be c) Verify the DEALER CODE entered on the online portal matches the code in
sure that the panel you are connecting the communicator to does not have the panel.
more than the number of support devices connected. d) THIS STEP IS ONLY REQUIRED ON PANEL VERSION 30 OR NEWER.
2. User codes that are added to the system or edited thru the communicator i) Disable “Enable Keypad 1 Only Programming”. (Location 2053, bit 7)
will have the default or previous partitions enabled. If you desire the users 5) Exit dealer programming.
to have different partitions enabled, you will need to modify the partitions
thru the NX keypad.
3. 6-digit access codes are not supported.
RE928X-01-00_RE928X-01-01_Flexible Bus CDMA Communicator Page 5 of 11 11-Nov-16 RE928X-01-00_RE928X-01-01_Flexible Bus CDMA Communicator Page 6 of 11 11-Nov-16
Tech Support: (715)808-0164 Tech Support: (715)808-0164
www.ResolutionProducts.com www.ResolutionProducts.com
Napco GEM Programming Continued Operation
6) THIS STEP IS ONLY REQUIRED ON PANEL VERSION 29 OR OLDER.
a) Move keypad 1 to a different keypad address. This will allow the RE928X to Event Reporting:
program the Napco panel. Events are reported to both the monitoring receiver and the interactive
i) Power down the panel. server. All events use Contact ID reporting codes. The following events
ii) Find the mode jumper located on the Napco panel board. are reported by default:
iii) Move the mode jumper to the “config” state.
iv) Return power to the system Alarms System Low Battery
v) The display should show “01 OUT OF SYSTEM”. Alarm cancels System Low Battery Restoral
vi) Press “1 1 1 2 3” + FUNCTION. Openings AC Power Fail (delayed by some panels)
vii) Cycle through the menu until you see “Keypad Address”. Closings AC Power Restoral (delayed by some panels)
viii) Change the keypad address to an open keypad location. Press enter
or on/off to save entry. Vista Only:
ix) Power down system and move the mode jumper back to “norm”. Additional events can be enabled for reporting if desired, by enabling
7) Set RE928X panel selector switch to DSC: DSC CDX HW UTC the desired event reports in system programming.
8) Connect the RE928X to the Napco panel as shown in the wiring instructions above.
9) Apply power to the Napco system. The RE928X will automatically program the Interactive Control:
system.
The system may be controlled remotely through the interactive platform.
a) Be sure all partitions are disarmed.
b) RE928X will start programming as soon as a connection is made to the The arm/disarm control and status applies to partition 1 only.
interactive server.
c) The module will read the following data fields: Z-Wave
Access Codes Z-Wave devices can be controlled via the Interactive function.
Reporting Codes
Enable Global Ambush Code Siren (Future capability)
Global Ambush Code Resolution Wireless Siren will be useable to indicate alarm and statuses.
d) The module will change the following fields:
CS Receiver 1 Format (C “Ademco Point ID”)
e) Programming will last roughly 3 minutes.
10) Finally, the keypad(s) should display “SYSTEM READY”.
11) Installation is complete. CDMA Signal Strength LEDs (A minimum of 2 Signal Strength LEDs is recommended)

LEDs CDMA Signal Strength

TroubleShooting the Panel Connection: 0 0-6 - Bad


If the “CS or “Platform” LEDs are blinking, here are possible 1 7-9 - Marginal
problems:
Incorrect wiring 2 10-12 - Good
Incorrect panel switch position
Unsupported panel version 3 13-17 - Better
Unsupported panel model 4 17+ - Best
Panel is in Installer Program Mode
Vista Specific:
AUI not enabled
AUI used for some other function
LRR not enabled
Another LRR or IP/GSM device connected to panel bus
Concord Specific:
Module not enrolled into the Concord Bus (perform another bus scan)
Another Automation device is enrolled on the Concord Bus

Factory Default Button


This button has two functions:
a) Holding this button for approximately 5 seconds will reset the RE928X
Communicator.
b) Holding this button for approximately 10 seconds (LEDs will flash off
twice) will set the RE928X to factory defaults.

RE928X-01-00_RE928X-01-01_Flexible Bus CDMA Communicator Page 7 of 11 11-Nov-16 RE928X-01-00_RE928X-01-01_Flexible Bus CDMA Communicator Page 8 of 11 11-Nov-16
Tech Support: (715)808-0164 Tech Support: (715)808-0164
www.ResolutionProducts.com www.ResolutionProducts.com
LEDs Specifications
Current Draw: 220 mA Nominal
Bus Board LEDs Indication Temperature Range: 0F to 120F
Housing dimensions: 4x6x1 inches
Green On when the board is powered and running
Red Flickers when module talks to panel Specifications subject to change without notice.

CDMA Card Indication


LEDs
ON and Flashing once per second when the board is powered and running
Power in Primary Mode Notices
(Green) ON and Flashing once every three seconds when the board is powered and “GE”, “Honeywell”, “DSC”, “2GIG” and “Napco” are trademarks owned by General Electric
running in Backup Mode Company, Honeywell International Inc., Tyco Safety Products Canada LTD, 2GIG Technologies
Inc., and NAPCO Security Systems, Inc., respectively.
CDMA ON when the unit is registered with the local CDMA network
(Red) Resolution Products, Inc. products will function with one of either GE, Honeywell, DSC or
Napco systems. However, no Resolution product is produced by, endorsed by, nor is officially
CS ON when the connection to the central station is established
associated with GE, Honeywell, DSC or Napco. Resolution recommends verifying proper
(Red) Flashes when there is a problem detecting the Panel type enrollment and operation, per control panel installation instructions, at installation.

ON when the connection to the Panel and connection to the interactive Warranty
Platform server is established Resolution Products, Inc. will replace products that are defective in their first five (5) years.
(Amber)
Flashes when there is a problem communicating with the panel

Picture
Board Revision FCC Notice
see
Revision Functionality This device complies with Part 15 of the FCC rules. Operation is subject to the
Table following two conditions:
(1)This device may not cause harmful interference.
(2)This device must accept any interference that may be received, including
CDMA interference that may cause undesired operation.
Antenna Changes or modifications not expressly approved by the Resolution Engineering, Inc.
Connector could void the user's authority to operate this equipment.
Panel
Selector This device contains FCC ID: R17CE910-DUAL
Switch Signal
Strength RF Exposure:
LEDs To satisfy FCC RF Exposure requirements for mobile and base station transmission
devices, a separation distance of 20 cm or more should be maintained between the
Data Bus antenna of this device and persons during operation. To ensure compliance, operation
Connector Z-Wave at closer than this distance is not recommended.
Module The antenna(s) used for this transmitter must not be co-located or operating in
conjunction with any other antenna or transmitter.

Z-Wave
Antenna

Revert to
Factory
Default Button

RE928X-01-00_RE928X-01-01_Flexible Bus CDMA Communicator Page 9 of 11 11-Nov-16 RE928X-01-00_RE928X-01-01_Flexible Bus CDMA Communicator Page 10 of 11 11-Nov-16
Tech Support: (715)808-0164 Tech Support: (715)808-0164
www.ResolutionProducts.com www.ResolutionProducts.com
IC Notice

This device complies with Industry Canada license-exempt RSS standard(s). Operation is
subject to the following two conditions:
(1)This device may not cause interference, and
(2)This device must accept any interference, including interference that may cause
undesired operation of the device.

Le présent appareil est conforme aux CNR d'Industrie Canada applicables aux appareils
radio exempts de licence. L'exploitation est autorisée aux deux conditions suivantes :
(1)l'appareil ne doit pas produire de brouillage, et
(2)l'utilisateur de l'appareil doit accepter tout brouillage radioélectrique subi,
même si le brouillage est susceptible d'en compromettre le fonctionnement.

This device contains IC: 5131A-CE910DUAL

Under Industry Canada regulations, this radio transmitter may only operate using an
antenna of a type and maximum (or lesser) gain approved for the transmitter by
Industry Canada. To reduce potential radio interference to other users, the antenna
type and its gain should be so chosen that the equivalent isotropically radiated power
(e.i.r.p.) is not more than that necessary for successful communication.

Conformément à la réglementation d'Industrie Canada, le présent émetteur radio peut


fonctionner avec une antenne d'un type et d'un gain maximal (ou inférieur)
approuvé pour l'émetteur par Industrie Canada. Dans le but de réduire les risques de
brouillage radioélectrique à l'intention des autres utilisateurs, il faut choisir le
typed'antenne et son gain de sorte que la puissance isotrope rayonnée équivalente
(p.i.r.e.) ne dépasse pas l'intensité nécessaire à l'établissement d'une communication
satisfaisante.

RE928X-01-00_RE928X-01-01_Flexible Bus CDMA Communicator Page 11 of 11 11-Nov-16


Tech Support: (715)808-0164
www.ResolutionProducts.com

S-ar putea să vă placă și