Sunteți pe pagina 1din 1

Intrinsically safe isolator

Profibus-DP and RS485 853-IS-DP


854-IS-DP
◆ typically up to 5 MTL8000 1/1 IS nodes/interface
◆ fieldbus and RS485 repeater
◆ multidrop interfaces on single Profibus-DP or
RS485 LAN

MODULE SPECIFICATION
See also System Specification

ENVIRONMENTAL
Ambient temp
Operating, optimum orientation* .......................–20°C to + 40°C
Ingress Protection ....................................IP20 to BS EN6529
(Additional protection by means of enclosure)
* see system specification
OUTPUT
PHYSICAL NETWORK Number of channels ..........................................................1
Profibus-DP/IS Profibus-DP .......................1.5Mbits/s (max.) INPUT
RS485/IS RS485 .........................................1.5Mbits/s (max.) Input voltage.......................................................20 - 30V dc
Current consumption
HOST CONNECTIONS ..............................................................95 mA (typical) at 20V
..............................................................83 mA (typical) at 24V
Profibus Power ..............................................................76 mA (typical) at 28V
A IS Profibus - DP A PE Protective Earth
A IS Profibus - DP A SAFETY
B IS Profibus - DP B L+ Power Supply +ve Location of module ................................................Safe area
B IS Profibus - DP B L– Power Supply 0V Location of field wiring ...............Zone 0, IIC hazardous area
Field wiring protection ..................................intrinsically safe
Type.......................................rising cage clamp screw terminals Certification Code..................................II [1] G EEx m [ia] IIC
Conductor size...............................................0.14 to 2.5mm2 Safety description
IS RS485/IS Profibus-DP ............................4.1V, 144mA, 0.15W
IS CONNECTION IS Power ................................................10.5V, 284mA, 0.75W
IS RS485 and Power .................................10.5V, 428mA, 0.9W
A IS Profibus - DP A
A IS Profibus - DP A
Applicable standards:
B IS Profibus - DP B
◆ EN 50014: Electrical apparatus for potentially explosive
B IS Profibus - DP B
atmospheres, general requirements
Plug connection .................spring latch connector QUICKON ◆ EN 50020: Electrical apparatus for potentially explosive
Conductor size ................................................0.34 - 0.5mm2 atmospheres, intrinsic safety "i"
Jacket diameter..................................................6.0 - 7.5mm ◆ EN 50028: Electrical apparatus for potentially explosive
Approved cable for plug atmospheres, encapsulation "m"
..........................Lapp-Kabel Unitronic-EB JE-LiYCY...BD blue(EEx i) ◆ EN 50039: Electrical apparatus for potentially explosive
......................................................................2 x 2 x 0.34mm2 atmospheres. Specification for intrinsically safe electrical
systems "i"
FIELDBUS TERMINATOR ◆ EC Directive 94/9/EC (ATEX 100A)
Host side
853-IS-DP ..........................................................................none Certification compatible with .......IS Profibus-DP specification
854-IS-DP .................................permanently connected terminator
IS side....................................permanently connected terminator MECHANICAL
Mounting ...................................................................DIN rail
Module width .............................................................30 mm
Weight..........................................................................300 g

EUROPE (EMEA) Tel: +44 (0)1582 723633 Fax: +44 (0)1582 422283
AMERICAS Tel: +1 603 926 0090 Fax: +1 603 926 1899 18 Sept 2002
ASIA PACIFIC Tel: +65 487 7887 Fax: +65 487 7997
E-mail: enquiry@mtl-inst.com Web site: www.mtl-inst.com