Sunteți pe pagina 1din 10

T

Number of
Main Location Room Sub Locations Indications

1. GSS LV
2. GSS MV
Plant GSS 3. GSS/DCP 5
4. GSS DEG LCP
5. GSS S/S

1. E/V MV
2. E/V LV
Plant EDC/VCM 4
3. E/V MV VFD
4. EV LV VFD

1. STG LV
STG 2. STG Field Station 3
3. STG MV

1. PVC II MV
Plant PVC II 2. PVC II LV 3
3. PVC-II DEG LCP

1. PVC MV
2. PVC I MAR (Rack Room)
Plant PVC I 4
3. PVC-I battery room
PVC LV

1. MAR UTY-PP
2. MAR CA
CCR 4
3. MAR EDC-VCM
4. MAR PVC II

GT A GT A Compartment 1

GT B GT B Compartment 1

GT Tornado Tornado HMI Room 1


Rectifier LCP Rectifier LCP 1

CA CA LV 1

28
Temperature Indications on DCS
Spares Channel Available in System
IO Panel Location System / Marshalling Location
AI RTD

GSS LV ABB - PP 16 14

E/V LV HW - EDC/VCM 24 3

STG LV ABB - PP 16 14

PVC II MV HW - PVCII 8 21

PVC1 LV Yamatake - PVCI 10 8

Direct PVC-II Marshalling HW - PVCII 8 21


Termination

From MK-VI Panel to ABB ABB - PP 16 14

From MK-VI Panel to ABB ABB - PP 16 14

From MK-II Panel to ABB ABB - PP 16 14


CA LV HW - CA 15 6

CA LV HW - CA 15 6
Remarks

1. No limitation from System point of view


2. RTD with head mount transmitter recommended to
cores of multi-core cable

1. No limitation from System point of view


2. RTD with head mount transmitter recommended to
cores of multi-core cable

1. No limitation from System point of view


2. RTD with head mount transmitter recommended to
cores of multi-core cable

1. RTD termination on RTD MUX recommended to


utilize channels availability

1. No limitation from System point of view


2. RTD with head mount transmitter recommended to
cores of multi-core cable

1. RTD termination on RTD MUX recommended to


utilize channels availability

1. No limitation from System point of view


2. RTD with head mount transmitter recommended to
cores of multi-core cable

1. No limitation from System point of view


2. RTD with head mount transmitter recommended to
cores of multi-core cable

No spare core in multicore cable. Approximate length


is 350 m.
1. No limitation from System point of view
2. RTD with head mount transmitter recommended to
cores of multi-core cable

1. No limitation from System point of view


2. RTD with head mount transmitter recommended to
cores of multi-core cable
System Channels Available Required Channels

ABB - PP 16 11

Honeywell - EDC/VCM 24 4

Honeywell - PVCII Analog Input 8 3

Honeywell - PVCII RTD Input CCR 21 4

Yamatake - PVCI 53 4

Honeywell - CA 15 2
Channels Availability after
Modification
5

20

17

49

13
BOM and Cost of Project (Thermocou
Material
Thermocouple + Transmitter
RTD + Transmitters
Single Pair Cable (Meters)
Multicore Cable (Meters)
Cable Laying Scaffolding
OM and Cost of Project (Thermocouple based)
Quantity Unit Cost Total
24 10200 244,800
4 20000 80,000
950 - 80,000
350 - 240,000
150,000

Total 794,800