INSTALLER SYSTEM TEST Installer system tests

FocusPRO® 5000 Series FocusPRO® 6000 Series Test the system’s heating, emergency heat, cooling, and fan.
Available tests vary by thermostat and system type.

1. To begin, press and hold the s and t buttons until the 1. To begin, press and hold the s and t buttons until the Table 2. Installer System Test
display changes. display changes. System Test Test Type System Status Number
Number and Description
10 Heating system 0 Heat and fan off

FocusPRO® 5000
1 First stage heat
on (Fan turns on if
Setup Function 1 is
set to 1, 5, 9, or 10

and 6000 Series


OR setup Function
3 is set to 1)
2 Second stage heat
on

Thermostats
3 Third stage heat
on
20 Emergency 0 Heat and fan off
2. Presss/t to turn system on/off. 2. Presss/t to turn system on/off. heating system 1 Heat and fan on
2 Second stage heat
(Aux. heat) turns on

Installer Setup and


System test System status System test System status 30 Cooling system 0 Compressor and
number number number number fan off

System Test pocket Guide


1 Compressor and
fan on

10 0 10 0 40 Fan system
2

0
1
Second stage
compressor on
Off
On

Done Next Done Next


caution
EQUIPMENT DAMAGE HAZARD.
Compressor protection is bypassed during testing.
To prevent equipment damage, avoid cycling the
3. Press NEXT to advance to next test. 3. Press NEXT to advance to next test. compressor quickly.
4. Press DONE to terminate system test. 4. Press DONE to terminate system test.
5. Proceed to Installer System Tests on page 8. 5. Proceed to Installer System Tests on page 8.

69-2026
6 7 8
installer setup installer setup functions
Available option and default settings vary by thermostat.

FocusPRO® 5000 Series FocusPRO® 6000 Series


Table 1. Installer Setup Table 1. Installer Setup
Setup functions Setting & Options Setup functions Setting & Options
1. To begin, press and hold the s and FAN buttons until 1. To begin, press and hold the s and FAN buttons until (factory default in bold) (factory default in bold)
the display changes. the display changes. 1 System type 0 1 heat / 1 cool Conv. 8 Emergency heat 9 Electric emergency heat
1 1 heat / 1 cool heat cycle rate 1 Steam or gravity
pump (no Aux. heat) 3 Hot water systems or fur-
2 Heat only (2-wire, 3-wire naces of 90%+ efficiency
zone valves [Series 20], 5 Gas or oil furnaces of
and normally open zone less than 90% efficiency
valves) [Other options: 1–12]
3 Heat only with fan 9 First stage 3 Recommended
4 Cool only compressor cycle [Other options: 1–6]
5 2 heat / 1 cool heat rate
pump (with Aux. heat)
6 2 heat / 2 cool Conv. 10 Second stage 3 Recommended
7 2 heat / 1 cool Conv. compressor cycle [Other options: 1–6]
8 1 heat / 2 cool Conv. rate
2. Press s or t to change settings. 2. Press s or t to change settings.
9 2 heat / 2 cool heat pump 12 Manual/Auto 0 Manual changeover
(no Aux. heat) changeover (Heat/Cool/Off)
Function Setting Function Setting 10 3 heat / 2 cool heat 1 Auto changeover (Heat/
pump (with Aux. heat) Cool/Auto/Off)
2 Changeover valve 0 Controls valve in cooling 2 Auto changeover only

1 1
(Auto)

0 0
(O/B terminal) 1 Controls valve in heating
3 Fan control 0 Gas/Oil heat (equipment 13 Adaptive Intel- 1 On
(heating) controls heating fan) ligent RecoveryTM 0 Off
1 Electric furnace (thermo- 14 Temperature 0 Fahrenheit
stat controls heating fan) display 1 Celsius
Done Next Done Next 5 First stage heat 5 Gas or oil furnaces of 15 Compressor 5 5-minute compressor
cycle rate less than 90% protection off time Printed in U.S.A. on recycled
efficiency [Other options: 0–4 paper containing at least 10%
1 Steam or gravity minutes] post-consumer paper fibers.
3. Press NEXT to advance to the next function. 3. Press NEXT to advance to the next function. 3 Hot water systems or fur- 16 Schedule format 0 5/2 (weekdays
4. Press DONE to exit and save settings. 4. Press DONE to exit and save settings. naces of 90%+ efficiency Automation and Control Solutions
and weekends
5. Proceed to Installer Setup Functions on page 4. 5. Proceed to Installer Setup Functions on page 4. 9 Electric furnaces programmable) Honeywell International Inc.
[Other options: 1–12] 1 5/1/1 (weekdays,
6 Second stage 5 Gas or oil furnaces of Saturday, and Sunday 1985 Douglas Drive North
heat/Aux heat less than 90% efficiency programmable)
Golden Valley, MN 55422
cycle rate 1 Steam or gravity 26 Auxiliary heat 0 Comfort
3 Hot water systems or fur- control 1 Economy
naces of 90%+ efficiency
9 Electric furnaces
27 Heat temperature 90 Max. heat temperature Honeywell Limited-Honeywell Limitée
range stops setting is 90°F (32°C)
[Other options: 1–12] 35 Dynamic Drive
[Other options: 40–89°F
7 Auxiliary heat 5 Gas or oil furnaces of (4.5°C to 32°C)]
cycle rate less than 90% efficiency Toronto, Ontario M1V 4Z9
28 Cool temperature 50 Min. cool temperature
1 Steam or gravity http://yourhome.honeywell.com
range stop setting is 50°F (10°C)
3 Hot water systems or fur-
[Other options: 51–99°F
naces of 90%+ efficiency ® U.S. Registered Trademark
(10.5°C to 37°C)]
9 Electric furnaces © 2006 Honeywell International Inc.
US Patent No. 6595430, D509151; other
[Other options: 1–12] Patents Pending. All Rights Reserved
Functions 13 and 16 only available on the 6000 series; 69-2026 M.S. 09-06