1. Product introduction
HGQB-C transformer calibrator, is a novel automated detection equipment, which
uses advanced electronic technology to collect and decompose the error signal of
transformer directly, after appropriate operation, the percentage points, in-phase error
and quadrature errors of transformer are displayed in digital at the same time.
HGQB-C transformer calibrator is simple, intuitive readings, measure quickly, can
reduce energy consumption, reduce labor intensity; small size, light weight, easy to
carry and field testing; instrument can be fixed at 5% Operating current (voltage)
under testing; otherwise required Electric Co., Ltd., Wuhan NARI can produce detect
S-class current transformer and the secondary voltage of the voltage transformer
calibrator 100/3V, then 1% of the rated instrument can measure the current
transformer operating current the error; instrument in the detection process can be
easily carried from the school at any time to ensure the accuracy of the instrument;
critical components using imported components, stable and reliable quality, widely
used in metering, power supply and other departments and transformer manufacturers,
Wuhan Nanrui Electric Co., LTD
Web: www.whnanrui.com Email: whnanrui@126.com

is to carry out transformer testing the ideal instrument.


2. Technical parameters
Temperature: -5°C ~ 40°C
Relative humidity: <80% (25°C)
Operating environment Height: < 2500m
Power frequency: 50Hz ± 0.5Hz
Power supply voltage: 220V ± 5V
In-phase component (%): 0.0001 ~ 200.0; Resolution: 0.0001
Quadrature component (%): 0.0001 ~ 700.0; Resolution:0.001
Test range
Impedance (Ω):0.0001~20.0; Resolution:0.0001
Admittance (ms): 0.0001~20.0; Resolution:0.0001
In-phase component: ΔX = ± ( X×2% + X×2%) ± Dx
Quadrature component: ΔY = ± ( Y×2% + X×2%×34.38) ± Dy
“X”,”Y”---Display value
Basic error
“Dx, Dy”--- error
Dx=2, Dy=5
Dial gauge:1.5 level (1.0 level can be optional)
(1) current: (1%-149%)In, (In =5A)
(5%-149%)In, (In =1A)
Working scope
(2) voltage: (5%-149%)Un, (Un =100V, 150V, 100V/3)
(5%-149%)Un, (Un =100V/3)
Working load (1) current: TO - TX < 0.12Ω COSΦ=1
(2) voltage: a - x < 0.25VA (100V)
Dimension (mm) 260(L)×350(W)×150(H)
Weight (kg) 6

3. Function and characteristics:

(1) It adopt with 320 × 240 dot matrix LCD, visible range, with a long-life back-light,
convenient to use;
(2) Full English operating interface;
(3) Dial gauge, ratio difference, angle difference using large font display, user-friendly
observation;
(4) Fully meet JJG314-1993 and JJG314-1994 requirements, automatic sampling;
(5) Automatic judgment of polarity error and ratio error
(6) PC software with virtual instruments open function;
(7) Completely solve the S-class measurement problems;
(8) Automatic switching range;
(9) Unique circuitry and advanced DSP technology combine to completely remove the
RC phase shifter circuit instability.
(10) power consumption: < 15VA (without micro-printer)
Wuhan Nanrui Electric Co., LTD
Web: www.whnanrui.com Email: whnanrui@126.com

< 25VA (with micro-printer)


(11) Harmonic rejection ratio: > 40db