3. ELECTRICAL TESTS
FUNCTION TEST
ITEM DESCRIPTION REMARKS
1. Case Earthing checked Yes N/A
2. Indication checked Yes N/A
3. Trip/Output contacts checked Yes N/A
4. Binary input checked Yes N/A
4. METERING CHECK.
4.1 CURRENT INPUT CHECK:
Injected Displayed Displayed Primary
Phase CT Ratio Applied
Amps(A) secondary value(A) value (A)
RN 1.00 800/1A 1.00 799
YN 1.00 800/1A 1.00 798
BN 1.00 800/1A 1.00 799
RN 0.50 800/1A 0.50 399
YN 0.50 800/1A 0.50 399
BN 0.50 800/1A 0.50 399
DISPLAYED
INPUT INJECTED VALUE EXPECTED VALUE
VALUE
RYB Frequency 3 ph nominal voltage 60HZ 60 .0HZ
& Current with 0
RYB P degree Phase shift. 159 MW 159.0 MW
Calculated :
P = √3 VI Cos Ф
Q = √3 VI Sin Ф
S = √3 VI
BI 1 K17-K18 OK BO 1 K5-K6 OK 1 OK
BI 2 J1-J2 OK BO 2 K5-K7 OK 2 OK
BI 3 J3-J5 OK BO 3 K5-K8 OK 3 OK
BI 4 J4-J5 OK BO 4 K9-K10 OK 4 OK
BI 5 J6-J5 OK BO 5 K11-K12 OK 5 OK
BI 6 J7-J8 OK BO 6 K13-K14 OK 6 OK
BI 7 J9-J10 OK BO 7 K15-K16 OK 7 OK
BI 8 J11-J12 OK BO 8 R1-R5 OK 8 OK
BI 9 P17-P18 OK BO 9 R2-R5 OK 9 OK
BI 10 N1-N2 OK BO 10 R3-R5 OK 10 OK
BI 11 N3-N5 OK BO 11 R4-R5 OK 11 OK
BI 12 N4-N5 OK BO 12 R6-R5 OK 12 OK
BI 13 N6-N5 OK BO 13 R7-R8 OK 13 OK
BI 14 N7-N8 OK BO 14 R9-R10 OK 14 OK
BI 15 N9-N10 OK BO 15 R11-R12 OK
BI 16 N11-N12 OK BO 16 P3-P4 OK
BI 17 H17-H18 OK BO 17 P6-P5 OK
BI 18 G1-G2 OK BO 18 P7-P5 OK
BI 19 G3-G5 OK BO 19 P8-P5 OK
BI 20 G4-G5 OK BO 20 P9-P10 OK
BI 21 G6-G5 OK BO 21 P11-P12 OK
BI 22 G7-G8 OK BO 22 P13-P14 OK
BI 23 G9-G10 OK BO 23 P15-P16 OK
BI 24 G11-G12 OK BO24 H3-H4 OK
BO 25 H6-H5 OK
BO 26 H7-H5 OK
BO 27 H8-H5 OK
BO 28 H9-H10 OK
BO 29 H11-H12 OK
BO 30 H13-H14 OK
BO 31 H15-H16 OK
5. DIFFERENTIAL PROTECTION.
Operating unit: 87L1: I diff> Remarks: Pick up tolerance 5% of set value or 10mA
Phase Setting current(A) Pick up value (A) Drop off value(A) Remarks
R 0.3 0.317 0.164 OK
Y 0.3 0.317 0.162 OK
B 0.3 0.317 0.164 OK
RY 0.3 0.317 0.164 OK
YB 0.3 0.316 0.162 OK
BR 0.3 0.316 0.162 OK
RYB 0.3 0.317 0.162 OK
5.2 MEASUREMENTS FOR DIFF & BIAS CURRENT WITH LOCAL RELAY.
Measurements are made in % of Idiff.L1 set.
Inj.
Phase Local end measurement in % of I diff set. Remote end measurement in % of I diff se
amps
I I I I I
Idiff. I diff. I diff. I rest. I rest. I rest. 3I0I Idiff 3I0I
diff diff rest rest rest
L1 L2 L3 L1 L2 L3 diff .L2 diff
.L1 .L3 . L1 . L2 . L3
1.0 99.6 0.00 0.00 31.9 31.4 31.4 99.5 99.5 0.00 0.00 31.6 31.3 31.4 99.5
A
1.0 0.00 99.6 0.00 31.3 32.1 31.6 99.6 0.00 99.5 0.00 31.4 32.4 31.4 99.4
B
1.0 0.00 0.00 99.7 31.3 31.6 31.6 99.6 0.00 0.00 99.6 31.3 31.4 32.4 99.7
C
1.0 99.7 99.6 99.6 32.1 32.1 31.9 0.00 99.3 99.5 99.6 32.1 32.5 32.4 0.00
ABC
I Diff set: 1A
I bias: I diff set (Diff Characteristic Angle 45 deg.)
Local end Remote injected I Diff I Restrain
Phase
injected amps(A) amps(A) Measured(%) measured(%)
A 1 1.333 33.2 33.6
B 1 1.333 33.3 33.6
C 1 1.332 33.0 33.3
6. DISTANCE PRORECTION:
Parameter Z1 Z1B Z2 Z3 Z4 Z5
Direction Forward Forward Forward Forward Reverse Non-directional
R 1.00 1.50 2.00 3.00 4.0 5.00
X 1.00 1.50 2.00 3.00 4.0 5.00
Re 1.00 1.50 2.00 3.00 4.0 5.00
Time (sec) 0.00 0.00 0.60 0.80 1.0 1.50
1. Operation checked : OK
8. DISTURBANCE RECORDER:
9. FAULT LOCATER:
Set: Z2=Z1B
Blocking scheme:
Z3 reverse
MEASURED MEASURED
DIRECTION SET VALUE
TRIPPING BLOCKING
α =338
α= 338
Sensitivity check:
Characteristics: DEF forward
Measured Io (amp) Measured Vo (Volts)
Set value Io (Amp) Set value Vo (Volts)
Pick up Drop off Pick up Drop off
0.5 0.504 0.474 2 2.01 1.86
1.0 1.006 0.946 5 5.01 4.66
Directional comparison:
Trip logic: forward fault +CR: OK Trip time without CR: 1.02 Sec.
Blocking
Trip logic: Forward fault +NO CR: OK Trip time without CR: 26.1 ms
Normal Inverse
Pickup value: Expected 10% set value above
Operate value(Amps) Set time Op.time at 3 x Is (sec)
Phase Set value I> delay Actual Expected
PICK UP DROP OFF
(Sec) time time
AN 1 1.100 1.027 0.50 3.15 3.18
BN 1 1.101 1.028 0.50 3.15 3.18
CN 1 1.100 1.026 0.50 3.15 3.18
Very Inverse
Operate value(Amps) Set time Op.time at 3 x Is (sec)
Phase Set value I> delay Actual Expected
PICK UP DROP OFF
(Sec) time time
AN 1 1.100 1.029 0.50 3.37 3.375
BN 1 1.100 1.028 0.50 3.37 3.375
CN 1 1.103 1.026 0.50 3.37 3.375
Extremely Inverse
Operate value(Amps) Set time Op.time at 3 x Is (sec)
Phase Set value I> delay Actual Expected
PICK UP DROP OFF
(Sec) time time