Sunteți pe pagina 1din 4

Princess Noura Bint Abdulrahman University for Women Project Joint venture

Riyadh, Kingdom of Saudi Arabia El Seif/CCC


part / package: package 3 - Utillity area references: time: date:
department: ENGINEERING 1:58 PM 1/16/2018
calcs by: Aleksandar Jankovic sr.str.eng

BRACKET PSIR 350-section BB


1.0 INPUT DATA
The wieght of fluid……….………………………………………………… 10 kN/m3
The weight of pipe…. 350 mm diameter…………………………. 80.5 kg/m
Adopted steel grade……………..…… ASTM A36 yield stren..Py= 245 N/mm2
The strength of the weld (Fexx=60% of Py)…….…………….…..Pyw= 147 N/mm2
The distance between two supports horizontaly………..….……...…L= 2.5 m
The pipe center line offset from the base……….……………………..H= 0.925 m
The compressive strength of concrete after 28 days……….…...... fc'= 35 MPa
The density of the steel...……….………………………….………...γs= 7860 kg/m3
The pipe diameter………………………………………………………..D= 350 mm
The clamp thk……………..…………………………………………. ...T= 10 mm
The width of clamp.……………………………………………………..Lc= 50 mm
The weight of the valve……………………………………………………… 195 kg
The weight of joints with fasteners……………………………………….. 195 kg
Adopted bolts are steel grade… 4.6 GR, diameter………. 20 mm
note: no pressure variation since the pipe is main header line, and any lateral force will be
taken either with concrete walls or concrete pump supports.

2.0 THE CONCEPT


The concept is based prior to esier process of erection of steel brackets and easier
process of loading / maintenance of DI pipes as per figure 1.
H

for H>1.5 m for H<=1.5 m


Figure 1- the concept
Building / area: PUMP STATION rev: THE PUMP STATION BLDG Sheet:
issued for: APPROVAL 0 the pipe support 0 3 7

Princess Noura Bint Abdulrahman University for Women Project Joint venture
Riyadh, Kingdom of Saudi Arabia El Seif/CCC
part / package: package 3 - Utillity area references: time: date:
department: ENGINEERING 1:58 PM 1/16/2018
calcs by: Aleksandar Jankovic sr.str.eng

3. LOADS ANALYSES
3.1 Dead load
The wieght of the pipe………………………………………………. 201.25 kg
The weight of the fluid……………………………………………….. 96.1625 kg
The weight of the clamp...………………………………………….. 4.9669305 kg
The weight of adopted beam………… C100x50x10 self weight 10 9.435 kg
total= 701.81443 kg
Total weight including stiffeners, bolts, nuts…………………………….. 708.83257 kg
total dead loa G=…………….. 7.0883257 kN

safety factor adopted………………………………………………………… 2


0 bar
Factored dead load…………………………………..…………….……G= 14.176651 kN
>Note: Lateral support will be provided by pipe it self<

4. THE CHECK OF THE STEEL BRACKET


4.1 The check of bearing capacity of steel column
Area of the section………………………………………………………….. 1300 mm2
Pbcap=Aa*Py=……. 318.5 > 14.17665 kN-total compression force…………………. safe
4.2. The check of compression strength of the concrete beneath base plate
the column dimensions:
bc= 50 mm
hc= 100 mm
The base plate dimensions
b1= 150 mm
h1= 200 mm
the concrete pressure pc=G/b*h=….. 0.472555 N/mm2 < 35 N/mm2 safe
4.3 The check of base plate thk
bending moment at plate due to pressure-longitudinal:
Mbpll=(h1-hc)*0.5*b1*pc*0.25*(h1-hc)= 88604.07 Nmm=……………….. 0.0886041 kNm
bending moment at plate due to pressure-longitudinal:
Mbplp=(b1-bc)*0.5*h1*pc*0.25*(b1-bc)= 118139 Nmm=……………….. 0.1181388 kNm
Mbplmax= 0.11814 kNm

Tp=((6*Mbplmax/Py*b1)^0.5=………. 3.803416 mm……adopted T= 6 mm

5. THE ANCHORING SYSTEM


Since there is a pressure force only adopted are two HILTI post drilled anchor HST M 10
Calculations for pressurised anchors are not required.
Building / area: PUMP STATION rev: THE PUMP STATION BLDG Sheet:
issued for: APPROVAL 0 the pipe support 0 3 8
H

for H<=1.5 m

S-ar putea să vă placă și