A. Application
Overcurrent function with time delay inversely proportional to the
current and definite minimum tripping time (IDMT).
B. Features
· operating characteristics (see Fig. 3.5.8.1) according to
British Standard 142:
c = 0.02 : normal inverse
c=1 : very inverse and long time earth fault
c=2 : extremely inverse.
· insensitive to DC component
· insensitive to harmonics
· single or three-phase measurement
· detection of the highest phase value in the three-phase mode
· wider setting range than specified in B.S. 142.
I. C.t./v.t. inputs:
· current
IV. Measurements:
· current amplitude.
3-159
ABB Switzerland Ltd REL 316*4 1MRB520050-Uen / Rev. F
ParSet4..1 P1 (Select)
Trip 00000000
c-Setting 1.00 (Select)
k1-Setting s 013.5 0.01 200.0 0.01
I-Start IB 1.10 1.00 4.00 0.01
t-min s 00.00 0.0 10.0 0.1
NrOfPhases 1 1 3 2
CurrentInp CT/VT-Addr 0
IB-Setting IN 1.00 0.045 2.50 0.01
BlockInp BinaryAddr F
Trip SignalAddr ER
Start SignalAddr ER
Explanation of parameters:
ParSet 4..1
Parameter for determining in which set of parameters a par-
ticular function is active (see Section 5.11.).
Trip
defines the tripping channel activated by the tripping O/P of
the function (matrix tripping logic).
c-Setting
Setting for the exponential factor determining the shape of
the operating characteristic according to BS 142 or for se-
lecting the RXIDG characteristic.
k1-Setting
Constant determining the parallel shift of the characteristic
(time grading).
I-Start
Pick-up current at which the characteristic becomes effective.
t-min
Definite minimum tripping time.
NrOfPhases
defines the number of phases measured.
3-160
REL 316*4 1MRB520050-Uen / Rev. F ABB Switzerland Ltd
CurrentInp
defines the c.t. input channel. All current I/P's may be
selected. In the case of three-phase measurement, the first
channel (R phase) of the group of three selected must be
specified.
IB-Setting
Base current for taking account of differences of rated current
IN.
BlockInp
defines the input for an external blocking signal.
F: - not used
T: - function always blocked
xx: - all binary inputs (or outputs of protection
functions).
Trip
Tripping signal.
Start
Pick-up signal.
3-161
ABB Switzerland Ltd REL 316*4 1MRB520050-Uen / Rev. F
E. Setting instructions
Settings:
Base current IB-Setting
Characteristic enabling current I-Start
Type of characteristic c-Setting
Multiplier k1-Setting
The IDMT overcurrent function is used to protect transformers,
feeders and loads of the auxiliaries supply system against phase
and earth faults. The function responds largely only to the fun-
damental component of the fault current.
Example:
Load current of protected unit IB1 = 800 A
C.t. rated current IN1 = 1000 A
IN2 = 5A
Relay rated current IN = 5A
Relay reference current “IB-Setting”:
IN2 5A
IB = IB1 = 800A = 4A
IN1 1000A
Setting:
IB 4 A
= = 0 .8
IN 5 A
3-162
REL 316*4 1MRB520050-Uen / Rev. F ABB Switzerland Ltd
3-163
ABB Switzerland Ltd REL 316*4 1MRB520050-Uen / Rev. F
Multiplier ‘k1-Setting’
The multiplier ‘k1-Setting’ enables the IDMT characteristic
chosen by the setting of parameter c to be shifted without
changing its shape. This is used for grading the operating times
of a series of IDMT relays along a line to achieve discrimination.
For example, in the case of the “very inverse” characteristic, the
constant c = 1 and the factor k1 £ 13.5. The operating time t is
given by the equation
k1
t=
I
-1
IB
t [s] k1 [s]
0.5 2.5
1 5
1.5 7.5
2 10
2.5 12.5
Typical settings:
IB-Setting corresponding to load current of the pro-
tected unit
I-Start 1.1 IB
c-Setting according to desired characteristic for the
protected unit
k1-Setting according to the time grading calculation
t-min 0.00
3-164