Sunteți pe pagina 1din 23

File E198726

Project 04NB01564

September 11, 1998

REPORT

on

PROGRAMMABLE CONTROLLERS
FOR USE IN HAZARDOUS LOCATIONS

Wago Kontakttechnik GmbH


Minden, Fed. Rep. of Germany

Copyright  1998 Underwriters Laboratories Inc.

Underwriters Laboratories Inc. authorizes the above named company to


reproduce this Report provided it is reproduced in its entirety.
File E198726 Vol. 1 Sec. 1 Page 1 Issued: 1998-09-11
and Report Revised: 2016-05-13

DESCRIPTION

PRODUCT COVERED:

USL, CNL - Open type, Programmable controller, WAGO I/O System, series
750-XXX or series 753-XXX, may be followed by /XXXX-
XXXX/XXXX-XXXX for use in Class I, Division 2, Groups A, B,
C, and D Hazardous locations.

* Where X denotes any alphanumeric character. The suffix extension means


a variant which doesn't have any influence for use in Class
I, Div.2 Hazardous Locations.

Consisting of the following modules/Cat. Nos.:


All series 750 represents series 753 (as applicable), except for the
differences described in this procedure eg. 750-300 represents 753-300 etc.

Designation Module No. Alternate


Module No.
WAGO I/O System

Bus Coupler 750-300


750-301
750-302
750-303
750-304
750-305
750-306
750-307
750-309
750-310
750-311
750-312
750-313
750-314
750-315
750-316
750-319
750-327
750-333
750-333/040-000
750-334
750-337 51205056
750-338
750-338/040-000
750-341
750-342
750-350
750-351
750-352
*
File E198726 Vol. 1 Sec. 1 Page 1A Issued: 1998-09-11
and Report Revised: 2016-05-13

Designation Module No. Alternate


Module No.
750-352/020-000
750-352/040-000
750-354
750-370
750-375
Bus Controller 750-804
750-806
750-812
750-814
750-815
750-816
750-819
750-829
750-830
750-833
750-837
750-838/....-....
750-838/040-000
750-841
750-842
750-843
750-849
750-852
750-860
750-871
750-872
750-873
750-880
750-880/040-000
750-880/040-001
750-881
750-882
750-885
750-889
750-8100
750-8101
750-8102
750-8202
750-8202/040-000
750-8202/040-001
750-8203
750-8204
750-8206
750-8206/040-000
750-8206/040-001

Bus Supply Module 750-613


750-613/040-000
File E198726 Vol. 1 Sec. 1 Page 2 Issued: 1998-09-11
and Report Revised: 2015-04-30

Designation Module No. Alternate


Module No.
Economy Bus coupler 750-320
750-323
750-324

Economy Bus coupler 750-343


750-344
750-345
750-346
750-347 51205055
750-348
750-354/000-001
750-377

Digital Input Module 750-400


750-401
750-402 51205054
750-403
750-408
750-409
750-412
750-422
750-429
750-432
750-433
753-440
File E198726 Vol. 1 Sec. 1 Page 2A Issued: 1998-09-11
and Report Revised: 2016-05-13

Designation Module No. Alternate


Module No.
Digital Input Module 750-410
750-411
750-434

Digital Input Module 750-430 51205053


750-431 51205052

Counter Module 750-404

Digital Input Module 750-405


750-406

Analog Input Module


750-450
750-451
750-452
750-453
750-453/040-000
750-454
750-455/040-000
750-455 51205051
750-455/020-000
750-456
750-457 51205050
750-457/040-000
750-458 51205049
750-459
750-461 51205048
750-462
750-463

750-464
750-464/040-000
750-465
750-466 51205047
750-467 51205046
750-468
750-468/040-000
750-469
750-469/040-000
750-482
750-484
750-487
File E198726 Vol. 1 Sec. 1 Page 3 Issued: 1998-09-11
and Report Revised: 2014-10-20

Designation Module No. Alternate


Module No.
Digital Output Module 750-501
750-504 51205045
750-506
750-531

Digital Output Module 750-502


750-507
750-508
750-508/040-000

Digital Output Module 750-509


750-518

Pulse Width Module 750-511

Relay Output Module 750-512


750-513 51205044
750-517
750-517/040-000

Analog Output Module 750-550 51205042


750-551
750-552
750-553
750-554 51205041
750-555 51205040
750-556
750-557 51205039
750-557/040-000
750-559 51205038
750-559/040-000
750-560
750-562
750-563
750-563/040-000
File E198726 Vol. 1 Sec. 1 Page 3A Issued: 1998-09-11
and Report Revised: 2014-10-20

Designation Module No. Alternate


Module No.
Supply Module 750-602 51205036
750-602/040-000
750-603
750-604
750-612
750-612/040-000
750-614
750-1605
750-1605/040-000
750-1606
750-1606/040-000
750-1607

Supply Module 750-601


750-610

*Supply Module 750-609


750-611
750-615

Supply Module 750-606


750-625

Supply Module 750-623

Interface Module 750-630 51205057

Interface Module 750-631

Interface Module 750-650


750-651
750-652
750-652/040-0000
750-653
File E198726 Vol. 1 Sec. 1 Page 4 Issued: 1998-09-11
and Report Revised: 2016-05-13

Designation Module No. Alternate


Module No.
End Module 750-600 51205037
750-600/040-000

Digital Input Module 750-414

Digital Output Module 750-519

Digital Input Module 750-415


750-423
750-428

Analog Input Module 750-472


750-474
750-476
750-478

Digital Output Module 750-516

Separation Module 750-616


750-616/040-000
750-621

Binary Space Module 750-622

Counter Module 750-417


750-638

Digital I/O Module 750-418


750-419
750-421

Intruder Detection 750-424


Module

Analog Input Module 750-479


750-480
750-483
750-492
750-492/040-001
750-496
750-497

Digital Output Module 750-522

Interface Module 750-637 51205116

Digital Input Module 750-425


750-427
750-427/040-000
750-429/040-001
File E198726 Vol. 1 Sec. 1 Page 4A Issued: 1998-09-11
and Report Revised: 2015-04-30

Designation Module No. Alternate


Module No.
Digital Output Module 750-530 51205043
750-534

Analog Input Module 750-475


750-477

Interface Module 750-635

Filter Module 750-624


750-624/000-001
750-624/020-000
750-624/020-001
750-624/040-001
750-626
750-626/020-000
750-626/040-000

Digital Input Module 750-435


750-438
750-439

Digital Input Module 750-436


750-437

Analog Input Module 750-470


750-473

Analog Input Module 750-485

Digital Output Module 750-532

Digital Output Module 750-535


750-538

Digital Output Module 750-536

Digital Output Module 750-537

Analog Output Module 750-585


750-586
File E198726 Vol. 1 Sec. 1 Page 4B Issued: 1998-09-11
and Report Revised: 2015-04-30

Designation Module No. Alternate


Module No.
RTC Module 750-640
750-644
753-648

Interface Module 750-641

Interface Module 750-642

Interface Module 750-655

Digital Input Module 750-660/000-001


750-661
750-662
750-663/000-003

Digital Input/Output Module 750-665/000-001


750-666/000-003
750-667

Field Bus Connector Module 750-960


750-961
750-962
750-970

Analog Input Module 750-481/003-000

Supply Module 750-625

Interface Module 750-643


750-658

Motor Controller Module 750-670


750-671

Digital Output module 753-540

Condition Monitoring Module 750-645


File E198726 Vol. 1 Sec. 1 Page 4C Issued: 1998-09-11
and Report Revised: 2016-05-13

Designation Module No. Alternate


Module No.
Digital Input Module 750-1400
750-1402
750-1405 (10)
750-1405/040-000
750-1406
750-1407
750-1407/040-000
750-1415
750-1415/040-000
750-1416
750-1416/040-000
750-1417
750-1418
750-1420750-1421
750-1422
750-1423

Digital Output Module 750-1500


750-1501
750-1504
750-1505
750-1515
750-1515/040-000
750-1516

Digital Input/Output Module 750-1502


750-1506
750-657
750-632

Counter 750-633

3-Phase Measuring 750-493


Module 750-493/000-001
750-494
750-494/000-001
750-494/000-005

*
PTC Module 750-1425
File E198726 Vol. 1 Sec. 1 Page 5 Issued: 1998-09-11
and Report Revised: 2016-05-13

GENERAL:

These devices are open-type devices intended for installation in tool-


secured enclosures.

The WAGO I/O System is a field bus independent bus system which can be
used for solving extended automation tasks such as storing signals for
pushbuttons, evaluating the position of selector switches, processing signals
from limit and safety switches and other programmable controllers, counting
low frequency pulses, controlling motor valves, actuators, etc.

ELECTRICAL RATINGS:

All series 750 represents series 753 except for the differences described in
this procedure eg. 750-300 represents 753-300 etc.

For alternate module numbers listed under "Product Covered" refer to the
ratings of the original module type.

Bus Coupler -

Models 750-300, -301, -302, -303, -304, -305, -306, -307, -309, -310,
-311, -312, -313, -314, -315, -316, -319, -327,
-333, -334, -337, -338, -341, -342, -350, -351, -352, -352/020-000, -354, -
370, -333/040-000, -338/040-000, -352/040-000, -375
- 24 V dc

Bus Controller –

Models 750-804, -806, -812, -814, -815, -816, -819, -829, -830, -833, -837,
-838/....-...., -841, -842, -843, -849, -852, -860, -871, -872 -873, -880,
-881, -882, -885, -889, -838/040-000, -880/040-000, -880/040-001, -8100,
-8101, -8102, -8202, -8202/040-000, -8202/040-001, ,-8203 , -8204 , -8206, -
8206/040-000, -8206/040-001
- 24 V dc.

Economy Bus Coupler –

Models 750-320, -323, -324, -343, -344, -345, -346, -347, -348, 750-354/000-
001 , 750-377,
- 24 V dc
File E198726 Vol. 1 Sec. 1 Page 6 Issued: 1998-09-11
and Report Revised: 2016-05-13

Digital Input Modules -

Model 750-400 - 24 V dc, two channels


Model 750-401 - 24 V dc, two channels
Model 750-402 - 24 V dc, four channels
Model 750-403 - 24 V dc, four channels
Model 750-405 - 230 V ac, two channels
Model 750-406 - 120 V ac, two channels
Model 750-407/040-000 - 220 V dc, two channels
Model 750-408 - 24 V dc, four channels
Model 750-409 - 24 V dc, four channels
Model 750-410 - 24 V dc, two channels
Model 750-411 - 24 V dc, two channels
Model 750-412 - 48 V dc, two channels
Model 750-414 - 5 V dc, four channels
Model 750-415 - 24 V dc/ac, four channels
Model 750-422 - 24 V dc, four channels
Model 750-423 - 24 V dc/ac, four channels
Model 750-425 - 24 V dc, two channels
Model 750-427 - 110 V dc, two channels
Model 750-427/040-000 – 110 V dc, two channels
Model 750-428 - 42 V ac/dc, four channels
Model 750-429/040-001 – 60 V dc, two channels
Model 750-430 - 24 V dc, eight channels
Model 750-431 - 24 V dc, eight channels
Model 750-432 - 24 V dc, four channels
Model 750-433 - 24 V dc, four channels
Model 750-434 – 5 V dc to 14 V dc, eight channels
Model 750-435 – 8.2 V dc, one channel
Model 750-436 - 24 V dc, eight channels
Model 750-437 - 24 V dc, eight channels
Model 750-438 - 24 V dc, two channels
Model 750-439 - 24 V dc, eight channels
Model 753-440 - 120 V ac / 230 V ac, four channels
Model 750-485 – 24 V dc, two channels

Model 750-660/000-001 - 24 V dc, eight channels


Model 750-661 – 24 V dc, four channels
Model 750-662 – 24 V dc, eight channels
Model 750-663/000-003 - 24 V dc, four channels
Model 750-1400 – 24 V dc, sixteen channels
Model 750-1402 – 24 V dc, sixteen channels
Model 750-1405 – 24 V dc, sixteen channels
Model 750-1405/040-000 – 24 V dc, sixteen channels
Model 750-1406 – 24 V dc, sixteen channels
Model 750-1407 – 24 V dc, sixteen channels
Model 750-1415 – 24 V dc, eight channels
Model 750-1415/040-000 – 24 V dc, eight channels
Model 750-1416 – 24 V dc, eight channels
Model 750-1416/040-000 – 24 V dc, eight channels
Model 750-1417 – 24 V dc, eight channels
*
File E198726 Vol. 1 Sec. 1 Page 6A Issued: 1998-09-11
and Report New: 2016-05-13

Model 750-1418 – 24 V dc, eight channels


Model 750-1420 – 24 V dc, four channels
Model 750-1421 – 24 V dc, four channels
Model 750-1422 – 24 V dc, four channels
Model 750-1423 – 24 V dc, four channels
File E198726 Vol. 1 Sec. 1 Page 7 Issued: 1998-09-11
and Report Revised: 2016-05-13

Analogue Input Modules -

Model 750-450 – four channels


Model 750-451 – eight channels
Model 750-452 - 24 V dc, two channels
Model 750-453 - 24 V dc, four channels
Model 750-453/040-000 - 24 V dc, four channels
Model 750-454 - 24 V dc, two channels
Model 750-455 - 24 V dc, four channels
Model 750-455/040-000 - 24 V dc, four channels
Model 750-456 - 24 V dc, two channels
Model 750-457 - 24 V dc, four channels
Model 750-457/040-00 – 24 V dc, four channels
Model 750-458 – eight channels
Model 750-459 – 24 V dc, four channels
Model 750-461 - 24 V dc, two channels
Model 750-462 - 24 V dc, two channels
Model 750-463 – 24 V dc, four channels
Model 750-464 – 24 V dc, two/four channels
Model 750-464/040-000 – 24 V dc, two/four channels
Model 750-465 - 24 V dc, two channels
Model 750-466 - 24 V dc, two channels
Model 750-467 - 24 V dc, two channels
Model 750-468 - 24 V dc, four channels
Model 750-468/040-000 - 24 V dc, four channels
Model 750-469 - 24 V dc, two channels
Model 750-469/040-000 - 24 V dc, two channels
Model 750-470 - 24 V dc, two channels
Model 750-472 - 24 V dc, two channels
Model 750-473 - 24 V dc, two channels
Model 750-474 - 24 V dc, two channels
Model 750-475 - 24 V dc, 1A two channels
Model 750-476 - 24 V dc, two channels
Model 750-477 - 24 V dc, two channels
Model 750-478 - 24 V dc, two channels
Model 750-479 - 24 V dc, two channels
Model 750-480 - 24 V dc, two channels
Model 750-481/003-000 - 24 V dc, two channels
Model 750-482 – 24 V dc, two channels
Model 750-483 - 24 V dc, two channels
Model 750-484 – 24 V dc, two channels
Model 750-487 – 24 V dc, two channels
Model 750-492 - 24 V dc, two channels
Model 750-492/040-001 – 24 V dc, two channels
Model 750-496 – 24 V dc, eight channels
Model 750-497 – eight channels
File E198726 Vol. 1 Sec. 1 Page 8 Issued: 1998-09-11
and Report Revised: 2015-04-30

Digital Output Modules -

Model 750-501 - 24 V dc, 0.5 A G.P, two channels


Model 750-502 - 24 V dc, 2 A G.P, two channels
Model 750-504 - 24 V dc, 0.5 A G.P, four channels
Model 750-506 - 24 V dc, 0.5 A G.P, two channels
Model 750-507 - 24 V dc, 2 A G.P, two channels
Model 750-508 - 24 V dc, 2 A G.P, two channels
Model 750-508/040-000 - 24 V dc, 2 A G.P, two channels
Model 750-509 - 230 V dc, 0.3 A G.P, two channels
Model 750-516 - 24 V dc, 0.5 A RES, four channels
Model 750-518 - 115 V ac, 0,5 A RES, two channels
Model 750-519 - 5 V dc, 20 mA RES, four channels
Model 750-522 - 230 V ac, 0.5 A G.P, two channels
Model 750-530 - 24 V dc, 0.5 A G.P, eight channels
Model 750-531 - 24 V dc, 0.5 A G.P, four channels
Model 750-532 - 24 V dc, 0.5 A G.P, four channels
Model 750-534 – 5 V dc to 14 V dc, 1 A G.P, eight channels
Model 750-535 - 24 V dc, 40 mA G.P, two channels
Model 750-536 - 24 V dc, 0.5 A G.P, eight channels
Model 750-537 - 24 V dc, 0.5 A G.P, eight channels
Model 750-538 – 100 V ac, 0.5 A G.P., two channels
Model 750-538 – 30 V dc, 1 A G.P., two channels
Model 753-540 - 120 V ac / 230 V ac, 0.25 A G.P. four channels
Model 750-632 – 24 V dc, 1.4 A pilot duty (1 chan.)
0.9 A pilot duty (2 chan.)
Model 750-657 – 24 V dc, 0.1 A
Model 750-1500 – 24 V dc, sixteen channels
Model 750-1501 – 24 V dc, sixteen channels
Model 750-1504 – 24 V dc, sixteen channels
Model 750-1505 – 24 V dc, sixteen channels
Model 750-1515 – 24 V dc, eight channels
Model 750-1515/040-000 – 24 V dc, 0.5 A G.P., eight channels
Model 750-1516 – 24 V dc, eight channels

Analog Output Modules -

Model 750-550 - 24 V dc, two channels


Model 750-551 - 24 V dc, four channels
Model 750-552 - 24 V dc, two channels
Model 750-553 - 24 V dc, four channels
Model 750-554 - 24 V dc, two channels
Model 750-555 - 24 V dc, four channels
Model 750-556 - 24 V dc, two channels
Model 750-557 - 24 V dc, four channels
Model 750-557/040-000 - 24 V dc, four channels
Model 750-559 - 24 V dc, four channels
Model 750-559/040-000 - 24 V dc, four channels
Model 750-585 - 24 V dc, two channels
Model 750-560 – 24 V dc, two channels
Model 750-562 – 24 V dc, two channels
Model 750-563 – 24 V dc, two channels
Model 750-563/040-000 - 24 V dc, two channels
File E198726 Vol. 1 Sec. 1 Page 9 Issued: 1998-09-11
and Report Revised: 2016-05-13

Counter Modules -

Model 750-404 - 24 V dc, two channels


Model 750-417 - 24 V dc, two channels
Model 750-638 - 24 V dc, two channels
Model 750-633 – 24 V dc, output 24 V dc

3-Phase Measuring Module

Model 750-493 – 277 V ac 1 A


Model 750-493/000-001 – 277 V ac 5 A
Model 750-494 – 277 V ac 1 A
Model 750-494/000-001 – 277 V ac 5 A
Model 750-494/000-005 - 277 V ac/dc Shunt

Supply Modules -

Model 750-601 - 24 V dc, 10 A maximum


Model 750-602 - 24 V dc, 10 A maximum
Model 750-602/040-000 – 24 V dc, 10 A maximum
Model 750-603 - 24 V dc, 10 A maximum
Model 750-604 - 24 V dc, 10 A maximum
Model 750-606 – 24 V dc, 1 A maximum
Model 750-609 - 230 V ac, 6.3 A maximum
Model 750-610 - 24 V dc, 10 A maximum
Model 750-611 - 230 V ac, 6.3 A maximum
Model 750-612 - 230 V ac/dc, 10 A maximum
Model 750-612/040-000 - 230 V ac/dc, 10 A maximum
Model 750-614 - 230 V ac/dc, 10 A maximum
Model 750-615 - 120 V ac, 10 A maximum
Model 750-623 – 24 V dc, output 5 V at 1 A or 8 to 15 V at 0.5 A
Model 750-625/000-001 – 24 V dc, 1 A maximum
File E198726 Vol. 1 Sec. 1 Page 9A Issued: 1998-09-11
and Report Revised: 2016-05-13

Model 750-1605 - 24 V dc, 5 A maximum


Model 750-1605/040-000 - 24 V dc, 5 A maximum
Model 750-1606 - 24 V dc, 5 A maximum
Model 750-1606/040-000 - 24 V dc, 5 A maximum
Model 750-1607 - 24 V dc, 5 A maximum

Model 750-625 – 24 V dc, 500 mA maximum

Separation Modules –

Model 750-616, 750-621


Model 750-616/040-000

Bus Supply Module -

Model 750-613, 24 V dc, 10 A maximum


Model 750-613/040-000, 24 V dc, 10 A maximum

Pulse Width Module –

Model 750-511 - 24 V dc

PTC Module

Model 750-1425 – eight channels


File E198726 Vol. 1 Sec. 1 Page 10 Issued: 1998-09-11
and Report Revised: 2015-04-30

Interface Modules –

Model 750-630 - 24 V dc
Model 750-631 - 24 V dc
Model 750-635 - 24 V dc
Model 750-637 - 24 V dc
Model 750-641 – 18 V dc
Model 750-642 – 5 V dc, RF output 5 V TTL
Model 750-643 – 24 V dc
Model 750-651 - 24 V dc
Model 753-648 – 24 V dc
Model 750-650 - 24 V dc
Model 750-652 – 24 V dc
Model 750-652/040-000 – 24 V dc
Model 750-653 - 24 V dc
Model 750-655 – 26.5 V dc – 31.6 V dc
Model 750-658 – 24 V dc

Binary Space Module –

Model 750–622, 24 V dc

Digital I/O Modules -

Model 750-418 - 24 V dc 0.5 A G.P, Input/Output 2 channels


Model 750-419 - 24 V dc 0.5 A G.P, Input/Output 2 channels
Model 750-421 - 24 V dc 0.5 A G.P, Input/Output 2 channels
Model 750-665/000-001 – 24 V dc, 0.5 A G.P, 4 channels
Model 750-666/000-003 – 24 V dc, 10 A G.P. Input/Output 4/2 channels
Model 750-667 – 24 V dc, Input/Output 4 channels
Model 750-1502 – 24 V dc, eight channels
Model 750-1506 – 24 V dc, eight channels

Intruder Detection Module –

Model 750-424 - 24 V dc, two channels

End Module –

Model 750-600 – No ratings


Model 750-600/040-000 – No ratings
File E198726 Vol. 1 Sec. 1 Page 11 Issued: 1998-09-11
and Report Revised: 2015-04-30

Filter Modules –

Model 750-624 – 24 V dc, max. 10 A


Model 750-624/000-001 – 24 V dc, max. 10 A
Model 750-624/020-000 – 24 V dc, max. 10 A
Model 750-624/020-001 – 24 V dc, max. 10 A
Model 750-624/040-001 – 24 V dc, max. 10 A
Model 750-626 – 24 V dc, max. 10 A
Model 750-626/020-000 – 24 V dc, max. 10 A
Model 750-626/040-000 – 24 V dc, max. 10 A

RTC Module -

Model 750-640 – 5 V dc internal


(only with passive antenna 758-910 – max. cable length 2.5 m)
Model 750-644 – 5 V dc internal

Field Bus Connector Modules –

Model 750-960 – 5 V dc bus


Model 750-961 – 5 V dc bus
Model 750-962 – 5 V dc bus
Model 750-970 – 5 V dc bus

Motor Controller Modules –

Model 750-670 – 24 V dc
*

Relay Output Modules –

Model 750-512 – 24 V dc, two channels, Relay Contact - 230 V ac, max. 2 A G.P
Model 750-513 - 24 V dc, two channels, Relay Contact - 230 V ac, max. 2 A G.P
Model 750-517 – 24 V dc, two channels, Relay Contact – 230 V ac, max. 1 A
G.P, or 40 V dc, max. 1 A, or 300 V dc, max. 0.15 A
Model 750-517/040-000 – 24 V dc, two channels, Relay Contact – 230 V ac, max.
1 A G.P, or 40 V dc, max. 1 A, or 300 V dc, max. 0.15 A

Condition Monitoring Modules –

Model 750-645 – 24 V dc, vibration/shock sensor inputs, two channels

Maximum Surrounding Air Temperature is 55 ºC unless specified otherwise.


Maximum Surrounding Temperature for Cat. No. with suffix /025-XXX is 60°C
Maximum Surrounding Temperature for Cat. No. with suffix /040-XXX is 70 °C.

All catalogue numbers may have suffix.


File E198726 Vol. 1 Sec. 1 Page 12H Issued: 1998-09-11
and Report Revised: 2015-04-30

MARKING:

The following markings are screen printed or etched on the device.

A. Listee's name, type number and electrical ratings are provided for
each catalog number.

B. Wiring terminals are marked to indicate proper connections for all


circuits.

C. The voltage, current and type of fuse used are marked near each
fuse holder.

D. Class I, Division 2, Groups A, B, C, and D Hazardous Locations as


specified under “Product Covered” section of this report.

E. Temperature code - « T4 ».

F. Date code

G. Marking for Service connectors (where used): These ports must


either be marked with “For maintenance only – See Installation
instructions” or with the Tri-Ex symbol.

H. Module 750-538 only:


Relay markings to include Tri-Ex symbol and statement in the
Installation instruction: “In Hazardous Locations, Non-Incendive
only when installed per Control Drawing No. 750538”.

I. The programmable controllers Cat. No. 750-632 shall be marked with


electrical ratings 0.9 A Pilot Duty (2 channels)on the device or in
the installation manual.

The programmable controllers shall also be marked with the max. specified
surrounding air temperature (55°C with no suffix) on the devices or in the
installation instructions. See Page 11.
File E198726 Vol. 1 Sec. 1 Page 12I Issued: 1998-09-11
and Report Revised: 2016-05-13

INSTALLATION AND OPERATING INSTRUCTIONS:

An installation manual shall be provided with each unit to direct


the user on proper installation and operation of the device and shall include
the following:

A. “This equipment is suitable for use in Class I, Division 2,


Groups A, B, C, D or non-hazardous locations only.

B. “This equipment is to be fitted within tool-secured enclosures


only.”

C. “WARNING - Explosion hazard - substitution of components may impair


suitability for Class I, Div. 2.”

* D. “WARNING - Do not disconnect equipment unless power has been


switched off or the area is known to be non-hazardous” applicable
for each operator accessible connector and fuse holder.”

E. When a fuse is provided, the following information shall be


provided: “A switch suitable for the location where the equipment is
installed shall be provided to remove the power from the fuse.”

F. For devices with Ether CAT/Ethernet connectors “Only for use in


LAN, not for connection to telecommunication circuits”.

G. “WARNING - Use Module 750-642 only with antenna module 758-910”.

H. For Couplers/Controllers and Economy bus modules only: The


instructions shall contain the following: “The configuration
interface Service connector is for temporary connection only. Do
not connect or disconnect unless the area is known to be non-
hazardous. Connection or disconnection in an explosive atmosphere
could result in an explosion.”

I. Modules containing fuses only:


“WARNING - “Devices containing fuses must not be fitted into
circuits subject to over loads, e.g. motor circuits”

J. Modules containing SD card reader sockets only: "WARNING: DO NOT


CONNECT OR DISCONNECT SD-CARD WHILE CIRCUIT IS LIVE UNLESS THE AREA
IS KNOWN TO BE FREE OF IGNITABLE CONCENTRANTIONS OF FLAMMABLE GASES
OR VAPORS."

K. The Modules 750-439, 750-538, 750-633, 750-663/000-003 shall only be


supplied with 750-606 or 750-625/000-001.
File E198726 Vol. 1 Sec. 1 Page 12I1 Issued: 1998-09-11
and Report New: 2014-11-07

L. Module 750-538 only


Manual shall contain CONTROL DRAWING No.750538 with its entity
parameters. “In Hazardous Locations, Non-Incendive only when
installed per Control Drawing No. 750538”.

S-ar putea să vă placă și