Sunteți pe pagina 1din 3

No-load Current Basics: Practical Guidelines For Assessment

no-load current, as a percentage of


FLA.
NLA
• The ratio of _____ is inversely
Full Load Current

FLA
(though not directly) proportional
to hp.

Current
Practical Guidelines
The intent of this article is to B
explain why those statements are A

valid and, in the process, to offer


practical guidelines for assessing no-
25% 50% 75% 100% 125%
load current. Many of us apply these Applied Voltage (% Of Rated)
principles daily.
By Chuck Yung Knowledge is power. We should,
Figure 1. Graph of applied voltage
EASA Technical Support Specialist whenever possible, improve our
against current.
knowledge by gathering facts:
How much no-load current should • Use the AC Motor Verification & rated voltage. Then you were able to
I expect when testing a motor? We Redesign Program to check switch up to rated voltage.
would like to have a ratio of no-load densities before rewinding the Figure 1 illustrates what happens
amps / full-load amps, for quality motor. when we run an uncoupled motor at
control purposes. • Keep records of tests for compari- varying voltage. As long as the motor
*** son of identical machines. will maintain speed, we can reduce
Many of us expect a motor to • Get information from the manufac- the voltage and expect a more-or-less
draw approximately one-third of rated turer to supplement your records. linear change in current.
current, when operating from rated Before we get to the simple table To demonstrate this, use a motor
voltage on our test panel. That is a of “expected” values for no-load without an external fan. Operate the
good rule of thumb—most of the current, we will lay out some tools to motor at rated voltage and record the
time. While there are lots of excep- use for understanding the exceptions current. Decrease the voltage slowly,
tions, most of them are predictable. to that “one-third of FLA” guideline. recording both voltage and current.
To explain the rule of thumb and First, let’s review our basic under- Now graph the results, and the result
the exceptions, we will use some standing of the relationship between will be similar to Figure 1. Along the
terms familiar to most readers: voltage, flux and torque. straight portion of the line, the flux
FLA = Full-load amps changes in proportion to the applied
Torque ∝ AGD2 ∝ V2 voltage. Consequently, we can expect
NLA = No-load amps; this is
magnetizing current plus some Effects Of Applied Voltage the current to change proportionally
losses (mostly windage) For any given motor, flux density also—within limits.
Flux = Lines of magnetic force changes in proportion to the applied If the applied voltage is too low, the
AGD = Airgap density; in lines of voltage. Torque produced by the motor slows down and the current
flux per unit area motor varies as the square of the flux. increases (left of Point A in Figure 1)
V = Applied voltage If we change the voltage applied to a as the motor tries to develop enough
motor, we expect the current to torque to keep turning. The speed
Here are some exceptions you
change proportionally. decreases because the torque is too low
probably recognize:
We apply this principle every time to overcome friction & windage losses.
• The higher the flux density, the
we start a motor at reduced voltage.
higher the no-load current will be 1
_____ 1
__
Remember that motor that was too big
as a percentage of FLA. Slip ∝ AGD2 ∝ V2
to start on the test panel? You simply
• The lower the speed, the higher the
brought it up to speed at a fraction of Continued On Page 2

EASA CURRENTS ■ February 2005 1


No-load Current Basics: Practical Guidelines For Assessment
Continued From Page 1

Next slowly raise the voltage hand, the motor is usually more of thumb. Likewise, the high-flux
above rated voltage, again recording forgiving of under-voltage conditions, design might be expected to draw a
the voltage and current. As the compared to a conservatively fluxed bit higher than the one-third rule.
voltage increases, the current increase motor. Knowing the influence of flux
will remain linear until we reach We can expect designs that operate density, we can evaluate motors that
saturation (Point B, Figure 1). When at or near the knee of the saturation deviate from our usual expectations.
the stator core becomes saturated, it curve to draw higher no-load current
Flux And Airgap
takes a disproportionate amount of than those operating along the linear
Because very low-speed ma-
current to increase the level of flux. portion of the curve.
chines are less common, a motor that
Between Points A and B, voltage What about conservative designs,
draws three-fourths of rated current
graphed against current will be more- such as older U-frame machines?
gets our attention. That anomaly is
or-less linear. Those, as well as two-pole
easy to explain. It takes more
That is one reason we should test machines, motors designed for high
current to drive flux through air
run all repaired motors at rated ambient temperatures (kiln motors) or
than through steel.
voltage, and record the voltage and high altitude use, are deliberately
A common test used by our
current on all phase leads. The no- “fluxed low” —meaning they are
industry—the open-stator test—
load test run is a critical step in designed to operate well below the
demonstrates this. We apply one-sixth
quality assurance. (See the February knee of that flux curve. We should
of rated voltage to an open stator,
2004 CURRENTS article “Avoiding expect relatively low no-load current.
with the expectation that it will draw
High No-Load Amps.”) While more tolerant of high voltage,
close to rated current. Why does it
Some manufacturers are very they are more susceptible to low
draw full-load current with only a
frugal with active materials (steel and voltage conditions.
fraction of rated voltage? There is no
copper cost money, after all), and
Different Designs Affect Rule rotor to complete the flux path, so the
some applications require a high hp or
Four-pole machines dominate flux must travel through air. That
kW rating in a small physical pack-
industry, so the “one-third of rated requires a lot more current—hence
age. From Figure 1, we can expect
current” rule is appropriate. But while the lower voltage used for the test.
such a “high flux” motor to draw
one 4-pole motor might be a conser- Note: Some service centers use
relatively high no-load current. It is
vative design for a variety of reasons, higher than 1/6th of rated voltage, and
also more sensitive to higher-than-
another might be fluxed higher. So we expect higher than FLA. But open
rated voltage—which may push the
should expect the conservative design stator tests at higher voltages make it
core into saturation. On the other
motor to draw a bit less than our rule difficult to interpret the results.
The greater the distance flux has to
travel through a non-ferrous medium,
the higher the current required. For
each trip around a stator, the flux in
each phase has to cross the airgap
twice per pole. Compare a 2-pole
machine to a 10-pole. (Figure 2.) For
each revolution around the stator, the
10-pole flux must cross the airgap 20
times, while the 2-pole flux only has
to cross it four times. It takes more
current to force flux across the airgap
than through the steel core.
Consider Number Of Poles
2-pole flux path 10-pole flux path It should be no surprise that low-
speed machines draw relatively high
no-load current. The no-load current
Figure 2. 2-pole and 10-pole flux path connection. Continued On Page 3

2 EASA CURRENTS ■ www.easa.com


No-load Current Basics: Practical Guidelines For Assessment
Continued From Page 2

increases incrementally with the


number of poles. (At the risk of Table 1
being redundant, more poles =
higher magnetizing current.) To Poles of 3-phase Expected no-load current Approximate
minimize the effect, machines induction motor as a fraction of FLA percent of FLA
with more poles are designed 2 1/4 to 1/3 25-33
with closer airgap between rotor
4 1/3 to >3/8 33-40
and stator.
The ratio of NLA/FLA varies 6 1/3 to <1/2 33-45
in inverse proportion to the 8 1/3 to >5/8 33-65
motor size and hp (kW) rating.
Depending on the design, the 10 or higher 3/5 to >FLA 60-110

ratio could be twice as large for a


After calculating the flux densities, we can better evaluate the ratio of no-load current to full-load
10 hp motor as for the same current. The higher the flux density, the higher the ratio current is likely to be.
manufacturer’s 300 hp motor.
• The higher the flux density, the higher the no-load current will be as a percentage of FLA.
Consider Scale, Manufactur- • The lower the speed, the higher the no-load current, as a percentage of FLA.
ing Tolerance NLA is inversely (though not directly) proportional to hp.
• The ratio of _____
FLA
Part of the explanation is one
of scale and manufacturing
tolerance. The average bore operating uncoupled at rated voltage. quick reference of expected ranges,
diameter of an 8-pole 300 hp motor is Verifying this on the test panel offers but we have to consider each motor
5 times the bore of the typical 10 hp 8- a quick quality control tool. If a motor individually. In general, we expect
pole motor. The 300 hp motor has an is misconnected, we can catch that by higher no-load current for motors
airgap of approximately 0.040” (1 mm). measuring the no-load current. Note with more poles, especially for
If everything was to scale, the 10 hp that we consider “no-load” as being smaller motors.
8-pole airgap would be only 0.008” “uncoupled” while many of our If we rewound the motor,
(40/5 = 8). customers interpret it as meaning “the someone should have used the AC
We know that airgap must be mile-long conveyor is not loaded with Motor Verification & Redesign
uniform within 10% to avoid electri- rock.” There is a big difference Program to check the flux densities.
cal noise and rotor pullover issues. between those two conditions. Armed with that information, we can
Ten percent of 0.008” is less than 1 Table 1 shows typical expected better assess the actual NLA. If there
thousandth—hardly practical. Even no-load current for evaluating motors is any question, compare the results
the bearings have more internal play when we test them uncoupled. The to historical records for tests of
than that. exceptions we have discussed can be identical motors.
The manufacturer has little choice used to evaluate each motor so that Finally, the NLA is affected by the
but to allow higher magnetizing current we can make a reasonable judgment grade of steel, annealing condition,
with a larger airgap distance. Knowing as to whether or not test results and small variation in airgap. A
this, we should anticipate the NLA outside these guidelines make sense. manufacturer’s published NLA may
variation based on hp rating as well as After calculating the flux densi- vary by 25% or more. In rare cases a
the number of poles. ties, we can better evaluate the ratio motor may draw higher current
(It is also impractical to design of no-load current to full-load operating at no-load conditions than
small cores specifically for low current. The higher the flux density, at rated load. But while that might be
speeds, so a 4-pole core is used.) the higher the expected no-load plausible for the 10-pole motor, it
Because there are a lot more 4- current is likely to be. surely spells trouble for a 2-pole. So
pole machines in industry than any keep those principles in mind next
other speed, we grow accustomed to Exceptions To Every Rule
time you test run a motor that falls
the no-load motor drawing approxi- Remember that there are excep-
outside these rules.
mately one-third of FLA when tions to every rule. Table 1 gives a

EASA CURRENTS ■ February 2005 3

S-ar putea să vă placă și