Sunteți pe pagina 1din 1

Petrol station cable (N)YYo

È -J 0,6/1 kV, with BAM*-Test report

Technical data Cable structure Application


± Power and data transmission cable ± Plain copper conductor, solid according Power and data transmission cables are
based on DIN VDE 0271 with VDE regis- to DIN VDE 0295 cl. 1 and IEC 60228 used for outdoor and underground appli-
tration number and BAM1)-test report cl. 1 cations, in water and in concrete
on manufacturing ± Core insulation of PVC, compound YI3 provided mechanical damage can be
± Temperature range according to DIN VDE 0207 part 4 ruled out. These cables are installed for
flexing ± 58 C to +508 C ± Concentric lay-up of cores applications such as petrol stations and
fixed installation ±308 C to +708 C ± Core identification according to oil refineries where resistance to oils and
± Limiting temperature at the DIN VDE 0293 fuels is required.
1)
conductor +708 C ± PVC outer jacket black according to
± Nominal voltage U0/U 0,6/1 kV DIN VDE 0207 part 5 VDE 0298 part 1 shall be observed.
± Test voltage 4 kV ± Oil and fuel-resistant according to
± Max. permissible tensile stress by DIN ISO 6722
cable grip for Cu-conductor ± PVC self-extinguishing and flame-retar-
= 50 N/mm2 dant, test method B according to
± Minimum bending radius DIN VDE 0472 part 804 and IEC 60332-1
approx. 12 x cable 1
= The product is conformed with the EC Low-Voltage Directive 73/23/EEC and 93/68/EEC.

Part No. of cores x Outer 1 Cop. weight Weight AWG-


No. cross-section ca. mm kg / km ca. kg / km no.*)
mm2
32592 2 x 1,5 12,2 29 180 16
32593 3 x 1,5 13,2 43 225 16
32594 4 x 1,5 14,2 58 260 16
32595 5 x 1,5 15,2 72 280 16
32596 7 x 1,5 16,2 101 370 16

Design: 7 x 1,5

*) Note
AWG sizes are approximate equivalent values.
The actual cross-section is in mm2 ± see page T 15.

* BAM = Bundesanstalt fuÈr MaterialpruÈfung.


1)
Version with blue outer jacket available upon request.


N 10