CALCULATION REPORT FOR

STEEL STAIR
Declaration

We, hereby declare that this report is a Corrective Action Plan report for structural
safety made for Stair of Four Story RCC Main Production Building (Main Building-
3) of Polo Knit Composite Ltd.

We also declare that this assessment has been done based on designed data following
mainly AISC Code, BNBC 2006. The objective is to support the Alliance program.

All rights reserved. This report and all other documents related to this project are
confidential and may contain information that is privileged or otherwise protected
from disclosure and are only for the intended recipient. No part of the contents of these
documents shall be reproduced or transmitted in any form or by any means without
the written permission of d.zignscape Consultants Ltd.

Sayeedur Rahman

Structural Engineer (Civil, KUET)


MIEB No: 19024

RAJUK Registration. No: DMINB-CE/00

Md. Bazlur Rahman

Structural Engineer (Civil, DUET)

MIEB No: 19024


This page is intentionally left blank
INDEX

ANNEXURE A: ENGINEERING ASSESSMENT.


EXECUTIVE SUMMARY

Stair of Chiller Room of Noman Terry Towel Mils Ltd .


A team from ALLIANCE conducted visual assessment of the building. They
recommended to perform Engineering Assessment of the building. On this
recommendation the authority of Building 2 (Finishing Unit) has engaged
‘d.zignscape Consultants Ltd.’ for performing Engineering Assessment along
with checking architectural and structural drawing of the building.

Considering the NTPA load combinations, we have analysed the structure and found
that all the steel members are inadequate (except few sub-beams).

Considering the BNBC load combinations, we have analysed the structure and found
that all the steel members are inadequate (except few sub-beams).

We recommend to maintain the steel structure & connections to protect these from
corrosion.

We strongly recommend to rectify the overstressed members to meet BNBC


requirement ALLIANCE recommended load combinations.
This page is intentionally left blank
Chapter 1
General Notes
Design Code: BNBC 2006, AISC 360-05

Material Property: ASTM A36


Chapter 2
Load Calculation
Load calculation:

Dead load:

Weight of steel plate


Self-weight of members

Live load:
84 psf load

Load Case
1. Dead Load, DL
2. Live Load, LL 84 psf

For the design of steel stair we have considered the load combination provided by the BNBBC-2006 for
Steel Structures. The following load combination has been used for design:

For Steel Structure:


 Combination Case1: 1.4 DL
 Combination Case2: 1.2 DL + 1.6 Lf + 0.5 Lr
 Combination Case3: 1.2 DL + 1.6 Lr + 0.5 Lf
 Combination Case4: 1.2 DL + 1.6 Lr + 0.8 Wx(+)
 Combination Case5: 1.2 DL + 1.6 Lr + 0.8 Wx(-)
 Combination Case6: 1.2 DL + 1.6 Lr + 0.8 Wy(+)
 Combination Case7: 1.2 DL + 1.6 Lr + 0.8 Wy(-)
 Combination Case8: 1.2 DL + 0.5 Lf + 0.5 Lr + 1.3 Wx(+)
 Combination Case9: 1.2 DL + 0.5 Lf + 0.5 Lr + 1.3 Wx(-)
 Combination Case10: 1.2 DL + 0.5 Lf + 0.5 Lr + 1.3 Wy(+)
 Combination Case11: 1.2 DL + 0.5 Lf + 0.5 Lr + 1.3 Wy(-)
 Combination Case12: 1.2 DL + 0.5 Lf + 1.5 Ex
 Combination Case13: 1.2 DL + 0.5 Lf - 1.5 Ex
 Combination Case14: 1.2 DL + 0.5 Lf + 1.5 Ey
 Combination Case15: 1.2 DL + 0.5 Lf - 1.5 Ey
 Combination Case16: 0.9 DL + 1.3 Wx(+)
 Combination Case17: 0.9 DL + 1.3 Wx(-)
 Combination Case18: 0.9 DL + 1.3 Wy(+)
 Combination Case19: 0.9 DL + 1.3 Wy(-)
 Combination Case20: 0.9 DL + 1.5 Ex
 Combination Case21: 0.9 DL - 1.5 Ex
 Combination Case22: 0.9 DL + 1.5 Ey
 Combination Case23: 0.9 DL - 1.5 Ey

Where, D = Dead Load, Lf = Floor live load, Lr = Roof live load, W = wind load and E = earthquake load.
Chapter 3
3d View of the Model
FIGURE: 3D FRAMING FOR STAIR
FIGURE: MEMBER SECTIONS FOR STAIR
Chapter 4
Loads Applied on the model
FIGURE: DEAD LOAD ON (SELF WT OF CONCRETE AND STEEL PLATE)
FIGURE: LIVE LOAD ON (SELF WT OF CONCRETE AND STEEL PLATE)
Chapter 6
Member Design Result
FIGURE: DCR VALUE OF STEEL MEMBER