1. GENERAL
1.1. Scope
2. CLIMATIC CONDITIONS
2.1. Rainfall
2.2. Snowfall
2.3. Wind
2.4. Earthquake
3. LOADS ON STRUCTURES
3.3.1. General
3.3.2. Loads produced by persons
3.3.3. Piping loads
4. LOAD COMBINATIONS
5. STRUCTURAL CONCRETE
5.1. General
5.9.1. Design
5.9.2. Clearance
5.9.3. Tolerance
5.10. Grouting
6. STRUCTURAL STEEL
6.1. General
6.3. Connections
7. SOIL CHARACTERISTICS
8. FOUNDATIONS
9. FIRE PROOFING
1.1. Scope
The purpose of this document is to define the design criteria for the concrete foundations
and structure applicable to the various projects of QAPCO in their Petrochemical Complex
located in UMM SAID, State of QATAR.
These design criteria shall apply to all concrete foundations, concrete and steel structures
and concrete paving for equipments and buildings, pipe supports and platforms at the above
site.
This specification is supplemented by other documents listed below and shall prevail over
the listed documents.
The following specifications, codes and standards, in their last revisions, shall be read in
conjunction with and shall be part of this specification.
- BS 639 : (1986) : Specification for covered carbon and carbon manganese steel
electrodes for manual metal arc welding.
- BS 4165 : (1984) : Specification for electrode wires and fluxes for the
submerged arc welding of carbon steel and medium tensile steel.
- BS 4320 : (1968) : Specification for metal washers for general engineering purposes.
- BS 4395 : : Specification for high strength friction grip bolts and associated nuts
and washers for structural engineering.
Spec RG -1700 -.01-Rev.5
Page 5 of 24
- BS 4449 : (1988) : Specification for carbon steel bars for the reinforcement of concrete.
- BS 4482 : (1985) : Specification for cold reduced steel wire for the reinforcement for
concrete.
- BS 5135 : (1984) : Specification for arc welding of carbon and carbon manganese steels.
- BS 6399 : part 1 : (1984) : Loading for building - Code of practice for dead and imposed
loads.
- BS 7295 : (1990) : Fusion bonded epoxy coated carbon steel bars for the reinforcement
of concrete.
- BS 8007 : (1987) : Code of practice for design of concrete structures for retaining
aqueous liquids.
- BS 8110 : Part 1 : (1985) Structural use of concrete code of practice for design and
construction.
- CP 2012 : part 1 : (1974) : Code of practice for foundations for machinery - Foundations
for reciprocating
machines).
2. CLIMATIC CONDITIONS
2.1. Rainfall
Spec RG -1700 -.01-Rev.5
Page 6 of 24
<5> Rainfall load should be at maximum 0.7 kN/m2 for the design.
2.2. Snowfall
2.3. Wind
Wind loads shall be calculated in accordance with, CP 3 : ch. V - Part 2 : 1972 "Code of
basic data for the design of buildings".
The wind is generally from the North, North West with occasional periods of southerly winds.
Structure and equipment which extend to more than 15 meters above grade will be designed
for a wind of 45 m/s.
Structure and equipment which extend less than 15 meters above grade will be designed for
a wind of 38m/s.
2.4. Earthquake
3. LOADS ON STRUCTURES
The design of foundations and structures will take into account the following loads.
All structural materials, floors, stairs, covering, fire proofing and all permanent materials
forming part of the structures shall be considered as dead loads.
3.1.2. Dead loads of equipment & machinery (except bridge cranes and lifting appliances)
Equipment and machinery loads without the liquid contained inside or without removable
parts shall be considered as dead loads.
a) Temporary large point loads shall be considered on structural frames during the
installation of equipment, such as gin pole loads on structures or foundations.
b) Vertical vessel foundations shall be designed for maximum overturning loads considering
vessels are at minimum vertically loaded condition.
c) Large rotary equipment part loads shall be investigated on framing members (e.g. rotors
during maintenance or installation).
3.3.1. General
- temporary loads such as bundle pulling loads, (for checking of ultimate load only),
The design live loads for floors, platforms, walkways and stairs shall be as follows :
Piping loads include all thrusts or moments due to thermal expansion or contraction of piping
and the blow-out forces of expansion joints, bell and spigot pipes, safety relief valves, etc.
Spec RG -1700 -.01-Rev.5
Page 8 of 24
Piping loads in general shall be considered as equipment loads.
Horizontal loads caused by pipe expansion and anchor shall be considered as operating
loads.
a) Vertical loads shall be computed according to size distribution and service conditions of
pipes which are supported.
For pipeways, use 1450 N/m² as a minimum pipe load. This approximates 6 inch pipes
filled with water (spacing between pipes : 12 inches).
b) Pipes larger than 12 inches diameter shall be considered as concentrated loads in their
actual locations.
- 10 % of the sum of all operating pipe loads acting longitudinally for pipes
less or equal to 12" diameter,
and
- 30 % for pipes larger than 12" diameter.
or
- Every main supporting girder (girder which supports all diameter pipes) shall be
calculated to withstand horizontally, in the direction of the pipes, friction forces
as mentioned above or an arbitrary anchor force minimum 5 kN located at the
most unfavourable position, whichever results in a greater member size.
During refinement of the design, when location of anchors is defined the proper
loads shall be considered.
b) Pipe rack frames shall be calculated taking into account following horizontal thermal
forces, at right angle with pipes, as a minimum :
c) Horizontal loads on the anchor bays of pipe racks shall be taken as the greatest of :
(per longitudinal file)
They shall be calculated, (in addition to the above), for the following :
- steel/steel 0.33
- PTFE/stainless steel 0.05 *)
or PTFE/PTFE
. when hydrostatic pressure testing of equipment is required at site, the weight of this
equipment completely filled with water shall be incorporated in the design of the
supporting structure.
. when more than one vessel, etc.. is supported by one structure, the structure and the
relevant foundation need to be designed on the basis that one vessel will be tested at any
one time and that the others will either be empty or still in operation.
a) Bridge crane
Loads applied from bridge cranes must be calculated in accordance with applicable codes
and standards but should not be less than the following :
Electric Hand
operation operation
When hoisting by means of chain hoist, air or electric hoist, increase loads on supporting
members by 50 % for impact.
Provision shall be made for the pulling force required when removing (or installing) a tube bundle
from a shell. The minimum horizontal force applied at the center of the bundle shall be equal to
50 % of the weight of the bundle with a 5 kN minimum.
Horizontal pulling force shall be assumed to act at the centre line of the exchanger and resisted
by the fixed support only. When exchangers are stocked, the force shall be taken as acting at the
upper exchanger centre line, with the lower exchanger bundle having been removed.
Due to the wide range of temperature occurring throughout the year expansion joints are to be
provided at convenient locations.
-5
- concrete linear expansion factor Ctc = 1.1 10
-5
- steel linear expansion factor Cts = 1.2 10
Such data can be neglected for concrete structures and for steel structure with expansion joints
provided at 30 meters maximum distance. Data shall be used to determine size of expansion joint
with a minimum joint width of 25 mm.
Piping, vessels, fire equipment, ducts and heat exchangers on structural supports shall be
analyzed for thermal forces to be resisted by the structures and provision shall be made to relieve
forces too large for the equipment or the supporting structure.
Trench covers in areas with vehicular access shall be designed for 50 kN wheel load. Contact
area of wheel on covers which has been considered is : 250 x 200 mm.
Spec RG -1700 -.01-Rev.5
Page 11 of 24
4. LOAD COMBINATIONS
The following combination of loads shall be investigated in the design of structural members and
foundations
Dead loads :
Structures X X X X X
Weight of equipment X X X X X
Live loads:
X X X (5)
Persons
Test load - X - - -
Thermal loads X X X
(1) The most unfavourable load combinations shall be taken into account.
(2) Crane loads with 50 % of wind pressure shall be applied on open structures and/or open
sided buildings. Crane loads with full wind shall be applied on closed buildings.
(3) 50 % of wind pressure shall be applied in test condition.
(4) For structures supporting equipment subject to water filling, in which 90 % or more of the live
load is water, applied for 72 hours or less, the basic allowable unit stresses for all loads
during the filled period may be increased by 20 %.
The following load combinations shall be used in assessing the design stability of tall vessels
subject to overturning.
Spec RG -1700 -.01-Rev.5
Page 12 of 24
a) Erection condition
. Dead load
. Live load
Wind.
b) Test condition
. Dead load
. Live load
c) Operating condition
. Dead load
. Live load
. Dead load
Vessels without operating fluids, with removable internals, platforms and ladders,
insulation and piping.
. Live load
Wind, platforms.
5. STRUCTURAL CONCRETE
5.1. General
The design and details of structural concrete shall be read in conjunction with relevant British
codes (refer to paragraph 1.2).
The allowable stress in concrete and reinforcing steel shall be in accordance with BS 8110 and
BS 8007.
The allowable stresses for members subjected to short time overload conditions may be
increased by 20 % where short time overload is defined as follows :Short-time overload
The structural and equipment operating and the piping dead loads, the design live load, lifting
points load, appropriate equipment and piping contents loads resulting from short-time
operational upsets (such as may occur during starting-up, shutting down, or an interruption in
operation of the process).
Spec RG -1700 -.01-Rev.5
Page 13 of 24
The magnitude and application of loads for the purpose of designing concrete structures and
foundations subject to hydrostatic test loading shall be as follows :
Case A : For small vessels where the hydrostatic test load will not be applied for more than 4
days, wind loading shall be ignored.
Case B : For large vessels and small vessels where the hydrostatic test load will be applied for
5 or more days, 50 % of wind load shall be considered to act simultaneously with the
hydrostatic test load.
The allowable stress for members subject to hydrostatic test loads may be increased by 20 %
for case A and by 25 % for case B.
Type I : . For plain blinding concrete . Minimum strength 15 MPa at 28 days (ref. OPC
15).
. 250 kg/m3 ordinary Portland cement minimum.
All aboveground concrete surfaced (including the internal surface of manholes) to be coated
with Hempel "Sealant O 597" as a primer and Hempel "Hempadur 4523" of DFT 100 microns as
a top coating.
Concrete paving shall be separated from the foundations piers with flexible material about 20
mm thick covered with heavy duty mastic 20 mm x 20 mm. The mastic must resist for water,
weather and chemical.
The arrangements of above clause 5.3 shall be applied and for paving slab as above mentioned
(clause 5.4.1.).
Formed concrete slabs and walls not against ground or not 20 mm³
exposed to weather
The bottom of excavations for reinforced concrete bases and footings shall be blinded with a 50
mm thick layer of concrete prior to the reinforcement being fixed.
Construction joints in columns shall be positioned at the soffit of girders, beams, haunches or
column capitals and also at an appropriate 'kicker' height above slabs or bases.
Construction joints in girders, beams and slabs shall be positioned at approximately a third of
the span from a support.
Construction joints shall be arranged to minimise the effect of shrinkage of the concrete.
Generally, the distance between joints shall not exceed 10 meters.
Where watertight construction is required, all construction joints shall have a continuous PVC
Water bar of approved type.
Where required, a 100 mm thick reinforced concrete slab shall be used in process unit areas not
subject to regular maintenance loads or other heavy loads.
A 150 mm thick reinforced concrete slab shall be used in areas regularly subject to maintenance
loads.
Spec RG -1700 -.01-Rev.5
Page 15 of 24
Paving areas which sustain constant concentrated equipment loadings (piping assembly
support, etc.) shall be properly thickened and reinforced in the loaded area to insure proper load
transfer to the subgrade.
In the paving slab, the expansion joints shall be spaced every 6.0 m in two directions.
An horizontal dowel will be inserted in the joint every 400 mm (as per sketch below) to prevent
the vertical movements but not the horizontal expansion.
The joint will be filled with a 2.0 cm thick flexible material, which will be covered at the top with
heavy duty mastic 20 mm x 20 mm, water, weather and chemical resistant.
The dowel shall be coated as per section 5.9. It will be cast on one side in the concrete. The
other half will be inserted in a closed p.v.c. pipe which will prevent the bonding of the dowel with
the concrete.
dowal bar
- Reinforcing steel shall be high yield deformed bars with a specified strength of 460 N/mm²
according to BS 4449. For design purpose the steel characteristic strength shall be limited to
425 N/mm².
- Mild steel bars may be used for links and binders. Characteristic strength shall be 250
N/mm² according to BS 4449.
The bending of bar reinforcement shall be carried out in accordance with BS 4466.
5.9.1 Design
Anchor bolts shall be designed to cater for initial tension, induced loads and horizontal shear.
The maximum allowable stresses for anchor bolts shall be based on the root area of the thread.
When anchor bolts are set in concrete and are subjected to combined shear and tensile loads,
the shear load shall be transmitted to the concrete by the anchor bolts and keys (if required).
When anchor bolts are to be set in sleeves, the sleeves shall be filled with grout. When required
to allow the equipment expansion due to temperature, sliding plates shall be provided ; anchor
bolts at sliding plates shall be hand tight only.
Bolt capacities embedments and plate sizes will be based on a concrete having a strength of 28
MPa at 28 days.
5.9.2 Clearance
Minimum clearance between anchor bolts axis and the face of the foundation shall be as follows
:
- diameter < or equal to 30 mm : 150 mm,
- 30 mm < diameter < or equal to 56 mm : 200 mm,
- 56 mm < diameter < or equal to 80 mm : 300 mm.
5.9.3 Tolerance
5.10. Grouting
Sand/cement grouts for use under stanchion base plates etc... shall consist in one part of
Portland cement to three parts of sharp sand by volume mixed with the minimum water for
workability.
The minimum thickness of grout shall be 25 mm unless specified otherwise on the design
drawings.
All grout shall have a compressive strength at least equal to the foundation concrete.
6. STRUCTURAL STEEL
6.1. General
Structural steel shall be designed in accordance with the local Code, Q.N.B.S. and the British
Standards to which it refers (in particular, BS449 Part 2).
For loads, refer to section 3 and 4 of this specification.
All structural steel shall be grade 43B to BS EN 10025 or equivalent.
Design shall be in accordance with the above standards with the following modifications :
6.2.2. For structural elements continuously exposed to heat above 260°C (500°F), allowable design
stresses shall be reduced in proportion to reductions in yield strength of the steel at the design
temperatures.
6.2.3. Special materials protection or material thickness allowance shall be employed for structural
elements subjected to severe corrosion or wear conditions.
6.2.4. For structures supporting equipment subject to water filling, in which 90% or more of the live
load is water, applied for 72 hours or less, the basic allowable unit stresses for all loads during
the filled period may be increased of 20%.
6.2.5. Where special design conditions require higher strength materials, they may be used but shall
be submitted to Engineering Contractor or to QAPCO for approval and must be designed,
designated and detailed accordingly.
- Design vertical deflections on structural steel members under the effect of dead loads,
equipment loads, live loads, crane loads and wind loads shall not exceed the following
values :
- Design horizontal deflections on structural steel frames under the effect of equipment loads,
live loads, crane loads and wind loads shall not exceed the following values :
- In case of pipe racks design deflection under the effect of dead loads and imposed loads
shall not exceed the following values :
6.3. Connections
6.3.1. Shop connections may be welded or bolted with high strength friction grip type bolts.
6.3.2. Field connections are to be bolted with high strength friction type bolts, conforming to BS 4604.
No field welding shall be permitted for structural steelwork unless approved by the Engineering
Contractor. The welding procedure specification and welders qualification test certificates will
have to be submitted to the Engineering Contractor for approval. If approved, field welding may
be used if facilities are available and if so, field welding shall be designed, detailed and
specified.
6.3.3. Minor connections such as handrail, floor plate, etc..., may be bolted with common black bolts of
grade 4.6, conforming to BS 4190 or welded if required on drawings.
6.3.4. Black bolts connecting members supporting vibrating equipment shall have lock-washer or other
equivalent system.
6.3.5. High strength bolts friction type shall be tightened in accordance with the minimum tension
specified in BS 4604.
6.3.6. The minimum bracing connection shall be made using two 20 mm (3/4 inch) diameter high
strength bolts or be capable of resisting to 59 kN if welded.
7. SOIL CHARACTERISTICS
For design purposes, the maximum height of the ground water shall be taken as follows :
- For ethylene plant area, design will be performed with 0,3 MPa at 2 meters depth on soil
substitution for foundations not less than 1 m wide. For foundations less than 1 m wide, the
bearing pressure will be reduced prorata.
- For new plants like LDPE Unit N° 2 and utility generation facilities extension, a specific soil
survey will be made.
8. FOUNDATIONS
8.1.1. Foundations subject to static loads only, shall be designed generally in accordance with the
British Code of Practice for foundations BS 8004.
8.1.2. Foundations subject to overturning moments, shear or uplift forces, shall be proportioned so that
under any condition of loading the Factor of Safety against overturning and shear, shall not be
less than described in section 8.2. The weight of earth superimposed over foundations may be
used in computing the resisting moment or load.
8.1.3. Foundations and structures for reciprocating machinery subject to vibration shall be designed
generally in accordance with the British Code of Practice for foundations for machinery, CP
2012 : Part 1 : 1974 or equivalent.
The horizontal eccentricity in any direction, between the centroid of mass of the
machine-foundation system and centroid of the base contact area, shall not exceed 5 % of the
respective dimension.
The center of gravity of the machine-foundation system should be as close as possible to the
lines of action of the unbalanced forces.
c) within the weight requirements of the foundation, the upper table and the foundation slab
shall be as rigid as possible in the horizontal plane.
Dynamic design shall show that the natural frequencies of foundation-soil system are either less
than 80 % or greater than 120 % of the operating frequency of the machine.
In case such a provision is impracticable, it shall be shown that the amplitudes are within the
allowable values indicated in fig. 1. A reasonable amount of damping shall be estimated.
8.1.5. Pump foundation block shall be reinforced only on exposed faces, however appendages to such
foundations shall be reinforced to ensure integral action.
8.1.6. Masonry walls shall be supported on either grade beams or continuous strip footings.
8.1.7. Allowance must be made for buoyancy where any foundations are submerged by ground water.
Foundations and structures shall be checked for resistance to overturning and sliding. The
minimum factors of safety shall be as follows :
a) 1.5 times the overturning moment for erection condition or test condition.
b) 2.0 times the overturning moment for operating condition or shut-down condition.
8.3. Settlement
Except for vibrating machinery a maximum settlement of any one foundation should be 25 mm
with maximum differential settlement of 12 mm from one foundation to another after hydrostatic
tests.
In general, foundations for equipment, structures, buildings etc...shall be shallow type (refer to
section 7.2. here above).
Foundation plinths for structural columns and equipment leg supports shall extend not less than
50 mm from the edges of base-plates 0.2 m sq. and less in area, and 75 mm for base-plates
over 0.2 m sq in area.
Foundations for equipment such as pumps and compressors shall extend not less than 75 mm
from the edge of base-plates except when otherwise specified on the manufacturer's drawings.
Foundations, for vessels supported on skirts, shall have the area within the skirt sloped for
drainage to a 50 mm pipe drain, cast in the foundation and directed to the paving or ground.
Spec RG -1700 -.01-Rev.5
Page 21 of 24
Unless otherwise specified, exposed edges of concrete above grade shall have a 25 mm
chamfer.
All reinforced concrete foundations shall be constructed on mass concrete blinding. The
thickness of blinding shall be 50 mm.
9. FIREPROOFING
Detail of design and calculations shall be shown on sketches showing structure arrangements,
loads, member sizes, etc... Computer printout shall supplement sketches whenever computers
are utilised.
All calculations shall be in English language, using S.I. units.
. Length m, mm
. Area m², mm²
. Volume m3, mm3
. Force N, kN
. Distributed loads kN/m²
. Stress N/mm² (MPa)