Sunteți pe pagina 1din 7

Available online at www.sciencedirect.

com
Proceedings
ScienceDirect of the
Combustion
Institute
Proceedings of the Combustion Institute 35 (2015) 2723–2729
www.elsevier.com/locate/proci

Characterization of interactions between hot air


plumes and water sprays for sprinkler protection
Xiangyang Zhou ⇑
FM Global, 1151 Boston-Providence Turnpike, Norwood, MA 02062, USA

Available online 22 October 2014

Abstract

One important aspect of the complex sprinkler protection process is the interaction between the water
spray and the fire plume. In order to provide suitable data for the development and validation of a LES-
based fire protection models, such as FireFOAM, a series of small-scale experiments were conducted to
examine the interaction of hot air plumes and water sprays through combined gas–liquid velocity and
droplet size measurements. Laser-based particle image velocimetry (PIV) was used to acquire the spa-
tially-resolved velocity data; and a shadow imaging system (SIS) was used to measure the water droplet
size and volume flux. Hot air plumes with three convective heat release rates (1.6, 2.1 and 2.6 kW) were
selected to interact with a water spray at a discharge rate of 0.084 Lpm. The velocity field of the hot air
plume and ceiling flow with/without water spray, the droplet size and volume flux of water spray with/
without hot air plume were measured. The interaction between the hot air plume and water spray was char-
acterized by the location of the interaction boundary with the momentum ratio of the hot air to that of the
spray. The results showed that that the momentum ratio and the evaporation effect due to hot air on the
water droplets played a significant role to change the interaction structure and the ceiling layer pattern.
Ó 2014 The Combustion Institute. Published by Elsevier Inc. All rights reserved.

Keywords: Fire plume; Sprinkler spray; Interaction; Flow velocity; PIV

1. Introduction evaporation) and heat transfer (due to droplet


heat-up and evaporation). The trajectories of fall-
Water sprays have been one of the most reli- ing droplets are modified by the upward fire
able and effective methods to control or suppress plume so that only a part of the spray can pene-
a fire. One important aspect of the complex fire trate through the plume to the top of the burning
protection process is the interaction which occurs fuel, and a part of the spray is deflected back
between the droplet spray and the turbulent buoy- toward the ceiling, finally falling to the floor well
ant gas flow induced by a fire. When a downward away from the fire source. In addition to the mod-
water spray is injected above a fire source, ification of the upward fire plume, there is also an
the droplet undergoes momentum transfer (due impact on ceiling-jet velocities and temperatures
to drag force), mass reduction (due to water induced by the droplet spray. The outcome of this
interaction determines how the droplet size and
momentum of the spray, the momenta of the
⇑ Fax: +1 (781) 255 4024. flames and hot plume, and the evaporation of
E-mail address: xiangyang.zhou@fmglobal.com spray in the flames influence the cooling of the fire

http://dx.doi.org/10.1016/j.proci.2014.05.078
1540-7489/Ó 2014 The Combustion Institute. Published by Elsevier Inc. All rights reserved.
2724 X. Zhou / Proceedings of the Combustion Institute 35 (2015) 2723–2729

plume, and the degree of water penetration 2. Experimental setup


through the fire plume to the burning fuel
surface. A small-scale plume-spray test facility was set
The fire research community has long been in a laboratory with dimensions of 8  9 m and
interested in the experimental measurement and 4 m in height. Figure 1 shows the schematic of
numerical modeling of the interaction between a the experimental setup, which mainly comprises
fire plume and a water spray from a sprinkler. an upward air flow, a downward water spray
The actual delivered density (ADD) test appara- and a horizontal ceiling. The four measurement
tus was developed at FM Global to characterize windows (or field of view) illustrated in the figure
and evaluate the capability of sprinkler sprays to were used for the PIV measurements. The ADD
penetrate the fire plume of a rack storage com- test apparatus [1,4] was referenced to design the
modity arrangement by collecting the water in current small-scale test facility.
pans placed beneath a fire [1]. When the ADD is The hot air source was designed to be a circular
greater than the RDD (required delivered nozzle with 72 mm in diameter. The origin of a
density), fire suppression is expected to occur. two-dimensional (2D) cylindrical coordinate sys-
The ADD apparatus has provided much useful tem (r–z) was located at the center of the top of
data; however, little experimental data are avail- the nozzle, where r is the radius from the centerline
able to detail how the characteristics of a fire and z is the height above the nozzle. Hot air was
plume and a droplet spray change during the forced into the nozzle through a Leister electric
interaction. Most of the knowledge of this interac- air heater and a tube. The tube was filled with
tion was gained through computer modeling [2–6]. metal screens to make the exit velocity profile uni-
A new computational code, FireFOAM, based on form. Several fire sizes were simulated by changing
the OpenFOAM framework has been developed the convective heat release rates (HRRs) of the hot
at FM Global to further the numerical modeling air. The convective HRR was calculated from the
of water-based fire protection including turbulent air flow rate and the temperature rise above ambi-
reactive flow [7], solid fuel pyrolysis [8], soot ent. The vertical exit velocity was up to 5.0 m/s,
radiation [9], water transport [10] and sprinkler and the exit air temperature was up to 205 °C.
sprays [11]. The hot air temperatures were measured using
This work was purposed to extend existing seven type K thermocouples (28 Gage).
studies of the interaction between the hot air A Delavan CT-1.5–30 B full cone nozzle was
plumes and water sprays through measurements selected to discharge the water spray. This spray
of gas–liquid two-phase velocity fields and droplet nozzle is rated to flow 0.08 Lpm of water at
size variation in a series of small-scale experi- 690 kPa with a 30° initial spray angle. Figure 1
ments. A diagnostic technique of laser-based par- shows that the spray nozzle was installed at
ticle image velocimetry (PIV) was used for z = 560 mm above the hot air nozzle and 30 mm
acquisition of spatially-resolved velocity data in below the center of an aluminum ceiling plate.
the gas–liquid interaction field. This measurement The ceiling plate size was 1.22  1.22 m with
was motivated by the need to develop and validate 3 mm thickness. Water flow to the nozzle was
numerical simulation tools for such flows. New accomplished by pressurizing a water storage tank
numerical techniques, such as Large Eddy Simula- with dry grade nitrogen. The nitrogen supply pres-
tion (LES), have combined spatial and temporal sure was regulated with a two-stage regulator and
resolution that cannot be fully validated by tradi- the tank pressure was monitored with a pressure
tional point-measurement techniques, in which
data are not spatially correlated. The variation
of water droplet size and volume flux in the inter-
action field was measured by a shadow imaging
system (SIS). The goals of this work were to
examine the characteristics of turbulent hot air
plume interacting with the water sprays through
combined gas–liquid velocity and droplet size
measurements, and to use the data for the devel-
opment and validation of LES-based fire protec-
tion model. The hot air plume experiments were
selected because the generation of turbulence
due to buoyancy and water spray can be studied
but the complexities of combustion chemistry
are removed. The region of interest in this study
was the velocity field of hot air plume and ceiling Fig. 1. Schematics of experimental setup: upward air
flow with/without spray, and droplet size and flow, downward water spray, horizontal ceiling and four
volume flux of water spray with/without hot air measurement windows (A, B, C and D) used for PIV
plume. measurements.
X. Zhou / Proceedings of the Combustion Institute 35 (2015) 2723–2729 2725

gauge. The water tank had a 151 L capacity and component (V) and three Reynolds stresses (uv,
was connected at its bottom by a high-pressure uu and vv) 30 mm above the hot air nozzle for a
flexible tube to the spray nozzle. The water flow low convective HRR of 1.6 kW. The data were
rate was monitored by a flow meter. averaged from a vector set with 200 pairs of PIV
In PIV measurements, flow velocity is deter- images or vector fields. Figure 2 shows that a near
mined from measurement of displacement of top-hat velocity profile existed at the nozzle exit
imaged droplets in a thin light sheet and the time and the maximum velocity was Vm = 3.3 m/s.
for displacement. In this work, the water droplets The turbulent Reynolds stresses were low in the
in the spray were directly used for imaging and centerline and then increased to peak values at
velocity calculation. The hot air and the surround- the nozzle edges (r = ±36 mm). The other two
ing air were seeded with oil droplets (soybean oil, hot air plumes had the same velocity profiles but
0.25-1 microns droplet size), which were produced a higher value of Vm = 4.2 m/s for 2.1 kW and
from a LaVision Aerosol generator. The droplets Vm = 5.1 m/s for 2.6 kW.
were illuminated by two light sheets expanded Figure 3 shows horizontal profiles of the air
from a dual-cavity-pulsed Nd:YAG laser with an temperatures 30 mm above the hot air nozzle mea-
optimized time difference. The maximum energy sured for three hot air plumes. The data were
in each pulse was 120 mJ and the wavelength was averaged over 3 min with a 1 Hz measuring fre-
532 nm. A 14-bit dual-frame CCD camera (LaVi- quency and the standard deviation was about
sion Imager ProX4M) with a 2048  2048 pixel 0.5 °C at the nozzle center. The peak temperature
resolution was used to image droplets. The light was Tm = 205 °C and the room temperature was
sheet was aligned vertically to the z-axis at the T0 = 21 °C. The peak value of Tm was controlled
spray center. The camera was aligned at 90° to to be constant for the three different convective
the light sheet and focused on the sheet/droplets. HRRs.
The SIS was used to measure water spray
droplet size, number density, and velocity [12]. It 3.2. Initial droplet size and velocity of water spray
is based on the shadowgraph technique with without hot plume
high-resolution imaging and pulsed backlight illu-
mination. After calibrating the detection system, Figure 4 shows a scatter plot of the droplet ver-
the current camera’s field of view was tical velocity versus its size for a large number
4.41  4.41 mm. The number of pixels in the cam- (>4000) of droplets detected in the spray center
era’s field of view was 2048  2048. The minimum and at two elevations: z = 530 mm (30 mm below
droplet size that could be detected was 0.012 mm. the spray nozzle) and z = 260 mm. In the near
LaVision’s DaVis 7.2 software was used to pro- field (z = 530 mm) of the spray nozzle, Fig. 4
cess the PIV and SIS data. shows a general trend with the velocity magnitude
To provide a plume-dominated flow and a increasing with droplet diameter from 1 m/s to
spray-dominated flow, three convective HRRs 27 m/s. In the far field (z = 260 mm) below the
(1.6, 2.1 and 2.6 kW) were generated by supplying nozzle, however, the small droplets (0.012 mm)
three air flow rates and maintaining a constant are in the same velocity range from 1.5 m/s to
exit air temperature. The water spray nozzle was 7 m/s as the larger droplets. This result means that
operated the pressure of 750 kPa and the mea- most water droplets in the far field are moving
sured water flow rate was 0.084 Lpm. Four mea-
surement area windows were selected for PIV
measurements and each window had the same size
of 257  257 mm. As shown in Fig. 1, two
windows A (z = 0–257 mm) and B (z = 253–
510 mm) were placed in the spray centerline, and
two windows C (r = 56-313 mm) and D
(r = 308–565 mm) were placed at the right side
of the spray nozzle and under the ceiling. A low
measuring frequency of 0.9 double exposures per
second was selected so that more images could
be stored directly in the computer hard disk.

3. Results and discussion

3.1. Initial velocity and temperature of hot air


plume without spray Fig. 2. Horizontal profiles of averaged vertical velocity
(V) and three Reynolds stresses measured at 30 mm
Figure 2 shows measurements of the radial above the hot air nozzle with convective HRR of
variation of the average vertical velocity 1.6 kW.
2726 X. Zhou / Proceedings of the Combustion Institute 35 (2015) 2723–2729

Fig. 5. Horizontal profiles of volume-median diameter


(dv50), average vertical velocity and vertical volume flux
of water droplets in the near field (z = 530 mm).
Fig. 3. Horizontal profiles of averaged air temperatures
measured at 30 mm above the hot air nozzle for three
convective HRRs.

Fig. 6. Horizontal profiles of volume-median diameter


(dv50), average vertical velocity and volume flux of water
droplets measured by SIS, and a PIV velocity profile at
z = 260 mm.
Fig. 4. Scatter plot of vertical droplet velocity versus
diameter in the near field (z = 530 mm) and the far field
(z = 260 mm) measured in the spray center.
downward velocity of 18 m/s and large size
droplets, dv50 = 0.056 mm. By integrating the vol-
ume flux and area, the total flow rate was calcu-
following the air flow induced by spray entrain- lated to be 0.075 Lpm, which is 9% lower than
ment. Because current PIV cannot measure the the measured value of 0.084 Lpm. This verifica-
two-phase velocity field simultaneously in the tion confirms that the SIS measurements were
spray region, the air velocity in the far field was reliable.
then approximated by imaging the water droplets. The initial spray pattern changed with distance
Figure 5 shows the horizontal profiles of the from the nozzle. In the far field, Fig. 6 shows that
volume-median diameter (dv50), averaged vertical the radial distribution area was larger, the down-
velocity, and vertical volume flux of water drop- ward droplet velocities and volume fluxes were
lets in the near field measured by the SIS. The vol- lower, and larger droplets moved toward the outer
ume-median diameter (dv50) denotes that 50% of spray edge. As a comparison, the velocity profile
the cumulated water volume is represented by obtained from the PIV is also presented in
droplets having a diameter smaller than dv50. Fig. 6. Because the spray was not so dense and
The volume flux (Lpm/m2) was calculated from droplet velocity was less size related, the figure
all detected droplets with droplet diameter, num- shows that the two results obtained from PIV
ber density and velocity. Because droplet velocity and SIS are in good agreement in the far field.
is related to droplet size, the average droplet
velocity was calculated by dividing the volume 3.3. Interaction between hot air plume and water
flux by the spray volume density. Figure 5 shows spray
that the initial spray in the near field was very
dense, so that the spray center had a peak down- After characterizing the initial conditions of
ward volume flux of 170 Lpm/m2, a maximum hot air plume and water spray, measurements
X. Zhou / Proceedings of the Combustion Institute 35 (2015) 2723–2729 2727

were conducted to investigate the interaction around the spray. At the higher HRR of 2.6 kW,
between the plume and the spray. For three con- the interaction boundary was pushed closer to the
vective HRRs and one spray flow rate, Fig. 7 spray nozzle and the spray entrainment effect was
shows the response of the velocity structure of reduced. The position of the interaction boundary
the hot plume to the spray. The vectors were aver- was determined as the location characterized by a
aged from a set with 500 pairs of PIV images. The zero vertical velocity at the centerline. Although
measurements in the two windows A and B were the average velocity was zero, the interaction
merged into one. The current PIV could distin- region itself was very turbulent. The peak value
guish two droplets (small oil droplets and larger of the turbulent Reynolds stresses (vv) at the inter-
water droplets) by light intensity in the region action boundary (z = 320 mm) was found to be
where there were no (or very little) water droplets; 20 times larger than that at the free hot air plume
however, this discrimination was not possible for (2.1 kW).
a dense spray. For similar densities of small and The other important effect of the hot plume is
large droplets, the PIV measurements would bias that water droplet sizes and the volume flux varied
toward the large droplets, which means that the with the plume-spray interaction. Figure 8 shows
velocity measured was close to the velocity of a comparison of the horizontal profiles of vol-
the larger droplets. Figure 7 shows that a stagna- ume-median diameter and downward volume flux
tion point was formed in the interaction boundary obtained from the spray with/without hot air
where the upward air flow met the downward flow plume (2.1 kW) at z = 320 mm. The figure shows
of air entrained with the spray, and the interaction that the droplet size in the spray center increased
boundary moved up with a higher HRR. At the with the hot air plume, indicating that some small
low HRR of 1.6 kW, the hot air column was droplets disappeared due to water evaporation.
almost suppressed and the interaction boundary Small droplets might also be pushed out from
was pushed closer to the base of the plume. As the centerline so that the droplets became smaller
the HRR increased to 2.1 kW, the upward flow toward the outer spray edge. The SIS measure-
pushed the interaction boundary to a higher posi- ments showed that the number of droplets and
tion (z = 320 mm) and formed two large vortexes the downward velocity were reduced in the

Fig. 7. Averaged vector fields measured by PIV for the interaction between the hot air plume with three convective
HRRs and the water spray with one discharge rate.
2728 X. Zhou / Proceedings of the Combustion Institute 35 (2015) 2723–2729

Fig. 8. Horizontal profiles of volume-median diameter Fig. 9. Position of the interaction boundary versus the
(dv50) and vertical volume flux of water droplets com- momentum ratio measured for three hot air plumes and
pared at z = 320 mm for spray with/without hot air one cold air flow.
plume (2.1 kW).

and horizontal velocity (U) contours of the ceiling


interaction region. Therefore, Fig. 8 shows that layer at the interaction between the hot air plume
the volume flux reduced significantly with the (2.1 kW) and the water spray. The vectors were
hot air plume, indicating that the degree of water averaged from a set with 200 pairs of PIV images.
penetration through the hot plume to the hot The measurements in the two windows C and D
source was reduced. were merged into one. The spray nozzle was
The interaction between a sprinkler and fire located beyond the left bound of the figure at
has often been discussed in terms of the competi- r = 0 mm. It is clear that a horizontal ceiling layer
tion between the momentum of the downward formed under the ceiling and moved out from
spray and the momentum of the upward fire the centerline. The left side of Fig. 10 shows a
plume [2,4]. In this work, the momentum (Ma) circular zone with negative horizontal velocities,
of the hot air plume without spray was calculated which means that air was entrained into the spray.
directly from the velocity and temperature mea- Figure 10 also shows a peak value of U = 0.43 m/s
surements near the nozzle exit. The initial momen- in the ceiling layer appeared at r = 310 mm. For
tum (Mw = 0.043 N) of the water spray was the two other hot air plumes interacting with the
approximated from the nozzle discharge rate same spray (shown in the supplemental material),
and the injection velocity. Figure 9 shows the the maximum U appeared at different locations:
position of the interaction boundary versus the r = 210 mm for 2.6 kW and r = 550 mm for
momentum ratio (Ma/Mw) for the three hot air 1.6 kW. This result indicates that a relative
plumes. The figure shows that the location of stronger spray will push the ceiling layer toward
the interaction boundary increased from the outer edge.
z = 60 mm to z = 440 mm with the momentum Figure 11 shows a comparison of the vertical
ratio going from 0.6 to 1.5. Because a ceiling profiles of averaged velocity (U) and turbulent
was installed, the height of the interaction bound- Reynolds stresses (uu) in the ceiling layer obtained
ary with the 2.6 kW plume might have been from the hot air plume (2.1 kW) with/without
reduced due to the effect of the ceiling. To under- water spray at r = 310 mm. The figure shows that
stand the effect of hot air temperature on the the peak value of U was reduced by 50%, and that
interaction, a cold air flow with Ma/Mw = 1.2 at of uu was reduced by 72% under the spray
room temperature was also measured and the
interaction boundary location is presented in
Fig. 9. The figure shows that the cold air flow
had a lower interaction height of z = 180 mm,
although its momentum was stronger than that
of the hot air plume with 2.1 kW. The meaning
of this observation is that the interaction structure
was changed not only by the momentum ratio but
also by the evaporation effect due to hot air on the
water droplets.

3.4. Ceiling air flow


Fig. 10. Averaged vector fields and horizontal velocity
The ceiling flow is important to sprinkler acti- (U) contours of the ceiling layer for the interaction
vation. Figure 10 shows the averaged vector fields between the hot air plume (2.1 kW) and the water spray.
X. Zhou / Proceedings of the Combustion Institute 35 (2015) 2723–2729 2729

with/without the plume-spray interaction were


measured. The results of the plume (2.1 kW)
showed that the peak velocity in the ceiling layer
was reduced by 50%, the layer thickness was
4 times increased and the location of the maxi-
mum velocity moved toward the outer edge due
to the interaction. It was shown that both, the
momentum ratio of the hot air to the spray and
the variation of droplet size and volume flux due
to water evaporation, played a significant role in
the plume–spray interaction.

Acknowledgements
Fig. 11. Vertical profiles of averaged horizontal velocity
(U) and Reynolds stress (uu) in the ceiling layer This study was funded by FM Global in its
compared at r = 310 mm for hot air plume (2.1 kW) sprinkler technology research program. The
with/without spray.
author is grateful to Hong-Zeng Yu and Stephen
D’Aniello for their assistance and discussions.
interaction. In the lower region below the ceiling,
however, the values of U and uu were larger with
the interaction than those without the interaction. Appendix A. Supplementary material
If the ceiling layer edge is defined as the location
with U = 0.01Umax, the ceiling layer thickness Supplementary data associated with this article
was 4 times increased from 60 mm for free hot can be found, in the online version, at http://
air (2.1 kW) to 250 mm for the hot air with spray, dx.doi.org/10.1016/j.proci.2014.05.078.
meaning that the plume-spray interaction can
make the ceiling layer more diffuse and thicker.
References

[1] H.Z. Yu, T.S. Chan, H.C. Kung, W.R. Brown, P.


4. Summary and conclusions
Stavrianidis, Sprinkler performance evaluation sys-
tem, US Patent number 6085585, July 11, 2000.
The characteristics of the interaction between [2] R.L. Alpert, Fire Safety J. 9 (1985) 157–163.
the hot air plume and the water spray have been [3] R.G. Bill Jr., Fire Safety J. 20 (1993) 227–240.
measured by using particle image velocimetry [4] S. Nam, Fire Safety J. 32 (1999) 307–329.
(PIV) and a shadow imaging system (SIS) with [5] Y.F. Li, W.K. Chow, Fire Technol. 44 (2008) 351–
the objective to generate a data set for validation 381.
of computational fire models. Hot air plumes with [6] N. O’Grady, V. Novozhilov, Combust. Sci. Technol.
three convective heat release rates (1.6, 2.1 and 181 (2009) 984–1006.
[7] Y. Wang, P. Chatterjee, J.L. de Ris, Proc. Combust.
2.6 kW) were selected to interact with a water
Inst. 33 (2011) 2473–2480.
spray at a discharge rate of 0.084 Lpm. First the [8] M. Chaos, M.M. Khan, S.B. Dorofeev, Proc.
initial conditions of velocity and temperature of Combust. Inst. 34 (2013) 2583–2590.
the hot air without spray, and droplet size and [9] P. Chatterjee, J.L. de Ris, Y. Wang, S.B. Dorofeev,
volume flux of water spray without hot air were Proc. Combust. Inst. 33 (2011) 2665–2671.
measured. The interaction between the hot air [10] K.V. Meredith, J. de Vries, Y. Wang, Y. Xin, Proc.
plume and water spray was then characterized Combust. Inst. 34 (2013) 2719–2726.
by the location of the interaction region. The [11] Y. Wang, K. Meredith, X. Zhou, P. Chatterjee, Y.
velocity vector fields showed that the height of Xin, M. Chaos, N. Ren, S. Dorofeev, Fire Safety
Science 11 (2014), (in press).
the interaction boundary above the base of the
[12] X. Zhou, H.Z. Yu, Fire Safety J. 46 (2011) 140–150.
plume increased with the heat release rates.
Finally the velocity fields of the ceiling layer

S-ar putea să vă placă și