Sunteți pe pagina 1din 93

Report for Over Current/Earth Fault Relay (CDG-36/31)

Testing Report No. ELECT/RLY/ Date: 20/6/15


01. Designation : Over Current/Earth Fault Relay :
Location: 541 LC3/541CB-17
02. Name plate Details:
Make:EE Serial No:M272555
Type: CDG36 CT Sec Current (A): 5A
Model:CDG36AF8052(B)
Aux.Voltage: Self Powered

Available Setting O/C E/F


PS (A) (2.5A-10A) (1A-4A)
TMS (0.1-1) (0.1-1)
Op. Time (Sec) at PS x 10 with TMS 1.0: 1.3 sec
3. General Inspection as per Checklist:
4. Insulation Resistance Test:
a) All Terminals to Body: >200M Ω
b) Between Terminals: >200M Ω
05. Coil Resistance Check: R-ph: 0.27Ω Y-ph/ E/F: 0.26 Ω B-ph: 0.56 Ω
6. Contact Pressure: 28gm
7. Secondary Injection Test:
Phase/Unit PS(A) TMS Starting Closing Operating Time (Sec) at multiples of P/s
Current(A) Current (A) 2 5 10

R(5-6) 5 0.3 5.38 5.88 - - -


1 - - 3.77 1.77 1.28
E/F(7-8) 1 0.3 1..08 1.125 0.98 0.5 0.38
1 - - 3.71 1.73 1.25
B(9-10) 5 0.3 5.5 5.67
1 - - 3.8 1.78 1.29

08.. Functional Check


a) Operation of Indicators/Aux. Unit:
b) Initiation of Alarm Contact: OK
c) Circuit Breaker Tripping Contact: OK
09..Service Settings:
O/C(R). E/F O/C(B)
PS(A): 5A 1A 5A
TMS: 1 0.3 1

10. Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By:


Over Current/Earth Fault Relay (CDG-36/31)
Testing Report No. ELECT/RLY/ Date: 20/6/15
01. Designation: Over Current/Earth Fault Relay :
Location: 541 LC3/ 541CB-18
02. Name plate Details:
Make:EE Serial No:M272556
Type: CDG36 CT Sec Current (A): 5A
Model: CDG36AF8052 (B)
Aux.Voltage: Self Powered

Available Setting O/C E/F


PS (A) (2.5A-10A) (1A-4A)
TMS (0.1-1) (0.1-1)
Op. Time (Sec) at PS x 10 with TMS 1.0: 1.3 sec
3. General Inspection as per Checklist:
4. Insulation Resistance Test:
a) All Terminals to Body: >200M Ω
b) Between Terminals: >200M Ω
05. Coil Resistance Check: R-ph: 0.27Ω Y-ph/ E/F: 0.26 Ω B-ph: 0.56 Ω
06. Contact Pressure: 27gm
07. Secondary Injection Test:

Phase/Unit PS(A) TMS Starting Closing Operating Time (Sec) at multiples of P/s
Current(A) Current (A) 2 5 10

R(5-6) 5 0.3 5.43 6.19 - - -


1 - - 3.35 1.69 1.28
E/F(7-8) 1 0.3 1.13 1.163 0.97 0.52 0.36
1 - - 3.96 1.91 1.29
B(9-10) 5 0.3 5.34 5.63 - - -
1 - - 3.75 1.77 1.29
8. Functional Check
a) Operation of Indicators/Aux. Unit:
b) Initiation of Alarm Contact: OK
c) Circuit Breaker Tripping Contact: OK
09. Service Settings:
O/C(R). E/F O/C(B)
PS (A): 5A 1A 5A
TMS: 1 0.3 1

10. Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By:


Test Report Lockout relay (VAJH-23)
Date: 20/6/15
01. Designation Lockout relay
Location: 541 CB-18 / 541 LC-3
02. Name plate Details:
Make: EE Serial No: M272601
Type: VAJH-23 Model: VAJH23BF8019 B (M)
Aux.Voltage: 110Vdc
3. General Inspection as per Checklist: OK
4. Insulation Resistance Test:
All Terminals to Body: >200 M Ω
Between terminals: >200 M Ω
05. Pick up/Drop off Test:

Ref Coil Pick up Drop off


Resistance voltage voltage

86-B 80.5 45V HR


86-C 79.5 32V HR
06 .Contact Pressure Check: 25 gms Contact Resistances: 0.29 Ω
07 Functional checks:

Correct operation of contacts: OK


Correct operation of appropriate indicator/flag: OK
Correct initiation of scheme function: OK
08 Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By


Test Report Lockout relay (VAJH-23)
Date: 20/6/15
01. Designation Lockout relay
Location: 541 CB-17/ 541 LC-3
02. Name plate Details:
Make: EE Serial No: M272598
Type: VAJH-23 Model: VAJH23BF8019 B (M)
Aux.Voltage: 110Vdc
3. General Inspection as per Checklist: OK
4. Insulation Resistance Test:
All Terminals to Body: >200 M Ω
Between terminals: >200 M Ω
05. Pick up/Drop off Test:

Ref Coil Pick up Drop off


Resistance voltage voltage

86-B 82.2 37 V HR
86-C 79.5 29 V HR
06 .Contact Pressure Check: 27 gms Contact Resistances: 0.37 Ω
07 Functional checks:

Correct operation of contacts: OK


Correct operation of appropriate indicator/flag: OK
Correct initiation of scheme function: OK
08 Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By


Auxiliary relay (VAA-11)
Date:20/6/15
1. Designation Auxiliary relay
Location: 541-LC3/54 CB-18
02. Name plate Details:
Make: EE Serial No: M272622
Type: VAA-11 Model: VAA11YF8007AH(M)
Aux.Voltage: 110VDC
3. General Inspection as per Checklist: OK
4. Insulation Resistance Test:
All Terminals to Body: >200M ohm
Between terminals: >200M ohm
05. Pick up/Drop off Test:

Unit Coil Pick up Drop off


Resistance voltage voltage

27/74 5.34 k Ω 57V 13.5V

06 .Contact Pressure Check: 23 gms Contact Resistances: 0.45 Ω


07 Functional checks:
Correct operation of contacts: OK
Correct operation of appropriate indicator/flag: OK
Correct initiation of scheme function: OK
08 Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By


Auxiliary relay (VAA-11)
Date: 20/6/15
1. Designation Auxiliary relay
Location: 541-LC3/54 CB-17
02. Name plate Details:
Make: EE Serial No: M272607
Type: VAA-11 Model: VAA11YF8007AH (M)
Aux.Voltage: 110VDC
3. General Inspection as per Checklist: OK
4. Insulation Resistance Test:
All Terminals to Body: >200M ohm
Between terminals: >200M ohm
05. Pick Coil Pick up Drop off
up/Drop Resistance voltage voltage
off Test:
Unit

27/74 5.4 k Ω 55V 17V


06 .Contact Pressure Check: 25 gms Contact Resistances: 0.39 Ω

07 Functional checks:

Correct operation of contacts: OK


Correct operation of appropriate indicator/flag: OK
Correct initiation of scheme function: OK
08 Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By


Test Report for Motor Protection Relay (CTMM-502)
Testing Report No. ELECT/RLY/ Date: 24/09/2015
1. Designation: Motor Protection Relay:
Location: MRS/ 3106 BM-1 /PANEL
02. Name plate Details:
Make: A Serial No: 89040512009
Type: CTMM-502 CT Sec Current (A):1A
Model: CTMM502 DF12A Auxiliary Voltage: 110VDC

Available Setting Current setting (A) Time setting


Thermal current (Ith ) (6-12) Curve -1,2,3,4
Inst.O/C current (I1) (1.5-6) Inst.
Inst.(or) Time delayed (0.3-6.3) (0.06-7.56)s
Unbalanced element (I2)
Earth fault current (I0) 10 mA to 160 mA for K=1 (0.06-7.56) s
50 mA to 800 mA for K=5
Stalling protection (I1 (t)) (1.5-6) (0-30) s
Thermal pre –trip alarm (sec) 0.68 (25-72.8)s
Stabilizing resistor (0-500) Ω -
3. General Inspection as per Checklist:
4. Insulation Resistance Test:
a) All Terminals to Body: >100 M Ω.
b) Between Terminals: >100 M Ω.
5. Contact Pressure: -
6. Contact Resistance:
Terminal Before cleaning(Ω) After cleaning (Ω)
1-2 0.75 0.53
3-4 0.97 0.37
3-15 1.3 0.51
07. Coil Resistance: 7-8: 0.37 Ω; 9-10: 0.41Ω; 11-12: 4.37 Ω.

8. Secondary Injection Test:

8.1 Thermal Unit (Ith ):

8.1.1 Thermal characteristic check:-

Phase/Unit Relay Current Injected Thermal Operating Time Remarks


Current 500% (A) curve
setting (A) Expected Actual

Y(7-8) 0.76 0.76X3.27=2.48 4 32 31.6


B (9-10) 0.76 0.76X3.27=2.48 4 32 32.1
8.1.2 Pick UP test (I 1, I 2, I 0, I 1 (t)): -
Unit Current injection Relay Operating current (A) Remarks
terminal Current
Expected Actual
setting (A)
I1 (7-8) 6 6X√3 X 0.85=8.85 Not op.
(9-10) 6X√3 X 1.0=10.39 10.61
(7-8) 6 6X√3 X 0.85=8.35 Not op.
(9-10) 6X√3 X 1.0=10.39 10.67
I2 (7-8) 1.9 2.3X√3 X 0.85=2.7 Not op.
(9-10) 1.9 2.3X√3 X 1.0=3.03 3.8
I1 (t) (7-8) 1.5 1.5X√3 X 0.85=2.2 Not op.
(9-10) 1.5 1.5X√3 X 1=2.59 2.77
I0 (11-12) 0.16 0.16 0.163
1 2, 0, 1
8.1.2 Operating Time test (I , I I I (t)): -

Unit Current injection Relay Current Injected Timer setting Actual op


terminal Current setting (A) (A) (Sec) time
I1 (7-9) 6 20.78 Inst 0.05
(8-10) 6 20.78 Inst 0.05
I2 (7-9) 1.9 6.06 0.06 0.1
(8-10) 1.9 6.06 0.06 0.09
I0 (11-12) 0.16 0.16 0.06 0.07
I1 (7-9) 1.5 5.2 6 6.07
(8-10) 6 5.2 6 6.01
09 Functional checks:-

a) Correct operation of contacts: OK


b) Correct operation of appropriate indicator/flag & aux relay : OK
c) Correct initiation of alarm contact: OK
10 Service setting:-

Unit I1 I2 I0 I1 (t) Ith Pre Trip Alarm


Current 6A 1.9A 0.16A 1.5A 0.76A 0.68(90% of Ith )
setting
Time Inst 0.06s(default 0.06s(default 6s Curve 4 Curve 4
setting min ) min ) (K=1)

11 Remarks: - Relay Operation Found Satisfactorily


Tested By: Checked By
Test Report for Motor Protection Relay (CTMM-44)

Testing Report No. ELECT/RLY/ Date: 23/09/2015


01. Designation: Motor Protection Relay :
Location: MRS/ 3106 BM- 2 / PANEL
02. Name plate Details:
Make: A Serial No:
Type: CTMM-44 CT Sec Current (A):5A
Model: CTMM44 DF12A Auxiliary Voltage: 110VDC

Available Setting Current setting(A) Time setting


Thermal current (Ith ) (3.5-6.5) 32 sec at 5 times current
Inst.O/C current (I1) (20-80) Inst
Inst.(or) Time delayed (10-40) Inst
Unbalanced element (I2)
Earth fault current (I0) 1.0 Inst
Stalling protection (t) - -
Thermal pre –trip alarm (sec) - -
Stabilizing resistor - -

3. General Inspection as per Checklist:


4. Insulation Resistance Test:
b) All Terminals to Body: >100 M Ω
b) Between Terminals: >100 M Ω
5. Contact Pressure: -
6. Contact Resistance:
Terminal Before cleaning(Ω) After cleaning (Ω)
1-2 1.5 0.61
3-4 1 0.73
3-15 2.7 0.53

7. Coil Resistance: 7-8:0.45 Ω; 9-10:0.47Ω; 11-12: 4.51Ω.

8. Secondary Injection Test:

8.1.1 Thermal characteristic check:-

Phase/Unit Relay Current Injected Timer Operating Time Remarks


Current 500% (A) setting Expected Actual
setting (A) 32 S at
500%
Y(7-9) 4 4X3.27=13.09 32S 32. 32.2
B (8-10) 4 4X3.27=13.09 32S 32. 29.97

8.1.2 Pick UP test (I1, I2, I0, I1 (t)):-

Unit Current injection Relay Operating current (A) Remarks


terminal Current setting (A)
Expected Actual
I1 (7-9) 30 30X√3 X 0.85=44.2 Not Operated
30X√3 X 1.15=59.8 57.6
(8-10) 30 30X√3 X 0.85=44.2 Not Operated
30X√3 X 1.15=59.8 55.3
I2 (7-9) 10 10X√3 X 0.85=14.7 Not Operated
10X√3 X 1.15=19.1 20
(8-10) 10 10X√3 X 0.85=14.7 Not Operated
10X√3 X 1.15=19.1 22
I0 (11-12) 1.0 1.0 1.03

8.1.2 Operating Time test (I1, I2, I0, I1 (t)):-

Unit Current injection Relay Current Injected Timer setting Actual op


terminal Current setting (A) (A) (Sec) time
I1 (7-9) 30 104 Inst 0.07
(8-10) 30 104 Inst 0.09
I2 (7-8) 10 34.64 Inst 0.137
(9-10) 10 34.64 Inst 0.11
I0 (11-12) 1.0 2 Inst 0.08

9 Functional checks:-
a) Correct operation of contacts: OK
b) Correct operation of appropriate indicator/flag & aux relay : OK
c) Correct initiation of alarm contact: OK
10 Service setting:-
Unit I1 I2 I0 Ith Pre Trip Alarm
Current 30 10 1.0 32 S at NA
setting 500%
Time Inst Inst Inst 32 S at NA
setting 500%

11 Remarks: - Relay Operation Found Satisfactorily


Tested By: Checked By
Auxiliary relay (VAA-11)
Date: 24/09/2015
1. Designation Auxiliary relay
Location: MRS/6.6 KV Switchgear/3106 BM-1
02. Name plate Details:
Make: EE Serial No: M227819
Type: VAA-11 Model: VAA11YF8006J(M)
Aux.Voltage: 110VDC
3. General Inspection as per Checklist: OK
4. Insulation Resistance Test:
All Terminals to Body: >200M ohm
Between terminals: >200M ohm
05. Pick Coil Pick up Drop off
up/Drop Resistance voltage voltage
off Test:
Unit

e-69 4.7 k Ω 63V 13.7V


06 .Contact Pressure Check: - Contact Resistances: 0.39 Ω

07 Functional checks:
Correct operation of contacts: OK
Correct operation of appropriate indicator/flag: OK
Correct initiation of scheme function: OK
08 Remarks: Relay Operation Found Satisfactorily
Tested By: Checked By
Auxiliary relay (VAA-11)
Date: 24/09/2015
1. Designation Auxiliary relay
Location: MRS/6.6 KV Switchgear/3106 BM-1
02. Name plate Details:
Make: EE Serial No: M227818
Type: VAA-11 Model: VAA11YF8006J (M)
Aux.Voltage: 110VDC
3. General Inspection as per Checklist: OK
4. Insulation Resistance Test:
All Terminals to Body: >200M ohm
Between terminals: >200M ohm
05. Pick up/Drop off:-
Test: Unit Coil Resistance Pick up Drop off
voltage voltage

e-70 4.7 k Ω 51V 15V


06 .Contact Pressure Check: - Contact Resistances: 0.37 Ω

07 Functional checks:
Correct operation of contacts: OK
Correct operation of appropriate indicator/flag: OK
Correct initiation of scheme function: OK
08 Remarks: Relay Operation Found Satisfactorily
Tested By: Checked By
Trip Circuit Supervision relay (VAX-31)
Date: 24/09/2015
1. Designation: Trip Circuit Supervision relay
Location: MRS/6.6 KV Switchgear/3106 BM-1
02. Name plate Details:
Make: EE Serial No: M246809
Type: VAX-31 Model: VAX31ZG8002B (M)
Aux.Voltage: 110VDC (external resistance)
3. General Inspection as per Checklist: OK
4. Insulation Resistance Test:
All Terminals to Body: >200M ohm
Between terminals: >200M ohm
05. Pick up/Drop off:-
Ref Coil Resistance(KΩ) Pick up Drop off
voltage voltage

A(11-12) 3.3 17 11
B(9-10) 3.5 13 10
C(17-18) 3.1 15 09

06 .Contact Pressure Check: - Contact Resistances: 0.57 Ω.


07 Functional checks:

Correct operation of contacts: OK


Correct operation of appropriate indicator/flag: OK
Correct initiation of scheme function: OK
08 Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By


Lock Out Relay (VAJH-23)
Date: 24/09/2015
1. Designation Trip Circuit Supervision relay

02. Name plate Details:


Make: EE Serial No: M246792
Type: VAJH-23 Model: VAJH13YF63 (B)
Aux.Voltage: 110Vdc
3. General Inspection as per Checklist: OK
4. Insulation Resistance Test:

All Terminals to Body: ∞

Between terminals: ∞

05. Pick Coil Pick up Drop off


up/Drop Resistance voltage voltage
off Test:
Ref

e 63 81.3 37 HR
06 .Contact Pressure Check: - Contact Resistances: 0.29 Ω

07 Functional checks:

Correct operation of contacts: OK


Correct operation of appropriate indicator/flag: OK
Correct initiation of scheme function: OK
08 Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By


Auxiliary relay (VAA-11)
Date: 25/09/2015
1. Designation Auxiliary relay
Location: MRS/6.6 KV Switchgear/3106 BM-2
02. Name plate Details:
Make: EE Serial No: M227820
Type: VAA-11 Model: VAA11YF8006J (M)
Aux.Voltage: 110VDC
3. General Inspection as per Checklist: OK
4. Insulation Resistance Test:
All Terminals to Body: >200M ohm
Between terminals: >200M ohm
05. Pick Coil Pick up Drop off
up/Drop Resistance voltage voltage
off Test:
Unit

e-69 4.9 k Ω 51V 17.3V


06 .Contact Pressure Check: - Contact Resistances: 0.39 Ω

07 Functional checks:
Correct operation of contacts: OK
Correct operation of appropriate indicator/flag: OK
Correct initiation of scheme function: OK
08 Remarks: Relay Operation Found Satisfactorily
Tested By: Checked By
Auxiliary relay (VAA-11)
Date: 25/09/2015
1. Designation Auxiliary relay
Location: MRS/6.6 KV Switchgear/3106 BM-2
02. Name plate Details:
Make: EE Serial No: M227807
Type: VAA-11 Model: VAA11YF8006J (M)
Aux.Voltage: 110VDC
3. General Inspection as per Checklist: OK
4. Insulation Resistance Test:
All Terminals to Body: >200M ohm
Between terminals: >200M ohm
05. Pick up/Drop off:-
Test: Unit Coil Resistance Pick up Drop off
voltage voltage

e-70 4.5 k Ω 47V 19V


06 .Contact Pressure Check: - Contact Resistances: 0.37 Ω

07 Functional checks:
Correct operation of contacts: OK
Correct operation of appropriate indicator/flag: OK
Correct initiation of scheme function: OK
08 Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By


Trip Circuit Supervision relay (VAX-31)
Date: 25/09/2015
1. Designation: Trip Circuit Supervision relay
Location: MRS/6.6 KV Switchgear/3106 BM-2
02. Name plate Details:
Make: EE Serial No: M246810
Type: VAX-31 Model: VAX31ZG8002B (M)
Aux.Voltage: 110VDC (external resistance)
3. General Inspection as per Checklist: OK
4. Insulation Resistance Test:
All Terminals to Body: >200M ohm
Between terminals: >200M ohm
05. Pick up/Drop off:-
Ref Coil Resistance(KΩ) Pick up Drop off
voltage voltage

A(11-12) 3.5 17.9 11


B(9-10) 3.9 13.7 15
C(17-18) 3.7 15.5 11

06 .Contact Pressure Check: - Contact Resistances: 0.57 Ω.


07 Functional checks:

Correct operation of contacts: OK


Correct operation of appropriate indicator/flag: OK
Correct initiation of scheme function: OK
08 Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By


Lock Out Relay (VAJH-23)
Date: 25/09/2015
1. Designation Trip Circuit Supervision relay

02. Name plate Details:


Make: EE Serial No: M246773
Type: VAJH-23 Model: VAJH13YF63 (B)
Aux.Voltage: 110Vdc
3. General Inspection as per Checklist: OK
4. Insulation Resistance Test:

All Terminals to Body: ∞

Between terminals: ∞

05. Pick Coil Pick up Drop off


up/Drop Resistance voltage voltage
off Test:
Ref

e 63 81.9 37.5 HR
06 .Contact Pressure Check: - Contact Resistances: 0.29 Ω

07 Functional checks:

Correct operation of contacts: OK


Correct operation of appropriate indicator/flag: OK
Correct initiation of scheme function: OK
08 Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By


Test Report for Over Current/Earth Fault Relay (CDG-56)
Testing Report No. ELECT/RLY/ Date: 20/06/15
01. Designation: Over Current Relay
Location: S/S A/ 541-LC3 /MCC-Q
02. Name plate Details:
Make: ALSTOM Serial No: M 272636
Type: CDG56 CT Sec Current (A): 5.0 A
Model: CDG56FF8051F (M) Auxiliary Voltage: SELF POWERED

Available Setting O/C E/F


PS (A) 2.5-10 1.0-4.0
TMS 0.1-1.0 0.1-1
INST.(A) 25-100 -
Op. Time (Sec) at PS x 10 with TMS 1.0: 1.3
3. General Inspection as per Checklist:
4. Insulation Resistance Test:
All Terminals to Body: >100M Ω
5. Coil Resistance Check: R-ph: 0.53 Ω ;Y-Ph: 0.55 Ω ; B-ph: 0.53 Ω
6. Contact Pressure: 28gm
7 Contact Resistance: 0.43 Ω

08. Secondary Injection Test:


Phase/Unit PS(A) TMS Starting Closing Operating Time (Sec) at multiples of Ps
Current(A) Current (A) 2 5 10

R 3.75 0.3 3.85 4.13 - - -


0.7 - - 2.41 1.25 0.89
1.0 - - 3.87 1.75 1.29
E/F 1 0.3 1.1 1.15 - - -
0.2 - - 0.54 0.28 0.21
1.0 - - 3.68 1.7 1.28
B 3.75 0.3 3.87 4.16 - - -
0.7 - - 2. 55 1.37 0.87
1.0 - - 3.55 1.61 1.27
09 Operating Current Check (for instantaneous unit):
Setting Current(A) Phase 25 50
Operating Current(A) R 27 51.9
B 28.9 53.7

10. Functional Check


a) Operation of Indicators/Aux. Unit: Ok
a) Initiation of Alarm Contact: Ok
c) Circuit Breaker Tripping Contact: Ok

11. Service Settings:


O/C(R) E/F O/C(B)
PS (A): 3.75 1 3.75

TMS: 0.7 0.16 0.7


Instant.Unit (A): 25 - 25

12. Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By


Test Report for Over Current/Earth Fault Relay (CDG-56)
Testing Report No. ELECT/RLY/ Date: 20/06/15
01. Designation: Over Current Relay
Location: S/S A/ 541-LC4/541-LC3
02. Name plate Details:
Make: ALSTOM Serial No: M 272635
Type: CDG56 CT Sec Current (A): 5.0 A
Model: CDG56FF8051F (M) Auxiliary Voltage: SELF POWERED

Available Setting O/C E/F


PS (A) 2.5-10 1.0-4.0
TMS 0.1-1.0 0.1-1
INST.(A) 25-100 -
Op. Time (Sec) at PS x 10 with TMS 1.0: 1.3
3. General Inspection as per Checklist:
4. Insulation Resistance Test:
All Terminals to Body: >100M Ω
5. Coil Resistance Check: R-ph: 0.53 Ω ;Y-Ph: 0.56 Ω ; B-ph: 0.59 Ω
6. Contact Pressure: 28gm
7 Contact Resistance: 0.49 Ω

08. Secondary Injection Test:


Phase/Unit PS(A) TMS Starting Closing Operating Time (Sec) at multiples of Ps
Current(A) Current (A) 2 5 10

R 3.75 0.3 3.87 4.17 - - -


0.4 - - 2.39 1.22 0.88
1.0 - - 3.78 1.73 1.3
E/F 1 0.3 1.12 1.17 - - -
0.16 - - 0.54 0.28 0.21
1.0 - - 3.68 1.7 1.28
B 3.75 0.3 3.91 4.19 - - -
0.4 - - 2. 53 1.3 0.89
1.0 - - 3.75 1.63 1.29
09 Operating Current Check (for instantaneous unit):
Setting Current(A) Phase 25 50
Operating Current(A) R 26 51.9
B 28 50.9

10. Functional Check


a) Operation of Indicators/Aux. Unit: Ok
b) Initiation of Alarm Contact: Ok
d) Circuit Breaker Tripping Contact: Ok

11. Service Settings:


O/C(R). E/F O/C(B)

PS (A): 3.75 1.0 3.75


TMS: 0.7 0.16 0.7
Instant.Unit (A): 25 - 25

12. Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By


Test Report for Over Current/Earth Fault Relay (CDG-56)
Testing Report No. ELECT/RLY/ Date: 20/06/15
01. Designation: Over Current Relay
Location: S/S A/ 541-LC5/541-LC3
02. Name plate Details:
Make: ALSTOM Serial No: M 272637
Type: CDG56 CT Sec Current (A): 5.0 A
Model: CDG56FF8051F (M) Auxiliary Voltage: SELF POWERED

Available Setting O/C E/F


PS (A) 2.5-10 1.0-4.0
TMS 0.1-1.0 0.1-1
INST.(A) 25-100 -
Op. Time (Sec) at PS x 10 with TMS 1.0: 1.3
3. General Inspection as per Checklist:
4. Insulation Resistance Test:
All Terminals to Body: >100M Ω
5. Coil Resistance Check: R-ph: 0.53 Ω ;Y-Ph: 0.57 Ω ; B-ph: 0.51 Ω
6. Contact Pressure: 28gm
7 Contact Resistance: 0.42 Ω
8. Secondary Injection Test:
Phase/Unit PS(A) TMS Starting Closing Operating Time (Sec) at multiples of Ps
Current(A) Current (A) 2 5 10

R 3.75 0.3 3.88 4.18 - - -


0.5 - - 1.9 0.91 0.7
1.0 - - 3.79 1.8 1.27
E/F 1 0.3 1.13 1.12 - - -
0.16 - - 0.54 0.28 0.21
1.0 - - 3.73 1.77 1.27
B 3.75 0.3 3.93 4.5 - - -
0.5 - - 1.76 0.83 0.63
1.0 - - 3.77 1.75 1.27
09 Operating Current Check (for instantaneous unit):
Setting Current(A) Phase 25 50
Operating Current(A) R 29 59
B 27.3 58

10. Functional Check


a) Operation of Indicators/Aux. Unit: Ok
c) Initiation of Alarm Contact: Ok
e) Circuit Breaker Tripping Contact: Ok

11. Service Settings:


O/C (R) E/F O/C (B)
PS (A): 3.75 1 3.75

TMS: 0.5 0.16 0.5


Instant. Unit (A): 25 - 25

12. Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By


Auxiliary relay (VAA-11)
Date: 26/05/15
1. Designation Auxiliary relay
Location: 541-LC3/541 CB-11/ 541DG-1
02. Name plate Details:
Make: EE Serial No: M764306
Type: VAA-11 Model: VAA11YF50A
Aux.Voltage: 110VDC
03. General Inspection as per Checklist: OK
04. Insulation Resistance Test:

All Terminals to Body: >200M ohm


Between terminals: >200M ohm
05. Pick up/Drop off Test:
Unit Coil Pick up Drop off
Resistance voltage voltage

52X2 5.57 k Ω 64V 37V

06 . Contact Resistances: 0.58 Ω


07 Functional checks:
Correct operation of contacts: OK
Correct operation of appropriate indicator/flag: OK
Correct initiation of scheme function: OK
08 Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By


Auxiliary relay (VAA-11)
Date: 26/05/15
01. Designation Auxiliary relay
Location: 541-LC3/541 DG no.1
02. Name plate Details:
Make: EE Serial No: M272772
Type: VAA-11 Model: VAA11YF50A
Aux.Voltage: 110VDC
03. General Inspection as per Checklist: OK
04. Insulation Resistance Test:

All Terminals to Body: >200M ohm


Between terminals: >200M ohm
05. Pick up/Drop off Test:

Unit Coil Pick up Drop off


Resistance voltage voltage

52Z 5.7 k Ω 77V 53V

6. Contact Resistances: 0.6 Ω


7 Functional checks:
Correct operation of contacts: OK
Correct operation of appropriate indicator/flag: OK
Correct initiation of scheme function: OK
8 Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By


Auxiliary relay (VAA-11)
Date: 26/05/15
1. Designation Auxiliary relay
Location: 541-LC3/541 DG no.1
02. Name plate Details:
Make: EE Serial No: M272610
Type: VAA-11 Model: VAA11YF807AH (M)
Aux.Voltage: 110VDC
3. General Inspection as per Checklist: OK
4. Insulation Resistance Test:
All Terminals to Body: >200M ohm
Between terminals: >200M ohm
05. Pick up/Drop off Test:
Unit Coil Pick up Drop off
Resistance voltage voltage

27/74 5.48 k Ω 71V 43.5V

06 . Contact Resistances: 0.58 Ω


07 Functional checks:
Correct operation of contacts: OK
Correct operation of appropriate indicator/flag: OK
Correct initiation of scheme function: OK
08 Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By


Auxiliary relay (VAA-11)
Date: 26/05/15
01. Designation Auxiliary relay
Location: 541-LC3/541 DG no.1
02. Name plate Details:
Make: EE Serial No: M27265
Type: VAA-11 Model: VAA11YF38B
Aux.Voltage: 110VDC
03. General Inspection as per Checklist: OK
04. Insulation Resistance Test:

All Terminals to Body: >200M ohm


Between terminals: >200M ohm
05. Pick up/Drop off Test:

Unit Coil Pick up Drop off


Resistance voltage voltage

27/94 5.6 k Ω 67V 54V

06 . Contact Resistances: 0.67 Ω


07 Functional checks:
Correct operation of contacts: OK
Correct operation of appropriate indicator/flag: OK
Correct initiation of scheme function: OK
08 Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By


Auxiliary relay (VAA-11)
Date: 26/05/15
01. Designation Auxiliary relay
Location: 541-LC3/541 DG no.1
02. Name plate Details:
Make: EE Serial No: M272752
Type: VAA-11 Model: VAA11YF189A
Aux.Voltage: 110VDC
03. General Inspection as per Checklist: OK
04. Insulation Resistance Test:

All Terminals to Body: >100M ohm


Between terminals: >100M ohm
05. Pick up/Drop off Test:

Unit Coil Pick up Drop off


Resistance voltage voltage

52X 5.62 k Ω 74V 46V

06 .Contact Pressure Check: 25 gms Contact Resistances: 0.48 Ω


07 Functional checks:

Correct operation of contacts: OK


Correct operation of appropriate indicator/flag: OK
Correct initiation of scheme function: OK
08 Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By


Lock Out Relay (VAJH-23)
Date: 26/05/15
01. Designation Lock out relay
Location: 541 DG-1/ 541 LC-3
02. Name plate Details:
Make: EE Serial No: M272604
Type: VAJH-23 Model: VAJH23BF64 (B)
Aux.Voltage: 110Vdc
3. General Inspection as per Checklist: OK
4. Insulation Resistance Test:
All Terminals to Body: >150M ohm
Between terminals: >150M ohm
5. Pick up/Drop off Test:

Ref Coil Pick up Drop off


Resistance voltage voltage

86-B 79.8 Ω 37.9V HR


86-C 80.5 Ω 39V HR

06 Contact Resistances: 0.58 Ω


07 Functional checks:
Correct operation of contacts: OK
Correct operation of appropriate indicator/flag: OK
Correct initiation of scheme function: OK
08 Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By


Report for Over Current/Earth Fault Relay (CDV-62)
Testing Report No. ELECT/RLY/ Date: 26/05/15
1. Designation: Over Current Relay/ Earth Fault Relay
Location: S/S A /541 DG-1 /541 LC-3
02. Name plate Details:
Make:EE Serial No: M272557
Type: CDV62 CT Sec Current (A): 5.0 A
Model: CDV62 FF21A5 Auxiliary Voltage: 110V DC
Normal Volt: 63.5V Under Volt: 40V

Available Setting O/C


PS (A) 2.5-10.0
TMS 0.1-1.0

Op. Time (Sec) at PS x 10 with TMS 1.0: 5.5 seconds (normal volt), 2.0 seconds (under volt)
3. General Inspection as per Checklist: Ok
4. Insulation Resistance Test:
a) All Terminals to Body: >200M Ω
b) Between terminals : >200 M Ω
05. CT Resistance Check: R-ph (5-6): 0.68 Ω; Y-Ph (7-8): 0.65 Ω; B-ph (9-10):0.71 Ω
06. Coil resistance & pick up / drop off test of AC element:

Phase Terminals Resistance pick up(AC) drop off(AC)


R-ph 15-16 1.63 41.5 37
Y-Ph 17-18 1.65 52.8 40
B-ph 19-20 1.61 59.3 39

07. Contact Resistance: 0.41 Ω.


08. Aux unit Coil resistance & pick up test of DC element:
Phase Terminals Resistance pick up(AC)
R-ph 3-12 1.83 82
Y-Ph 3-12 1.87 80.9
B-ph 3-12 1.89 73.7
9. Secondary Injection Test:-
Phase/Unit PS(A) TMS Starting Closing Operating Time (Sec) at multiples of Ps
Current(A) Current (A) 2 5 7
Normal Volts:110V AC :-
R 5.0 0.3 5.45 5.87 - - -
0.45 - - 10.51 4.5 3.2
1.0 - - 23.8 8.6 8.12
Y 0.3 5.47 5.78 - - -
0.45 - - 10.49 4.51 3.3
1.0 - - 23.7 8.3 8.12
B 0.3 5.41 5.74 - - -
0.45 - - 10.59 4.7 3.7
1.0 - - 24.3 8.63 8.13
Under Volts:40V AC :-
R 0.45 - - 1.9 1.28 0.99
1.0 - - 4.31 2.63 2.27
Y 0.45 - - 1.9 1.31 1.1
1.0 - - 4.31 2.65 2.13
B 0.45 - - 2.1 1.25 1.3
1.0 - - 4.31 2.57 2.15

10. Functional Check


a) Operation of Indicators/Aux. Unit: Ok
c) Initiation of Alarm Contact: Ok
f) Circuit Breaker Tripping Contact: Ok
11. Service Settings:
O/C(R) O/C(Y) O/C(B)
PS(A) 5 5 5
TMS 0.45 0.45 0.45

12. Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By


Test Report Reverse Power relay (CCUM-31)
Date: 26/05/15
1. Designation: Reverse Power relay
Location: S/S A /541 DG-1 /541 LC-3
02. Name plate Details:
Make: EE Serial No: M 272561
Type: CCUM-31 CT Sec Current (A):5.0
Model: CCUM 31 PFF A Aux. Voltage: 24V DC
Time range: (2-10.0) Sec Rated voltage : 110VAC
3. General Inspection as per Checklist:
4. Insulation Resistance Test:
a) All Terminals to Body: value
b) Between Terminals:: value
5. Coil Resistance: 0.53 Ω
6. Contact Resistance: 0.78 Ω
7. Secondary Injection Test:
Applied Volts (V) Current Injected Direction of current Operation of relay
110 4.98 Forward Not operated
110 0.98 Reverse Operated
OP. time test:-

Applied Volts (V) Current Injected Timer setting Operation Time


110 0.98 2 1.97
5 4.99
10 10.03

9. Functional Check
a) Operation of Indicators/Aux. Unit: Ok
b) Initiation of Alarm Contact: Ok
c) Circuit Breaker Tripping Contact: Ok
10. Service Settings: Timer Setting: 5.0s
11. Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By:


UNDER VOLTAGE RELAY (VAG21)
Date: 26/05/15
1. Designation: Under Voltage Relay
Location: 541-LC3/541 CB-11
02. Name plate Details:
Make: EE Serial No: 31110149.
Type: VAG-21 Model: VAG21ZG8189G CH
Aux.Voltage: 110VDC
3. General Inspection as per Checklist: OK
4. Insulation Resistance Test:
All Terminals to Body: >200M ohm
Between terminals: >200M ohm
05. Pick up/Drop off Test
: Unit Coil Pick up Drop off
Resistance voltage voltage

B27RY 2.4M Ω 81VAC 23VAC


B27RYX 5.3 k Ω 55.9Vdc 13.7Vdc

06 Contact Resistances: 0.59Ω


07 Functional checks:
Correct operation of contacts: OK
Correct operation of appropriate indicator/flag: OK
Correct initiation of scheme function: OK
08 Remarks: Relay Operation Found Satisfactorily

Tested By Checked By
UNDER VOLTAGE RELAY (VAG21)
Date: 26/05/15
1. Designation: Under Voltage Relay
Location: 541-LC3/541 CB-11
02. Name plate Details:
Make: EE Serial No: 131221130727005
Type: VAG-21 Model: VAG21ZG8189G CH
Aux.Voltage: 110VDC
3. General Inspection as per Checklist: OK
4. Insulation Resistance Test:
All Terminals to Body: >200M ohm
Between terminals: >200M ohm
05. Pick up/Drop off Test
: Unit Coil Pick up Drop off
Resistance voltage voltage

B27YB 2.41M Ω 83.7VAC 23.7VAC


B27YBX 5.7 k Ω 53.9Vdc 12.8Vdc

06 Contact Resistances: 0.73Ω


07 Functional checks:
Correct operation of contacts: OK
Correct operation of appropriate indicator/flag: OK
Correct initiation of scheme function: OK
08 Remarks: Relay Operation Found Satisfactorily

Tested By Checked By
Auxiliary relay (VAA-11)
Date: 28/05/15
01. Designation Auxiliary relay
Location: 541-LC3/541 DG no.2
02. Name plate Details:
Make: EE Serial No: M272775
Type: VAA-11 Model: VAA11YF189A
Aux.Voltage: 110VDC
03. General Inspection as per Checklist: OK
04. Insulation Resistance Test:

All Terminals to Body: >100M ohm


Between terminals: >100M ohm
05. Pick up/Drop off Test:

Unit Coil Pick up Drop off


Resistance voltage voltage

52Z 5.63 k Ω 68V 40V

06 . Contact Resistances: 0.53 Ω


07 Functional checks:
Correct operation of contacts: OK
Correct operation of appropriate indicator/flag: OK
Correct initiation of scheme function: OK
08 Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By


Auxiliary relay (VAA-11)
Date: 28/05/15
01. Designation Auxiliary relay
Location: 541-LC3/541 DG no.2
02. Name plate Details:
Make: EE Serial No: M272765
Type: VAA-11 Model: VAA11YF189A
Aux.Voltage: 110VDC
03. General Inspection as per Checklist: OK
04. Insulation Resistance Test:

All Terminals to Body: >100M ohm


Between terminals: >100M ohm
05. Pick up/Drop off Test:
Unit Coil Pick up Drop off
Resistance voltage voltage

52Y 5.70 k Ω 70V 48V

06 .Contact Pressure Check: 25 gms Contact Resistances: 0.56 Ω


07 Functional checks:
Correct operation of contacts: OK

Correct operation of appropriate indicator/flag: OK


Correct initiation of scheme function: OK
08 Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By


Auxiliary relay (VAA-11)
Date: 28/05/15
01. Designation Auxiliary relay
Location: 541-LC3/541 DG no.2
02. Name plate Details:
Make: EE Serial No: M764307
Type: VAA-11 Model: VAA11YF50A
Aux.Voltage: 110VDC
03. General Inspection as per Checklist: OK
04. Insulation Resistance Test:

All Terminals to Body: >100M ohm


Between terminals: >100M ohm
05. Pick up/Drop off Test:
Unit Coil Pick up Drop off
Resistance voltage voltage

52X 5.48 k Ω 48V 28V

06 .Contact Pressure Check: 27 gms Contact Resistances: 0.53 Ω


07 Functional checks:
Correct operation of contacts: OK

Correct operation of appropriate indicator/flag: OK


Correct initiation of scheme function: OK
08 Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By


Auxiliary relay (VAA-11)
Date: 28/05/15
1. Designation Auxiliary relay
Location: 541-LC3/541 DG no.2
02. Name plate Details:
Make: EE Serial No: M272775
Type: VAA-11 Model: VAA11YF38B
Aux.Voltage: 110VDC
3. General Inspection as per Checklist: OK
4. Insulation Resistance Test:
All Terminals to Body: >200M ohm
Between terminals: >200M ohm
05. Pick up/Drop off Test:

Unit Coil Pick up Drop off


Resistance voltage voltage

27/94 5.6 k Ω 67V 54V

06 . Contact Resistances: 0.67 Ω


07 Functional checks:
Correct operation of contacts: OK
Correct operation of appropriate indicator/flag: OK
Correct initiation of scheme function: OK
08 Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By


Auxiliary relay (VAA-11)
Date: 28/05/15
1. Designation Auxiliary relay
Location: 541-LC3/541 DG no.2
02. Name plate Details:
Make: EE Serial No:M272615
Type: VAA-11 Model: VAA11YF807AH (M)
Aux.Voltage: 110VDC
3. General Inspection as per Checklist: OK
4. Insulation Resistance Test:
All Terminals to Body: >100M ohm
Between terminals: >100M ohm
05. Pick up/Drop off Test:

Unit Coil Pick up Drop off


Resistance voltage voltage

27/74 5.62 k Ω 74V 46V

6 Contact Resistances: 0.48 Ω


7 Functional checks:
Correct operation of contacts: OK
Correct operation of appropriate indicator/flag: OK
Correct initiation of scheme function: OK
8 Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By


Lock Out Relay (VAJH-23)
Date: 28/05/15
1. Designation Lock out relay
Location: 541 DG-2/ 541 LC-3
02. Name plate Details:
Make: EE Serial No:
Type: VAJH-23 Model: VAJH23BF64 (B)
Aux.Voltage: 110Vdc
3. General Inspection as per Checklist: OK
4. Insulation Resistance Test:
All Terminals to Body: >150M ohm
Between terminals: >150M ohm
5. Pick up/Drop off Test:

Ref Coil Pick up Drop off


Resistance voltage voltage

86-B 79.8 Ω 37.9V HR


86-C 80.5 Ω 39V HR

06 Contact Resistances: 0.58 Ω


07 Functional checks:
Correct operation of contacts: OK
Correct operation of appropriate indicator/flag: OK
Correct initiation of scheme function: OK
08 Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By


Report for Over Current/Earth Fault Relay (CDV-62)
Testing Report No. ELECT/RLY/ Date: 28/05/15
1. Designation: Over Current Relay/ Earth Fault Relay
Location: S/S A /541 DG-2 /541 LC-3
02. Name plate Details:
Make:EE Serial No: M272558
Type: CDV62 CT Sec Current (A): 5.0 A
Model: CDV62 FF21A5 Auxiliary Voltage: 110V DC
Normal Volt: 63.5V Under Volt: 40V

Available Setting O/C


PS (A) 2.5-10.0
TMS 0.1-1.0

Op. Time (Sec) at PS x 10 with TMS 1.0: 5.5 seconds (normal volt), 2.0 seconds (under volt)
3. General Inspection as per Checklist: Ok
4. Insulation Resistance Test:
d) All Terminals to Body: >200M Ω
e) Between terminals : >200 M Ω
05. CT Resistance Check: R-ph (5-6): 0.68 Ω; Y-Ph (7-8): 0.65 Ω; B-ph (9-10):0.71 Ω
06. Coil resistance & pick up / drop off test of AC element:

Phase Terminals Resistance pick up(AC) drop off(AC)


R-ph 15-16 1.67 59 37.7
Y-Ph 17-18 1.67 65 40.6
B-ph 19-20 1.67 63 39.9

07. Contact Resistance: 0.41 Ω.


08. Aux unit Coil resistance & pick up test of DC element:
Phase Terminals Resistance pick up(AC)
R-ph 3-12 1.83 82.3
Y-Ph 3-12 1.87 80.9
B-ph 3-12 1.89 73.7
9. Secondary Injection Test:-
Phase/Unit PS(A) TMS Starting Closing Operating Time (Sec) at multiples of Ps
Current(A) Current (A) 2 5 7
Normal Volts:110V AC :-
R 5.0 0.3 5.43 5.8 - - -
0.45 - - 10.51 4.59 3.29
1.0 - - 23.7 8.8 8.28
Y 0.3 5.45 5.95 - - -
0.45 - - 10.49 4.51 3.3
1.0 - - 23.7 8.3 8.12
B 0.3 5.53 6.13 - - -
0.45 - - 10.59 4.73 3.7
1.0 - - 24.3 8.67 8.13
Under Volts:40V AC :-
R 0.45 - - 1.9 1.28 1.21
1.0 - - 4.31 2.63 2.3
Y 0.45 - - 1.9 1.31 1.1
1.0 - - 4.31 2.65 2.13
B 0.45 - - 2.3 1.35 1.45
1.0 - - 4.45 2.67 2.25

10. Functional Check


a) Operation of Indicators/Aux. Unit: Ok
f) Initiation of Alarm Contact: Ok
g) Circuit Breaker Tripping Contact: Ok
11. Service Settings:
O/C(R) O/C(Y) O/C(B)
PS(A) 5 5 5
TMS 0.45 0.45 0.45

12. Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By


Test Report Reverse Power relay (CCUM-31)
Date: 28/05/15
1. Designation: Reverse Power relay
Location: S/S A /541 DG-2 /541 LC-3
02. Name plate Details:
Make: EE Serial No: M 272562
Type: CCUM-31 CT Sec Current (A):5.0
Model: CCUM 31 PFF A Aux. Voltage: 24V DC
Time range: (2-10.0) Sec Rated voltage : 110VAC
3. General Inspection as per Checklist:
4. Insulation Resistance Test:
c) All Terminals to Body: value
d) Between Terminals:: value
5. Coil Resistance: 0.53 Ω
6. Contact Resistance: 0.78 Ω
7. Secondary Injection Test:
Applied Volts (V) Current Injected Direction of current Operation of relay
110 4.98 Forward Not operated
110 0.98 Reverse Operated
OP. time test:-

Applied Volts (V) Current Injected Timer setting Operation Time


110 0.98 2 2.0
5 5.37
10 10.13

9. Functional Check
a) Operation of Indicators/Aux. Unit: Ok
b) Initiation of Alarm Contact: Ok
c) Circuit Breaker Tripping Contact: Ok
10...Service Settings: Timer Setting: 5.0s
11. Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By:


UNDER VOLTAGE RELAY (VAG21)
Date: 28/05/15
1. Designation: Under Voltage Relay
Location: 541-LC3/541 CB-12
02. Name plate Details:
Make: EE Serial No: 131221130727013.
Type: VAG-21 Model: VAG21ZG8189G CH
Aux.Voltage: 110VDC
3. General Inspection as per Checklist: OK
4. Insulation Resistance Test:
All Terminals to Body: >200M ohm
Between terminals: >200M ohm
05. Pick up/Drop off Test
: Unit Coil Pick up Drop off
Resistance voltage voltage

B27YR 2.4M Ω 82VAC 25.7VAC


B27RYX 5.35 k Ω 56Vdc 14.0Vdc

06 Contact Resistances: 0.59Ω


07 Functional checks:
Correct operation of contacts: OK
Correct operation of appropriate indicator/flag: OK
Correct initiation of scheme function: OK
08 Remarks: Relay Operation Found Satisfactorily

Tested By Checked By
UNDER VOLTAGE RELAY (VAG21)
Date: 28/05/15
1. Designation: Under Voltage Relay
Location: 541-LC3/541 CB-12
02. Name plate Details:
Make: EE Serial No: 131221130727014
Type: VAG-21 Model: VAG21ZG8189G CH
Aux.Voltage: 110VDC
3. General Inspection as per Checklist: OK
4. Insulation Resistance Test:
All Terminals to Body: >200M ohm
Between terminals: >200M ohm
05. Pick up/Drop off Test
: Unit Coil Pick up Drop off
Resistance voltage voltage

B27YB 2.41M Ω 83.5VAC 25.7VAC


B27YBX 5.7 k Ω 54.9Vdc 32Vdc

06 Contact Resistances: 0.48Ω


07 Functional checks:
Correct operation of contacts: OK
Correct operation of appropriate indicator/flag: OK
Correct initiation of scheme function: OK
08 Remarks: Relay Operation Found Satisfactorily

Tested By Checked By
Auxiliary relay (VAA-11)
Date: 03/06/15
01. Designation Auxiliary relay
Location: 541-LC3/541 DG no.3
02. Name plate Details:
Make: EE Serial No: M272759
Type: VAA-11 Model: VAA11YF189A
Aux.Voltage: 110VDC
03. General Inspection as per Checklist: OK
04. Insulation Resistance Test:

All Terminals to Body: >100M ohm


Between terminals: >100M ohm
05. Pick up/Drop off Test:
Unit Coil Pick up Drop off
Resistance voltage voltage

52X 5.64 k Ω 75V 50V

06 Contact Resistances: 0.48 Ω


07 Functional checks:
Correct operation of contacts: OK
Correct operation of appropriate indicator/flag: OK
Correct initiation of scheme function: OK
08 Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By


Auxiliary relay (VAA-11)
Date: 03/06/15
01. Designation Auxiliary relay
Location: 541-LC3/541 DG no.3
02. Name plate Details:
Make: EE Serial No: M272779
Type: VAA-11 Model: VAA11YF189A
Aux.Voltage: 110VDC
03. General Inspection as per Checklist: OK
04. Insulation Resistance Test:

All Terminals to Body: >100M ohm


Between terminals: >100M ohm
05. Pick up/Drop off Test:
Unit Coil Pick up Drop off
Resistance voltage voltage

52Y 5.89 k Ω 74V 58V

06 Contact Resistances: 0.53 Ω


07 Functional checks:
Correct operation of contacts: OK
Correct operation of appropriate indicator/flag: OK
Correct initiation of scheme function: OK
08 Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By


Auxiliary relay (VAA-11)
Date: 03/06/15
01. Designation Auxiliary relay
Location: 541-LC3/541 DG no.3
02. Name plate Details:
Make: EE Serial No: M272763
Type: VAA-11 Model: VAA11YF189A
Aux.Voltage: 110VDC
03. General Inspection as per Checklist: OK
04. Insulation Resistance Test:

All Terminals to Body: >100M ohm


Between terminals: >100M ohm
05. Pick up/Drop off Test:
Unit Coil Pick up Drop off
Resistance voltage voltage

52Z 105.8 k Ω 70V 60V

06 Contact Resistances: 0.48 Ω


07 Functional checks:
Correct operation of contacts: OK
Correct operation of appropriate indicator/flag: OK
Correct initiation of scheme function: OK
08 Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By


Auxiliary relay (VAA-11)
Date: 03/06/15
01. Designation Auxiliary relay
Location: 541-LC3/541 DG no.3
02. Name plate Details:
Make: EE Serial No: M27619
Type: VAA-11 Model: VAA11YF8007AH(M)
Aux.Voltage: 110VDC
03. General Inspection as per Checklist: OK
04. Insulation Resistance Test:

All Terminals to Body: >100M ohm


Between terminals: >100M ohm
05. Pick up/Drop off Test:
Unit Coil Pick up Drop off
Resistance voltage voltage

27/74 5.51 k Ω 57.6V 31V

06 Contact Resistances: 0.53 Ω


07 Functional checks:
Correct operation of contacts: OK
Correct operation of appropriate indicator/flag: OK
Correct initiation of scheme function: OK
08 Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By


Auxiliary relay (VAA-11)
Date: 03/06/15
01. Designation Auxiliary relay
Location: 541-LC3/541 DG no.3
02. Name plate Details:
Make: EE Serial No: M27627
Type: VAA-11 Model: VAA11YF8007AH(M)
Aux.Voltage: 110VDC
03. General Inspection as per Checklist: OK
04. Insulation Resistance Test:

All Terminals to Body: >100M ohm


Between terminals: >100M ohm
05. Pick up/Drop off Test:
Unit Coil Pick up Drop off
Resistance voltage voltage

27/94 5.81 k Ω 64.5V 33V

06 Contact Resistances: 0.57 Ω


07 Functional checks:
Correct operation of contacts: OK
Correct operation of appropriate indicator/flag: OK
Correct initiation of scheme function: OK
08 Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By


Lock out relay (VAJH-23)
Date: 03/06/15
01. Designation Lock out relay
Location: 541 DG-3/ 541 LC-3
02. Name plate Details:
Make: EE Serial No: M272605
Type: VAJH-23 Model: VAJH23BF64 (B)
Aux.Voltage: 110Vdc
3. General Inspection as per Checklist: OK
4. Insulation Resistance Test:
All Terminals to Body: >200M Ω
Between terminals: >200M Ω
05. Pick up/Drop off Test:

Ref Coil Pick up Drop off


Resistance voltage voltage

86-B 78.7Ω 45.9V HR


86-C 80.5 Ω 44.3V HR
06 Contact Resistances: 0.51 Ω
07 Functional checks:
Correct operation of contacts: OK
Correct operation of appropriate indicator/flag: OK
Correct initiation of scheme function: OK
08 Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By


UNDER VOLTAGE RELAY (VAG21)
Date: 03/06/15
1. Designation: Under Voltage Relay
Location: 541-LC3/541 CB-13
02. Name plate Details:
Make: EE Serial No: 131221130727006.
Type: VAG-21 Model: VAG21ZG8189G CH
Aux.Voltage: 110VDC
3. General Inspection as per Checklist: OK
4. Insulation Resistance Test:
All Terminals to Body: >200M ohm
Between terminals: >200M ohm
05. Pick up/Drop off Test
: Unit Coil Pick up Drop off
Resistance voltage voltage

B27RY 2.4M Ω 82VAC 25.7VAC


B27RYX 5.35 k Ω 56Vdc 14.0Vdc

06 Contact Resistances: 0.59Ω


07 Functional checks:
Correct operation of contacts: OK
Correct operation of appropriate indicator/flag: OK
Correct initiation of scheme function: OK
08 Remarks: Relay Operation Found Satisfactorily

Tested By Checked By
UNDER VOLTAGE RELAY (VAG21)
Date: 03/06/15
1. Designation: Under Voltage Relay
Location: 541-LC3/541 CB-13
02. Name plate Details:
Make: EE Serial No: 311104154
Type: VAG-21 Model: VAG21ZG8189G CH
Aux.Voltage: 110VDC
3. General Inspection as per Checklist: OK
4. Insulation Resistance Test:
All Terminals to Body: >200M ohm
Between terminals: >200M ohm
05. Pick up/Drop off Test
: Unit Coil Pick up Drop off
Resistance voltage voltage

B27YB 2.48M Ω 82VAC 28VAC


B27YBX 5.5 k Ω 55.3Vdc 29.7Vdc

06 Contact Resistances: 0.57Ω


07 Functional checks:
Correct operation of contacts: OK
Correct operation of appropriate indicator/flag: OK
Correct initiation of scheme function: OK
08 Remarks: Relay Operation Found Satisfactorily

Tested By Checked By
Report for Over Current/Earth Fault Relay (CDV-62)
Testing Report No. ELECT/RLY/ Date: 03/06/15
1. Designation: Over Current Relay/ Earth Fault Relay

02. Name plate Details:


Make:EE Serial No: M272560
Type: CDV62 CT Sec Current (A): 5.0 A
Model: CDV62 FF21A5 Auxiliary Voltage: 110V DC
Normal Volt: 63.5V Under Volt: 40V

Available Setting O/C


PS (A) 2.5-10.0
TMS 0.1-1.0

Op. Time (Sec) at PS x 10 with TMS 1.0: 5.5 seconds (normal volt), 2.0 seconds (under volt)
3. General Inspection as per Checklist: Ok
4. Insulation Resistance Test:
g) All Terminals to Body: >200M Ω
h) Between terminals : >200 M Ω
05. CT Resistance Check: R-ph (5-6): 0.68 Ω; Y-Ph (7-8): 0.65 Ω; B-ph (9-10):0.71 Ω
06. Coil resistance & pick up / drop off test of AC element:

Phase Terminals Resistance pick up(AC) drop off(AC)


R-ph 15-16 1.63 41.0 39.6
Y-Ph 17-18 1.63 52.85 40.1
B-ph 19-20 1.63 59.0 39.3

07. Contact Resistance: 0.41 Ω.


08. Aux unit Coil resistance & pick up test of DC element:
Phase Terminals Resistance pick up(AC)
R-ph 3-12 1.83 82.0
Y-Ph 3-12 1.85 80.9
B-ph 3-12 1.91 85.0
9. Secondary Injection Test:-
Phase/Unit PS(A) TMS Starting Closing Operating Time (Sec) at multiples of Ps
Current(A) Current (A) 2 5 7
Normal Volts:110V AC :-
R 5.0 0.3 5.43 5.89 - - -
0.45 - - 10.51 4.5 3.2
1.0 - - 23.8 8.6 8.23
Y 0.3 5.44 5.87 - - -
0.45 - - 10.49 4.51 3.3
1.0 - - 23.7 8.3 8.25
B 0.3 5.49 5.99 - - -
0.45 - - 10.59 4.7 3.7
1.0 - - 24.3 8.63 8.15
Under Volts:40V AC :-
R 0.45 - - 1.9 1.28 0.99
1.0 - - 4.35 2.69 2.37
Y 0.45 - - 1.9 1.31 1.1
1.0 - - 4.31 2.65 2.23
B 0.45 - - 2.1 1.25 1.3
1.0 - - 4.31 2.55 2.55

10. Functional Check


a) Operation of Indicators/Aux. Unit: Ok
i) Initiation of Alarm Contact: Ok
h) Circuit Breaker Tripping Contact: Ok
11. Service Settings:

O/C(R) O/C(Y) O/C(B)


PS(A) 5 5 5
TMS 0.45 0.45 0.45

12. Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By


Test Report Reverse Power relay (CCUM-31)
Date: 03/06/15
1. Designation: Reverse Power relay
Location: S/S A /541 DG-3 /541 LC-3
02. Name plate Details:
Make: EE Serial No: M 115298
Type: CCUM-31 CT Sec Current (A):5.0
Model: CCUM 31 PFF A Aux. Voltage: 24V DC
Time range: (2-10.0) Sec Rated voltage : 110VAC
3. General Inspection as per Checklist:
4. Insulation Resistance Test:
e) All Terminals to Body: value
f) Between Terminals:: value
5. Coil Resistance: 0.53 Ω
6. Contact Resistance: 0.78 Ω
7. Secondary Injection Test:
Applied Volts (V) Current Injected Direction of current Operation of relay
110 4.98 Forward Not operated
110 0.99 Reverse Operated
OP. time test:-

Applied Volts (V) Current Injected Timer setting Operation Time


110 0.99 2 2.13
5 5.3
10 5.23

9. Functional Check
a) Operation of Indicators/Aux. Unit: Ok
b) Initiation of Alarm Contact: Ok
c) Circuit Breaker Tripping Contact: Ok
10...Service Settings: Timer Setting: 5.0s
11. Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By:


Auxiliary relay (VAA-11)
Date: 05/06/15
01. Designation Auxiliary relay
Location: 541-LC3/541 DG no.4
02. Name plate Details:
Make: EE Serial No: M272757
Type: VAA-11 Model: VAA11YF189A.
Aux.Voltage: 110VDC
03. General Inspection as per Checklist: OK
04. Insulation Resistance Test:

All Terminals to Body: >100M ohm


Between terminals: >100M ohm
05. Pick up/Drop off Test:
Unit Coil Pick up Drop off
Resistance voltage voltage

52X 5.76 k Ω 75V 57V

06 Contact Resistances: 0.53 Ω


07 Functional checks:
Correct operation of contacts: OK
Correct operation of appropriate indicator/flag: OK
Correct initiation of scheme function: OK
08 Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By


Auxiliary relay (VAA-11)
Date: 05/06/15
01. Designation Auxiliary relay
Location: 541-LC3/541 DG no.4
02. Name plate Details:
Make: EE Serial No: M812805
Type: VAA-11 Model: VAA11YF50A.
Aux.Voltage: 110VDC
03. General Inspection as per Checklist: OK
04. Insulation Resistance Test:

All Terminals to Body: >100M ohm


Between terminals: >100M ohm
05. Pick up/Drop off Test:
Unit Coil Pick up Drop off
Resistance voltage voltage

52Z 6kΩ 62V 32V

06 Contact Resistances: 0.57 Ω


07 Functional checks:
Correct operation of contacts: OK
Correct operation of appropriate indicator/flag: OK
Correct initiation of scheme function: OK
08 Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By


Auxiliary relay (VAA-11)
Date: 05/06/15
01. Designation Auxiliary relay
Location: 541-LC3/541 DG no.4
02. Name plate Details:
Make: EE Serial No: M272777
Type: VAA-11 Model: VAA11YF189A.
Aux.Voltage: 110VDC
03. General Inspection as per Checklist: OK
04. Insulation Resistance Test:

All Terminals to Body: >100M ohm


Between terminals: >100M ohm
05. Pick up/Drop off Test:
Unit Coil Pick up Drop off
Resistance voltage voltage

52Y 5.76 k Ω 72V 44V

6 Contact Resistances: 0.51 Ω


7 Functional checks:
Correct operation of contacts: OK
Correct operation of appropriate indicator/flag: OK
Correct initiation of scheme function: OK
8 Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By


Auxiliary relay (VAA-11)
Date: 05/06/15
01. Designation Auxiliary relay
Location: 541-LC3/541 DG no.4
02. Name plate Details:
Make: EE Serial No: M272616
Type: VAA-11 Model: VAA11YF8007AH (M).
Aux.Voltage: 110VDC
03. General Inspection as per Checklist: OK
04. Insulation Resistance Test:

All Terminals to Body: >100M ohm


Between terminals: >100M ohm
05. Pick up/Drop off Test:
Unit Coil Pick up Drop off
Resistance voltage voltage

27/74 5.33 k Ω 67V 31V

06 .Contact Pressure Check: 26 gms Contact Resistances: 0.57 Ω


07 Functional checks:
Correct operation of contacts: OK

Correct operation of appropriate indicator/flag: OK


Correct initiation of scheme function: OK
08 Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By


Auxiliary relay (VAA-11)
Date: 05/06/15
01. Designation Auxiliary relay
Location: 541-LC3/541 DG no.4
02. Name plate Details:
Make: EE Serial No: M272626
Type: VAA-11 Model: VAA11YF38B.
Aux.Voltage: 110VDC
03. General Inspection as per Checklist: OK
04. Insulation Resistance Test:

All Terminals to Body: >100M ohm


Between terminals: >100M ohm
05. Pick up/Drop off Test:
Unit Coil Pick up Drop off
Resistance voltage voltage

27/94 5.67 k Ω 71V 51V

06 .Contact Pressure Check: 25 gms Contact Resistances: 0.57 Ω


07 Functional checks:
Correct operation of contacts: OK

Correct operation of appropriate indicator/flag: OK


Correct initiation of scheme function: OK
08 Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By


Lock out relay (VAJH-23)
Date: 05/06/15
01. Designation: Lock out relay
Location: 541 DG-4/ 541 LC-3
02. Name plate Details:
Make: EE Serial No: M272603
Type: VAJH-23 Model: VAJH23BF62 (B)
Aux.Voltage: 110Vdc
3. General Inspection as per Checklist: OK
4. Insulation Resistance Test:
All Terminals to Body: >200M Ω
Between terminals: >200M Ω
05. Pick up/Drop off Test:

Ref Coil Pick up Drop off


Resistance voltage voltage

86-B 89.2Ω 31V HR


86-C 89.6 Ω 33.7V HR
06 .Contact Pressure Check: 23 gms Contact Resistances: 0.51 Ω
07 Functional checks:

Correct operation of contacts: OK


Correct operation of appropriate indicator/flag: OK
Correct initiation of scheme function: OK
08 Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By


UNDER VOLTAGE RELAY (VAG21)
Date: 05/06/15
1. Designation: Under Voltage Relay
Location: 541-LC3/541 CB-20
02. Name plate Details:
Make: EE Serial No: 31110151.
Type: VAG-21 Model: VAG21ZG8189G CH
Aux.Voltage: 110VDC
3. General Inspection as per Checklist: OK
4. Insulation Resistance Test:
All Terminals to Body: >200M ohm
Between terminals: >200M ohm
05. Pick up/Drop off Test
: Unit Coil Pick up Drop off
Resistance voltage voltage

B27RY 2.44M Ω 83.7VAC 24VAC


B27RYX 5.55 k Ω 58Vdc 25.0Vdc

06 Contact Resistances: 0.59Ω


07 Functional checks:
Correct operation of contacts: OK
Correct operation of appropriate indicator/flag: OK
Correct initiation of scheme function: OK
08 Remarks: Relay Operation Found Satisfactorily

Tested By Checked By
UNDER VOLTAGE RELAY (VAG21)
Date: 05/06/15
1. Designation: Under Voltage Relay
Location: 541-LC3/541 CB-20
02. Name plate Details:
Make: EE Serial No: 13121130727009
Type: VAG-21 Model: VAG21ZG8189G CH
Aux.Voltage: 110VDC
3. General Inspection as per Checklist: OK
4. Insulation Resistance Test:
All Terminals to Body: >200M ohm
Between terminals: >200M ohm
05. Pick up/Drop off Test
: Unit Coil Pick up Drop off
Resistance voltage voltage

B27YB 2.48M Ω 82VAC 29VAC


B27YBX 5.57 k Ω 58Vdc 32Vdc

06 Contact Resistances: 0.57Ω


07 Functional checks:
Correct operation of contacts: OK
Correct operation of appropriate indicator/flag: OK
Correct initiation of scheme function: OK
08 Remarks: Relay Operation Found Satisfactorily

Tested By Checked By
Report for Over Current/Earth Fault Relay (CDV-62)
Testing Report No. ELECT/RLY/ Date: 05/06/15
1. Designation: Over Current Relay/ Earth Fault Relay
Location: S/S A /541 DG-4/ 541 LC-3
02. Name plate Details:
Make:EE Serial No: M272559
Type: CDV62 CT Sec Current (A): 5.0 A
Model: CDV62 FF21A5 Auxiliary Voltage: 110V DC
Normal Volt: 63.5V Under Volt: 40V

Available Setting O/C


PS (A) 2.5-10.0
TMS 0.1-1.0

Op. Time (Sec) at PS x 10 with TMS 1.0: 5.5 seconds (normal volt), 2.0 seconds (under volt)
3. General Inspection as per Checklist: Ok
4. Insulation Resistance Test:
j) All Terminals to Body: >200M Ω
k) Between terminals : >200 M Ω
05. CT Resistance Check: R-ph (5-6): 0.68 Ω; Y-Ph (7-8): 0.65 Ω; B-ph (9-10):0.71 Ω
06. Coil resistance & pick up / drop off test of AC element:

Phase Terminals Resistance pick up(AC) drop off(AC)


R-ph 15-16 1.63 41.5 37.6
Y-Ph 17-18 1.61 52.5 40.5
B-ph 19-20 1.61 59.4 39.9

07. Contact Resistance: 0.41 Ω.


08. Aux unit Coil resistance & pick up test of DC element:
Phase Terminals Resistance pick up(AC)
R-ph 3-12 1.81 82.6
Y-Ph 3-12 1.85 80.9
B-ph 3-12 1.93 73.7
9. Secondary Injection Test:-
Phase/Unit PS(A) TMS Starting Closing Operating Time (Sec) at multiples of Ps
Current(A) Current (A) 2 5 7
Normal Volts:110V AC :-
R 5.0 0.3 5.43 5.89 - - -
0.45 - - 10.51 4.5 3.24
1.0 - - 23.64 8.64 8.12
Y 0.3 5.47 5.95 - - -
0.45 - - 10.49 4.51 3.3
1.0 - - 23.7 8.3 8.12
B 0.3 5.43 5.91 - - -
0.45 - - 10.59 4.73 3.79
1.0 - - 24.3 8.63 8.13
Under Volts:40V AC :-
R 0.45 - - 1.9 1.28 0.99
1.0 - - 4.33 2.65 2.20
Y 0.45 - - 1.94 1.37 1.17
1.0 - - 4.31 2.65 2.13
B 0.45 - - 2.17 1.25 1.35
1.0 - - 4.31 2.57 2.15

10. Functional Check


a) Operation of Indicators/Aux. Unit: Ok
l) Initiation of Alarm Contact: Ok
i) Circuit Breaker Tripping Contact: Ok
11. Service Settings:
O/C(R) O/C(Y) O/C(B)
PS(A) 5 5 5
TMS 0.45 0.45 0.45

12. Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By


Test Report Reverse Power relay (CCUM-31)
Date: 05/06/15
1. Designation: Reverse Power relay
Location: S/S A /541 DG-4 /541 LC-3
02. Name plate Details:
Make: EE Serial No: M 272561
Type: CCUM-31 CT Sec Current (A):5.0
Model: CCUM 31 PFF A Aux. Voltage: 24V DC
Time range: (2-10.0) Sec Rated voltage : 110VAC
3. General Inspection as per Checklist:
4. Insulation Resistance Test:
g) All Terminals to Body: value
h) Between Terminals:: value
5. Coil Resistance: 0.53 Ω
6. Contact Resistance: 0.78 Ω
7. Secondary Injection Test:
Applied Volts (V) Current Injected Direction of current Operation of relay
110 5.0 Forward Not operated
110 0.98 Reverse Operated
OP. time test:-

Applied Volts (V) Current Injected Timer setting Operation Time


110 0.98 2 2.37
5 5.55
10 11.53

9. Functional Check
a) Operation of Indicators/Aux. Unit: Ok
b) Initiation of Alarm Contact: Ok
c) Circuit Breaker Tripping Contact: Ok
10...Service Settings: Timer Setting: 5.0s
11. Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By:


Auxiliary relay (VAA-11)
Date: 11/06/15
01. Designation Auxiliary relay
Location: 541-LC3/541 CB 14
02. Name plate Details:
Make: EE Serial No: M272769
Type: VAA-11 Model: VAA11YF14A.
Aux.Voltage: 110VDC
03. General Inspection as per Checklist: OK
04. Insulation Resistance Test:

All Terminals to Body: >100M ohm


Between terminals: >100M ohm
05. Pick up/Drop off Test:
Unit Coil Pick up Drop off
Resistance voltage voltage

52Y 5.3 k Ω 73V 37V

6 Contact Resistances: 0.57 Ω


7 Functional checks:
Correct operation of contacts: OK
Correct operation of appropriate indicator/flag: OK
Correct initiation of scheme function: OK
8 Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By


Auxiliary relay (VAA-11)
Date: 11/06/15
01. Designation Auxiliary relay
Location: 541-LC3/541 CB 14
02. Name plate Details:
Make: EE Serial No: M732479
Type: VAA-11 Model: VAA11Y8006A
Aux.Voltage: 110VDC
03. General Inspection as per Checklist: OK
04. Insulation Resistance Test:

All Terminals to Body: >100M ohm


Between terminals: >100M ohm
05. Pick up/Drop off Test:
Unit Coil Pick up Drop off
Resistance voltage voltage

52X 4.87 k Ω 59V 25V

6 Contact Resistances: 0.53 Ω


7 Functional checks:
Correct operation of contacts: OK
Correct operation of appropriate indicator/flag: OK
Correct initiation of scheme function: OK
8 Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By


Auxiliary relay (VAA-11)
Date: 11/06/15
01. Designation Auxiliary relay
Location: 541-LC3/541 CB 14
02. Name plate Details:
Make: EE Serial No: M272773
Type: VAA-11 Model: VAA11YF189A.
Aux.Voltage: 110VDC
03. General Inspection as per Checklist: OK
04. Insulation Resistance Test:

All Terminals to Body: >100M ohm


Between terminals: >100M ohm
05. Pick up/Drop off Test:
Unit Coil Pick up Drop off
Resistance voltage voltage

52Z 5.95 k Ω 72V 42V

6 Contact Resistances: 0.57 Ω


7 Functional checks:
Correct operation of contacts: OK
Correct operation of appropriate indicator/flag: OK
Correct initiation of scheme function: OK
8 Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By


Auxiliary relay (VAA-11)
Date: 11/06/15
01. Designation Auxiliary relay
Location: 541-LC3/541 CB 14
02. Name plate Details:
Make: EE Serial No: M272611
Type: VAA-11 Model: VAA11YF8007AH (M).
Aux.Voltage: 110VDC
03. General Inspection as per Checklist: OK
04. Insulation Resistance Test:

All Terminals to Body: >100M ohm


Between terminals: >100M ohm
05. Pick up/Drop off Test:
Unit Coil Pick up Drop off
Resistance voltage voltage

27/74 5.27 k Ω 67V 32V

06 Contact Resistances: 0.53 Ω


07 Functional checks:
Correct operation of contacts: OK
Correct operation of appropriate indicator/flag: OK
Correct initiation of scheme function: OK
08 Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By


Lock out relay (VAJH-23)
Date: 11/06/15
01. Designation: Lock out relay
Location: 541 CB 14/ 541 LC-3
02. Name plate Details:
Make: EE Serial No: M272600
Type: VAJH-23 Model: VAJH23BF8019B (M).
Aux.Voltage: 110Vdc

3. General Inspection as per Checklist: OK


4. Insulation Resistance Test:
All Terminals to Body: >200M Ω
Between terminals: >200M Ω
05. Pick up/Drop off Test:
Ref Coil Pick up Drop off
Resistance voltage voltage

86-B 81.67Ω 40V HR


86-C 80.53 Ω 37V HR
06 Contact Resistances: 0.51 Ω
07 Functional checks:
Correct operation of contacts: OK
Correct operation of appropriate indicator/flag: OK
Correct initiation of scheme function: OK
08 Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By


UNDER VOLTAGE RELAY (VAG21)
Date: 11/06/15
1. Designation: Under Voltage Relay
Location: 541-LC3/541 CB-14
02. Name plate Details:
Make: EE Serial No: M 272584.
Type: VAG-21 Model: VAG21ZG8190G (M)
Aux.Voltage: 110VDC
3. General Inspection as per Checklist: OK
4. Insulation Resistance Test:
All Terminals to Body: >200M ohm
Between terminals: >200M ohm
05. Pick up/Drop off Test
: Unit Coil Pick up Drop off
Resistance voltage voltage

B27RY 2.54 M Ω 80VAC 22VAC


B27RYX 5.17 k Ω 45Vdc 10Vdc

06 Contact Resistances: 0.59Ω


07 Functional checks:
Correct operation of contacts: OK
Correct operation of appropriate indicator/flag: OK
Correct initiation of scheme function: OK
08 Remarks: Relay Operation Found Satisfactorily

Tested By Checked By
UNDER VOLTAGE RELAY (VAG21)
Date: 11/06/15
1. Designation: Under Voltage Relay
Location: 541-LC3/541 CB-14
02. Name plate Details:
Make: EE Serial No: M 272584.
Type: VAG-21 Model: VAG21ZG8190G (M)
Aux.Voltage: 110VDC
3. General Inspection as per Checklist: OK
4. Insulation Resistance Test:
All Terminals to Body: >200M ohm
Between terminals: >200M ohm
05. Pick up/Drop off Test
: Unit Coil Pick up Drop off
Resistance voltage voltage

B27YB 3.26 M Ω 80VAC 19.5VAC


B27YBX 5.37 k Ω 47Vdc 11Vdc

06 Contact Resistances: 0.67Ω


07 Functional checks:
Correct operation of contacts: OK
Correct operation of appropriate indicator/flag: OK
Correct initiation of scheme function: OK
08 Remarks: Relay Operation Found Satisfactorily

Tested By Checked By
Auxiliary relay (VAA-11)
Date: 12/06/15
01. Designation Auxiliary relay
Location: 541-LC3/541 CB 15
02. Name plate Details:
Make: EE Serial No: M272756
Type: VAA-11 Model: VAA11YF189A.
Aux.Voltage: 110VDC
03. General Inspection as per Checklist: OK
04. Insulation Resistance Test:
All Terminals to Body: >100M ohm
Between terminals: >100M ohm
05. Pick up/Drop off Test:

Unit Coil Pick up Drop off


Resistance voltage voltage

52X 5.67 k Ω 82V 40V

06 Contact Resistances: 0.53 Ω


07 Functional checks:
Correct operation of contacts: OK
Correct operation of appropriate indicator/flag: OK
Correct initiation of scheme function: OK
08 Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By


Auxiliary relay (VAA-11)
Date: 12/06/15
01. Designation Auxiliary relay
Location: 541-LC3/541 CB 15
02. Name plate Details:
Make: EE Serial No: M272770
Type: VAA-11 Model: VAA11YF114A.
Aux.Voltage: 110VDC
03. General Inspection as per Checklist: OK
04. Insulation Resistance Test:
All Terminals to Body: >100M ohm
Between terminals: >100M ohm
05. Pick up/Drop off Test:

Unit Coil Pick up Drop off


Resistance voltage voltage

52Y 5.47 k Ω 75V 42V

06 Contact Resistances: 0.53 Ω


07 Functional checks:
Correct operation of contacts: OK
Correct operation of appropriate indicator/flag: OK
Correct initiation of scheme function: OK
08 Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By


Auxiliary relay (VAA-11)
Date: 12/06/15
01. Designation Auxiliary relay
Location: 541-LC3/541 CB 15
02. Name plate Details:
Make: EE Serial No: M764309
Type: VAA-11 Model: VAA11YF50A.
Aux.Voltage: 110VDC
03. General Inspection as per Checklist: OK
04. Insulation Resistance Test:
All Terminals to Body: >100M ohm
Between terminals: >100M ohm
05. Pick up/Drop off Test:

Unit Coil Pick up Drop off


Resistance voltage voltage

52Z 5.95 k Ω 65V 22V

06 Contact Resistances: 0.37 Ω


07 Functional checks:
Correct operation of contacts: OK
Correct operation of appropriate indicator/flag: OK
Correct initiation of scheme function: OK
08 Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By


Lock Out relay (VAJH-23)
Date: 12/06/15
01. Designation Lock Out relay
Location: 541 CB 15/ 541 LC-3.
02. Name plate Details:
Make: EE Serial No: M2726502
Type: VAJH-23 Model: VAJH23BF8019B (M).
Aux.Voltage: 110Vdc
3. General Inspection as per Checklist: OK
4. Insulation Resistance Test:
All Terminals to Body: >200M Ω
Between terminals: >200M Ω
05. Pick up/Drop off Test:
Ref Coil Pick up Drop off
Resistance voltage voltage

86-B 80.5Ω 37V HR


86-C 90.1 Ω 41V HR
06 Contact Resistances: 0.51 Ω
07 Functional checks:
Correct operation of contacts: OK
Correct operation of appropriate indicator/flag: OK
Correct initiation of scheme function: OK
08 Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By


UNDER VOLTAGE RELAY (VAG21)
Date: 12/06/15
1. Designation: Under Voltage Relay
Location: 541-LC3/541 CB-15
02. Name plate Details:
Make: EE Serial No: M 272584.
Type: VAG-21 Model: VAG21ZG8190G (M)
Aux.Voltage: 110VDC
3. General Inspection as per Checklist: OK
4. Insulation Resistance Test:
All Terminals to Body: >200M ohm
Between terminals: >200M ohm
05.: Pick up/Drop off Test
Unit Coil Pick up Drop off
Resistance voltage voltage

B27RY 3.59 M Ω 82.1VAC 20.3VAC


B27YBX 5.07 k Ω 47Vdc 11Vdc

06 Contact Resistances: 0.51Ω


07 Functional checks:
Correct operation of contacts: OK
Correct operation of appropriate indicator/flag: OK
Correct initiation of scheme function: OK
08 Remarks: Relay Operation Found Satisfactorily

Tested By Checked By
UNDER VOLTAGE RELAY (VAG21)
Date: 12/06/15
1. Designation: Under Voltage Relay
Location: 541-LC3/541 CB-15
02. Name plate Details:
Make: EE Serial No: M 272585.
Type: VAG-21 Model: VAG21ZG8190G (M)
Aux.Voltage: 110VDC
3. General Inspection as per Checklist: OK
4. Insulation Resistance Test:
All Terminals to Body: >200M ohm
Between terminals: >200M ohm
05. Pick up/Drop off Test
: Unit Coil Pick up Drop off
Resistance voltage voltage

B27RY 3.09 M Ω 31.9VAC 18.37VAC


B27YBX 5.11 k Ω 47.3Vdc 11.73Vdc

06 Contact Resistances: 0.51Ω


07 Functional checks:
Correct operation of contacts: OK
Correct operation of appropriate indicator/flag: OK
Correct initiation of scheme function: OK
08 Remarks: Relay Operation Found Satisfactorily

Tested By Checked By
Auxiliary relay (VAA-11)
Date: 19/06/15
01. Designation Auxiliary relay
Location: 541-LC3/541 CB 16
02. Name plate Details:
Make: EE Serial No: M272758
Type: VAA-11 Model: VAA11YF189A
Aux.Voltage: 110VDC
03. General Inspection as per Checklist: OK
04. Insulation Resistance Test:
All Terminals to Body: >100M ohm
Between terminals: >100M ohm
05. Pick up/Drop off Test:

Unit Coil Pick up Drop off


Resistance voltage voltage

52X 5.76 k Ω 72V 42V

06 Contact Resistances: 0.57 Ω


07 Functional checks:
Correct operation of contacts: OK
Correct operation of appropriate indicator/flag: OK
Correct initiation of scheme function: OK
08 Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By


Auxiliary relay (VAA-11)
Date: 19/06/15
01. Designation Auxiliary relay
Location: 541-LC3/541 CB 16
02. Name plate Details:
Make: EE Serial No: M763405
Type: VAA-11 Model: VAA11YF50A
Aux.Voltage: 110VDC
03. General Inspection as per Checklist: OK
04. Insulation Resistance Test:
All Terminals to Body: >100M ohm
Between terminals: >100M ohm
05. Pick up/Drop off Test:

Unit Coil Pick up Drop off


Resistance voltage voltage

52Y 5.78 k Ω 71V 37V

06 .Contact Pressure Check: 25 gms Contact Resistances: 0.57 Ω


07 Functional checks:
Correct operation of contacts: OK
Correct operation of appropriate indicator/flag: OK
Correct initiation of scheme function: OK
08 Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By


Auxiliary relay (VAA-11)
Date: 19/06/15
01. Designation Auxiliary relay
Location: 541-LC3/541 CB 16
02. Name plate Details:
Make: EE Serial No: M272778
Type: VAA-11 Model: VAA11YF189A
Aux.Voltage: 110VDC
03. General Inspection as per Checklist: OK
04. Insulation Resistance Test:
All Terminals to Body: >100M ohm
Between terminals: >100M ohm
05. Pick up/Drop off Test:

Unit Coil Pick up Drop off


Resistance voltage voltage

52Z 5.98 k Ω 71V 51V

06 .Contact Pressure Check: 25 gms Contact Resistances: 0.57 Ω


07 Functional checks:
Correct operation of contacts: OK
Correct operation of appropriate indicator/flag: OK
Correct initiation of scheme function: OK
08 Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By


Lock Out relay (VAJH-23)
Date: 19/06/15
01. Designation: Lock Out relay
Location: 541 CB 16/ 541 LC-3.
02. Name plate Details:
Make: EE Serial No: M272599
Type: VAJH-23 Model: VAJH23BF8019B (M).
Aux.Voltage: 110Vdc
3. General Inspection as per Checklist: OK
4. Insulation Resistance Test:
All Terminals to Body: >200M Ω
Between terminals: >200M Ω
05. Pick up/Drop off Test
: Ref Coil Pick up Drop off
Resistance voltage voltage

86-B 81.5Ω 33V HR


86-C 82.5 Ω 37V HR
06 .Contact Pressure Check: 23 gms Contact Resistances: 0.51 Ω
07 Functional checks:

Correct operation of contacts: OK


Correct operation of appropriate indicator/flag: OK
Correct initiation of scheme function: OK
08 Remarks: Relay Operation Found Satisfactorily

Tested By: Checked By


UNDER VOLTAGE RELAY (VAG21)
Date: 19/06/15
1. Designation: Under Voltage Relay
Location: 541-LC3/541 CB-16
02. Name plate Details:
Make: EE Serial No: M 272583.
Type: VAG-21 Model: VAG21ZG8190G (M)
Aux.Voltage: 110VDC
3. General Inspection as per Checklist: OK
4. Insulation Resistance Test:
All Terminals to Body: >200M ohm
Between terminals: >200M ohm
05. Pick up/Drop off Test
: Unit Coil Pick up Drop off
Resistance voltage voltage

B27RY 3.23 M Ω 87VAC 20.3VAC


B27RYX 5.17 k Ω 41Vdc 8Vdc

06 .Contact Pressure Check: 23 gms Contact Resistances: 0.51Ω


07 Functional checks:
Correct operation of contacts: OK

Correct operation of appropriate indicator/flag: OK


Correct initiation of scheme function: OK
08 Remarks: Relay Operation Found Satisfactorily

Tested By Checked By
UNDER VOLTAGE RELAY (VAG21)
Date: 19/06/15
1. Designation: Under Voltage Relay
Location: 541-LC3/541 CB-16
02. Name plate Details:
Make: EE Serial No: M 272586.
Type: VAG-21 Model: VAG21ZG8190G (M)
Aux.Voltage: 110VDC
3. General Inspection as per Checklist: OK
4. Insulation Resistance Test:
All Terminals to Body: >200M ohm
Between terminals: >200M ohm
05. Pick up/Drop off Test:
Unit Coil Pick up Drop off
Resistance voltage voltage

B27YB 3.18 M Ω 77.5VAC 19.55VAC


B27YBX 5.31 k Ω 57Vdc 13Vdc

06 .Contact Pressure Check: 23 gms Contact Resistances: 0.51Ω


07 Functional checks:
Correct operation of contacts: OK

Correct operation of appropriate indicator/flag: OK


Correct initiation of scheme function: OK
08 Remarks: Relay Operation Found Satisfactorily

Tested By Checked By