Sunteți pe pagina 1din 2

IT. NEMA vs.

IEC
Application Note

Rating Methods rated operational current (Ie), rated AC-3


insulation voltage (Ui), rated operational
voltage (Ue), and the IEC Standard to Utilization Category AC-3 is typical for
There are two basic rating methods
which the device was tested. most common applications utilizing
in common use in the Americas for
a standard squirrel cage induction
Contactors and Starters — NEMA and
motor. The Contactor or Starter is
IEC. They differ significantly in their
requirements for design and test.
NEMA Rating closed to line start the motor, and then
opened while the motor is running to
The size rating applied to a Contactor stop it. Opening the Contactor while
NEMA or Starter is specified by NEMA Stan- the motor is running reduces the cur-
NEMA Contactors and Starters are dards. The standards require the rent the Contactor has to break to the
designed in standardized sizes from 00 device to be designed with sufficient motor’s full load value. Under this con-
to 9. Each of these sizes has a defined margins to allow its use, in the major- dition only a low voltage is developed
current, and a resultant voltage and ity of applications, without the need of across the contacts as a result of the
frequency dependent horsepower rat- assessing the impact of the application small difference between the motor’s
ing. No matter who manufactures the on the device’s operational life. The back EMF voltage and the line voltage.
device, the current and horsepower capabilities are independent of who Many manufacturers are also combin-
rating will be identical for a given size. manufactured the device. ing a lesser used AC-2 slip ring motor
If a standard motor is being used, once starting and stopping Utilization Cate-
its horsepower rating is selected, the Normal Duty gory with AC-3.
Contactor or Starter horsepower rating Contactors and Starters are typically
is simply matched to that of the motor. used in applications where a motor is AC-4
The nameplate of the Contactor or periodically started at zero speed or Utilization Category AC-4 typically also
Starter is labeled with the NEMA size, stopped while running at full speed applies to standard induction motors,
the various horsepower and voltage with a relatively long run or off time. but in this case the start and stop actions
ratings assigned to the size, and its The device is primarily only required to are more severe. The Contactor or
continuous current capability at which make locked rotor current and break Starter makes into the locked rotor cur-
the NEMA Standard temperature rise full load current. A jog may occur to set rent of the motor, but can be opened
will not be exceeded. up a machine, but it is very infrequent. while the locked rotor current is still
flowing, with a large voltage present
IEC Plugging or Jogging Duty across the contacts, because the motor’s
Contactors and Starters can be used back EMF voltage is still low while start-
IEC Contactors and Starters are not ing. The combination of high current
designed to a standardized size. Instead on applications which have a high
occurrence of plugging or jogging, and voltage significantly reduces the life
a manufacturer certifies that he/she has of the contacts. Typical applications
designed the device to meet a number where a current in excess of locked
rotor can be made and locked rotor require jogging or plugging. Plugging
of defined applications referred to as duty can be more severe because the
Utilization Categories. To properly current broken. The Contactor or
Starter will have a lower rating for this motor is rotating in the reverse direction
match the IEC Contactor or Starter to when one Contactor is opened and a
the application requirements, the user type of duty than it would for a more
normal duty application. second closed, potentially causing a
must know both the application require- much larger current to flow for a longer
ments and the capability of the Contac- time period. If a Contactor or Starter
tor or Starter being selected. If the IEC Utilization Categories carries both an AC-3 and AC-4 rating,
Contactor or Starter will not provide the AC-4 operating life is usually a
a reasonable operational life in the A Contactor or Starter as specified fraction of the AC-3 value.
application, a larger device would under IEC Standards is designed for a
need to be selected. particular grouping of Utilization Cate-
gories. As such, the device’s opera-
The nameplate of the Contactor or tional life is dependent upon the load
Starter is labeled with the maximum requirements with regards to the
rating in kilowatts or horsepower for design Utilization Category. The two
each operational voltage and specific most common Utilization Categories
Utilization Category (typically AC-3 as for motor control are AC-3 and AC-4.
defined), rated thermal current (Ith),

AP03501001E For more information visit: www.cutler-hammer.eaton.com


Application Note IT. NEMA vs. IEC
Page 2 Effective: February 2002

NEMA and IEC Additional Comparisons


Ratings Comparison The following table summarizes the key differences between NEMA and IEC devices.
NEMA Contactors and Starters can be
Table 1. NEMA and IEC devices
applied to AC-3 applications. They may
also be applied at their normal stan- Characteristic NEMA IEC
dardized ratings to AC-4 applications Rated by Horsepower Manufacturer determined current
where there will be no more than five and Utilization Category (AC-1, AC-2,
openings per minute and no more than AC-3, AC-4…)
10 openings during a 10-minute Size — Electrical Standardized — 00 to 9 No standard
period. Beyond this level, NEMA pro- Jogging/Plugging Standard product has some Must use higher Utilization rating and
vides a plug reversing and jogging capability possibly increased current rating
duty table with modified ratings for Interchangeability Meets AC-3 and limited AC-4 Many do not meet NEMA
improved operating life. Many IEC operation requirements
devices also have a NEMA rating. The Fault Current Meets NEC requirements Usually has lesser fault current
manufacturer can advise on this. withstand
Mounting Dimensions not standardized Below 20 hp equivalent, standard
Other Factors DIN rail mounting is typical
Terminal Markings L1, L2, L3 and T1, T2, T3 1, 3, 5 and 2, 4, 6
The operational life of a Contactor or Power — In/Out No standard A1, A2, A3, B1, B2
Coil No standard Two digits, first digit for sequence,
Starter may be affected by other fac-
Control second digit for type of contact:
tors not controllable by the manufac- 1-2 for normally closed and 3-4 for
turer and independent of whether the normally open
device was designed per NEMA or
IEC standards. These factors include
such items as temperature, altitude, References
vibration, shock, humidity, and envi-
ronmental issues such as dust, dirt For a more detailed discussion of the differences between NEMA and IEC devices,
or corrosive chemicals. refer to NEMA Standard ICS 2.4 available as a free download at the NEMA website
at www.nema.org.

Eaton Corporation
Cutler-Hammer business unit
1000 Cherrington Parkway
Moon Township, PA 15108-4312
USA
tel: 1-800-525-2000
www.cutler-hammer.eaton.com

© 2002 Eaton Corporation


All Rights Reserved
Printed in USA
Publication No. AP03501001E
February 2002

S-ar putea să vă placă și