Service Manual
Residential A/Cs
CONTENTS
1. DIAGNOSTIC CHART 1
3. MAS 8
4. MES 45
5. CES/CED/CEM 65
6. G E S 97
7. G I S 115
8. LIS 127
9. CUS 139
Please find CAS, CAD, CAM (R or I), CMP, etc.. in separate papers!
Diagnostic Chart(5000Btu/h-12000Btu/h)
1. Self-diagnose the failure
COOLWEX units have self-diagnose function.
Note: for the following series
CES
CED
CEM
2. After energizing, no indicator is lighted and the air conditioner can’t be operated.
Yes
Yes No
No Yes
No
No Yes
After changing indoor fan motor, check if the failure releases. Indoor PCB is defective
No
Power supply circuit has problems.
1
4. Failure phenomenon for cooling only type
Failure phenomenon Operation lamp Timer lamp
Indoor fan speed has been out of control for over 1 minute ☆ X
Indoor room temp. or evaporator sensor is open circuit or short circuit ☆ On
Over current protection of the compressor occurs 4 times X ☆
EEPROM error On ☆
r Extinguish
☆ Flash at 5Hz
4.1 Operation lamp flashes and Timer lamp off.
Yes
yes No
Replace the sensor Repair connector
After changing the main control board, check if the failure releases.
No Yes
The voltage of power supply is too low (less than 187V)? Indoor PCB is defective
Yes No
2
5. Failure phenomenon(heat pump)
Failure phenomenon Operation lamp Timer lamp Defrosting lamp
Over current protection of the compressor occurs 4
☆ X ☆
times
Indoor fan speed has been out of control for over 1
X ☆ ☆
minute
No over-zero signal ☆ ☆ ☆
Temp. sensor on indoor evaporator is open circuit or
X X ☆
short circuit
Indoor room temp. sensor is open circuit or short circuit X ☆ X
EEPROM error On ☆ X
r Extinguish
☆ Flash at 5Hz
5.1 Operation lamp flashes ,Timer lamp off and Defrosting lamp flashes.
Operation lamp flashes ,Timer lamp off and Defrosting lamp flashes
After changing the main control board, check if the failure releases.
No Yes
The voltage of power supply is too low (less than 187V)? Indoor PCB is defective
Yes No
5.2 Operation lamp off, Timer lamp flashes and Defrosting lamp flashes.
Yes No
5.3 Operation lamp flashes, Timer lamp flashes and Defrosting lamp flashes .
This is alarm signal when the main chip can’t detect over-zero signal. When such
failure occurs, the main control board must have fault.
3
Operation lamp flashes and Timer lamp off.
Yes
5.4 Operation lamp off ,Timer lamp off and Defrosting lamp flashes.
yes No
5.5 Operation lamp off, Timer lamp flashes and Defrosting lamp off
yes No
5.6 Operation lamp on, Timer lamp flashes and Defrosting lamp off
EEPROM error, main PCB has fault.
Temporarily turn off the power supply and turn it on again in about 1 minutes
Yes
4
The service rules of the R407C product
The service rules of the R410A product
1. The service rules of the new refrigerant R407C product
COOLWEX uses the green refrigerant R407C firstly in China.
Its thermal characters are similar to R22, but there is little difference between them.
1.1 The main difference between R407C and R22:
R407C R22
Component HFC32/125/134a HCFC22
The ratio of mix Wt% 23/25/52 100
The saturation liquid density Kg/m3 1136 1191
Specific heat Normal pressure kj/kg.k 0.835 0.622
The saturation liquid kj/kg.k 1.554 1.256
Evaporating pressure kpa 499 498
Condensing pressure kpa 2112 1943
Temperature slippage ℃ 4.3-7.1 0
Heating capacity w 92-97 100
Input power w 106 100
COP 97 100
The consistent with the oil Fat oil Mineral oil
5
about 30 minutes, and vacuity is less than 133Pa.
1.3 Precautions:
1.3.1 Regulations
Being liquefied vapor, R-407C and R-410A are high-pressure vapor, the high-pressure gas regulation is
applicable. Before use it, please refer to high-pressure gas regulation. To prevent the high-pressure
vapor from causing damage, the regulation should be followed.
1.3.2 Usage of vessel
Being high-pressure vapor, R-407C and R-410A are contained in high-pressure vessel. The
safety condition of vessel is good, but if you don’t use it carefully, you may damage the vessel
and cause accident.
1.3.3 Storage
Although R-407C and R-410A are nonflammable, when they are stored with the normal
high-pressure gas, we should place them in the good ventilation area.
In addition, there are safe devices in the high-pressure vessel. Please note that when the
temperature (fusible valve) or pressure (spring safe valve) is up to a certain value, it will eject
vapor.
1.3.4 Ventilation
Because R-407C and R-410A are heavier then air, they will go down. If room is full of the
leakage vapor, the density of oxygen will decrease, and cause people suffocated.
In addition, if you light the fire when there is R-407C in the air, it will produce the toxic gas with
pungent odor and corrosiveness.
1.3.5 Precautions about health
For R-407C, R-410A and normal liquefied high-pressure vapor, please don’t contact with skin
directly, and prevent being splashed into eyes and avoid drinking.
1.3.6 The following are the urgent disposal methods:
Splash into eyes:
Wash eyes with pure water for more than 15 minutes, and don’t knead the eyes or blink.
Please wash eyes with watery boric acid water if the ache gets heavy.
To avoid the accident, please ensure that you wear the protection glasses.
Contact with skin directly
The temperature will decrease rapidly by evaporation if R-407C and R-410A expose to air in
liquid phase. So if the liquid contacts with skin directly, it may cause frostbite. If there are freeze
burns, please go to see the doctor immediately.
7
CES, CED & CEM
1. Features 66
2. Specification 67
3. Dimensions 73
5. Operation limits 78
6. Wiring diagram 79
7. Troubleshooting 86
8. Electronic function 86
1.Features
1.1 Compact design
1.2 High efficiency and quiet operation
66
2.Specification
Model CES-05.R.....................CES-07.R.........................CES-07.RC...................CES-09.R....................CES-09.RC
Starting current A 16 18 18 25 25
Capacitor uF 15 25 25 25 25
Refrigerant oil ml MS-56 270 ATOMOS M60 270 ATOMOS M60 270 SUNISO 350 SUNISO 350
Speed(hi/mi/lo) r/min 1020/ 960/ 900 1020/ 960/ 900 1020/ 960/ 900 1100/1020/950 1100/1020/950
Indoor air flow (Hi/Mi/Lo) m3/h 300/270/240 380/350/320 380/350/320 450/420/390 450/420/390
Indoor noise level (Hi/Mi/Lo) dB(A) 32/28/25 32/28/25 32/28/25 33/31/27 33/31/27
Capacitor uF 3 3 3 3 3
Liquid side/ Gas side mm(inch) Ф6.35/Ф9.53 Ф6.35/Ф9.53 Ф6.35/Ф9.53 Ф6.35/Ф9.53 Ф6.35/Ф9.53
Refrigerant piping Max. refrigerant pipe length m 10 10 10 10 10
Connection wiring No No No No No
Thermostat type Electronic control Electronic control Electronic control Electronic control Electronic control
★1 The noise date is base on anechoic chamber, during actual operation, these values are normally somewhat different as a result of ambient condition.
67
Model CES-12.RC CES-12.R CES-18.RC CES-18.R
Capacitor uF 25 35 35 35
Input W 70 70 96 96
Outdoor fan motor
Capacitor uF 2.5 2.5 2.5µF/450V 2.5µF/450V
★1 The noise date is base on anechoic chamber, during actual operation, these values are normally somewhat different as a result of ambient condition.
68
Model C ES-21 .R C C E S-21 .R
Power supply Ph-V-Hz 220-240V~,50Hz 220-240V~,50Hz
Capacity Btu/h 21000 21000
Input W 2300 2300
Cooling
Rated current A 10.5 10.5
EER Btu/w.h 9.1 9.1
Capacity Btu/h 23500
Input W 2400
Heating
Rated current A 11.0
COP w/w 2.9
Moisture Removal L/h 2.0 2.0
Max. input consumption W 2500 2600
Max. current A 11.3 14.5
Starting current A 42 42
Model 2V36S225AUD 2V36S225AUD
Type rotary rotary
Capacity Btu/h 20600 20600
Input W 2010 2010
Compressor Rated current(RLA) A 9。5 9。5
Locked rotor Amp(LRA) A 42 42
Thermal protector INNER INNER
Capacitor uF 50 50
Refrigerant oil ml 680 680
Model RPG25 RPG25
Brand WELLING WELLING
Indoor fan motor Input W 53 53
Capacitor uF 1.5uF/450V 1.5uF/450V
Speed(hi/mi/lo) r/min 1325 1325
Indoor air flow (Hi/Mi/Lo) m3/h 920\760\700 920\760\700
Indoor noise level (Hi/Mi/Lo) dB(A) 41/37/33 41/37/33
Dimension (W*H*D) mm 906×286×235 906×286×235
Indoor unit Packing (W*H*D) mm 1020X380X328 1020X380X328
Net/Gross weight Kg 13.5/16.5 13.5/16.5
Model YDK53-6 YDK53-6
Input W 100 100
Outdoor fan motor
Capacitor uF 2.5μF/450V 2.5μF/450V
Speed r/min 640 640
Outdoor air flow m3/h 2600 2600
Outdoor noise level dB(A) 53 53
Dimension(W*H*D) mm 845×695×335 845×695×335
Outdoor unit Packing (W*H*D) mm 970×770×395 970×770×395
Net/Gross weight Kg 52/57 55/60
Refrigerant type R22 g 1220 1740
Design pressure MPa 2.6 2.6
Liquid side/ Gas side mm(inch) Ф6.35/Ф12.7 Ф6.35/Ф12.7
Refrigerant piping Max. refrigerant pipe length m 15 15
Max. difference in level m 8 8
Thermostat type Electronic control Electronic control
Operation temp ℃ 17-30 17-30
Ambient temp ℃ 10-43 (-5~43)
Application area m2 34-49 34-49
★1 The noise date is base on anechoic chamber, during actual operation, these values are normally somewhat different as a result of ambient condition.
69
Comfort
Model CES-07_R7______________CES-07_R7C____________CES-09_R7_________CES-09_R7C
Power supply Ph-V-Hz 220-240V~,50Hz 220-240V~,50Hz 220-240V~,50Hz 220-240V~,50Hz
Capacity Btu/h 7000 7000 9000 9000
Input W 800 800 1050 1050
Cooling
Rated current A 3.5 3.5 4.6 4.6
EER Btu/w.h 8.8 8.8 8.6 8.6
Capacity Btu/h 8500 10000
Input W 880 1050
Heating
Rated current A 4 4.6
COP w/w 2.9 2.93
Moisture Removal L/h 0.6 0.6 0.8 0.8
Max. input consumption W 1000 1000 1330 1330
Max. current A 4.4 4.4 6 6
Model PG135X1C-4DZ2 PG135X1C-4DZ2 PG180X1C-4DZ3 PG180X1C-4DZ3
Type Rotary Rotary Rotary Rotary
Brand TOSHIBA TOSHIBA TOSHIBA TOSHIBA
Capacity Btu/h 8086/8172 8086/8172 10800 10800
Input W 765/785 765/785 1015 1015
Compressor
Rated current(RLA) A 3.52/3.34 3.52/3.34 4.5 4.5
Locked rotor Amp(LRA) A
Thermal protector UP3SE0591-T71 UP3SE0591-T71 UP3SE0591-T61 UP3SE0591-T61
Capacitor uF 25 25 30 30
Refrigerant oil ml 400 400 400 400
Model RPG13H RPG13H RPG13H RPG13H
Input W 36.5 37.5 38.5 39.5
Indoor fan motor
Capacitor uF 1.2 1.2 1.2 1.2
Speed(hi/mi/lo) r/min 1020/960/900 1020/960/900 1100/1020/950 1100/1020/950
Indoor air flow (Hi/Mi/Lo) m3/h 430/400/370 430/400/370 470/440/410 470/440/410
Indoor noise level (Hi/Mi/Lo) dB(A) 35/32/30 35/32/30 36/32/30 36/32/30
Dimension (W*H*D) mm 750×250×188 750×250×188 750×250×188 750×250×188
Indoor unit Packing (W*H*D) mm 830×336×280 830×336×280 830×336×280 830×336×280
Net/Gross weight Kg 8.5/10.5 8.5/10.5 8.5/10.5 8.5/10.5
Model YDK24-6T YDK24-6T YDK24-6T YDK24-6T
Outdoor fan
Input W 70 70 70 70
motor Capacitor uF 3 3 3 3
Speed r/min 850 850 850 850
Outdoor air flow m3/h 1600 1600 1900 1600
Outdoor noise level dB(A) 49 49 49 49
Dimension(W*H*D) mm 700X535X235 700X535X235 700X535X235 700X535X235
Outdoor unit Packing (W*H*D) mm 815X580X325 815X580X325 815X580X325 815X580X325
Net/Gross weight Kg 30/33 29/32 29/32 30/33
Refrigerant type R407C g 740 650 840 770
Design pressure MPa 2.8 2.8 2.8 2.8
Refrigerant Liquid side/ Gas side mm(inch Ф6.35/Ф9.53 Ф6.35/Ф9.53 Ф6.35/Ф9.53 Ф6.35/Ф9.53
Max. refrigerant pipe length m 10 10 10 10
piping
Max. difference in level m 5 5 5 5
Operation temp ℃ 17 30 17 30 17 30 17 30
Ambient temp ℃ -7-45 18-45 -7-45 18-45
Application area m2 10-14 10-14 14-21 14-21
★1 The noise date is base on anechoic chamber, during actual operation, these values are normally somewhat different as a result of ambient condition.
70
Model CES-12_R7C____________________________CES-12_R7
Input W 1360
Heating
Rated current A 6
Starting current A
Thermal protector
Capacitor uF 35 35
Input W 85 85
Outdoor fan motor
Capacitor uF 2.5 2.5
Speed r/min 900 900
★1 The noise date is base on anechoic chamber, during actual operation, these values are normally somewhat different as a result of ambient condition.
71
Comfort
Model CES-07_R7______________CES-07_R7C____________CES-09_R7________CES-09_R7C
Power supply Ph-V-Hz 220-240V~,50Hz 220-240V~,50Hz 220-240V~,50Hz 220-240V~,50Hz
Capacity Btu/h 7000 7000 9000 9000
Input W 800 800 1050 1050
Cooling
Rated current A 3.5 3.5 4.6 4.6
EER Btu/w.h 8.8 8.8 8.6 8.6
Capacity Btu/h 8500 10000
Input W 880 1050
Heating
Rated current A 4 4.6
COP w/w 2.9 2.93
Moisture Removal L/h 0.6 0.6 0.8 0.8
Max. input consumption W 1000 1000 1330 1330
Max. current A 4.4 4.4 6 6
Model PG135X1C-4DZ2 PG135X1C-4DZ2 PG180X1C-4DZ3 PG180X1C-4DZ3
Type Rotary Rotary Rotary Rotary
Brand TOSHIBA TOSHIBA TOSHIBA TOSHIBA
Capacity Btu/h 8086/8172 8086/8172 10800 10800
Input W 765/785 765/785 1015 1015
Compressor
Rated current(RLA) A 3.52/3.34 3.52/3.34 4.5 4.5
Locked rotor Amp(LRA) A
Thermal protector UP3SE0591-T71 UP3SE0591-T71 UP3SE0591-T61 UP3SE0591-T61
Capacitor uF 25 25 30 30
Refrigerant oil ml 400 400 400 400
Model RPG13H RPG13H RPG13H RPG13H
Input W 36.5 37.5 38.5 39.5
Indoor fan motor
Capacitor uF 1.2 1.2 1.2 1.2
Speed(hi/mi/lo) r/min 1020/960/900 1020/960/900 1100/1020/950 1100/1020/950
Indoor air flow (Hi/Mi/Lo) m3/h 430/400/370 430/400/370 470/440/410 470/440/410
Indoor noise level (Hi/Mi/Lo) dB(A) 35/32/30 35/32/30 36/32/30 36/32/30
Dimension (W*H*D) mm 750×250×188 750×250×188 750×250×188 750×250×188
Indoor unit Packing (W*H*D) mm 830×336×280 830×336×280 830×336×280 830×336×280
Net/Gross weight Kg 8.5/10.5 8.5/10.5 8.5/10.5 8.5/10.5
Model YDK24-6T YDK24-6T YDK24-6T YDK24-6T
Outdoor fan
Input W 70 70 70 70
motor Capacitor uF 3 3 3 3
Speed r/min 850 850 850 850
Outdoor air flow m3/h 1600 1600 1900 1600
Outdoor noise level dB(A) 49 49 49 49
Dimension(W*H*D) mm 700X535X235 700X535X235 700X535X235 700X535X235
Outdoor unit Packing (W*H*D) mm 815X580X325 815X580X325 815X580X325 815X580X325
Net/Gross weight Kg 30/33 29/32 29/32 30/33
Refrigerant type R407C g 740 650 840 770
Design pressure MPa 2.8 2.8 2.8 2.8
Refrigerant Liquid side/ Gas side mm(inch Ф6.35/Ф9.53 Ф6.35/Ф9.53 Ф6.35/Ф9.53 Ф6.35/Ф9.53
Max. refrigerant pipe length m 10 10 10 10
piping
Max. difference in level m 5 5 5 5
Operation temp ℃ 17 30 17 30 17 30 17 30
Ambient temp ℃ -7-45 18-45 -7-45 18-45
Application area m2 10-14 10-14 14-21 14-21
★1 The noise date is base on anechoic chamber, during actual operation, these values are normally somewhat different as a result of ambient condition.
70
3.Dimensions
3.1 Indoor unit
CES-05/07/09_R(7)(C),CES-12_R(7)(C)
73
3.3 Indoor unit CES-18/21_R(7)(C))
74
3.5 Outdoor unit CES-12_R(7)(C) & CES-18_R(7)(C)
750
285
590
62
315
290
530 110
75
3.7 Outdoor unit CES-21_R(7)(C)
12.5
76
4.Refrigeration cycle diagram
4.1 Cooling/heating
Indoor unit outdoor unit
Valve
. 4 way valve
Compressor
Valve Capillary
Valve
Compressor
Valve Capillary
77
5.Operation limits
5.1Cooling operation
Outdoor unit air temp.℃ DB
45
40 DRY COOLING
35
30
25
20
10 15 20 25 30 35 40
Indoor air temp. ℃ DB
Note : The chart is the result from the continuous operation under constant air temperature
conditions. However, excludes the initial pull-down stage.
5.2Heating operation
Indoor air temp. ℃ DB
30
25
20
15
10
-5 5 15 25
Outdoor unit air temp.℃ DB
Note : The chart is the result from the continuous operation under constant air
temperature conditions. However, excludes the initial pull-down stage.
78
6.Wiring diagram
6.1 Cooling only
6.1.1 CES-05_R(7)(C) Indoor unit
POWER SUPPLY
INDOOR UNIT
O
U
T
D
O
O
R
U
N
I
T
1
2
(
N
)
Y&G
B
L
A
C
K
B
L
A
C
K
O
VR
EE
RL
LA
OY
A
D
R
E
D
R
E
D
B
L
A R
C E
K D
C
O
M
P
R
E
S
S
O
R
C
FM
AO
NT
R
E
D
O
R
R
Y&G
S
Y&G
B
L
U
E
B
L
U
E
COMPRESSOR FAN
CAPACITOR CAPACITOR
79
6.1.2 CES-07_R(7)(C) & CES-09_R(7)(C)
POWER SUPPLY
INDOOR UNIT
O
U
T
D
O
O
R
U
N
I
T
1
2
(
N
)
Y&G
B
L
A
C
K
B
L
A
C
K
O
V
ER
R
LL
O
AY
D
E
A
R
E
D
R
E
D
B
L
A
C
K
C
O
M
P
R
E
S
S
O
R
C
R
E
D
F
AO
NT
R
E
D
M
O
R
R
Y&G
S
Y&G
B
L
U
E
B
L
U
E
COMPRESSOR FAN
CAPACITOR CAPACITOR
80
6.1.3 CES-12_R(7)(C) Indoor unit (A Type)
POWER SUPPLY
INDOOR UNIT
O
U
T
D
O
O
R
U
N
I
T
1
2
(
N
)
Y&G
B
L
A
C
K
B
L
A
C
K
O
VR
E
RE
L
O
AY
D
L
A
R
E
D
R
E
D
B
L
A
C
K
C
O
M
P
R
E
S
S
O
R
C
R
E
D
FM
A
NT
R
E
D
O
O
R
R
Y&G
S
Y&G
B
L
U
E
B
L
U
E
COMPRESSOR FAN
CAPACITOR CAPACITOR
81
CAPACITOR
D
E
FAN
R D
E
Y&G
K
C R E
A U
L
L NTR
O B
B
82
A
F O
M
)
N
Y&G
(
2 D
E
R
COMPRESSOR
1
CAPACITOR
K
C
A
L
B D
K E E
C R R U
T A L
6.1.4 CES-12_R(7)(C) (B Type)
I L B
B
INDOOR UNIT
N
U D
A C S
R
O O Y R
O L A
L O
D R
E E S
T R S
Y&G
U V
O E
O R
P
M
O
C
6.1.5 CES-18_R7(C) & CES-21_R7(C)
BLUE
WHITE
BROWN
SWITCH BOARD
CN14
CN9 CN4
CN2
CURRENT DETECTOR
DISPLAY BOARD
CN12
CN1
CN6 CN5
BLACK
WHITE
CN8 CN7 CN10
AMBIENT SENSOR
HEAT EXCHANGER
LOUVER MOTOR
LOUVER MOTOR
SENSOR
INDOOR MOTOR
INDOOR UNIT
O
U
T
D
O
O
R
U
N
I
T
1
2
(
N
)
Y&G
B
L
A
C
K
B
L
A
C
K
O
V
E
R
L
O
A
D
R
E
L
A
Y
R
E
D
R
E
D
B
L
A
C
K
C
O
M
P
R
E
S
S
O
R
C
R
E
D
F
A
NT
R
E
D
M
O
O
R
R
Y&G
S
Y&G
B
L
U
E
B
L
U
E
COMPRESSOR FAN
CAPACITOR CAPACITOR
83
6.2 Heating/cooling
6.2.1 CES-07_R(7),CES-09_R(7) & CESG-09HRN2,
84
6.2.2 CES-12_R7(B TYPE) & CES-12_R7
85
6.2.3 CES-18_R(7) & CES-21_R(7)
BLUE
WHITE
BROWN
SWITCH BOARD
CN14
CN9 CN4
CN2
CURRENT DETECTOR
DISPLAY BOARD
CN12
CN1
YELLOW
CN6 CN5
GREEN
BLACK
WHITE
CN8 CN7 CN3 CN10
AMBIENT SENSOR
HEAT EXCHANGER
LOUVER MOTOR
LOUVER MOTOR
SENSOR
INDOOR MOTOR
86
7.Troubleshooting
7.1 For all cooling only model
Failure phenomenon Operation lamp Timer lamp
Indoor fan speed has been out of control for over 1 minute ☆ X
EEPROM error On ☆
No over-zero signal ☆ ☆
r Extinguish
☆ Flash at 5Hz
7.2 For all heat pump model
Failure phenomenon Operation lamp Timer lamp Defrosting lamp
Indoor fan speed has been out of control for over 1 minute X ☆ ☆
No over-zero signal ☆ ☆ ☆
EEPROM error On ☆ X
r Extinguish
☆ Flash at 5Hz
8 Electronic function
8.1 Electric Control working environment
8.1.1 input voltage: 175~253V
8.1.2 Input power frequency:50Hz
8.1.3 Ambient temperature: -7°C~+43°C
8.1.4 Indoor fan normal working amp is less than 1A,
8.1.5 Outdoor fan. Normal working amp is less than 1.5A
8.1.6 Four-way valve normal working amp is less than 1A.
8.1.7 Swing motor: DC12V.
8.1.8 Compressor: single-phase power supply. Its normal working amp is less than 15A
8.2 Proper symbols and their meanings:
TA: Indoor ambient temperature
TE: Indoor evaporator temperature
TS: Setting temperature through the remote controller
I3sec: Self-protection amp of compressor, continue three seconds until turns off the compressor.
I5MIN: Self-protection amp of compressor, continue five minutes until turns off the compressor.
IFAN: Self-protection amp of outdoor fan/indoor fans when they change from higher wind to lower wind.
IRESTORE: Amp self-protection return value
THDEFROST: High wind, defrosting temperature difference
TMDEFROST: Middle wind, defrosting temperature difference
TLDEFROST: Low wind, defrosting temperature difference
TE1: Anti-cold wind, from Fan Off to Breeze temperature
87
TE2: Anti-cold wind, from Breeze to Setting Fan Speed temperature
TE3: Anti-cold wind, from Setting Fan Speed to Breeze temperature
TE4: Anti-cold wind, from Breeze to Fan Off temperature
TE5: Evaporator low temperature protection entering temperature
TE6: Evaporator low temperature protection restoring temperature
TE7: Evaporator high temperature protection, compressor off temperature
TE8: Evaporator high temperature protection, fan off temperature
TE9: Evaporator high temperature protection, restoring temperature
I< IRESTORE On On On
If compressor turns off for continuously 4 times due to current protection in 5 minutes from
Compressor On, the unit stops and LED displays failure information and can’t returns to normal
operation automatically.
88
8.5 Fan-only mode
Fan speed is high/mid/low/ Auto
8.6 Cooling mode
The 4-way valve is closed at cooling mode.
The action of the compressor and the outdoor fan:
Condition Compressor Outdoor fan
Temp. up T> Ts+1 On On
T<Ts+1 Off Off
Temp. down T> Ts On On
T<Ts Off Off
89
8.7.3 Low room temperature protection:
When room temperature decreases to below 10℃, compressor and outdoor fan will stop(indoor fan
is Breeze). Dehumidifying operation will be resumed when room temperature restores to over 13℃.
8.7.4 At dehumidifying mode, the anti-freezing function of the indoor heat exchanger is the same as that
of cooling mode.
8.8 Heating mode
8.8.1 Generally, the 4-way valve is open in heating mode, but it is closed in defrosting mode. 4-way valve
must delay 2 minutes compared with compressor if the compressor changed into non-heating mode
or turned off. 4-way valve doesn't delay in dehumidifying mode.
8.8.2 Generally, the outdoor fan is turned off with the on-off action of compressor in heating mode, except
for the defrosting mode or the end of defrost.
8.8.3 Action of compressor and outdoor fan motor at heating mode: compressor must run for 7 minutes
after starting and then judge temperature. Meanwhile other protections are still valid.
Condition Compressor Outdoor fan
T<Ts+3 On On
TE1<T<TE2 Breeze
TE3<T<TE4 Breeze
T<TE4 Off
T>2℃ Med.
T<0℃ High
90
8.8.6 Indoor evaporator high-temperature protection at heating mode
Condition Compressor Outdoor fan
TE8<T<TE7 On Off
T<TE9 On On
② Calculate from the end of latest defrost, evaporator high temp. protection only closes outdoor fan
with the compressor still running. Add up to 90 minutes.
8.9.2 Defrosting time
If the temp. difference condition ① is satisfied for less than 40 minutes, this can be regarded as
severe frosting. The defrosting time is 10 minutes.
If the temp. difference condition ② is satisfied for more than 40 minutes, the defrosting time is 6
minutes.
If the temp. difference condition ① is satisfied out of 40 minutes, generally the defrosting time is 6
minutes, after three continuous 6-minute defrost, the fourth should be 10 minutes defrost. The
circulation is as following:
→6-minute defrost → 6-minute defrost→6-minute defrost→10-minute defrost→
91
8.9.4 Defrosting Actions:
45S 25S
Compressor
Indoor Fan
10S
8.9.7 Turn into heating mode, turn off the heating mode in 7 minutes.
TA—TS>2℃ Cooling
-1℃≤TA—TS≤+2℃ Fan-only
93
8.16 Models and Parameters
Model CES-07_RC CES-07_R CES-09_RC CES-09_R CES-12_RC CES-12_R
TE5 2℃ 2℃ 2℃ 2℃ 3℃ 3℃
TE6 7℃ 7℃ 7℃ 7℃ 8℃ 8℃
ANGLHEAT 0° 0° 0°
94
Model CES-07_R7C CES-07_R7 CES-09_R7C CES-09_R7
TE5 4℃ 4℃ 4℃ 4℃
ANGLHEAT 0° 0°
95
Model CES-12_RC CES-12_R* CES-18_R_C CES-18_R CES-21_RC CES-21_R
(B type) (B type)
CES-12_R7C______CES-12_R7________CES-18_R7C_______CES-18_R7_______CES-21_R7C_____CES-21_R7
TE5 2℃ 2℃ 3℃ 3℃ 3℃ 3℃
96
COOLWEX Group USA
[Models]
CES 7 I7
CES 7 I7
CES 12 I7
Contents
1. Features 2
2. Specification 3
3. Dimensions 4
5. Operation limits 7
6. Wiring diagram 8
7. Troubleshooting 10
8. Electronic function 11
1
1.Features
1.1 Powerful at cooling/heating, 1.3 times and 1.6 times relatively higher than normal same type of
models.
1.2 Low voltage start-up function, even at 160 V it can normally start.
1.3 Anti-icing function at cooling mode.
1.4 Anti-cold air function at heating mode.
1.5 Auto-defrosting and heating recovering function at heating mode.
1.6 Outdoor whole electric current protection
1.7 Temperature protection of the outdoor compressor top.
1.8 Restart protection for the compressor.
1.9 24 hours on/off mode time setting.
1.10 Error self diagnosis function.
1.11 Protection against over-load or too-low current inputted through alternating current.
2
2. Specification
Speed level 3 3 3
(outdoor)
Net weight kg 37 37 40
★1 The noise date is base on anechoic chamber, during actual operation, these values are normally somewhat different as a result of ambient
condition.
3
3. Dimensions
3.1 Indoor Unit
CES 12 I7
4
3.3 Outdoor Unit
5
4. Refrigeration Cycle Diagram
Valve
. 4 way valve
Sensor
Compressor
Valve Capillary
6
5. Operation Limits
50
40
30
20
10
10 17 25 30 35 40
Indoor air temp. ℃
Note :the chart is the result from the continuous operation under constant air temperature
conditions. however, excludes the initial pull-down stage.
5.2 Heating operation
Indoor air temp. ℃
30
20
10
-5
-15
-15 -5 5 15 25 30
Outdoor unit air temp.℃
Note :the chart is the result from the continuous operation under constant air
temperature conditions. however, excludes the initial pull-down stage.
7
6. Wiring Diagram
6.1 Indoor unit(CES 7 I7, CES 9 I7)
8
6.3 Outdoor unit (CES 7 I7 / CES 9 I7 / CES 12 I7)
S
L N
9
7.Troubleshooting
7.1 Indoor Unit Error Display Function
LED4 operation LED2 defrosting LED1 timer LED4 auto
LED2 LED1 LED3 LED4
LED STATUS
defrost Timer Auto operation
X X O ☆ Mold protection
10
8 .Electronic Function
8.1 General Protection
8.1.1 Temperature Protection of Compressor Top
8.1.2 3 minutes Delayed Starting Protection of the Compressor
8.1.3 Voltage Protection
8.1.4 The frequency Up-Down speed at which the compressor starts, operates and shuts off will be
subject to the following principles (outdoor chip):
HZ
1HZ/S
92Hz 2HZ/S
57Hz 1HZ/S
1HZ/S
6HZ/S
time
50 Sec
2 min
11
8.2.5 Performance at Auto mode at Fan-only status is the same as that at Auto mode at cooling status,
provided that the set temperature is 24°c.
°C
27.5 High
27.0
25.5 Mid
25.0
Low
frequency down
(8.8A) 6.8 A
frequency unchanged
(7.4A) 5.4 A
resume to normal
Note: The frequency down at the diagram is in accordance with the present frequency dropping
down, to determine every 2 seconds whether the frequency is keeping going down or is
recovering.
12
8.3.4 Indoor fan operates in accordance with the following principles:
8.3.4.1 When indoor fan is in operation, it can be remote controlled to High/Mid/Low/Auto modes.
8.3.4.2 The fan speed at Auto mode in cooling status is subject to the following:
+4.0 High
+3.0
+1.5 Mid
+1.0
Low
8.3.5 Indoor fan vanes at cooling mode will swing in accordance with the following:
When just plugged in for cooling, the vanes will open to the standard angle 50°.
The vane angle can be set by remote control at any angle between 50° and 105° (every setting
can adjust 6°) or set swinging (swinging angle will be 25°).
8.4 Dehumidifying Mode Requirements
8.4.1 At dehumidifying mode, the 4 way valve is shut off
8.4.2 At dehumidifying mode, the indoor fan is fixed in Breeze status and not adjustable.
8.4.3 At dehumidifying mode, the compressor operates in accordance with the following principles:
2.5 F3
2.0
1.5 F2
1.0
0.5 F1
0.0
F1
37°c
Set rotational speed
34°c
33°c
breeze
18°c
fan off
8.5.4 Indoor fan can be set by remote control to any mode like High/Mid/Low/Auto, however anti-cold
air function comes first.
Auto fan
-0.5
Low
-1.0
-1.5 Mid
-2.0
High
14
8.5.5 Outdoor Unit current control when heating
Note:
CES 9 I : -4°c
CES 12 I : -6°c
CES 9 I7 : -9°c
CES 9 I7 : -9°c
15
② The temperature of outdoor heat exchanger remains consecutively lower than 3°c for more than
80 minutes, and the temperature remains consecutively Ti2 for more than 3 minutes.
Model Ti2:
CES 9 I : -2°c
CES 12 I : -4°c
CES 9 I7 : -7°c
CES 9 I7 : -7°c
③ The temperature of outdoor heat exchanger remains consecutively lower than 3°c for more than
120 minutes, and the temperature remains consecutively Ti3 for more than 3 minutes.
Model Ti3:
CES 9 I : -0°c
CES 12 I : -2°c
CES 9 I7 : -5°c
CES 9 I7 : -5°c
Note: The time period starts to count when outdoor heat exchanger temperature is lower than
3°c, the defrosting operation starts when the exchanger temperature remains lower than the
starting temperatures which are Ti3, Ti2, Ti1.
8.5.8.2 Conditions of defrost ending
Defrosting ends when meeting any of the following three conditions and it turns to normal
heating operation.
① When the temperature of outdoor heat exchanger rises up to 12°c.
② When the temperature of outdoor heat exchanger rises up to 8°c and this continues for more
than 80 seconds.
③ When defrosting action continues for 10 minutes.
8.5.8.3 Defrosting Action
Max 10 mins
30 sec.
ON 10 sec. ON 30 sec
Compressor OFF
ON ON
4 way valve OFF
ON ON
Outdoor fan OFF
ON ON
Indoor fan OFF
16
8.5.9 Set Function Test
When it is detected that the outdoor temperature is between 5 - 9°c and room temperature is
between 18 - 22°c, provided that the heating operation remains consecutively more than 30
minutes, the compressor's highest operational frequency is FMAX=F8=96HZ. If any of the above
conditions is not met, it will quit from set frequency operation.
8.6 Auto Mode Function
Using remote control to choose auto mode, under which the set temperature can be adjusted in a
range of 17 - 30°c.
8.6.1 When entering auto mode, the A/C will choose cooling, heating or fan only according to the
difference between room temperature (TA) and set temperature (TS).
TA - TS Operation status
8.6.2 At auto mode, the indoor fan will choose auto fan in corresponding mode.
8.6.3 At auto mode, the vane action of indoor fan is the same as that of chosen mode.
8.6.4 Once a mode is chose, it will take 5 minutes after shutting off the compressor to re-choose
another mode according to the difference between room temperature and set temperature, or
you can re-choose mode when set temperature is changed.
8.7 Forced Operation Function
8.7.1 Forced operation is controlled by the switch on switch board and divided into forced cooling and
forced auto. Remote control doesn't work at forced operation control.
8.7.2 At forced operation status, all protection functions in general protection fore-mentioned apply.
8.7.3 At forced cooling mode, the compressor operates at a fixed frequency of F2=42HZ, indoor fan is
Breeze, anti-icing control and general current control of cooling outdoor unit work; forced
operation will transfer to auto mode whose set temperature is 24°c automatically after 30
minutes.
8.7.4 At forced auto mode, the remote control controls in a set temperature of 24°c.
8.8 Timer Function Requirement
8.8.1 The maximum length of timer is 24 hours and the minimum resolving power is 15 minutes.
8.8.2 Timer on function: first turn off the A/C, the A/C will be automatically on at the set time.
8.8.3 Timer off function: first turn on the A/C, the A/C will be automatically off at the set time.
8.8.4 Timer on/off function( on time is earlier than off time): first turn off the A/C, it will be automatically
on at set time, and later be off at the set time.
8.8.5 Timer off/on function( off time is earlier than on time): first turn on the A/C, it will be automatically
off at set time, and later be on at the set time.
8.8.6 Timer function execution is applicable upon one operation only.
8.8.7 Timer error is less than 1 min/h.
17
INVERTER COMFORT - Multiple
2. Specification 199
3. Dimensions 203
197
1. Product Features
Both indoor units can be operated either simultaneously or separately through the utilization of the advanced
converter technique and microcomputer control.
The flowing volume of refrigerant is adjustable through the electronic expansion valve.
High Cooling and Heating capacity is facilitated through the famous-brand frequency converter compressor.
Indoor noise is minimized through the optimization of the air flow system design, a four-folded evaporator and a
big diameter Cross Flow Fan.
The system is operable under low-voltage.
Effective and prompt defrosting correlates into no cold feelings.
High heating effects under extremely low temperatures.
The systems purging function improves the quality of the air in the room.
Wireless remote controlled function:
---A Manual Switch can operate the air conditioner when the remote controller is misplaced and the batteries are
exhausted.
---Horizontal and vertical louvers can swing automatically and the customized setting flows the air as desired.
---Grounding's have been connected and are safe to use.
---Compressor protection function enabled.
Indoor unit:
1) 4-Bend heat exchanger.
2) Trapeziform innergroove copper.
3) Hydrophilic Aluminum Fin.
4) Two-direction air vane technology.
5) Sleep mode.
6) Anti-rust cabinet.
7) Easy-cleaned panel.
8) Self-diagnosis auto-protection function.
198
2. Specification
Model CED 9-9 I7
Indoor unit 7000Btu/h 9000Btu/h 12000Btu/h
Power supply Ph-V-Hz 1Ph, 220-240V~, 50Hz
Capacity Btu/h single: 7000-12000; Twin:16000-24000
Input W single: 1000W-1350W; Twin:2570W-2900W
Cooling Rated current A single: 4.8A-6.7A; Twin:11.7A-13.8A
EER Btu/w.h single: 7.0-8.9; Twin:6.2-8.3
Capacity Btu/h single: 10000-14000; Twin:24000-27000
Input W single: 1300W-1650W; Twin:2100W-2800W
Heating Rated current A single: 6.3A-8.0A; Twin:11.0A-13.5A
COP Btu/w.h single: 7.7-8.5; Twin:11.4-9.6
Moisture Removal L/h 0.7 0.9 1.2
Max. input consumption W single: 1800W; Twin:3200W
Max. current A single: 13A; Twin:20A
Starting current A 10
Model BG240X2CS-20KU
Type Rotary inverter
Brand GD Toshiba
Capacity Btu/h 18000
Compress Input W 1690
or Rated current(RLA) A 11.6
Locked rotor Amp(LRA) A 60
Thermal protector Internal
Capacitor uF 85UF/250V
Refrigerant oil ml RB68AF/α68TF/T-68 750 ml
Model RPG13H RPG13H RPG13C
Brand Welling Welling Matsushita
Indoor
Input W 36 36 50
fan motor
Capacitor uF 1.2uF/≥450VAC 1.2uF/≥450VAC 1.5uF/≥450VAC
Speed(hi/mi/lo) r/min 1050/950/750 1100/1000/800 1060/900/800
Indoor Number of rows 2 2 2
coil Tube pitch(a)x row pitch(b) mm 21×13.37 21×13.37 21×13.37
Fin spacing mm 1.5 1.5 1.3
Hydrophilic Hydrophilic Hydrophilic
Fin type (code)
aluminium aluminium aluminium
φ7, innergroove
Tube outside dia.and type mm φ7, innergroove
φ7, innergroove tube
tube tube
Coil length x height x width mm 578×252×27.34 578×252×27.34 635×315×27.34
199
Number of circuits 2 2 2
Indoor air flow (Hi/Mi/Lo) m3/h 500/410/320 520/430/330 560/460/380
Indoor noise level (Hi/Mi/Lo) dB(A) 35/32/26 36/32/26 36/32/26
Dimension (W*H*D) mm 750*250*188 750*250*188 815*280*195
Indoor
Packing (W*H*D) mm 830*336*280 830*336*280 915*360*275
unit
Net/Gross weight kg 8.5/11 8.5/11 11/14
Model YDK53-6M
Brand Welling
Outdoor
Input W 148
fan motor
Capacitor uF 3.0
Speed r/min 775
Number of rows 1.5
Tube pitch(a)x row pitch(b) mm 25.4×22
Fin spacing mm 1.7
Outdoor
Fin type (code) Hydrophilic aluminium
coil
Tube outside dia.and type mm φ9.53 innergroove trube
Coil length x height x width mm 776×660×22
Number of circuits 2
Outdoor air flow m3/h 2500
Outdoor noise level dB(A) 60
Dimension(W*H*D) mm 845X695X335
Outdoor
Packing (W*H*D) mm 975X772X405
unit
Net/Gross weight kg 71/74
Refrigerant type R407C g 2200
Design pressure(Hi/Lo) MPa 2.8/1.2
Liquid side/ Gas side mm Ф6.35/Ф9.53 Ф6.35/Ф9.53 Ф6.35/Ф12.7
Refrigera
Max. refrigerant pipe length m 10 10 10
nt piping
Max. difference in level m 5 5 5
Connection wiring No
Plug type No
Controller Remote
Operation temp ℃ 17~30
Ambient temp ℃ 18~43(cooling); -15~24(heating)
Application area m2 14-18 18-24 20-30
200
Model CAM 9-9-9 I7
Indoor unit 7000Btu/h 9000Btu/h 12000Btu/h
Power supply Ph-V-Hz 1Ph, 220-240V~, 50Hz
Capacity Btu/h single: 7000-12000; Twin:16000-24000; Three:24000
Input W single: 1000W-1350W; Twin:2570W-2900W; Three:2900W
Cooling Rated current A single: 4.8A-6.7A; Twin:11.1A-13.8A; Three: 13.8A
EER Btu/w.h single: 7.0-8.9; Twin: 6.2-8.3; Three: 8.3
Capacity Btu/h single: 10000-14000; Twin: 24000-27000; Three: 27000
Input W single: 1300W-1650W; Twin: 2100W-2800W; Three: 2800W
Heating Rated current A single: 6.3A-8.0A; Twin: 11.0A-13.5A; Three: 13.5A
COP Btu/w.h single: 7.7-8.5; Twin: 11.4-9.6; Three: 9.6
Moisture Removal L/h 0.7 0.9 1.2
Max. input consumption W 3200
Max. current A 20
Starting current A 10
Model BG240X2CS-20KU
Type Rotary inverter
Brand GD Toshiba
Capacity Btu/h 18000
Compress Input W 1690
or Rated current(RLA) A 11.6
Locked rotor Amp(LRA) A 60
Thermal protector Internal
Capacitor uF 85UF/250V
Refrigerant oil ml RB68AF/α68TF/T-68 750 ml
Model RPG13H RPG13H RPG13C
Brand Welling Welling Matsushita
Indoor
Input W 36 36 50
fan motor
Capacitor uF 1.2uF/≥450VAC 1.2uF/≥450VAC 1.5uF/≥450VAC
Speed(hi/mi/lo) r/min 1050/950/750 1100/1000/800 1060/900/800
Indoor Number of rows 2 2 2
coil Tube pitch(a)x row pitch(b) mm 21×13.37 21×13.37 21×13.37
Fin spacing mm 1.5 1.5 1.3
Hydrophilic Hydrophilic Hydr0philiC
Fin type (code)
aluminium aluminium aluminium
201
Tube outside dia.and type mm φ7, innergroove tube φ7, innergroove tube
φ7, innergroove tube
Coil length x height x width mm 578×252×27.34 578×252×27.34 635×315×27.34
Number of circuits 2 2 2
Indoor air flow (Hi/Mi/Lo) m3/h 500/410/320 520/430/330 560/460/380
Indoor noise level (Hi/Mi/Lo) dB(A) 35/32/26 36/32/26 36/32/26
Dimension (W*H*D) mm 750*250*188 750*250*188 815*280*195
Indoor
Packing (W*H*D) mm 830*336*280 830*336*280 915*360*275
unit
Net/Gross weight Kg 8.5/11 8.5/11 11/14
Model YDK53-6M
Brand Welling
Outdoor
Input W 148
fan motor
Capacitor uF 3.0
Speed r/min 775
Number of rows 1.5
Tube pitch(a)x row pitch(b) mm 25.4×22
Fin spacing mm 1.7
Outdoor
Fin type (code) Hydrophilic aluminium
coil
Tube outside dia.and type mm φ9.53 innergroove trube
Coil length x height x width mm 776×660×22
Number of circuits 2
Outdoor air flow m3/h 2500
Outdoor noise level dB(A) 60
Dimension(W*H*D) mm 845X695X335
Outdoor
Packing (W*H*D) mm 975X772X405
unit
Net/Gross weight Kg 72/76
Refrigerant type R407C g 2400
Design pressure(Hi/Lo) MPa 2.8/1.2
Liquid side/ Gas side mm Ф6.35/Ф9.53 Ф6.35/Ф9.53 Ф6.35/Ф12.7
Refrigera
Max. refrigerant pipe length m 10 10 10
nt piping
Max. difference in level m 5 5 5
Connection wiring No
Plug type No
Controller Remote
Operation temp ℃ 17~30
Ambient temp ℃ 18~43(cooling); -15~24(heating)
Application area m2 14-18 18-24 20-30
Notes: 1. Nominal cooling capacities are based on the following conditions:
Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; Equivalent ref. Piping: 8m(horizontal)
2. Nominal heating capacities are based on the following conditions:
Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. Piping: 8m(horizontal)
202
3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an
anechoic room.
3 Dimensions
1. Indoor unit 7/9K
3. Outdoor unit
203
4 Refrigeration Cycle Diagram
Refrigeration circuit drawing of inverter trinary type
heat filter
inverter compressor
exchanger
high-pressure
switch 1
filter
oil separator
discharge
sensor
up part
capillary low-pressure
switch 2
capillary
heat
2
exchanger
down part
filter capillary
3
filter
condenser
heat
exchanger
filter
outdoor unit
inverter compressor
high-pressure
switch 1
oil separator
discharge
sensor
up part
capillary low-pressure
switch 2
capillary
heat
2
exchanger
down part
filter capillary
3
filter
condenser
heat
exchanger
filter
204
5 Operation Limits
5.1 Cooling operation
Outdoor unit air temp.℃
60
50
40
30
20
10
10 17 25 30 35 40
Indoor air temp. ℃
Note :the chart is the result from the continuous operation under constant air temperature
conditions. however, excludes the initial pull-down stage.
5.2 Heating operation
Indoor air temp. ℃
30
20
10
-5
-15
-15 -5 5 15 25 30
Outdoor unit air temp.℃
Note :the chart is the result from the continuous operation under constant air
205
temperature conditions. however, excludes the initial pull-down stage.
6 Capacity Table
6.1 Capacity table of Inverter Comfort Binary type
Indoor units can be combined by
7000Btu/h+9000 Btu/h;
7000Btu/h+12000 Btu/h
9000Btu/h+9000 Btu/h
9000Btu/h+12000 Btu/h
12000Btu/h+12000 Btu/h
Cooling
Indoor unit a (W) Indoor unit b (W)
7000Btu/h 2800
9000Btu/h 3000
12000Btu/h 3400
7000Btu/h+7000 Btu/h 2300 2300
7000Btu/h+9000 Btu/h 2500 2500
7000Btu/h+12000 Btu/h 2200 2800
9000Btu/h+9000 Btu/h 2500 2500
9000Btu/h+12000 Btu/h 2400 3200
12000Btu/h+12000 Btu/h 3200 3200
Heating
Indoor unit a (W) Indoor unit b (W)
7000Btu/h 3400
9000Btu/h 3600
12000Btu/h 4000
7000Btu/h+7000 Btu/h 2800 2800
7000Btu/h+9000 Btu/h 3000 3000
7000Btu/h+12000 Btu/h 2600 3400
9000Btu/h+9000 Btu/h 3000 3000
9000Btu/h+12000 Btu/h 3000 3900
12000Btu/h+12000 Btu/h 3900 3900
206
12000Btu/h*2+9000 Btu/h
7000Btu/h+9000Btu/h+12000 Btu/h
Cooling
Indoor unit a (W) Indoor unit b (W) Indoor unit c (W)
7000Btu/h 2800
9000Btu/h 3000
12000Btu/h 3400
7000Btu/h+7000 Btu/h 2300 2300
7000Btu/h+9000 Btu/h 2500 2500
7000Btu/h+12000 Btu/h 2200 2800
9000Btu/h+9000 Btu/h 2500 2500
9000Btu/h+12000 Btu/h 2400 3200
12000Btu/h+12000 Btu/h 3200 3200
7000Btu/h*2+9000 Btu/h 2200 2200 2200
7000Btu/h*2+12000 Btu/h 2000 2000 2600
7000Btu/h*3 2200 2200 2200
9000Btu/h*2+7000 Btu/h 2200 2200 2200
9000Btu/h*2+12000 Btu/h 2100 2100 2600
9000Btu/h*3 2200 2200 2200
12000Btu/h*2+7000 Btu/h 2000 2400 2400
12000Btu/h*2+9000 Btu/h 2000 2400 2400
Heating
Indoor unit a (W) Indoor unit b (W) Indoor unit c (W)
7000Btu/h 3400
9000Btu/h 3600
12000Btu/h 4000
7000Btu/h+7000 Btu/h 2800 2800
7000Btu/h+9000 Btu/h 3000 3000
7000Btu/h+12000 Btu/h 2600 3400
9000Btu/h+9000 Btu/h 3000 3000
9000Btu/h+12000 Btu/h 3000 3900
12000Btu/h+12000 Btu/h 3900 3900
7000Btu/h*2+9000 Btu/h 2600 2600 2600
7000Btu/h*2+12000 Btu/h 2300 2300 3200
7000Btu/h*3 2400 2400 2400
9000Btu/h*2+7000 Btu/h 2700 2700 2700
9000Btu/h*2+12000 Btu/h 2500 2500 3200
9000Btu/h*3 2700 2700 2700
12000Btu/h*2+7000 Btu/h 2400 3200 3200
12000Btu/h*2+9000 Btu/h 2400 3200 3200
207
7. Wiring Diagram
7.1 Indoor unit 7/9K
208
7.3 Outdoor unit CED 9-9 I7
209
8. Electric Control Functions
8.1 Control system
The control system adopts modular design, that is, all indoor units communicate with outdoor units, ref. to the
following figures for the control structure between indoor units and outdoor units. In the structure, the indoor control
board receives the information from users (for exam. set temp., fan speed etc.) and environment (ex, indoor coil
temp., indoor temp. etc.) ,and organize it to control the action of relevant parts, then transmits the signals to outdoor
control board through the following communication circuit. Outdoor control board can deal with the information
from indoor unit and figure out the best running mode, then transfer the instruction to indoor units to carry out it.
Indoor unit receive the user’s remote control signals.
Indoor unit Outdoor unit
T2B
T1、T2、Ts T3、 T4、T3
Fan Speed Pressure switch
Pressure switch
4-way valve
Fan Fan motor
通讯 Co Compressor
Swing motor mote control EXV
210
3、 T2B Indoor evaporator outlet temp.
4、 Ts Indoor setting temp.
5、 T3 Outdoor heat-exchanger outlet temp.
6、 T4 Outdoor ambient temp.
Volt(V)
Volt increase (Resume)
198
190 MAX=78Hz 190
180
172 MAX=70Hz 172
167
Stop
211
The High-pressure switch and Low-pressure switch are installed at suction pipe and discharge pipe separately. And
users can select to install. Normally, the high-pressure switch is cut down when higher than 425Psi (3.3Mpa Cut
down, 2.4Mpa Resume). While the low-pressure switch is cut down when lower than 7Psi (0.05Mpa
On, 0.15Mpa Resume).
Under high-pressure protection or low-pressure protection, the compressor will stop and restart 3
minutes later.
212
8.3.1 Checking function
The indoor and outdoor operation condition can be examined by check button.
Normal display Operation mode Capacity request Number of indoor units ambient temp.
Outdoor pipe temp. Compressor current No.1 PMV opening No.2 PMV opening
213
214
COOLWEX Group USA.
[Models]
CAS 7 R10 C
CAS 7 R10
CAS 9 R10 C
CAS 9 R10
CAS 12 R10 C
CAS 12 R10
Contents
1. Features………………………………………………………………….. 2
2. Specification………………………………………………………..……..3
3. Dimensions…………………………………………………………..……4
5. Pressure table…………….……………………………………….………8
6. Capacity table………………………………………………………….…11
7. Wiring diagram…………………………………………………..……….16
8. Electronic function………………………………………….………….…21
9. Troubleshooting……………………………………………………….….29
1
1.Features
1.1 Compact design
1.2 High efficiency and quiet operation
1.3 A class energy level
2
2.Specification
Model CAS 07 R10 C CAS 7 R10 CAS 9 R10 C CAS 9 R10 CAS 12 R10 C CAS 12 R10
Factory Model CE-KF20GW/N1Y-H CE-KFR20GW/N1Y-H CE-KF26GW/N1Y-H CE-KFR26GW/N1Y-H CE-KF36GW/N1Y-H CE-KFR36GW/N1
Y-H
Power supply Ph-V-Hz 1, 220-240V~, 50Hz 1, 220-240V~, 50Hz 1, 220-240V~, 50Hz 1, 220-240V~, 50Hz 1, 220-240V~, 50Hz 1, 220-240V~,
50Hz
Capacity Btu/h 7000 7000 9000 9000 12000 12000
Input W 640 640 820 820 1120 1120
Cooling
Rated current A 2.8 2.8 3.6 3.6 5.0 5.0
Btu/w.h,
EER 11,3.2 11,3.2 11,3.2 11,3.2 11,3.2 11,3.2
w/w
Capacity Btu/h 8500 11000 —— 15000
Input W 690 890 —— 1180
Heating
Rated current A 3.0 3.9 —— 5.3
COP W/W 3.6 3.6 —— 3.6
Moisture Removal L/h 0.7 0.7 1.0 1.0 1.2 1.2
Max. input consumption W 850 1000 1000 1200 1550 1550
Max. current A 3.8 4.5 4.5 5.3 10 10
Starting current A 30 30
Model PA82X1C-4DZ2 PA82X1C-4DZ2 PA108X1C-4FT PA108X1C-4FT PA145X2C-4FT PA145X2C-4FT
Type Rotary Rotary Rotary Rotary rotary rotary
Capacity Btu/h 6680 6680 8870 8870 12000 12000
Input W 675 675 890 890 1200 1200
Compressor Rated current(RLA) A 3.11 3.11 4.07 4.07 5.6 5.6
Locked rotor Amp(LRA) A 15.0 15.0 21.7 21.7 29.9 29.9
Thermal protector UP3QE0591-T71 UP3QE0591-T71 UP3QE0591-T61 UP3QE0591-T61 UP3RE0591-T56 UP3RE0591-T56
Capacitor uF 25 25 25 25 35 35
Refrigerant oil ml 350 350 330 330 480 480
Model RPG13H RPG13H RPG13H RPG13H RPG20D RPG20D
Input W 36.5 36.5 36.5 36.5 51.5 51.5
Indoor fan motor
Capacitor uF 1.2 1.2 1.2 1.2 1.5 1.5
Speed(hi/mi/lo) r/min 1050/9200/820 1050/9200/820 1200/950/850 1200/950/850 1250/1000/800 1250/1000/800
Number of rows 2 2 2 2 2 2
Fin type (code) Hydrophilic aluminium Hydrophilic aluminium Hydrophilic aluminium Hydrophilic aluminium Hydr0philiC Hydr0philiC
Indoor coil aluminium aluminium
Tube outside dia.and type mm φ7, innergroove tube φ7, innergroove φ7, innergroove φ7, innergroove φ7, innergroove φ7, innergroove
tube tube tube tube tube
Number of circuits 2 2 2 2 2 2
Indoor air flow (Hi/Mi/Lo) m3/h 450/400/350 450/400/350 500/460/410 500/460/410 680/520/420 680/520/420
Indoor noise level (Hi/Mi/Lo) dB(A) 34/32/30 34/32/30 36/34/32 36/34/32 39/33/28 39/33/28
Dimension (W*H*D) mm 750*250*205 750*250*205 750*250*205 750*250*205 815*280*215 815*280*215
Indoor unit Packing (W*H*D) mm 830X285X335 830X285X335 830X285X335 830X285X335 915X290X360 915X290X360
Net/Gross weight Kg 8/10 8/10 8/10 8/10 10/12 10/12
Model YDK24-6T YDK24-6T YDK24-6F YDK24-6F YDK36-6 YDK36-6
Input W 56 56 56 56 68 68
Outdoor fan motor
Capacitor uF 2.5 2.5 2.5 2.5 2.5 2.5
Speed r/min 800 800 800 800 900 900
Number of rows 2 2 2 2 2 2
Fin type (code) Unhydrophilic aluminium Hydrophilic aluminium Unhydrophilic Hydrophilic aluminium Unhydrophilic Hydrophilic
aluminium aluminium aluminium
Outdoor coil Tube outside dia.and type mm Ф7,innergroove tube Ф7,innergroove tube Ф7,innergroove tube Ф7,innergroove tube Ф9.53,innergroove Ф9.53,innergroove
tube tube
Coil length x height x width mm 750x508x26.74 750x508x26.74 810x508x26.74 810x508x26.74 680x550x44 680x550x44
Number of circuits 2 2 2 2 2 2
Outdoor air flow m3/h 1500 1500 1800 1800 1900 1900
Outdoor noise level dB(A) 49 49 50 50 52 52
Dimension(W*H*D) mm 700X535X235 700X535X235 780X540X250 780X540X250 760X590X285 760X590X285
Outdoor unit Packing (W*H*D) mm 815X580X325 815X580X325 910X575X335 910X575X335 890X655X360 890X655X360
Net/Gross weight Kg 31/34 32/35 36/39 37/40 41/45 41.5/45.5
Refrigerant type R410A g 800 820 900 920 1160 1170
Design pressure MPa 4.2 4.2 4.2 4.2 4.2 4.2
Liquid side/ Gas side mm(inch) Ф6.35/Ф9.53 Ф6.35/Ф9.53 Ф6.35/Ф9.53 Ф6.35/Ф9.53 Ф6.35/Ф12.7 Ф6.35/Ф12.7
Refrigerant piping Max. refrigerant pipe length m 10 10 10 10 10 10
Max. difference in level m 5 5 5 5 5 5
Connection wiring No No No No No No
Plug type 16A 16A 16A 16A 16A 16A
Thermostat type Electrolic control Electrolic control Electrolic control Electrolic control Electrolic control Electrolic control
Operation temp ℃ 17-30 17-30 17-30 17-30 17-30 17-30
Ambient temp ℃ 18~-45 -7 -~ 45 18~-45 -7 -~ 45 18~-45 -7 -~ 45
★1 The noise date is base on hemi-anechoic chamber, during actual operation, these values are normally somewhat different as a result of ambient
condition.
3
3.Dimensions
3.1 Indoor unit
CAS 7 R10 C, CAS 7 R10, CAS 9 R10 C, CAS 9 R10
4
3.4 Outdoor unit
CAS 7 R10 C, CAS 7 R10
5
3.6 Outdoor unit
CAS 12 R10 C, CAS 12 R10
750
285
590
62
315
290
530 110
6
4.Refrigeration cycle diagram
7
5. Pressure table
Note:
*The pressure data is from 3 way valve, the pressure data are pressure above atmosphere.
*D: Dry bulb temp.
*W: Wet bulb temp.
5.1 CAS 12 R10 C
Cooling mode Outdoor temperature (Dry bulb temp)
Indoor Conditions Pressure 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
21ºC D Pressure
6.2 6.8 7.2 8.0 8.5 9.5
15ºC W ( kg/cm2 )
24ºC D Pressure
6.3 6.5 7.5 8.0 8.7 9.5
17ºC W ( kg/cm2 )
27ºC D Pressure
6.1 6.9 7.7 8.2 9.1 10.0
19ºC W ( kg/cm2 )
21ºC D Pressure
6.2 6.8 7.2 8.0 8.5 9.5
15ºC W ( kg/cm2 )
24ºC D Pressure
6.3 6.5 7.5 8.0 8.7 9.5
17ºC W ( kg/cm2 )
27ºC D Pressure
6.1 6.9 7.7 8.2 9.1 10.0
19ºC W ( kg/cm2 )
8
5.3 CAS 12 R10 C
Cooling mode Outdoor temperature (Dry bulb temp)
Indoor Conditions Pressure 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
21ºC D Pressure
7.8 8.1 8.4 9.0 9.3 10.0
15ºC W ( kg/cm2 )
24ºC D Pressure
7.9 8.2 8.7 9.0 9.5 10.1
17ºC W ( kg/cm2 )
27ºC D Pressure
8.0 8.5 9.2 9.9 10.2 10.8
19ºC W ( kg/cm2 )
21ºC D Pressure
7.8 8.1 8.4 9.0 9.3 10.0
15ºC W ( kg/cm2 )
24ºC D Pressure
7.9 8.2 8.7 9.0 9.5 10.1
17ºC W ( kg/cm2 )
27ºC D Pressure
8.0 8.5 9.2 9.9 10.2 10.8
19ºC W ( kg/cm2 )
9
5.5 CAS 12 R10 C
Cooling mode Outdoor temperature (Dry bulb temp)
Indoor Conditions Pressure 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
21ºC D Pressure
8.4 8.5 8.8 8.9 9.4 9.9
15ºC W ( kg/cm2 )
24ºC D Pressure
8.6 8.8 9.2 9.4 10.0 10.4
17ºC W ( kg/cm2 )
27ºC D Pressure
8.8 9.2 9.4 9.8 10.3 10.9
19ºC W ( kg/cm2 )
24ºC D Pressure
8.6 8.8 9.2 9.4 10.0 10.4
17ºC W ( kg/cm2 )
27ºC D Pressure
8.8 9.2 9.4 9.8 10.3 10.9
19ºC W ( kg/cm2 )
10
6. Capacity table
6.1 CAS 7 R10 C
SUMMER OUTDOOR TEMPERATURE DRY
Indoor
25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
Conditions
Total capacity kW 2.06 1.95 1.75 1.51 1.58 1.41
21ºC D
Sensitive capacity kW 1.52 1.37 1.39 1.32 1.19 1.07
15ºC W
Input kW. 0.53 0.58 0.62 0.63 0.78 0.80
Total capacity kW 2.14 2.05 1.96 1.72 1.73 1.52
24ºC D
Sensitive capacity kW 1.61 1.46 1.45 1.54 1.23 1.15
17ºC W
Input kW. 0.60 0.60 0.66 0.65 0.78 0.83
Total capacity kW 2.31 2.24 2.10 1.90 1.73 1.67
27ºC D
Sensitive capacity kW 1.78 1.65 1.42 1.43 1.26 1.28
19ºC W
Input kW. 0.55 0.63 0.64 0.70 0.79 0.84
Total capacity kW 2.33 2.33 2.31 2.38 2.15 2.07
32ºC D
Sensitive capacity kW 1.83 1.67 1.65 1.64 1.57 1.53
23ºC W
Input kW. 0.53 0.65 0.69 0.73 0.83 0.88
11
WINTER OUTDOOR CONDITIONS
Indoor 12ºC D 7ºC D 4ºC D 0ºC D -4ºC D -7ºC D
Conditions 11ºC W 6ºC W 3ºC W -1ºC W -6ºC W -8ºC W
Capacity kW 3.01 2.73 2.47 1.76 1.65 1.58
15ºC
Input kW. 0.76 0.66 0.60 0.58 0.50 0.45
Capacity kW 2.86 2.64 2.34 1.69 1.53 1.41
18ºC
Input kW. 0.78 0.67 0.62 0.59 0.62 0.47
Capacity kW 2.77 2.49 2.28 1.62 1.59 1.33
20ºC
Input kW. 0.81 0.69 0.64 0.59 0.53 0.48
Capacity kW 2.61 2.43 2.13 1.58 1.26 1.17
22ºC
Input kW. 0.83 0.68 0.65 0.60 0.56 0.51
12
6.4 CAS 9 R10
SUMMER OUTDOOR TEMPERATURE DRY
Indoor
25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
Conditions
Total capacity kW 2.42 2.41 2.24 2.03 1.87 1.75
21ºC D
Sensitive capacity kW 1.72 1.69 1.65 1.53 1.43 1.36
15ºC W
Input kW. 0.72 0.75 0.80 0.84 0.89 0.97
Total capacity kW 0.65 2.55 2.45 2.24 2.11 1.98
24ºC D
Sensitive capacity kW 1.83 1.73 1.70 1.63 1.63 1.57
17ºC W
Input kW. 0.68 0.76 0.81 0.88 0.93 1.02
Total capacity kW 2.89 2.80 2.63 2.45 2.23 2.05
27ºC D
Sensitive capacity kW 1.99 1.95 1.81 1.78 1.66 1.63
19ºC W
Input kW. 0.65 0.78 0.82 0.92 0.96 1.03
Total capacity kW 3.03 2.98 2.92 2.83 2.69 2.46
32ºC D
Sensitive capacity kW 2.05 1.88 1.96 1.87 1.87 1.85
23ºC W
Input kW. 0.65 0.80 0.86 0.95 0.99 1.08
13
6.5 CAS 12 R10 C
SUMMER OUTDOOR TEMPERATURE DRY
Indoor
25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
Conditions
Total capacity kW 3304 3198 3921 2856 2787 2684
21ºC D
Sensitive capacity kW 2607 2497 2411 2304 2242 2111
15ºC W
Input kW. 907 1006 1096 1184 1259 1457
Total capacity kW 3683 3511 3339 3166 3066 2960
24ºC D
Sensitive capacity kW 2938 2790 2745 2580 2470 2359
17ºC W
Input kW. 926 1035 1127 1230 1278 1380
Total capacity kW 3896 3718 3646 3387 3235 3232
27ºC D
Sensitive capacity kW 3076 2938 2856 2690 2580 2470
19ºC W
Input kW. 943 1058 1120 1265 1322 1437
Total capacity kW 4199 4009 3850 3614 3541 3370
32ºC D
Sensitive capacity kW 3098 2990 2900 2745 2607 2552
23ºC W
Input kW. 977 1090 1190 1310 1368 1495
14
WINTER OUTDOOR CONDITIONS
Indoor 12ºC D 7ºC D 4ºC D 0ºC D -4ºC D -7ºC D
Conditions 11ºC W 6ºC W 3ºC W -1ºC W -6ºC W -8ºC W
Capacity kW 4446 4264 4132 3838 3335 305
15ºC
Input kW. 1141 1106 1059 1035 895 812
Capacity kW 4380 4248 3954 3761 3258 2948
18ºC
Input kW. 1188 1153 1142 1082 953 918
Capacity kW 4261 4153 3877 3683 3189 2871
20ºC
Input kW. 1224 1180 1129 1082 976 941
Capacity kW 4106 3989 3761 3567 3045 2876
22ºC
Input kW. 1259 1212 1153 1106 1000 836
15
7. Schematic diagram and wiring diagram
7.1 Schematic diagram
1 2 3 4 5 6 7 8
GND
D13
GND
R16 12K REC1
4 A A Q2 R20 1K IN4148 +12V-a CN4
E1 C1 E2 C3 E3 C4 REC
3 D3 REC
R15R17 9014 V
2 B 104 104 104 D11 1N4148 C9 R215.1K 3
D4 D12 1N4148 12K12K C10 C11 GND FANSP_FEEDBACK 2
1 104
2
2
B E7 1
RECEIVER_V C12
TRANS
2200uF/25V 1000uF/16V 470uF/16V 102 104 103 FAN_BACK
D D
IC10 7812 +12V-b 10uF/16V
D16 IN4007*4 1 3
Vin Vout COM1 COM2 COM3
GND
D19
2200uF/25V 1000uF/16V 10K 10K 10K
GNDB
+5V
R4 12K Q8 Q9 Q10
+5V
C5 1
3
104 RST 9012 9012 9012
2
C26 IC4
C25
IC5 KIA7042 104 1 42 X1 R7 X1 DIS1
104 VSS0 X1 +5V C2
+5V 1M WT4021BG
2 41 X2 IC2
+12V VDD0 X2
4M R1 R2 104
JR8 FAN_IN 3 40 RST 8 1 +12V-a CN9
FAN_IN P25 RESET RST 10K 10K VCC A0
10K 7 2 LOAD_HEAT N
R5 6
WC A1
3
Only For Heat Pump 1
1K HEAT BUZ BUZ 4
P26 XT1
39 SCL SCL A2 D21
5 4 HEAT_N
SDA SDA GND RY2
BUZ1 JR9 STEP_I1 5 38
BUZ ' STEP_I1 P00 XT2 RELAY-SPST
BUZZER1 10K 24C04
+5V STEP_I2 6 37 IN4148
C STEP_I2 P01 Vpp/IC C
N
a
e
d
b
com1
com2
h
g
f
STEP_I3 7 36 SCL Q3
R38 STEP_I3 P02 P24 SCL R27
IC8 9014
10K STEP_I4 8 35 SDA 7 13
STEP_I4 P03 P23 SDA GND Q7 2K
C24 R44 330
SW_TEST 104
R39 COMP 9 34 COM1 14 12
C22 COMP P04 P22 COM1 Vcc Q6
5.1K 104 JR1 R45 330
10 33 COM2 11
VSS1 P21 COM2 Q5
+12V-a CN10
10K R46 330
HEAT 11 32 9 10 LOAD_HEAT L
P05 VDD1 +5V +5V MR Q4 LED6 1
SW1
R47 330 自动 D22
SEG1 12 31 COM3 8 6 HEAT_L
SEG1 P50 P20 COM3 SEG3 CP Q3 LED7 IN4148 RY3
R48 330 化霜 RELAY-SPST
SEG2 13 30 FAN_OUT FAN_OUT C16 5
SEG2 P51 P33 102 Q2
R49 330 LED8
SEG3 14 29 FANSP FANSP_FEEDBACK 2 4 定时
SEG3 P52 P32 SEG4 Dsb Q1 FUSE2
LED9 Q5
R54 330 R33
SEG4 15 28 ZERO C17 1 3 运行灯 9014
SEG4 P53 P31 ZERO 102 Dsa Q0 HEAT 10A
R55 330 2K
16 27 REC REC 74HC164
+5V AVDD P30 +5V SW2 CN16
17 26 VALVE VALVE +12V-b 1
CN2 +5V AVREF P11
FRESH
R59 R60 +12V-a CN13
2 T1_room T1 18
AN10 P10
25 FRESH FRESH 2
10K 10K JR4 10K LOAD_FAN OUT
D5 1
1 IN4148 T2_I.pipe T2 19
AN11 AVSS
24
JR5 10K R62 IC9 R63 D23
+5V R61 Q12 RY4 2
T1_room
B R10 2K Current CURRENT 20 AN12 AN15
23
2K
1K 5.1K
RELAY-SPST B
JR2 10K 9014
T1_room IN4148
AUTO_SELECT AUTO_SELECT 21 22 SW SW_TEST Q11
D6 E4 C6 AN13 AN14 JR3 10K +12V-a PC817 +12V-b L1
R8 UPD789166 9014 GNDB Q6
8.1K/1% IN4148 10uF/16V 104 IC7 R34 9014
FAN_OUT
1 16 2K
STEP_I1 IN1 OUT1 1
CN3 +5V
2 15
STEP_I2 IN2 OUT2 2 CN12
2
D7 3 14
STEP_I3 IN3 OUT3 3
1 IN4148 +12V-a
4 13 LOAD_VALVE
T2_I.pipe STEP_I4 IN4 OUT4 4
R11 2K C20
T2_I.pipe 5 12 D24
FAN_IN IN5 OUT5 FAN_IN ' 5 333
RY5
D8 E5 C7
6 11 +12V-a SWING RELAY-SPST
R9 +5V BUZ IN6 OUT6 BUZ ' IN4148
8.1K/1% IN4148 10uF/16V 104
7 10 R36
COMP IN7 OUT7 COMP ' 51/1W
Q7
JR6 R35
8 9 9014
10K VSS VDD VALVE
2K
R23 2K C19 UJN2003 L1
104 FUSE1
AUTO_SELECT
+5V
CN6 3.15A/250V
JR7 C13 +12V-a
1 +12V-a LOAD_COMP
D9 10K 104 R25 51/1W C15 L1 C21
1N4148 CN15
A 2 333 A
E9 C23 1 RY6 333
R12 2K R14 ? ZR1
3 T2 T1 470uF/25V COMP
Current 10D471K 0.1uF/275VAC
1.4K/1% L2 Z1 R28 R29 2
CT1 BT131 D15 t COMP ' R37
D10 4 C14 12V 11K/2W 11K/2W TRANS_IN
C8 R13 TR1 N 51/1W
1N4148 0057h
104 E6 16K R6 1.2uF/450V L(POWER_IN PORT)
5 IC6 PC817 IN4007 PTC
G
1 2 3 4 5 6 7 8
16
7.2 Wiring diagram
7.2.1 Cooling only
INDOOR UNIT
O
U
T
D
O
O
R
U
N
I
T
1
2
(
N
)
Y&G
B
L
A
C
K
B
L
A
C
K
O
V
E
RE
L
O
A
D
R
L
A
Y
R
E
D
R
E
D
B
L
A
C
K
C
O
M
P
R
E
S
S
O
R
C
R
E
D
F
A
NT
R
E
D
M
O
O
R
R
Y&G
S
Y&G
B
L
U
E
B
L
U
E
COMPRESSOR FAN
CAPACITOR CAPACITOR
17
7.2.1.2 CAS 12 R10 C
18
7.2.2 Heating/cooling
7.2.2.1 CAS 7 R10, CAS 9 R10
19
7.2.2.2 CAS 12 R1
20
8 Electronic function
8.1 Electric Control working environment
8.1.1 input voltage: 175~253V
8.1.2 Input power frequency:50Hz
8.1.3 Ambient temperature: -7°C~+43°C
8.1.4 Indoor fan normal working amp is less than 1A,
8.1.5 Outdoor fan. Normal working amp is less than 1.5A
8.1.6 Four-way valve normal working amp is less than 1A.
8.1.7 Swing motor: DC12V.
8.1.8 Compressor: single-phase power supply. Its normal working amp is less than 15A
8.2 Proper symbols and their meanings:
TA: Indoor ambient temperature
TE: Indoor evaporator temperature
TS: Setting temperature through the remote controller
I3sec: Self-protection amp of compressor, continue three seconds until turns off the compressor.
I5MIN: Self-protection amp of compressor, continue five minutes until turns off the compressor.
IFAN: Self-protection amp of outdoor fan/indoor fans when they change from higher wind to lower wind.
IRESTORE: Amp self-protection return value
THDEFROST: High wind, defrosting temperature difference
TMDEFROST: Middle wind, defrosting temperature difference
TLDEFROST: Low wind, defrosting temperature difference
TE1: Anti-cold wind, from Fan Off to Breeze temperature
TE2: Anti-cold wind, from Breeze to Setting Fan Speed temperature
TE3: Anti-cold wind, from Setting Fan Speed to Breeze temperature
TE4: Anti-cold wind, from Breeze to Fan Off temperature
TE5: Evaporator low temperature protection entering temperature
TE6: Evaporator low temperature protection restoring temperature
TE7: Evaporator high temperature protection, compressor off temperature
TE8: Evaporator high temperature protection, fan off temperature
TE9: Evaporator high temperature protection, restoring temperature
8.3 Functions
Remote receiving
Testing and forced running
Position set for indoor unit wind vane
LED displaying and alarm
On or off Timer
Protection for the compressor
Current protection
High temperature protection of indoor heat exchanger at heating mode
Auto defrosting and heating recovery at heating mode
Anti cold air at heating mode
Anti frozen at cooling mode
21
8.4 Protection
8.4.1 3 minutes delay at restart for compressor.
8.4.2 Sensor protection at open circuit and breaking disconnection
8.4.3 Fan Speed is out of control. When Indoor Fan Speed is too high(higher than High Fan+300RPM)or
too low(lower than 400RPM), the unit stops and LED displays failure information and can’t returns to
normal operation automatically.
8.4.4 Cross Zero signal error warning. If there is no Cross Zero signals in 4 minutes, the unit stops and LED
displays failure information and can’t returns to normal operation automatically.
8.4.5 The current protection of the compressor
Condition Indoor fan Compressor Outdoor fan Remark
I< IRESTORE On On On
If compressor turns off for continuously 4 times due to current protection in 5 minutes from
Compressor On, the unit stops and LED displays failure information and can’t returns to normal
operation automatically.
23
8.7.3 Low room temperature protection:
When room temperature decreases to below 10℃, compressor and outdoor fan will stop(indoor fan
is Breeze). Dehumidifying operation will be resumed when room temperature restores to over 13℃.
8.7.4 At dehumidifying mode, the anti-freezing function of the indoor heat exchanger is the same as that
of cooling mode.
8.7.5 At dehumidifying mode, the action of fans of indoor is the same as that of air-only mode.
8.8 Heating mode
8.8.1 Generally, the 4-way valve is open in heating mode, but it is closed in defrosting mode. 4-way valve
must delay 2 minutes compared with compressor if the compressor changed into non-heating mode
or turned off. 4-way valve doesn't delay in dehumidifying mode.
8.8.2 Generally, the outdoor fan is turned off with the on-off action of compressor in heating mode, except
for the defrosting mode or the end of defrost.
8.8.3 Action of compressor and outdoor fan motor at heating mode: compressor must run for 7 minutes
after starting and then judge temperature. Meanwhile other protections are still valid.
Condition Compressor Outdoor fan
T<Ts+3 On On
TE1<T<TE2 Breeze
TE3<T<TE4 Breeze
T<TE4 Off
T>2℃ Med.
T<0℃ High
24
8.8.6 Indoor evaporator high-temperature protection at heating mode
Condition Compressor Outdoor fan
TE8<T<TE7 On Off
T<TE9 On On
8.8.7. The louver opens to Standard Angle ANGLHEAT when power is on for the first time
8.9 Defrosting operation (Available for heating only).
8.9.1 Defrosting condition: Defrosting starts when either of the following ①&②:
① A and B are satisfied:
A: The compressor keeps running for 40 minutes or more.
B: The temperature difference of evaporator and room temperature meets one of the following:
② Calculate from the end of latest defrost, evaporator high temp. protection only closes outdoor fan
with the compressor still running. Add up to 90 minutes.
8.9.2 Defrosting time
If the temp. difference condition ① is satisfied for less than 40 minutes, this can be regarded as
severe frosting. The defrosting time is 10 minutes.
If the temp. difference condition ② is satisfied for more than 40 minutes, the defrosting time is 6
minutes.
If the temp. difference condition ① is satisfied out of 40 minutes, generally the defrosting time is 6
minutes, after three continuous 6-minute defrost, the fourth should be 10 minutes defrost. The
circulation is as following:
→7.5-minute defrost → 7.5-minute defrost→7.5-minute defrost→10-minute defrost→
25
8.9.4 Defrosting Actions:
45S 25S
Compressor
Indoor Fan
10S
TA—TS>2℃ Cooling
-1℃≤TA-TS≤+2℃ Fan-only
27
8.16 Models and Parameters
TE5 4℃ 4℃ 4℃ 4℃ 3℃ 3℃
ANGLHEAT 0° 0° 10°
28
9.Troubleshooting
Infrared Signal
1 2 3 4 5 6
Receiver
1: AUTO indicator
2: TIMER indicator
3: PRE.-DEF. Indicator
4: OPERATION indicator
5: SLEEP indicator
Indoor fan speed has been out of control for over 1 minute ☆ X
EEROM error On ☆
No over-zero signal ☆ ☆
r Extinguish
☆ Flash at 5Hz
29
☆
9.3 Diagnostic Chart
9.3.1 After energizing, no indicator is lighted and the air conditioner can’t be operated.
Yes
Yes No
No Yes
No
9.3.2 Resetting phenomenon often occurs during operation. (That is automatically entering to the status when
power is on.)
The reason is that the instantaneous voltage of main chip is less than 4.5V. Check according to the following procedure:
Yes
No Yes
After changing indoor fan motor, check if the failure releases. Indoor PCB is defective
No
Power supply circuit has problems.
30
9.3.3 Failure phenomenon
Failure phenomenon Operation lamp Timer lamp
Indoor fan speed has been out of control for over 1 minute ☆ X
EEROM error On ☆
No over-zero signal ☆ ☆
r Extinguish
☆ Flash at 5Hz
9.3.3.1 Operation lamp flashes and Timer lamp off.
Yes No
Yes No
No
Yes
After changing the main control board, check if the failure releases.
Yes
No Yes
The voltage of power supply is too low (less than 187V)? Indoor PCB is defective
Yes No
-4 44 23 10.9731 50 3.451
-2 39.8239 25 10 52 3.1918
32
COOLWEX Group USA
[Models]
CAS 7 I10
CAS 9 I10
CAS 12 I10
Contents
1. Features…………………………………………………………………… 2
2. Specification………………………………………………………..………3
3. Dimensions…………………………………………………………………4
5. Pressure table…………….……………………………………….………7
6. Capacity table………………………………………………………….….9
7. Operation Limits………………………………………………………….11
8. PCB diagram……………………………………………………………..12
9. Wiring diagram…………………………………………………..……….14
11. Troubleshooting……………………………………………………….…23
1
1.Features
1.1 Powerful at cooling/heating.
1.2 Low voltage start-up function.
1.3 Anti-icing function at cooling mode.
1.4 Anti-cold air function at heating mode.
1.5 Auto-defrosting.
1.6 Outdoor electric current protection
1.7 Temperature protection of the outdoor compressor top.
1.8 Restart protection for the compressor.
1.9 Error self diagnosis function.
1.10 Protection against over-load or too-low current inputted through alternating current.
2
2.Specification
M odel CAS 7 I10 CAS 9 I10 CAS 12 I10
F a c to r y M o d e l C E - K F R 2 6 G W /B P 2 N 1 Y C E - K F R 2 6 G W /B P 2 N 1 Y C E - K F R 3 5 G W /B P 2 N 1 Y
P o w e r s u p p ly P h -V -H z 1 , 2 2 0 -2 4 0 V ~ , 5 0 H z 1 , 2 2 0 -2 4 0 V ~ , 5 0 H z 1 , 2 2 0 -2 4 0 V ~ , 5 0 H z
C a p a c ity B tu /h 7 0 0 0 (1 5 5 0 -9 6 6 0 ) 9 0 0 0 (2 0 5 0 -1 1 2 6 0 ) 1 2 0 0 0 (2 3 5 0 -1 4 5 0 0 )
In p u t W 6 1 5 (2 0 0 -1 1 5 0 ) 7 6 0 (2 5 0 -1 3 5 0 ) 1 0 7 0 (2 7 0 -1 7 5 0 )
C o o lin g
R a te d c u r r e n t A 2 .6 7 ( 1 .3 - 6 .5 ) 3 .3 ( 1 .5 - 7 .0 ) 4 .8 ( 1 .5 ~ 8 .5 )
EER B tu /w .h ,W /W 1 1 .5 , 3 .4 1 1 .5 , 3 .4 1 1 .3 , 3 .3
C a p a c ity B tu /h 9 0 0 0 (2 2 0 0 -1 2 5 0 0 ) 1 0 0 0 0 (2 4 0 0 -1 3 8 0 0 ) 1 4 0 0 0 (2 8 0 0 -2 0 5 0 0 )
In p u t W 7 1 0 (2 2 0 -1 4 0 0 ) 7 8 0 (2 4 0 -1 5 5 0 ) 1 1 2 0 (2 6 0 -2 0 5 0 )
H e a tin g
R a te d c u r r e n t A 3 .1 ( 1 .3 - 7 .3 ) 3 .4 ( 1 .4 - 7 .5 ) 5 .1 ( 1 .5 - 1 0 .0 )
COP W /W 3 .5 3 .7 3 .7
M o is tu r e R e m o v a l L /h 1 .0 1 .0 1 .2
M a x . in p u t c o n s u m p tio n W 2000 2100 2550
M a x. c u rre n t A 9 .5 1 0 .0 12
S ta r tin g c u r r e n t A 14 15 18
M odel 5CS090XC B 5CS090XCB 5C S102XFB
Type S c r o ll S c r o ll S c r o ll
B ra n d N a tio n a l N a tio n a l N a tio n a l
C a p a c ity B tu /h 10510 10510 11840
In p u t W 1000 1000 1150
C o m p re s s o r
R a te d c u r r e n t( R L A ) A 4 .4 4 .4 5 .2
L o c k e d r o to r A m p ( L R A ) A 40 40 50
T h e r m a l p r o te c to r C S -7 L N 1 1 5 C S -7 L N 1 1 5 C S -7 L N 1 1 5
C a p a c ito r uF No No No
R e fr ig e r a n t o il ml 360 360 360
M odel R PG 13H RPG 13H R PG 20D
B ra n d W e llin g W e llin g W e llin g
In d o o r fa n m o to r In p u t W 3 6 .5 3 6 .5 5 1 .5
C a p a c ito r uF 1 .2 1 .2 1 .5
S p e e d ( h i/m i/lo ) r /m in 1 3 0 0 /1 0 0 0 /8 5 0 1 3 0 0 /1 0 0 0 /8 5 0 1 3 0 0 /1 0 0 0 /9 0 0
a .N u m b e r o f r o w s 2 2 2
b .T u b e p itc h ( a ) x r o w p itc h ( b ) mm 2 1 x 1 3 .3 7 2 1 x 1 3 .3 7 2 1 x 1 3 .3 7
c .F in s p a c in g mm 1 .3 1 .3 1 .3
In d o o r c o il d .F in ty p e ( c o d e ) H y d r o p h ilic a lu m in iu m H y d r o p h ilic a lu m in iu m H y d r o p h ilic a lu m in iu m
e .T u b e o u ts id e d ia .a n d ty p e mm φ 7 IN N E G R O O V E T U B E φ 7 IN N E G R O O V E T U B E φ 7 ,in n e r g r o o v e tu b e
f.C o il le n g th x h e ig h t x w id th mm 5 7 8 X 2 5 2 X 2 6 .7 4 5 7 8 X 2 5 2 X 2 6 .7 4 6 3 5 X 3 1 5 X 2 7 .3 4
g .N u m b e r o f c ir c u its 2 2 2
In d o o r a ir flo w ( H i/M i/L o ) m 3 /h 5 7 0 /4 8 0 /3 5 0 5 7 0 /4 8 0 /3 5 0 7 0 0 /5 2 0 /4 2 0
In d o o r n o is e le v e l ( H i/M i/L o ) d B (A ) 4 2 /3 5 /3 0 4 2 /3 5 /3 0 4 2 /3 5 /3 0
D im e n s io n ( W * H * D ) mm 750×250×205 750×250×205 815×280×215
In d o o r u n it P a c k in g (W *H *D ) mm 830×335×285 830×335×285 915×360×290
N e t/G r o s s w e ig h t Kg 8 .0 /1 0 .0 8 .0 /1 0 .0 1 0 .0 /1 2 .0
M odel Y D K 2 4 -6 F Y D K 2 4 -6 F Y D K 3 6 -6
B ra n d W e llin g W e llin g W e llin g
O u td o o r fa n m o to r In p u t W 56 56 68
C a p a c ito r uF 2 .5 2 .5 2 .5
Speed r /m in 800 800 900
a .N u m b e r o f r o w s 2 2 2
b .T u b e p itc h ( a ) x r o w p itc h ( b ) mm 2 5 .4 x 2 2 2 5 .4 x 2 2 2 5 .4 x 2 2
c .F in s p a c in g mm 1 .4 1 .4 1 .5
O u td o o r c o il d .F in ty p e ( c o d e ) H y d r o p h ilic a lu m in iu m H y d r o p h ilic a lu m in iu m H y d r o p h ilic a lu m in iu m
e .T u b e o u ts id e d ia .a n d ty p e mm φ 9 .5 3 ,in n e r g r o o v e tu b e φ 9 .5 3 ,in n e r g r o o v e tu b e Ф 9 .5 3 ,in n e r g r o o v e tu b e
f.C o il le n g th x h e ig h t x w id th mm 6 8 0 x5 5 0 x4 4 6 8 0 x5 5 0 x4 4 6 8 0 x5 5 0 x4 4
g .N u m b e r o f c ir c u its 2 2 2
O u td o o r a ir flo w m 3 /h 1900 1900 1900
O u td o o r n o is e le v e l d B (A ) 52 55 55
D im e n s io n ( W * H * D ) mm 760X590X285 760X590X285 760X590X285
O u td o o r u n it P a c k in g ( W * H * D ) mm 890X655X360 890X655X360 890X655X360
N e t/G r o s s w e ig h t Kg 4 2 /4 5 4 2 /4 5 4 2 /4 5
R e fr ig e r a n t ty p e R 4 1 0 A g 1000 1000 1140
D e s ig n p r e s s u r e MPa 4 .2 4 .2 4 .2
L iq u id s id e / G a s s id e m m ( in c h ) Ф 6 .3 5 /Ф 9 .5 3 Ф 6 .3 5 /Ф 9 .5 3 Ф 6 .3 5 /Ф 1 2 .7
R e fr ig e r a n t p ip in g M a x . r e fr ig e r a n t p ip e le n g th m 10 10 10
M a x . d iffe r e n c e in le v e l m 5 5 5
C o n n e c tio n w ir in g No No No
P lu g ty p e 16A 16A 16A
T h e r m o s ta t ty p e E le c tr o lic c o n tr o l E le c tr o lic c o n tr o l E le c tr o lic c o n tr o l
O p e r a tio n te m p ℃ 17 30 17 30 17 30
A m b ie n t te m p ℃ -1 5 ? 45 -1 5 ? 45 -1 5 ? 43
A p p lic a tio n a r e a m2 1 4 -1 8 1 8 -2 4 2 0 -3 0
Q ty ’p e r 2 0 ’ /4 0 ’ /4 0 'H Q set 9 3 /2 0 9 /2 4 9 9 3 /2 0 9 /2 4 9 9 2 /1 9 5 /2 2 8
T O S H IB A R o ta r y T O S H IB A R o ta r y T O S H IB A R o ta r y
R e m a r k ( a lte r n a te c o m p r e s s o r )
D A 8 9 X 1 C -2 3 F Z D A 8 9 X 1 C -2 3 F Z D A 1 0 8 X 1 C -2 0 F Z
★1 The noise date is base on hemi-anechoic chamber, during actual operation, these values are normally somewhat different as a result of ambient
condition.
3
3.Dimensions
3.1 Indoor unit
CAS 7 I10, CAS 9 I10
4
3.4 Outdoor unit
750
285
590
62
315
290
530 110
5
4.Refrigeration cycle diagram
6
5. Pressure table
Note:
*The pressure data is from 3 way valve, the pressure data are pressure above atmosphere.
*D: Dry bulb temp.
*W: Wet bulb temp.
5.1 CAS 9 I10
Cooling mode Outdoor temperature (Dry bulb temp)
Indoor
Pressure 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
Conditions
21ºC D Pressure
8.7 8.7 8.9 9.0 10.0 10.6
15ºC W ( kg/cm2 )
24ºC D Pressure
9.0 8.9 8.9 9.0 10.5 11.0
17ºC W ( kg/cm2 )
27ºC D Pressure
9.0 9.0 9.0 9.6 11.0 11.5
19ºC W ( kg/cm2 )
7
5.2 CAS 12 I10
Cooling mode Outdoor temperature (Dry bulb temp)
Indoor
Pressure 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
Conditions
21ºC D Pressure
6.4 6.6 6.8 7.2 7.6 8.1
15ºC W ( kg/cm2 )
24ºC D Pressure
6.6 6.9 7.0 7.6 8.2 8.7
17ºC W ( kg/cm2 )
27ºC D Pressure
6.9 7.0 7.3 7.6 8.6 9.2
19ºC W ( kg/cm2 )
8
6. Capacity table
9
6.2 CAS 12 I10
COOLING OUTDOOR TEMPERATURE DRY
Indoor
21ºC 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
Conditions
Total capacity kW 3.187 3.48 3.30 3.01 2.81 2.38 2.16
21ºC D
Sensitive capacity kW 2.23 2.40 2.38 2.28 2.25 2.10 1.90
15ºC W
Input kW. 0.924 1.08 1.18 1.30 1.39 1.45 1.59
Total capacity kW 3.579 3.76 3.65 3.43 2.98 2.70 2.44
24ºC D
Sensitive capacity kW 2.505 2.61 2.66 2.61 2.41 2.35 2.20
17ºC W
Input kW. 0.957 1.10 1.19 1.33 1.41 1.49 1.61
Total capacity kW 3.879 4.09 3.90 3.50 3.19 2.99 2.79
27ºC D
Sensitive capacity kW 2.792 2.86 2.89 2.80 2.58 2.60 2.45
19ºC W
Input kW. 0.979 1.11 1.20 1.07 1.45 1.51 1.60
Total capacity kW 4.087 4.32 4.02 3.80 3.62 3.40 3.28
32ºC D
Sensitive capacity kW 3.168 3.80 3.01 3.07 3.11 2.96 2.89
23ºC W
Input kW. 0.989 1.12 1.25 1.40 1.48 1.55 1.68
10
7. Operation Limits
11
8 PCB diagram
8.1 Display board
1 2 3 4 5 6
+5
R7
221
D Q4 D
R8
9012
+5 102
104
IC1
1 14 C1
Dsa Vcc
2 13
Dsb Q7
3 12
Q0 Q6
LED1 LED2 LED3
4 11 DISP2
Q1 Q5
5 10
Q2 Q4
6 9
Q3 MR
R17 221
R15 221
R16 391
R9 221
7 8
GND CP
R11 391
R12 391
R13 391
R14 391
74HC164
CN1 8LED
C 7 C
6 CLK DEF R
5 DATA
4 +5 TIME Y
FROM INDOOR PCB DIGI +5
3 +5V AUTO G
2 REMOTE
1 GND E2 C3 C6 R6
47u/16V 221
104 102
Q1
9012
R5
102
+5
Q2
R1 102 9013 R10
151
R4 221 REC1
dig.1 g f a b
B DISP1 E4 B
C5
+5 d dp e c dig.2 10u/16V
R3 221 104
Q3
R2 102 9012
A A
Scale Sheet
0 of 0
1 2 3 4 5 6
CN1
1 CN10 IC4 CN3
R2 51/1W C2 FUSE1
L 1 16
1 STEP1 IN1 OUT1 1
2 L
333/250VAC E2 3.15A/250V 2
ZR1 2 15
470uF/25V 2 STEP2 IN2 OUT2 3
3 T2 T1 C5
14D681K 4
L1 DZ1 R4 R5 333/250VAC 3 14
TR1 D5 CN9 STEP3 IN3 OUT3 5
4 C25 12V 11K/2W 11K/2W
BT131 N
1.2(1.5)uF/450V 1 4 13
N STEP4 IN4 OUT4
5 IN4007 +12V
G
D D
2 5 12
FAN_IN +5V BUZZ IN5 OUT5
PTC1 B1
2K R1 R3 6 11 R8
t
GND
D3 IC8 ISO+12V
1 42 R10 X1
2200uF/25V 470uF/16V E7 C10 VSS0 X1
B 100uF/16V 105
2
2
1
223 2 41
CN5 D6 IN4007*4 IC12 7812 ISO+12V VDD0 X2
1 3 2.5M CN6 CN12
4 Vin Vout +5V 3 40
14.5VAC 350mA D7 INDOORFAN P25 RESET RST
GND
3 +5V
2 E5 C8 E6 C9 4 39 R11 10K
14.5VAC 200mA D9 BUZZ P26 XT1 IC9
1 104 104
5 38 R12 10K 2
TRANS_OUT D8 1000uF/25V STEP1 P00 XT2 3
2
RST C11
1
6 37 E8 104
2200uF/25V STEP2 P01 Vpp/IC
C ISOGND 7042 C
7 36 47uF/16V R13 103
STEP3 P02 P24 LED_C +5V
1 2 3 4 5 6 7 8
12
8.3 Outdoor main PCB
1 2 3 4 5 6
+5V
R49 +5V D3
10K
REST
C35 C41 C10
224 101 10uf/16v D2
SW1 +5V
3
2
1
D D
RESET
GND
VDD
D1
D8 AC-IN VOLTAGE SAMPLE
LED +5V W-
1
W+
4007 D7 2
R3 5.1K V-
CURRENT SAMPLE 3
IC1 R6 V+
S1 CT2 +5V 4
7042 R1 U-
390 C5 0057W 4007 5
U+
C6 6
POWER RLY
Q1 R2 R4 C7 7
FAN RLY
13
9 Wiring diagram
9.1 CAS 7 I10, CAS 9 I10 indoor unit
B
L
U
E
3 3 5
Y /G
B
R
O
W
N
CN3
CN9 CN1 CN13 ROOM TEMP. SENSOR
POWER SUPPLY
W
H
I
T
E
B
L
A
C
K
CN14 2
CN11
R
E
D
CN10
CN2 INDOOR PCB 2
RED CN4 P IPE T EMP. SENS OR
Y
E
L
L
O
W
CN8 CN6 7
HE AT EXC HANGER
SENSO R
OLP TEMP. SENSOR 2
2
Y/G 2
COMPRES SOR Y/G
AM BI ENT S EN S OR
RED
BLACK
RED
BLUE
BLUE
R ED 4- WAY OUTDOOR
YELLO W
3 FILTER
FAN
BLACK
4
RED
BLUE
RED
W V U N P
BL ACK
CN 16
BL UE
10
CN1 CN1
CN8
CN2 CN21 P-1
BLUE
2
O
UM
T
DA
O NB
O
R
CN13 CN12
CN2 3
I
CN4 3 TE RM I NA L
P
C
Y ELLOW
RLY1 4
WHITE
~ + +
B LACK
RED CN5
~
S
N
-
R ECTIFI ER
~ -
RECTIFIER
~ CT2
CN17 CN18
RED
L
REAC TOR1 LN S
ORANG E OR ANGE
14
9.3 CAS 12 I10 indoor unit
B
L
U
E
3
Y/G 3 5
B
R
O
W
N
W
H
I
T
E
CN14
B
L
A
C
K
2
CN11
R
E
D
CN10 INDOOR PCB
CN2 CN 4 2
RED P IPE TEMP. SENSOR
Y
E
L
L
O
W
CN8 CN6 7
JX1 CN5
CN12 CN 7
L N S
Y/ G DISPLAY BOARD
4 2 2 2
AUTO RESTART
(CHOICE)
L N S MICRO SWITCH
PLASMA
OUTDOOR UNIT TRANSFORMER
HE AT EXC HANGER
SENSO R
OLP TEMP. SENSOR 2
2
Y/G 2
COMPRES SOR Y/G
AM BI ENT S EN S OR
RED
BLACK
RED
BLUE
BLUE
R ED 4- WAY OUTDOOR
YELLO W
3 FILTER
FAN
BLACK
4
RED
BLUE
RED
W V U N P
BL ACK
CN 16
BL UE
10
CN1 CN1
CN8
CN2 CN21 P-1
BLUE
2
O
U
TM
D
O NB
O
R
CN13 CN12
CN2 3
AP
IC
CN4 3 TE RM I NA L
Y ELLOW
RLY1 4
WHITE
~ + +
B LACK
RED CN5
~
S
N
-
R ECTIFI ER
~ -
RECTIFIER
~ CT2
CN17 CN18
RED
L
REAC TOR1 LN S
ORANG E OR ANGE
2 20 -2 40 V~ 5 0Hz
12 000Btu /h 25A 1.5 mm2
15
10 Electronic function
10.1 Electric Control working environment.
10.1.1 Input voltage: 175~253V.
10.1.2 Input power frequency:50Hz.
10.1.3 Indoor fan normal working amp is less than 1A.
10.1.4 Outdoor fan. Normal working amp is less than 1.5A.
10.1.5 Four-way valve normal working amp is less than 1A.
10.1.6 Swing motor: DC12V.
1 2 3 4 5 6
10.2.1 AUTO indicator
This indicator illuminates when the air conditioner is in AUTO operation.
10.2.2 TIMER indicator
This indicator illuminates when TIMER is set ON/OFF.
10.2.3 PRE.-DEF. Indicator (For Cooling & Heating models only)
This indicator illuminates when the air conditioner starts defrosting automatically or when the warm air
control feature is activated in heating mode.
10.2.4 TEMPERATURE indicator
Usually it displays the temperature settings. When change the setting temperature, this indicator begins
to flash, and stops 20 seconds later.
It displays the room temperature when the air conditioner is in FAN only operation.
When the unit stops operation, it returns to original factory settings.
Displays the malfunction code or protection code.
10.2.5 OPERATION indicator
This indicator flashes after power is on and illuminates when the unit is in operation.
10.2.6 FREQUENCY indicator
This indicator appears only when the compressor is in operation and indicates the current operating
frequency.
16
10.3 Protection
10.3.1. 3 minutes delay at restart for compressor.
10.3.2. Temperature protection of compressor top, compressor stops when the temp. of top of compressor is
more than 115℃, compressor runs when the temp. of top of compressor is less than 100℃.
10.3.3. Voltage protection, unit stop when the voltage is more than 260V and less than 175V.
10.3.4. Inverter module Protection , Inverter module Protection itself has a protection function against current,
voltage and temperature.
10.3.5. Sensor protection at open circuit and breaking disconnection
10.3.6. Fan Speed is out of control. When Indoor Fan Speed is too high(higher than High Fan+300RPM)or
too low(lower than 400RPM), the unit stops and LED displays failure information and can’t return to
normal operation automatically.
10.3.7. Cross Zero signal error warning. If there is no Cross Zero signals in 4 minutes, the unit stops and LED
displays failure information and can’t return to normal operation automatically.
17
10.5.5 Current protection
Model Current Compressor
T<Ts+3 On On
34℃<T<37℃ Breeze
18℃<T<33℃ Breeze
T<18℃ Off
1.5℃<T<2.5℃ Med.
T>2.5℃ Low
1.0℃<T<2.0℃ Med.
T>2.0℃ Low
T<48℃ On
I< 10.5A On
I< 8.5A On
19
10.8. Defrosting operation (Available for heating only).
10.8.1 Defrosting condition:
10.8.1.1 When outdoor temp. is more than 0℃,
Defrosting starts when meeting one of the following conditions,
a. The temperature of outdoor heat exchanger remains consecutively lower than 3°c for more than
40 minutes, and the temperature remains consecutively -6°c for more than 3 minutes,
b. The temperature of outdoor heat exchanger remains consecutively lower than 3°c for more than
80 minutes, and the temperature remains consecutively -4°c for more than 3 minutes
10.8.1.2 When outdoor temp. is less than 0℃,
Defrosting starts when meeting one of the following conditions,
a. The temperature of outdoor heat exchanger remains consecutively lower than 3°c for more than
40 minutes, and the temperature remains consecutively -6°c for more than 3 minutes,
b. The temperature of outdoor heat exchanger remains consecutively lower than 3°c for more than
40 minutes, and the temperature remains consecutively -6°c for more than 3 minutes,
c. The temperature of indoor unit pipe decreases 5°c than before
10.8.1.3 The temperature of outdoor heat exchanger remains consecutively lower than 3°c for more than
120 minutes, and the temperature remains consecutively -2°c for more than 3 minutes
20
10.8.4 Rated capacity test
Set mode to cooling mode
Set temp. to 30 °C
Set fan speed to high speed
Push turbo button 5 times in 10 seconds.
Using special remoter controller
After 5 hours, cancel rated capacity test
TA—TS>2℃ Cooling
-1℃≤TA-TS≤+2℃ Fan-only
10.11.2. At Cooing mode, after 30 minutes cooling operation whose fan speed is set as low, the A/C operates
with a setting temp. of 24℃.
10.11.3. At auto mode, the A/C operates with a set temp. of 24℃
10.12. Timer Function
10.12.1. The maximum length of timer is 24 hours and the minimum resolving power is 15 minutes.
10.12.2. Timer on: first turn off the A/C, the A/C will be automatically on at the set time.
10.12.3. Timer off: first turn on the A/C, the A/C will be automatically off at the set time
10.12.4. Timer on/off function( on time is earlier than off time): first turn off the A/C, it will be automatically on
at set time, and later be off at the set time, then unit turns on at set time.
10.12.5. Timer off/on function( off time is earlier than on time): first turn on the A/C, it will be automatically off
at set time, and later be on at the set time, then unit turns off at set time.
22
11.Troubleshooting
11.1 Indoor Unit Error Display
Display LED STATUS
E0 EEPROM error
E4
P0 Module protection
E0 EEPROM error
Temporarily turn off the power supply and turn it on again in about 1 minutes
Yes
23
11.1.2
Display LED STATUS
Yes
No
1. check the signal wire between, is it
connected good.
2. replace the PCB of indoor unit ,is the
unit ok?
3. replace the PCB of power supply
board ,is the unit ok?
4
Yes
Yes
If PC817 or PC851 are defective, change indoor PCB or outdoor power PCB .
24
11.1.3
Display LED STATUS
Yes
Yes
11.1.4
Display LED STATUS
Yes
(rang 90v-160v between mid pin and N on CN2 Repair the connector
Yes
11.1.5
Display LED STATUS
11.1.7
Display LED STATUS
P0 Module protection
Yes
Check the outdoor inverter module.
No Yes
Check compressor
Inverter module is defective
26
11.1.8
Display LED STATUS
Yes
11.1.9
Display LED STATUS
No Replace protector
Yes
Gas charging
No
27
11.1.10
Display LED STATUS
No
Yes
11.1.11
Display LED STATUS
Yes
Yes
No
Yes
If the problem comes to again, check wingding resistance of inverter compressor, is it 0.64 ohm?
No
28
12. Characteristic of temp. sensor
Temp.℃ Resistance KΩ Temp.℃ Resistance KΩ Temp.℃ Resistance KΩ
-4 44 23 10.9731 50 3.451
-2 39.8239 25 10 52 3.1918
29
COOLWEX Group USA
Mobile Series
[Models]
Electronic Control
CMP 9 R7 (C)*
CMP 10 R7 (C)*
CMP 12 R7 (C)*
CMP 14 R7 (C)*
Remote Control
CMP 9 R7 (C)
CMP 10 R7 (C)
CMP 12 R7 (C)
CMP 14 R7 (C)
Contents
1. Features 2
2. Specification 3
3. Wiring diagram 6
4. Trouble shooting 8
5. Electronic function 11
1
1.Features
There is one exhaust pipe, which makes the A/C easier to use.
With water pump
The products have multiple uses: dehumidifying and cloth drying.
There is no need for special installation; they can be moved around for simple and
convenient use.
The heating system uses PTC electrical heater and will not be affected by ambient
temperature, which saves energy.
They are suitable for zone cooling and heating.
2.Specification
Thermostat type Electronic control Electronic control Electronic control Electronic control
Number of rows 2 2 2 2
Fin type (code) Hydrophilic aluminium Hydrophilic aluminium Hydrophilic aluminium Hydrophilic aluminium
Evaporator
Tube outside dia.and type mm Ф7x0.25, innergroove tube Ф7x0.25, innergroove tube Ф7x0.25, innergroove tube Ф7x0.25, innergroove tube
Number of circuits 2 2 2 2
Number of rows 2 2 2 2
Fin type (code) Unhydrophilic aluminium Unhydrophilic aluminium Unhydrophilic aluminium Unhydrophilic aluminium
Condenser Tube outside dia.and type mm Ф7x0.25, innergroove tube Ф7x0.25, innergroove tube Ф7x0.25, innergroove tube Ф7x0.25, innergroove tube
Number of circuits 2 2 2 2
1
Model CMP 10 R7* CMP 10 R7 C* CMP 10 R7 CMP 10 R7 C
Thermostat type Electronic control Electronic control Electronic control Electronic control
Number of rows 2 2 2 2
Fin type (code) Hydrophilic aluminium Hydrophilic aluminium Hydrophilic aluminium Hydrophilic aluminium
Evaporator Tube outside dia.and type mm Ф7x0.25, innergroove tube Ф7x0.25, innergroove tube Ф7x0.25, innergroove tube Ф7x0.25, innergroove tube
Number of circuits 2 2 2 2
Number of rows 2 2 2 2
Fin type (code) Unhydrophilic aluminium Unhydrophilic aluminium Unhydrophilic aluminium Unhydrophilic aluminium
Condenser Tube outside dia.and type mm Ф7x0.25, innergroove tube Ф7x0.25, innergroove tube Ф7x0.25, innergroove tube Ф7x0.25, innergroove tube
Number of circuits 2 2 2 2
2
Model CMP 12 R7* CMP 12 R7 C* CMP 12 R7 CMP 12 R7 C
EER Btu/w.h 9 9 9 9
Thermostat type Electronic control Electronic control Electronic control Electronic control
Number of rows 2 2 2 2
Fin type (code) Hydrophilic aluminium Hydrophilic aluminium Hydrophilic aluminium Hydrophilic aluminium
Evaporator Tube outside dia.and type mm Ф7x0.25, innergroove tube Ф7x0.25, innergroove tube Ф7x0.25, innergroove tube Ф7x0.25, innergroove tube
Number of circuits 2 2 2 2
Number of rows 2 2 2 2
.Fin type (code) Unhydrophilic aluminium Unhydrophilic aluminium Unhydrophilic aluminium Unhydrophilic aluminium
Condenser Tube outside dia.and type mm Ф7x0.25, innergroove tube Ф7x0.25, innergroove tube Ф7x0.25, innergroove tube Ф7x0.25, innergroove tube
Number of circuits 2 2 2 2
3
Model CMP 14 R7* CMP 14 R7 C* CMP 14 R7 CMP 14 R7 C
EER Btu/w.h 9 9 9 9
Thermostat type Electronic control Electronic control Electronic control Electronic control
Water tank volume L Inner water tank 3L Inner water tank 3L Inner water tank 3L Inner water tank 3L
Input W 16 16 16 16
Water Pump
Water flow 70 70 70 70
Height lift m 4 4 4 4
Number of rows 2 2 2 2
Fin type (code) Hydrophilic aluminium Hydrophilic aluminium Hydrophilic aluminium Hydrophilic aluminium
Evaporator Tube outside dia.and type mm Ф7x0.25, innergroove tube Ф7x0.25, innergroove tube Ф7x0.25, innergroove tube Ф7x0.25, innergroove tube
Number of circuits 2 2 2 2
Number of rows 2 2 2 2
Fin type (code) Unhydrophilic aluminium Unhydrophilic aluminium Unhydrophilic aluminium Unhydrophilic aluminium
Condenser Tube outside dia.and type mm Ф7x0.25, innergroove tube Ф7x0.25, innergroove tube Ф7x0.25, innergroove tube Ф7x0.25, innergroove tube
Number of circuits 2 2 2 2
4
3.Wiring diagram
3.1 all only-cooling types (C)
5
4. Malfunction and troubleshooting
Y
Is there DC5V between pin 3 and pin 7 of main chip
Is CN5 , CN6 and CN7 connector connected good? Check if AC230V exists at the
primary coil of transformer.
Check if 14V exists at the
secondary coil of transformer.
N Y Y
N
Y
Y
Is AC230V on fan motor?
c. No compressor working.
Is CN5 connector connected good?
Y
Is AC230V on R and S in compressor?
7
d. No water pump running.
Is CN5 and CN7 connector connected good?
Y
Y
Is AC230V on water pump?
Check fan motor and capacitor Is the RY4 normal in Control board
N
Y
Y
PTC is defective
N
Control board or display
board is defective
8
5.Electronic function
5.1 Cooling mode
The air flow speed can be set at high, medium and low.
The temperature can be set from 17℃~-30℃.
The action of the compressor
Condition Compressor
Temp. up T> Ts+1 On
T<Ts+1 Off
Temp. down T> Ts On
T<Ts Off
.
5.2 Heating mode
The air flow speed can be set at high or low;
The temperature can be set from 17℃~-30℃.
The action of the PTC heater:
Condition PTC heater
Temp. up T> Ts+1 Off
T<Ts+1 On
Temp. down T> Ts Off
T<Ts On
5.5 Timer
5.5.1 Timer On
Push the Timer On button to start the timer;
Time is relative time, from
0.5-1.0-1.5-2.0-2.5-3.0-3.5-4.0-4.5-5.0-5.5-6.0-6.5-7.0-7.5-8.0-8.5-9.0-9.5-10-11-12-13-1
4-15-16-17-18-19-20-21-22-23-24-0.0;
5.5.2 Timer Off
Push the Timer On button to start the timer;
Time is relative time, from
0.5-1.0-1.5-2.0-2.5-3.0-3.5-4.0-4.5-5.0-5.5-6.0-6.5-7.0-7.5-8.0-8.5-9.0-9.5-10-11-12-13-1
4-15-16-17-18-19-20-21-22-23-24-0.0;
.
9
5.6 Operation panel
5.6.1 With PTC model
OPERATION PANEL OF THE AIR CONDITIONER(COOLING AND HEATING)
COOL/ DRY /FAN /HEA T IN DIC ATOR
DI GITA L DISPLA Y FAN SPEE D IN DIC ATOR Gr een lamp wi ll l ight w hen the mode is s e lect ed
WATER FU LL IN DICAT OR
Red lamp wil l bli nk when the tank i s ful l
TE MP SET T ING BUT TON
Pr ess y our des ir ed ro om te mpe ratu re
se tting by pr es si ng th e but ton " " ( up)
or butto n " "( dow n)
P OWE R IN DICAT OR
IN FRA RED
SIGNA L R ECEIV ER POWE R BU TTON
Tu rn on/off the u nit
WATER FU LL IN DICAT OR
Red lamp wil l bli nk when the tank i s ful l
TE MP SET T ING BUT TON
Se lect your desir ed ro om temp eratu re
se tting by pr es si ng th e but ton " " ( up)
or butto n " "( dow n)
P OWE R IN DICAT OR
IN FRA RED
SIGNA L R ECEIV ER POWE R BU TTON
Tu rn on/off the u nit
10
off; the lamp of heating will flash at 2Hz, when the temperature lowers to 55℃, the PTC
returns to work.
At heating mode, when the temperature at air outlet is more 90℃, the fuse of PTC will be
broken.
.
5.7.4 The delayed protection for compressor
When the power is on for the first time, the compressor starts without waiting for 3
minutes; re-starting the machine after the compressor is stopped needs to wait for 3
minutes.
11