Documente Academic
Documente Profesional
Documente Cultură
I. INTRODUCTION
Fig.1 Structure of Experimental Apparatus
Internal conditions of SF6-insulated equipments are usually 2.2 Discharge Models
diagnosed by means of partial discharge detection [1]. Partial Partial discharges in SF6 insulated equipments are induced
discharge functions as both precursor and embodier of by the insulation deficiency. Different types of insulation
insulation failure. Long-standing partial discharge results in deficiencies cause different types of partial discharge. In light
gradual insulation degradation which may lead to the surface of fault frequency, fault attributes and modeling difficulties,
flashover and insulation breakdown [2-3]DŽ the present research simulates three types of partial discharge
Conventionally, what is applied in partial discharge models, i.e. protrusion discharge, floating discharge and
detection in SF6 insulated equipments [4-8] includes impulsive surface discharge.
current, ultra high frequency (UHF), acoustic and gas
decomposition. Compared to others, gas decomposition shows 2.2.1 Protrusion Discharge Model
apparent advantage in terms of anti-interference against It is simulated with a cooper wire of 2mm in diameter and
electromagnetic noises and vibration and easy applicability for 26mm in length. The cooper wire is fixated to the high-voltage
the diagnosis of overheating fault. Substantial studies [9-11] conductor. The distance from the ends of the cooper wire to
have analyzed the complicated physical and chemical process the apparatus surface is 4mm. An image of the actual
of SF6 decomposition. Among them, the relation between protrusion discharge model is shown in Fig.2.
partial discharge and SF6 decomposition products remains one
of the important issues worth addressing. However, a review
of literature in this regard finds little about that. To fill in the
gap, the present research attempts to analyze the impacts of
partial discharge pattern, PD discharge strength and SF6 gas
pressure over the concentration of SF6 decomposition
products. These findings are expected to provide a technical
reference and basis for the on-line fault detection and
diagnosis of SF6 insulated equipments. Fig.2 Protrusion Discharge Model
393
Fig.7 Change in HF Concentrations as a Function of Voltage Application Fig.8 Change in OF2+SO2 Concentrations as a Function of Voltage
Time Application Time
From Tab.2, Tab.3, Tab.4, Fig.6 and Fig.7, it is observed that
i) protrusion discharge, floating discharge, and surface
discharge all produce SOF2+SO2 and HF gases, which could
be identified as characteristic gases for detecting partial
discharge in SF6 insulated equipments; ii) both concentrations
of SOF2+SO2 and HF increase as the voltage application time
extends; iii) production speeds of SOF2+SO2 and HF
increases with the time of voltage application; iv) under all
three partial discharge patterns involved, the concentrations of
SOF2+SO2 is observed to be always higher than that of HF. Fig.9 Change in HF Concentrations as a Function of Voltage Application
Time
IV. PARTIAL DISCHARGE STRENGTH AND SF6 From the tables 6 and 7, and the figures 8 and 9, it could be
DECOMPOSITION PRODUCTS learned that after 10 hours of voltage application, SF6
4.1 Experimental Methods undertakes zero decomposition under 65kV and 75 kV, and
The present research selects floating discharge model (Fig.3) only a limited amount of 0.05ul/L SOF2+SO2 under 80 kV.
for different voltage application experiments. During the After 20, 30 and 40 hours of the voltage application, both the
experiments, PDM records Qmax, Qave, N, and Qtotal under concentrations of SOF2+SO2 and HF increase with increasing
differentiated discharge strength. After every 10 hours of the applied voltage. The higher the number of partial discharge
voltage application, concentrations are measured. is, the larger the discharge charge will be, and hence the
4.2 Experimental Results greater the discharge energy will be. The volume of SF6
Discharge properties under three PD strength (65kV, 75kV decomposition products bears direct relation with the total
and 80kV) are displayed in Table.5. Measurements of partial discharge energy. As all three experiment voltages are
SOF2+SO2 concentrations are provided in Table.6. The concerned, 80kV witnesses larger total discharge value and
measurements of HF concentrations are presented in Table.7. energy, and hence higher concentration in SF6 decomposition
Tab.5 products, compared to 65kV and 75kV. It can be inferred that i)
Discharge Characteristics under Three PD Severities
the stronger the PD is, the easier SF6 gas decomposes, and the
([SHULPHQW
9ROWDJH
4PD[S& 4DYHS& 1 4WRWDOS& greater decomposition concentrate are; ii) The gas detection
65kV 5000 1500 method is well applicable on consecutive and severe PD faults
75kV 10000 1099 whereas it shows little sensitivity to micro PD faults.
80kV 25000 3140
Tab.6 V. SF6 PRESSURE AND SF6 DECOMPOSITION
SOF2+SO2 Concentrations under Three PD Severities PRODUCTS
Experiment Results, ul/L
Voltage 10h 20h 30h 40h
5.1 Experimental Methods
65kV 0.00 0.05 0.12 0.18 In the present experiment, floating discharge model (Fig.3)
75kV 0.00 0.02 0.11 0.23 is selected to study the relation between SF6 pressures
80kV 0.05 0.12 0.16 0.29 (0.2MPa, 0.3MPa and 0.4MPa) and SF6 decomposition
Tab.7 products. During the experiments, PDM records Qmax, Qave,
HF Concentrations under Three PD Severities
Experiment Results, ul/L
N, and Qtotal under differentiated SF6 pressures. The
Voltage 10h 20h 30h 40h concentrations of decomposition products are measured every
65kV 0.00 0.00 0.05 0.13 10 hours period of the voltage application.
75kV 0.00 0.10 0.16 0.23 5.2 Experimental Results
80kV 0.00 0.13 0.19 0.32 Discharge properties under three differentiated pressures
4.3 Experiment Data Analysis (0.2MPa, 0.3MPa, and 0.4MPa) are listed in Table 8 below.
The tables 6 and 7, and the figures 8 and 9 show the change Measurements of SOF2+SO2 concentrations are shown in
in SOF2+SO2 and HF concentrations under differentiated Table 9 while measurements of HF concentrations are
discharge strength scales as a function of voltage application presented in Table 10.
time.
394
Tab.8 VI. CONCLUSIONS
Discharge Characteristics under Three SF6 Pressures
1) Protrusion discharge, floating discharge, and surface
3UHVVXUH 4PD[S& 4DYHS& 1 4WRWDOS&
0.2MPa 5000 1405
discharge in SF6 insulated equipments all produce SOF2+SO2
231825
0.3MPa 4800 1239 240366
and HF gases, which are suggested to be the characteristic
0.4MPa 5000 1588 225496 gases for detecting partial discharge in SF6 insulated
Tab.9 equipments. In light of all three partial discharge patterns
SOF2+SO2 Concentrations under Three Differentiated SF6 Pressures involved, the concentration of SOF2+SO2 is observed to be
Pressure
Results , ul/L always higher than that of HF. The production speeds of
10h 20h 30h 40h 50h SOF2+SO2 and HF increase as the voltage application time
0.2MPa 0.00 0.02 0.16 0.22 ˉ
prolongs.
0.3MPa 0.00 0.05 0.12 0.18 ˉ
0.4MPa 0.00 0.00 0.00 0.04 0.07
2) In presence of different degrees of partial discharge strength,
Tab.10 the concentrations of SOF2+SO2 and HF appear to be
HF Concentrations under Three Differentiated SF6 Pressures different. The more severe the partial discharge is, the higher
Pressure
Results, ul/L the concentrations of SOF2+SO2 and HF will be. The gas
10h 20h 30h 40h 50h detection method applies well on consecutive and severe
0.2MPa 0.00 0.02 0.08 0.17 ˉ partial discharge faults in SF6 insulated equipments while it
0.3MPa 0.00 0.00 0.05 0.13 ˉ shows little sensitivity to micro partial discharge faults.
0.4MPa 0.00 0.00 0.00 0.02 0.11
3) As SF6 pressure increases, the generation speed of
SOF2+SO2 and HF decreases.
5.3 Experiment Data Analysis
In accordance with the data in the tables 9 and 10, the REFERENCES
figures 10 and 11 demonstrate the change in SOF2+SO2 and
[1] CIGRE Working Group 33/32-12. Insulation Co-ordination of GIS:
HF concentrations under various pressure rates as a function
Return of Experience, on Site Tests and Diagnostic techniques. Electra,
of voltage application time.
1998, 176(2): 67-95.
[2] IEEE Substations Committee Working Group K4. Partial Discharge
Testing of Gas Insulated Substations [J]. IEEE Transactions on Power
Delivery, 1992, 7(2): 499-506.
[3] J.S.Pearson, O.Farish, B.F.Hampton, M.D.Judd, D.Templeton. Partial
Discharge Diagnostics for Gas Insulated Substations [J]. IEEE
Transactions on Dielectrics and Electrical Insulation, 1995, 2(5): 893-905.
[4] CIGRE WG 15. 03. Diagnostic Methods for Gas Insulating systems[C].
CIGRE Report 15/23-01, 1992.
Fig.10 Change in SOF2+SO2 Concentrations as a Function of Voltage [5] IEC60270 High-voltage Test Techniques- Partial discharge measurements
Application Time [S], International Standard, 2000.
[6] A.G.Sellars, O.Farish, M.M.Peterson. UHF Detection of Leader
Discharges in SF6 [J].IEEE Transactions on Dielectrics and Electrical
Insulation, 1995, 2 (1): 143-154.
[7] L.E.Lundgaard, G.Tangen, B.Skyberg, et al. Acoustic diagnoses of GIS:
field experience and development of expert system [J]. IEEE
Transactions on Power Delivery, 1992, 7(1): 287-294.
[8] S.Tominaga, H.Kuwahara, K.Hirooka, T.Yoshioka. SF6 gas analysis
technique and its application for evaluation of internal conditions in SF6
gas equipment[J]. IEEE Transactions on Power Apparatus and Systems,
Fig.11 Change in HF Concentrations as a Function of Voltage Application 1981, 100(9) : 4196-4206.
Time
[9] ZHANG Xiao-xing, YAO Yao, TANG Ju, et al. Actuality and Perspective
From the tables 9, 10, and the figures 10 and 11, it is known
of Proximate Analysis of SF6 Decomposed Products Under Partial
that SF6 starts to decompose after 30 hours of voltage
Discharge[J] [In Chinese]. High Voltage Engineering, 2008, 34(4):664-
application at 0.4MPa whereas SF6 decomposition occurs
669.
after only 10 hours at 0.2MPa and 0.3MPa. It could be
[10] F.Y.Chu. SF6 decomposition in gas-insulated equipment [J] IEEE
indicated that the higher the pressure is, the more difficult the
Transactions on Electrical Insulation, 1986, 21 (5): 693-725.
decomposition occurs. After 40 hours of voltage application,
under 0.2, 0.3 and 0.4 MPa, the concentrations of SOF2+SO2 [11] Derdouri A, J Casanovas. Spark decomposition mixtures of SF6/ H2O [J].
are recorded as 0.22, 0.18 and 0.04ul/L respectively, while IEEE Transactions on Electrical Insulation, 1989, 24 (6):1147-1157.
those of HF are measured as 0.17, 0.13 and 0.02 ul/L [12] IEC60480:2004 Guidelines for the checking and treatment of sulfur
separately. Both the concentrations and generation speeds of hexafluoride (SF6) taken from electrical equipment and specification for
SOF2+SO2 and HF decrease as the SF6 pressure increase. its re-use [S], IEC, 2004.
395