Analog Panel & Switchboard Meters - Introduction

General Specifications High Voltage Test permanent magnet. They can be used on
Standards All instruments are designed to withstand alternating current with a suitable rectifier
All instruments are designed in accordance 2.5kV RMS, 50Hz, for 1min. inserted in the circuit.
with the following international and national Shock and Vibration Resistance Moving Coil instruments above 50A, the
regulations : IS-1248; IEC-51; IEC-1010; ammeters are to be used with external Shunts
All meter movements are mounted on spring
BS89; EN60051 respectively various having 60mV or 75mV drop. The Shunts are
loaded shock absorbing type of jewel
instruments. The overall dimensions comply usually calibrated for a lead resistance of
bearings which make the instrument capable
with DIN43700 - 43718. usually less than 0.07 Ohm. When lead
of offering good resistance to shocks and
Technical Specifications resistance is greater than 0.1 Ohm, it is
vibration. This mechanism is much superior
advisable to use shunts of 100, 150 or
Materials to traditional Taut-Band construction which
300mV drop.
Case : Complies to DIN 43700 is highly fragile. The Pivot Jewel mechanism
is ideal for aviation, traction and marine Electronic Analog Watt, Var, PF & Hz
Colour : White
applications. Meters
Front Frame : Complies with DIN 43718
Pointer These instruments are available for
Colour : Black measuring Active and Reactive Power in
Front Glass : Flat glass The pointers are in accordance with DIN
single phase and three phase balanced or
43802.
Protection unbalanced load conditions. In addition to
Case : IP52; IP54 on request Zero Adjustment these we manufacture Power Factor Meters
Terminals : IP00 A screw for zero adjustment is located on the for single phase and three phase balanced
front glass. load systems and line Frequency meters for
IP20 (with terminal cover)
Scales different voltage ratings and different
Overload Capabilities frequency bands.
Withstand continuous overloads of 1.2 times Instrument scales are in accordance with
DIN43802 regulations. Special scales are Electronic Power meters use multiplier
for Ammeter and Voltmeter the nominal
available on request. circuits which multiply instantaneous
value and short duration overloads of upto
voltage and current.
10 times for Ammeter and upto 2 times for Markings and Symbols on Instruments /
Voltmeter the nominal values for 5 seconds. Meters The average of the product is in the form of
Climatic Conditions analog DC current directly proportional to
According to IEC51 requirements, all the AC power. This power is measured with
Reference temperature for these instruments measuring instruments and their accessories
0 0 DC moving coil meter. Scale is adjusted to
is 27 C ± 2 C. The standard instruments can bear on the dial, or on the external surface of indicate power. Sometimes these meters are
operate at a maximum relative humidity of the case, the markings indicating :
used along with CTs and PTs. Bi-directional
90%.
l Manufacturers name or trade mark Watt/Var Meters to indicate export / import
Operating Temperature can be supplied on request.
0 0
l Symbol of the measured parameter
-10 C to + 55 C, RH<90%
l Accuracy / Accuracy Class In Frequency meter a DC current
Storage Temperature proportional to the input frequency is
0 0
l Type of power supply and the number of
-20 C to + 70 C, RH<90% measuring elements obtained by using an electronic circuit. This
Accuracy Class output is calibrated in terms of frequency.
l Test Voltage
All instruments are calibrated according to The circuit for Powerfactor meter gives
l Operating method of the instrument current output proportional to phase angle.
Accuracy Class specified below as per
applicable international standards : l Rated value This output is bidirectional to discriminate
l Moving Iron Meters : 1.5 l Symbol for mounting position between leading and lagging Powerfactor.
l Moving Coil Meters : 1.0, 1.5, 2.5 l Symbol of the accessory or the transformer Scale is marked in terms of Cosf, f being the
ratio for which the instrument has been phase angle between voltage and current
l Electronic Analog Watt / Var Meters :
calibrated. vector.
1.5/1.0
0 Since these Watt meters and Var meters are
l Power Factor Meters : ±2 Phase Angle Moving Iron Meters
self powered, it is essential that the input
l Frequency Meters : 1.0 These instruments consist of a moving piece voltage is within ±15% of the nominal
Influence of External Magnetic Fields of ferro magnetic material, which is under value. At lower voltage, the instrument will
Moving Iron Meters are provided with an influence of a current carrying fixed coil. function erratically.
internal shield cup in order to prevent the Considering the above mentioned operating
To get proper accuracy from Powerfactor
influence of stray and low intensity magnetic process, these instruments are ideally suited
for measuring TRMS current and voltage in meter, please ensure input voltage is within
fields.
alternating current circuits. Accuracy for ±15% of the rated value & current is
Moving Coil and all other instruments have a between 20% to 120% of the rated value.
center core self-shielding construction these meters is applicable only within the
which protects against stray and external low nominal working range and not in the Note
intensity magnetic fields. overscale range. When using external Power meters and Powerfactor meters are
current transformer, please ensure that the normally supplied for 47 to 53 Hz operation.
Mounting Position
secondary current value of the CT must be On request meters to suit 60Hz or 400 Hz
The nominal operating position of the panel the rated current of the Ammeter i.e., In. can be supplied.
meters is vertical. The required mounting
position is shown on the scale of the Moving Coil Meters Active power, Reactive power & Low
instrument. Instruments with horizontal and The operation of these instruments depends Powerfactor Wattmeter are calibrated at
angular mounting positions can be supplied on the reaction of the current circulating in a Cosf = 1, Sinf = 1 and Cosf = 0.2 Lag
on request. moving coil and the field of a fixed respectively.

62
Electronic Analog W / VAR / PF / Hz Meters
- Connection Diagram, Scale & Method of Working

Burden 1
Electronic meters impose lower burden on supply than the conventional meters.
Typical values are given below.
Watt & Var Meters 1-Phase, 230/250V < 1.0
Voltage Rating Total Burden(VA) 3-Phase, 110V < 0.4
1-Phase, 63.5V < 0.5 3-Phase, 400/440V < 1.5
1-Phase, 230/250V < 2.0 Current Rating Total Burden (VA)
3-Phase, 110V < 3x0.5 1.0 A < 0.5 1 f1 Element Watt Meter and Var Meter
3-Phase, 400/440V < 3x2.0 5.0 A < 0.5
Current Rating Total Burden (VA) Frequency Meters 2
1.0A < 1VA/Phase Voltage Rating Total Burden (VA)
5.0A < 1VA/Phase 63.5V < 0.7
Powerfactor Meters 110V < 1.2
Voltage Rating Total Burden (VA) 230/250V < 2.5
1-Phase, 63.5V < 0.25 400/440V < 4.5

3 f1 Element Watt Meter and Var Meter


Scale for balanced load only
Watt & Var Meters
Upper limits of measuring range is one of the decimal or subdecimal values from the 3
following,
1, 1.2, 1.5, 2, 2.5, 3, 4, 5, 6, 7.5 & 8.
In the interest of standardisation it is recommended that the maximum value of the measuring
range is chosen accordingly. Following examples will illustrate the method of working out
these values.
i) Single Phase
V=250V , I = 5A, Cosf =1
Power = V.I.Cosf =250x5x1 = 1250W 3 f1 Element - D Type Watt Meter and Var Meter
for balanced load only
Maximum upper limit in this case should be 1200 or 1500W.
ii) Three Phase
V = 110V, PTR = 33k V/110V
4
I = 5A, CTR = 500/5A, Cosf= 1
Power = £3.V.I.Cosf.PTR.CTR
Power = £3x110x5x1x33x1000x500
110 5
= 28.578x10 = 28.578MW
Maximum upper limit in this case should be 25MW or 30MW.
3 f 2 Element - D Type Watt Meter and Var Meter
for balanced and unbalanced load
Ordering Information
Please give the following details while 5
ordering : Example :
Model :_____________ Model : 96QW32
Full Scale Range :_____________ Full Scale Range : 0-6 MW
CTR :_____________ CTR : 600/5A
Voltage (Ph-Ph or Ph-N) :_____________ Voltage Ph-Ph : 110V AC
PTR ( if any ) :_____________ PTR : 6.6KV/110V
Connection diagram number :_____________ Connection diagram number :4 3 f 3 Element Watt Meter and Var Meter
for balanced and unbalanced load

6 7 8

Note : P=2, N=4, k=7 & l=9 only for 144LF11 Note : M=2, L=4, Y=7 & B=9 only for 144LF31

3 f 1 Element Pf Meter
1 f 1 Element Pf Meter Frequency Meter
for balanced load only

63