PROJECT DATA:
Project name: WATER SECURITY MEGA RESERVOIR PACKAGE APRPS-1 UMM BRIKA
Subject/Topic:
Description:
Notes/Remarks:
Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines and must be checked for plausibility.
www.powers.com - Powers Fasteners (See website for regional contact info). anchorbolt design.pcp2
Company name: ASMA
Project: WATER SECURITY MEGA Date: 11/25/2017
RESERVOIR PACKAGE APRPS-
1 UMM BRIKA
Version: 2.3.5822.18147 Project number: GTC 626/2014 Page: 2/6
GEOMETRY:
Eccentric profile
e x = 0 mm; e y = 75 mm
Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines and must be checked for plausibility.
www.powers.com - Powers Fasteners (See website for regional contact info). anchorbolt design.pcp2
Company name: ASMA
Project: WATER SECURITY MEGA Date: 11/25/2017
RESERVOIR PACKAGE APRPS-
1 UMM BRIKA
Version: 2.3.5822.18147 Project number: GTC 626/2014 Page: 3/6
SUMMARY:
Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines and must be checked for plausibility.
www.powers.com - Powers Fasteners (See website for regional contact info). anchorbolt design.pcp2
Company name: ASMA
Project: WATER SECURITY MEGA Date: 11/25/2017
RESERVOIR PACKAGE APRPS-
1 UMM BRIKA
Version: 2.3.5822.18147 Project number: GTC 626/2014 Page: 4/6
Steel failure:
γ M,s 1.90
h 39.47 kN
N Rd,s
h 6.91 kN
N Sd
Design proof: h h
N Sd/N Rd,s= 0.18 ≤ 1.00
0
N Rk,c 43.80 kN 5.2.2.4
ψ ec,N,x 1.000
ψ ec,N,y 0.855
ψ re,N 1.000
ψ s,N 1.000
ψ ucr,N 1.000
γ M,c 1.80
N Rd,c 52.00 kN
N Sd 20.63 kN
Design proof: N Sd/N Rd,c= 0.40 ≤ 1.00
Pullout failure:
γ M,p 1.8
N Rd,p 13.52 kN
h 6.91 kN
N Sd
Design proof: h
N Sd/N Rd,p= 0.51 ≤ 1.00
Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines and must be checked for plausibility.
www.powers.com - Powers Fasteners (See website for regional contact info). anchorbolt design.pcp2
Company name: ASMA
Project: WATER SECURITY MEGA Date: 11/25/2017
RESERVOIR PACKAGE APRPS-
1 UMM BRIKA
Version: 2.3.5822.18147 Project number: GTC 626/2014 Page: 5/6
γ Ms 1.60
h 30.63 kN
V Rd,s
h 7.50 kN
V Sd
Design proof: h h
V Sd/V Rd,s= 0.24 ≤ 1.00
h ef 100 mm 5.2.3.3
0 43.80 kN
N Rk,c
A c,N 300000 mm²
0 90000 mm²
A c,N
k 2.0
ψ ec,N,x 1.000
ψ ec,N,y 1.000
ψ s,N 1.000
ψ re,N 1.000
ψ ucr,N 1.000
V Rk,cp 291.97 kN
γ Mcp 1.50
V Rd,cp 194.65 kN
g 45.00 kN
V Sd
Design proof: g
V Sd/V Rd,cp= 0.23 ≤ 1.00
Displacements
The resulting displacements of the highest loaded anchor shall be calculated according to the requirements in the corresponding
approval.The characteristic loadings sum up to a total of:
h = 5.12 kN
N
Sk
Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines and must be checked for plausibility.
www.powers.com - Powers Fasteners (See website for regional contact info). anchorbolt design.pcp2
Company name: ASMA
Project: WATER SECURITY MEGA Date: 11/25/2017
RESERVOIR PACKAGE APRPS-
1 UMM BRIKA
Version: 2.3.5822.18147 Project number: GTC 626/2014 Page: 6/6
h = 5.56 kN
V
Sk
The allowable displacements depend on the construction fastened with the anchors. They shall be defined by the responsible engineer!
The transfer of the anchor loads in the structural element must be shown according to the design guideline ETAG 001
or TR 029, Section 7.1!
The design proof for shear loads is necessary according to the approval and/or according to EC 2(or other national
regulations).
Fastening ok!
WARNINGS / REMARKS:
Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines and must be checked for plausibility.
www.powers.com - Powers Fasteners (See website for regional contact info). anchorbolt design.pcp2