17. A generator rated at 30MVA, 11KV has a reactance of 20%.Calculate its per unit
reactance for a base of 50 MVA and 10KV.
MVA new = 50 ; KV new = 10 ; MVA old = 30 ; KV old = 11
X p.u = 20% = 20/100 = 0.2 p.u
𝐵𝑎𝑠𝑒 𝐾𝑉𝑜𝑙𝑑 2 𝐵𝑎𝑠𝑒 𝑀𝑉𝐴𝑛𝑒𝑤
𝑋𝑝.𝑢,𝑛𝑒𝑤 = 𝑋𝑝.𝑢,𝑜𝑙𝑑 × [ ] ×[ ]
𝐵𝑎𝑠𝑒 𝐾𝑉𝑛𝑒𝑤 𝐵𝑎𝑠𝑒 𝑀𝑉𝐴𝑜𝑙𝑑
11 2 50
𝑋𝑝.𝑢,𝑛𝑒𝑤 = 𝑗0.2 × [ ] × [ ] = 𝑗0.4033 𝑝. 𝑢
10 30
18. What is the new p.u impedance if the new base MVA is twice the old base MVA?
𝑀𝑉𝐴𝑛𝑒𝑤 = 2 𝑀𝑉𝐴𝑜𝑙𝑑
𝐵𝑎𝑠𝑒 𝐾𝑉𝑜𝑙𝑑 2 𝐵𝑎𝑠𝑒 𝑀𝑉𝐴𝑛𝑒𝑤
𝑍𝑝.𝑢,𝑛𝑒𝑤 = 𝑍𝑝.𝑢,𝑜𝑙𝑑 × [ ] ×[ ]
𝐵𝑎𝑠𝑒 𝐾𝑉𝑛𝑒𝑤 𝐵𝑎𝑠𝑒 𝑀𝑉𝐴𝑜𝑙𝑑
𝐵𝑎𝑠𝑒 𝐾𝑉𝑜𝑙𝑑 2 2 𝐵𝑎𝑠𝑒 𝑀𝑉𝐴𝑜𝑙𝑑
𝑍𝑝.𝑢,𝑛𝑒𝑤 = 𝑍𝑝.𝑢,𝑜𝑙𝑑 × [ ] ×[ ]
𝐵𝑎𝑠𝑒 𝐾𝑉𝑛𝑒𝑤 𝐵𝑎𝑠𝑒 𝑀𝑉𝐴𝑜𝑙𝑑
𝐵𝑎𝑠𝑒 𝐾𝑉𝑜𝑙𝑑 2
𝑍𝑝.𝑢,𝑛𝑒𝑤 = 2 𝑍𝑝.𝑢,𝑜𝑙𝑑 × [ ]
𝐵𝑎𝑠𝑒 𝐾𝑉𝑛𝑒𝑤