STRUCTURAL NOTES REINFORCED CONCRETE


CONCRETE WORK SHALL CONFORM TO ALL REQUIREMENTS OF "ACI 301", LATEST EDITION,
INDICATES 14" DIAMTER AUGER
CAST PILE 35 TON CAPACITY
- - -

GENERAL ENGINEERING AND CONSTRUCTION "SPECIFICATIONS FOR STRUCTURAL CONCRETE FOR BUILDINGS," EXCEPT AS MODIFIED BY THE 4,000 PSI CONCRETE, 10 TON
SUPPLEMENTAL REQUIREMENTS BELOW. TENSILE CAPACITY, 2 TON
LATERAL CAPACITY R I O A R A G O N
DESIGN AND CONSTRUCTION SHALL BE IN COMPLIANCE WITH THE 2014 FLORIDA BUILDING PORTLAND CEMENT :
CODE, LATEST BROWARD CO. EDITION, AND THE REQUIREMENTS SET FORTH BY SECTION 16B-33 PORTLAND CEMENT SHALL BE TYPE "I", CONFORMING TO ASTM C-150.
OF THE FLORIDA ADMINISTRATIVE CODE AND CHAPTER 161 OF THE FLORIDA STATUTES.
CONCRETE AGGREGATES :
GENERAL: NOMINAL MAXIMUM SIZE OF COARSE AGGREGATES SHALL NOT BE LARGER THEN 3/4 INCHES.
CONSTRUCTION METHODS, PROCEDURES, AND SEQUENCES ARE THE RESPONSIBILITY OF THE
CONTRACTOR. THE CONTRACTOR SHALL TAKE THE NECESSARY MEANS TO MAINTAIN AND ADMIXTURES:
PROTECT THE STRUCTURAL INTEGRITY AND SERVICEABILITY OF THE CONSTRUCTION AT ALL CONCRETE MAY CONTAIN A WATER REDUCING ADMIXTURE CAPABLE OF INCREASING 6'-4" 6'-10"

2'-6"
TIMES. WORKABILITY AND REDUCING THE AMOUNT OF MIXING WATER, CONFORMING TO ASTM C-494,
TYPE "A", OTHER ADMIXTURES MAY BE USED IF APPROVED BY THE ENGINEER.
CONSTRUCTION LOADS:
STRUCTURAL MEMBERS AS SHOWN IN THE WORKING DRAWINGS HAVE BEEN DESIGNED TO QUALITY OF CONCRETE:
CARRY THE CODE REQUIRED SERVICE LOADS ONLY. THE STRUCTURAL DESIGN OF THIS (a) CONCRETE SHALL BE NORMAL WEIGHT, AND SHALL ATTAIN A 28-DAY MINIMUM 1 1 2 . 6 7 F T. EXISTING SEAWALL
PROJECT HAS NOT CONSIDERED LOADS IMPOSED DURING CONSTRUCTION. CONSTRUCTION COMPRESSIVE STRENGTH OF 4000 psi, UNLESS OTHERWISE STATED IN THE PLANS.

4"

2'

2'
LOADS MAY EXCEED THE SERVICE DESIGN LOADS. THE CONTRACTOR SHALL BE RESPONSIBLE (b) THE MAXIMUM WATER-CEMENT RATIO SHALL BE 0.55.

Florida #37467
FOR ENGAGING THE NECESSARY CONSTRUCTION ENGINEERING AND DESIGN, AND (c) THE MINIMUM CEMENT CONTENT FOR CONCRETE SHALL BE 5 BAGS PER CUBIC YARD.

TIES #3@12" 0.C.


DETERMINING AND EMPLOYING THE METHODS NECESSARY TO SUPPORT ALL LOADS IMPOSED (d) UNLESS OTHERWISE PERMITTED OR SPECIFIED, THE MAXIMUM ALLOWABLE SLUMP OF VARIES (SEE PLANS)
DURING CONSTRUCTION. CONCRETE SHALL BE FOUR INCHES. NO WATER SHALL BE ADDED AT THE JOB SITE TO BOTTOM OF PILE CAP
READY-TO-USE CONCRETE WITHOUT THE APPROVAL OF THE ENGINEER, AND THEN ONLY

12' 0"
CONSTRUCTION COORDINATION :

James F. Biagi P.E.


WHEN SLUMP TESTS ARE MADE AND THE CONCRETE SO DELIVERED IS KNOWN TO BE OF

15'

15'
THE CONTRACTOR SHALL COORDINATE ALL WORK REQUIRED BY THE ARCHITECTURAL, LESS THAN THE SLUMP SPECIFIED.
STRUCTURAL, MECHANICAL, PLUMBING AND ELECTRICAL WORKING DRAWINGS, AND SHALL

T: 954.776-8004 | F:954.776.8015
VERIFY ALL DIMENSIONS, ELEVATIONS, AND THE LOCATION AND SIZES OF ALL CHASES, TEST ON CONCRETE:

1915 NE 45th Street, Suite 107


INSERTS, OPENINGS, SLEEVES, FINISHES, DEPRESSIONS, AND OTHER PROJECT REQUIREMENTS (a) 1) TESTS ON CONCRETE USED IN CONSTRUCTION SHALL BE MADE BY AN APPROVED
NOT SHOWN ON THE STRUCTURAL WORKING DRAWINGS. TESTING LABORATORY, AND REPORTS SUBMITTED TO THE ENGINEER. THE COSTS OF SUCH
POOL

Ft. Lauderdale, Florida 33308


TESTS SHALL BE ASSUMED BY THE OWNER.
FAUX TURF SPA
CONFLICTS: 2) NOT LESS THAN THREE SPECIMENS SHALL BE MADE FOR EACH STANDARD TEST, NOT

Consulting Engineer
WHEREVER CONFLICTS, DISCREPANCIES, OR AMBIGUITIES EXIST IN THE STRUCTURAL LESS THAN ONE TEST FOR EACH 50 CUBIC YARDS OF CONCRETE USED ON THE PROJECT.
DRAWINGS, SCHEDULES OR NOTES, THEY SHALL BE BROUGHT TO THE ATTENTION OF THE 3) SPECIMENS SHALL BE TESTED IN ACCORDANCE WITH THE STANDARD METHOD OF TEST COMPRESSION PILE
ARCHITECT AND ENGINEER FOR CORRECTION AND/OR CLARIFICATION. FOR COMPRESSION STRENGTH OF MOLDED CONCRETE CYLINDERS, ASTM C39-72. REPORTS
TO THE ENGINEER SHALL BE SUBMITTED FOR EACH TEST PERFORMED.
SHOP DRAWINGS: (b) THE AGE FOR STRENGTH TESTS OF CONCRETE SHALL BE 28-DAYS. STRENGTH TESTS FOR
(a) THE CONTRACTOR SHALL SUBMIT SHOP DRAWINGS DETAILING CONCRETE REINFORCING AN EARLIER AGE SHALL BE SUBMITTED IF THE ENGINEER HAS APPROVED CONCRETE IN

15'

15'
STEEL, PRECAST AND PRESTRESSED STRUCTURAL CONCRETE UNITS, STRUCTURAL AND

SEE SOIL REPORT


THE STRUCTURE TO RECEIVE ITS FULL WORKING LOADS AT SUCH EARLIER TIME. SEVEN
MISCELLANEOUS STEEL, WOOD ROOF TRUSSES, AND OTHER CONSTRUCTION REQUIRING

END OF PILE
DAY TESTS MAY BE USED WITH THE APPROVAL OF THE ENGINEER, PROVIDED THAT THE
OFF-SITE FABRICATION INCLUDED IN THE STRUCTURAL DRAWINGS FOR THE APPROVAL OF RELATION BETWEEN THE SEVEN AND 28-DAY STRENGTHS OF THE CONCRETE IS
THE ENGINEER. ESTABLISHED BY TEST FOR THE MATERIALS AND PROPORTIONS USED.
(c) WHEN THERE IS A QUESTION AS TO THE QUALITY OF THE CONCRETE IN THE STRUCTURE,
(b) APPROVAL OF SHOP DRAWINGS BY THE ENGINEER IS FOR DESIGN AND LAYOUT ONLY, AND THE ENGINEER SHALL HAVE THE RIGHT TO REQUIRE CORE TESTS IN ACCORDANCE WITH
IS NOT FOR THE PURPOSE OF AUTHORIZING CHANGES TO THE CONTRACT DRAWINGS OR THE STANDARD METHODS OF OBTAINING AND TESTING DRILLED CORES AND SAWED
APPROVING SUBSTITUTIONS. THE CONTRACTOR SHALL COMPLY WITH THE REQUIREMENTS BEAMS OF CONCRETE, (ASTM C42), TO ORDER LOAD TESTS ON THAT PORTION OF THE
OF THE CONTRACT DRAWINGS, GENERAL CONDITIONS, SUPPLEMENTAL GENERAL STRUCTURE WHERE THE QUESTIONABLE CONCRETE HAS BEEN PLACED, OR TO REQUIRE
CONDITIONS, SPECIAL CONDITIONS, AND SPECIFICATIONS APPLICABLE TO THE SHOP OTHER REASONABLE TESTS TO EVALUATE THE STRENGTH OF THE STRUCTURE.
DRAWINGS AND THE SUBMITTALS. THE CONTRACTOR SHALL CHECK AND APPROVE THE
SHOP DRAWINGS BEFORE SUBMISSION TO THE ENGINEER. THE CONTRACTOR SHALL BE CURING OF CONCRETE :
RESPONSIBLE FOR DIMENSIONS, QUANTITIES, JOB CONDITIONS, AND COORDINATION AS A CURING COMPOUND SHALL BE APPLIED TO THE TOP OF "GREEN" CONCRETE SLABS AS SOON SEE SOIL REPORT
DEFINED HEREIN, AND WITH OTHER CONSTRUCTION TRADES. IF THE SHOP DRAWINGS ARE AS PRACTICAL AFTER PLACEMENT OF THE CONCRETE, FOLLOWING THE MANUFACTURE'S FOR DEPTH OF PILE

15'

15'
DISAPPROVED BY THE ENGINEER, THE CONTRACTOR SHALL RESUBMIT CORRECT SPECIFICATIONS AND RECOMMENDATIONS. SPECIFICATIONS FOR CURING COMPOUNDS SHALL (FIELD ADJUST WITH TEST PILE)
DRAWINGS TO COMPLY WITH THE CONTRACT DOCUMENTS. 1
BE SUBMITTED TO THE ARCHITECT AND ENGINEER FOR APPROVAL. ALTERNATIVELY,
CONCRETE SHALL BE KEPT IN A WET CONDITION FOR THE FIRST 24 HOURS AFTER PLACEMENT, S1.0
(c) THE CONTRACTOR SHALL USE MANUFACTURER'S CERTIFIED SHOP DRAWINGS AND AND SHALL BE MAINTAINED IN A MOIST CONDITION FOR AT LEAST THE FIRST SEVEN DAYS
SPECIFICATIONS FOR SPECIAL EQUIPMENT AND/OR CONSTRUCTION INSTALLATIONS, AFTER PLACING.
INCLUDING SKYLIGHTS, HEATING AND COOLING EQUIPMENT, POOL EQUIPMENT, ETC. THE
CONTRACTOR SHALL COORDINATE INSTALLATION WITH THE WORKING DRAWINGS, AND
PROVIDE ALL ADDITIONAL MATERIAL REQUIRED FOR THE INSTALLATION NOT SHOWN IN
REINFORCING:
REINFORCING STEEL SHALL BE GRADE 60.
TYP AUGERCAST PILE

1 1 8 . 0 0 ' (PLAT)
THE WORKING DRAWINGS.
CONCRETE PROTECTION FOR REINFORCEMENT:
SCALE: 1/2" = 1'-0"
1
(d) THE CONTRACTOR SHALL SUBMIT SUFFICIENT COPIES OF THE SHOP DRAWINGS TO ALLOW THE FOLLOWING MINIMUM CONCRETE COVER SHALL BE PROVIDED FOR REINFORCEMENT: S1.0
THE ENGINEER TO KEEP ONE SET OF DOCUMENTS FROM EACH SUBMITTAL FOR HIS
RECORDS. ITEM MINIMUM

15'

15'
COVER, IN.
(e) THE CONTRACTOR SHALL ALLOW A MINIMUM OF ONE WEEK FOR THE ENGINEER TO a) CONCRETE CAST AGAINST AND PERMANENTLY
REVIEW SHOP DRAWINGS, AFTER DATE OF RECEIPT BY THE ENGINEER. FOR LARGE EXPOSED TO EARTH............................................................................ 3
SUBMITTALS, ADDITIONAL TIME MAY BE REQUIRED. b) CONCRETE EXPOSED TO EARTH OR WEATHER:
NOTE:
#6 THROUGH #11 BARS........................................................................ 2
ENGINEER'S LIMITATIONS OF RESPONSIBILITY: #5 BARS AND SMALLER...................................................................... 11 2
AUGER CAST PILES TO BE PLACED
A MAXIMUM OF 15 FT. APART. DEPTH
NEW 2 STORY
THE ENGINEER SHALL NOT BE RESPONSIBILITY FOR THE QUALITY OR COMPOSITION OF c) CONCRETE NOT EXPOSED TO EARTH OR WEATHER: OF PILES TO BE DETERMINED BY
MATERIALS, SHOP DRAWINGS OR FABRICATIONS, CONSTRUCTION INSPECTION, SUPERVISION,
OR REVIEW, SPECIAL INSPECTION, OR THE QUALITY AND CORRECTNESS OF CONSTRUCTION
SLABS, WALL, JOINTS (#11 OR SMALLER)..................................... 3
4 GEOTECHNICAL INVESTIGATION SINGLE FAMILY SEAL

1 1 8 . 0 0 ' (PLAT)
UNLESS THE APPROPRIATE SUBMISSIONS, REPORTS, APPROVALS, SHOP DRAWINGS,
RESIDENCE

1 1 7 . 1 1 ' (W/F)
d) THE ABOVE PROTECTIVE COVERING ARE MINIMUMS, BUT PROTECTION SHALL NOT BE
INSPECTIONS, SITE VISIT, CONSTRUCTION REVIEW, OR SPECIAL INSPECTIONS ARE PERFORMED LESS THAN REQUIRED FOR FIRE-RESISTIVE RATINGS.
BY THE ENGINEER OR HIS REPRESENTATIVE AS REQUIRED HEREIN, AND THEN ONLY SUCH e) THE CONTRACTOR SHALL PROVIDE THE NECESSARY BOLSTER, CHAIRS, AND

Privacy Wall for the Leshner Residence


RESPONSIBILITY AS IS ASSOCIATED WITH THE SPECIFIC WORK PERFORMED AS IS COMMONLY MISCELLANEOUS REINFORCEMENT REQUIRE FOR THE SUPPORT OF REINFORCING. STEEL
ASSIGNED A STRUCTURAL ENGINEER IN RELATION TO OTHER ENGINEERING AND WIRE BAR SUPPORTS USED SHALL BE CLASS "C", PLASTIC PROTECTED.

15'

15'

Ft. Lauderdale, Florida 33301


CONSTRUCTION DISCIPLINES ASSOCIATED WITH THE PROJECT.
SPLICES IN REINFORCEMENT,
THE ENGINEER SHALL NOT BE RESPONSIBLE FOR SITE AND CONSTRUCTION SAFETY AND/OR THE (a) IN SLABS, BEAMS, AND GIRDERS, SPLICES IN REINFORCEMENT AT POINTS OF MAXIMUM 16"X16" MASONRY
SAFETY OF CONSTRUCTION WORKERS. SITE AND CONSTRUCTION SAFETY IS THE STRESS SHALL BE AVOIDED WHEREVER POSSIBLE. SUCH SPLICES WHERE USED SHALL BE COLUMN W/ (4) -
RESPONSIBILITY OF THE CONTRACTOR. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE WELDED, LAPPED OR OTHERWISE FULLY DEVELOPED, BUT, IN ANY SUCH CASE SHALL #5 BARS FILLED
SAFETY OF HIS EMPLOYEES AND THE SAFETY OF THE EMPLOYEE OF ALL SUBCONTRACTORS TO W/ GROUT

6'-6"
TRANSFER THE ENTIRE STRESS FROM BAR TO BAR WITHOUT EXCEEDING THE ALLOWABLE
THE PROJECT. BOND AND SHEAR STRESSES. THE MINIMUM OVERLAP FOR A LAPPED SPLICE SHALL BE 24
BAR DIAMETERS, BUT NOT LESS THAN 12 INCHES. THE CLEAR DISTANCE BETWEEN BARS
ENGINEER'S STATEMENT OF COMPLIANCE :

8'-8"
SHALL ALSO APPLY TO THE CLEAR DISTANCE FROM A CONTACT SPLICE AND ADJACENT
TO THE BEST OF THE ENGINEER'S KNOWLEDGE, THE STRUCTURAL PLANS AND SPECIFICATIONS SPLICES OR BARS.
PRESENTED HEREIN COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES, STANDARDS, (b) WELDED WIRE FABRIC REINFORCEMENT SHALL BE LAPPED ONE MESH PLUS TWO INCHES.
AND PRACTICES. 12 INCHES OR AS NOTED IN THE PLANS.
(c) SPLICES IN COLUMNS, BEAMS, GIRDERS, AND SLABS NOT SHOWN IN THE PLANS SHALL BE

15'

15'
CLASS "C" CONTACT LAP SPLICES.
(d) INTERIOR AND EXTERIOR HORIZONTAL LAPPED CORNER BARS SHALL BE PROVIDED AT ALL
CORNERS TO MATCH THE SIZE, TYPE, AND SPACING OF HORIZONTAL FOOTING, WALL,
14" 12"

MASONRY BOND BEAM, OR CONCRETE TIE BEAMS REINFORCEMENT.


EXCAVATION AND FOUNDATION 24" X 14" CONTINUOUS
PIPES AND CONDUIT EMBEDDED IN CONCRETE: GRADE BEAM W/ (3) #5
EXCAVATION: UNTIL PROVISIONS FOR PERMANENT SUPPORT HAVE BEEN MADE, ELECTRIC CONDUIT AND OTHER PIPES SHALL NOT DISPLACE THAT CONCRETE ON WHICH BARS TOP & BOTTOM &
STRESS IS CALCULATED OR WHICH IS REQUIRED FOR FIRE PROTECTION TO A GREATER EXTENT #3 STIRRUPS @ 12" O.C.
ALL EXCAVATIONS SHALL BE PROPERLY GUARDED AND PROTECTED SO AS TO PREVENT
THAN FOUR PERCENT OF THE AREA OF THE CROSS SECTION. SLEEVES OR OTHER PIPES PASSING

4" CLEAR
THE SAME FROM BECOMING DANGEROUS TO LIFE AND PROPERTY AND SHALL BE SHEET

TYP.
PILED, BRACED AND/OR SHORED, WHERE NECESSARY TO PREVENT THE ADJOINING EARTH THROUGH FLOORS, WALLS, OR BEAMS SHALL NOT BE OF SUCH SIZE OR IN SUCH LOCATION AS
FROM CAVING IN; SUCH PROTECTION TO BE BY THE PERSON CAUSING THE EXCAVATION TO UNDULY TO IMPAIR THE STRENGTH OF THE CONSTRUCTION. EMBEDDED PIPES AND CONDUITS
BE MADE. NO EXCAVATION, FOR ANY PURPOSE, SHALL EXTEND WITHIN ONE FOOT OF THE OTHER THAN THOSE MERELY PASSING THROUGH SHALL NOT BE LARGER IN OUTSIDE DIAMETER
ANGLE OF REPOSE OF ANY SOIL BEARING FOOTING OR FOUNDATION UNLESS SUCH THAN ONE-THIRD THE THICKNESS OF THE SLAB, WALL, OR BEAM IN WHICH THEY ARE
EMBEDDED; SHALL NOT BE SPACED CLOSER THAN THREE DIAMETERS ON CENTERS, NOR SO

15'

15'
FOOTING OR FOUNDATION IS FIRST PROPERLY UNDERPINNED OR PROTECTED AGAINST EXTEND STEEL INTO
LOCATED AS TO UNDULY IMPAIR THE STRENGTH OF THE CONCRETE.
SETTLEMENT. GRADE BEAM 10" MIN. DRIVEWAY
3" PILE EMBEDEMENT
24" INTO FTG.
SOIL INVESTIGATION : THE OWNER HAS RETAINED THE SERVICES OF A DRIVEWAY
GEOTECHNICAL ENGINEERING CONSULTANTS FOR THE PURPOSE OF SUBSURFACE
EXPLORATION, EVALUATION OF THE SITE SOIL AND/OR ROCK CONDITIONS AND GEOLOGY,
FOR RECOMMENDATIONS FOR THE SOIL AND/OR ROCK BEARING CAPACITY, AND FOR MASONRY COLUMN
REVIEW OF THE PROPOSED FOUNDATION TYPES AND DESIGN. THE CONTRACTOR SHALL SCALE: 3/8" = 1'-0"
REFER AND FOLLOW THE RECOMMENDATIONS CONTAINED IN THE SOILS REPORT BY P

S1.0

S1.0
L

2
30' 4' 13'

7'

7'
FOUNDATION SYSTEM - AUGER-CAST CONCRETE PILES
(a) AUGER-CAST CONCRETE PILES SHALL BE OF SIZE SPECIFIED IN DRAWINGS AND (2) #5 CONTINUOUS

2401 Castilla Isle


INSTALLED TO THE MINIMUM DEPTH SPECIFIED IN DRAWINGS. THE MAXIMUM DESIGN BOND BEAM

3'

3'

3'

3'
CAPACITY SHALL BE 50 TONS AND MUST BE VERIFIED BY PILE LOAD TESTS OR AS
RECOMMENDED BY THE SOLS CONSULTANT. THE CONCRETE FOR THE PILES SHALL BE DASHED INDICATES
MINIMUM 4000PSI 28 DAYS AND REINFORCING SHALL BE PROVIDED AS SPECIFIED IN THE NEW 36" HIGH DECORATIVE 15' 3' 25" 19'-2" 25" 11' 11' 6'-6"
DRAWINGS. METAL FENCE (PER ARCHITECT)
8" MASONRY WALL WITH
#5 @ 48" O.C. (GROUT 16"X16" MASONRY COL.
(b) VERIFICATION: ALL CELLS SOLID) 18' 19'-2" 22'
6'-0"

(1) THE ENGINEER SHALL NOT BE RESPONSIBLE FOR THE DESIGN AND
AT EA. END OF FRONT WALL
SERVICEABILITY OF THE FOUNDATIONS FOR THE PROJECT WITHOUT THE VERIFICATION OF (2) #5 CONTINUOUS (SEE MASONRY COLUMN
THE SITE SOIL AND/OR ROCK CONDITIONS AND GEOLOGY, VERIFICATION OF THE BOND BEAM
8'-2"

PRESUMED BEARING CAPACITY OF THE SOIL AND/OR ROCK, AND THE VERIFICATION OF NOTE:
DETAIL) (TYP. OF 8)
SATISFACTORY AND SUITABLE SUBSURFACE CONDITIONS AND GEOLOGY FOR THE AUGER CAST PILES TO BE PLACED
3'-0"

PROPOSED FOUNDATION TYPE AND DESIGN. DURING INSTALLATION OF PILING THE SOILS A MAXIMUM OF 15 FT. APART. DEPTH 8" MASONRY WALL WITH
CONSULTANT'S REPRESENTATIVE SHALL MAINTAIN A PILING LOG FOR EACH INDIVIDUAL OF PILES TO BE DETERMINED BY #5 @ 48" O.C. (GROUT
PILE WHICH SHALL INCLUDE THE DATE OF INSTALLATION, THE SIZE OF THE AUGER, THE GEOTECHNICAL INVESTIGATION ALL CELLS SOLID)
5'-2"

LENGTH OF THE PILE, THE PUMPING PRESSURES FOR THE GROUT AND ANY VARIATIONS
14" 12"

OBSERVED, ANY UNUSUAL RESISTANCE TO THE AUGER PENETRATION AND ANY


DISCONTINUITIES OR INTERRUPTIONS DURING PLACEMENT. ALL PILE LOGS SHALL BE
14" 12"

SUBMITTED TO THE ENGINEER FOR HIS RECORDS. THE ENGINEER SHALL ASSUME NO drawn by: CEH
RESPONSIBILITY FOR THE FOUNDATION PERFORMANCE WITHOUT SUCH VERIFICATION, 24" X 14" CONTINUOUS GRADE BEAM
AND THEN UPON VERIFICATION ONLY SUCH RESPONSIBILITY AS IS COMMONLY ASSIGNED W/ (3) #5 BARS TOP & BOTTOM AND
#3 STIRRUPS @ 12" O.C.
24" X 14" CONTINUOUS GRADE BEAM CASTILLA ISLE checked by: J. Biagi
A STRUCTURAL ENGINEER IN RELATION TO OTHER ENGINEERING DISCIPLINES ASSOCIATED W/ (3) #5 BARS TOP & BOTTOM AND
4" CLEAR

WITH A PROJECT. #3 STIRRUPS @ 12" O.C. 10/16/2015


date:
TYP.

4" CLEAR

NOTE:
TYP.

AUGER CAST PILES TO BE PLACED JB15-334


SITE PREPARATION AND PLACEMENT OF FILL: job no:
A MAXIMUM OF 15 FT. APART. DEPTH
(a) REFER TO SOILS CONSULTANT'S RECOMMENDATIONS OF PILES TO BE DETERMINED BY sheet:
STEEL INTO GRADE BEAM 10" MIN. 3" GEOTECHNICAL INVESTIGATION
(b) SITE PREPARATION PLACEMENT OF FILL, SOIL SAMPLING AND TESTING OF PILE EMBEDEMENT INTO FOOTING
STEEL INTO GRADE BEAM 10" MIN. 3"
COMPACTED FILL SHALL BE CONDUCTED UNDER THE SUPERVISION OF A GEOTECHNICAL
24" PILE EMBEDEMENT INTO FOOTING
SITE PLAN
S1
ENGINEER.
24"
COMMENCEMENT OF CONSTRUCTION: THE CONTRACTOR SHALL NOT PROCEED WITH THE
CONSTRUCTION OF FOUNDATIONS OR SUPERSTRUCTURE WITHOUT PERMISSION FROM THE
ENGINEER, UPON THE ENGINEER'S COMPLETION OF ANY NECESSARY REVISIONS TO THE
1 PERIMETER WALL SECTION
FOUNDATION PLANS RESULTING FROM THE GEOTECHNICAL ENGINEER'S REPORTS, EVALUATION S1.0 SCALE: 3/8" = 1'-0" 2 PERIMETER WALL SECTION
AND RECOMMENDATIONS, REVISED PLANS SHALL BE ISSUED FOR COMMENCEMENT OF SCALE: 3/8" = 1'-0"
CONSTRUCTION. S1.0