A)Line parameters
B)CT/PT details
1)CT primary rating - 500A
2)CT secondary rating - 1A
3)PT primary rating - 66000 V
4)PT secondary rating - 110 V
C)Source Impedance
1)Fault MVA at local end - 392 MVA
2)Fault MVA at remote end - 642 MVA
D)Fault resistance
1)Fault resistance in primary for phase-earth faults(Rfe) - 15 ohms
2)Fault resistance in primary for phase-phase faults(Rfp )- 10 ohms
Calculations :-
Zone-1 setting
Positive sequence resistance , R1PP&R1PE = 4 x 0.184 x 80%
= 0.59 ohms/phase
Positive sequence reactance , X1PP&X1PE = 4 x 0.44 x 80%
= 1.4 ohms/phase
Zero sequence resistance , R0PE = 4 x 0.736 x 80%
= 2.35 ohms/phase
Zero sequence reactance , X0PE = 4 x 1.76 x 80%
= 5.632ohms/phase
Resistive reach for phase-phase faults,
Zone-2 setting
Positive sequence resistance , R1PP&R1PE = 0.736 + (0.184*4*50%)
= 1.104 ohms/phase = 1.2(approx)
Positive sequence reactance , X1PP&X1PE = 1.76+ (0.44*4*50%)
= 2.64 ohms/phase
Zero sequence resistance , R0PE = 2.94 + (0.736*4*50%)
= 4.416 ohms/phase
Zero sequence reactance , X0PE = 7.04 + (1.76*4*50%)
= 10.56 ohms/phase
Zone-3 setting
Positive sequence resistance , R1PP&R1PE = 0.736 + (0.184*26*110%)
= 5.90ohms/phase
Positive sequence reactance , X1PP&X1PE = 1.76 + (0.44*26*110%)
= 14.34 ohms/phase
Zero sequence resistance , R0PE = 2.94 + (0.736*26*110%)
= 23.99 ohms/phase
Zero sequence reactance , X0PE = 7.04 + (1.76*26*110%)
= 57.37 ohms/phase