Sample Calculations Sample Calculations

Sample Calculation 4. Given the following data:


Width = 15 m
Length = 100 m
Ceiling height = 3.5 m
Desired Illumination = 400 lux
Type of Luminaire = 200mf Downlight w/ 26W TC-D Lamp
Luminaire : 8" Downlight with 70W Metal Halide Lamp
Lamp Flux : 6600 lumens (from manufacturer’s data) from Table
(Figure 9-28) of IESNA handbook CU of metal halide downlight #10
@ 70/50/20 reflectance & RCR of 1.34

Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)

Sample Calculations Sample Calculations


Compute for the Light Loss Factor (LLF) Compute for the the total initial lamp lumens (TILL)

LLF = Ballast factor x LLD x LDD x RSDD


Ballast factor = 0.95
LLD of metal halide lamp = 0.85
LDD = 0.96
RSDDF = 0.976
LLF = 0.95 x 0.85 x 0.96 x 0.976
LLF = 0.76

Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)

Sample Calculations Sample Calculations


Compute for the number of luminaires Compute for the number of luminaires/row
Spacing Criterion = 1.2, does not apply since total of 179
luminaires cannot be placed on the given area.
Assuming spacing criterion = 0.9
Spacing distance between luminaries = MH x SC
Spacing (Longitudinal) = 3.5 m x 0.9 = 3.15
Number of luminaires/column = 100/3.15 = 31 luminaires
Total length of column = 31 x 3.15 = 97.65 m
Space at end of column = (100-97.65)/2 = 1.175 m
Total luminaires at each row = 179/31 = 5.7 ~ 6 luminaires

Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)