Documente Academic
Documente Profesional
Documente Cultură
Group : (A1)
The objective of the experiment
On/off control of flow (Closed loop)
entering the network to avoid this type of congestion. This is one of the
main functions of flow control.Flow control is also sometimes necessary
between two users for speed matching,
that is, for ensuring that a fast transmitter does not overwhelm a slow
receiver with more packets than the latter can handle. Some authors
reserve the term "flow control" for this type of speed matching and use
the ten n "congestion control" for regulating the packet
population with in the subnet work. We will not make this distinction in
tenninology; the type and objective of flow control being discussed will
be clear from the context.
Theory
On/off control of flow (Closed loop)
Choose the PID box on the mimic diagram, set the Proportional Band to
Time to 0 and Derivation time to 0 then set the Set Point to 0 %, Integral
1.5 L/min (default at start up). Click ‘Apply’ to enter the changes to the
setting
Choose the Automatic Mode of Operation
Select the (Go) icon to begin data logging
The pump will switch on, the flowrate will quickly increase and water
the flow indicator tube. The flow will instantaneously will flow into to
set on the controller i.e. the setpoint of increase until it reaches the flow
setpoint by a fixed amoun 1.5 L/min. When the flow rises above the
(The dead band) the pump will switch off and the water flow will rapidly
drop-off as the pump has stopped. When the flow falls below the
setpoint by a fixed amount (the dead band) the pump will switch on
cycle will continue resulting in widely fluctuating again and the
flowrate that is completely unacceptable. Observe that the level rises and
falls in the flow indicator but reduced amplitude because of the time
indicate instantaneous constant of the indicator (the tube does not
In the PID .)flowrate because it must fill or drain to indicate a new level
controller adjust the set point to 1.0 L/min, click ‘Apply’ then observe
the same behaviour at the reduced setpoin Adjust the set point to 2.5
L/min and observe the same behaviour the increased
DISCUSSIONS
The device controlled by an on\off controller (in this case a water pump) is simply
on or off as required to maintain the process variable
The flow meter and the flow indicator have different response times so the
indication from the two devices is different. The flow meter with a fast response
indicates the instantaneous flow rate but the indicator tube with a slow response
indicates more of an average
When the valve is closed and the speed of the pump (50) set point (1.5), the flow is
turbulent and the payment of the pump frequency and a high load on the pump
In the case of raising the group gradually to a point (2.5), the load on the pump
increases and disorder flow increases
In the case of LED Open and set point (1.5), the load on the pump less and less
.runoff disorder
When a set point change to (2.5), the load gradually at least on the pump
4.00
3.50
3.00
2.50
2.00
flow
1.50 Series1
1.00
0.50
87, 0.04 0.00
100 80 60 40 20 0 -0.50
time
1.50
flow
1.00
Series1
0.50 Linear (Series1)
0.00
01:26 01:09 00:52 00:35 00:17 00:00
time
open valve position ,speed pump=50,pid set point=1.5,integral time =50,proportional band=200