Sunteți pe pagina 1din 21

MiCOM P631, P632, P633 and P634

Transformer Differential Protection Devices

Application and scope • Inverse-time overcurrent • Fault recording


protection, single-stage, phase- (time-tagged signal logging with
The MiCOM P63x series differential
selective, separate measuring fault value recording of the phase
protection devices are intended for
systems for phase currents, currents of each winding and,
fast and selective
negative-sequence current and depending on the design version,
short-circuit protection of
residual current of the neutral-point current of
transformers, motors, generators
each winding and of the voltage)
and other installations with two, • Thermal overload protection,
three or four windings respectively. choice of relative or absolute The MiCOM P63x series differential
thermal replica protection devices are of modular
Functions design. The plug-in modules are
• Over/underfrequency protection
housed in a robust aluminium case
The differential protection devices • Over/undervoltage protection and electrically connected via an
have the following main functions analogue and a digital bus printed
(with differences between the • Limit value monitoring
circuit board.
models as shown in the table on • Programmable logic
page 3): The nominal currents or the nominal
All main functions are individually voltage, respectively, of the
• Three-phase differential protection configurable and can be disabled measuring inputs can be set with
•Amplitude and vector group or enabled by the user as desired. the help of function parameters.
matching By means of a straight-forward
configuration procedure, the user The nominal voltage range of the
•Zero-sequence current filtering can adapt the device flexibly to the optical coupler inputs is
for each winding, may be scope of protection required in each 24 to 250 V DC without
deactivated individually for particular application. Due to the internal switching.
each end powerful, freely configurable logic The auxiliary voltage input for the
•Triple-slope tripping of the device, special applications
power supply is a wide-range
characteristics can be accommodated.
design with a nominal voltage
•Harmonic restraint with second In addition to the features listed range of 48 to 250 V DC and
harmonic component, optionally above, as well as comprehensive 100 to 230 V AC. An additional
with or without cross blocking; self-monitoring, the following global version is available for the lower
may be deactivated functions are available in the nominal voltage range of
MiCOM P63x series differential 24 to 36 V DC.
•Overfluxing restraint with fifth
protection devices:
harmonic component, may be All output relays are suitable for
deactivated • Parameter subset selection both signals and trip duties.
•Through-stabilization with • Measured operating data to
The optional PT 100 input is lead-
saturation discriminator support the user during
compensated, balanced and
commissioning, testing and
• Ground differential protection linearized for PT 100 resistance
operation
(UK: Restricted earth fault thermometers per IEC 60751.
protection, REF) • Operating data recording
(time-tagged signal logging) The optional 0 to 20 mA input
• Definite-time overcurrent provides open-circuit and overload
protection, three stages, phase- • Overload data acquisition
monitoring, zero suppression
selective, separate measuring • Overload recording (time-tagged defined by a setting, plus the option
systems for phase currents, signal logging) of linearizing the input variable via
negative-sequence current and • Fault data acquisition 20 adjustable interpolation points.
residual current

2
Two freely selected measured Control and display Models available
signals (cyclically updated
• Local control panel The main functions and the inputs
measured operating data and
and outputs available for the
stored measured fault data) can be • 17 LED indicators, 12 of which P63x series design types are listed
output as a load-independent direct allow freely configurable function in the table below. Where a main
current via the two optional 0 to assignment function is available more than
20 mA outputs. The characteristics once for a particular design type,
are defined via 3 adjustable • PC interface
the user can assign these functions
interpolation points allowing a • Communication interface to the individual windings as
minimum output current (4 mA, for (optional) required.
example) for receiver-side open- For 11/2 switched and ring-busbar
circuit monitoring, knee-point Information exchange is via the
systems, the devices allow the
definition for fine scaling and a local control panel, the PC interface definition of a virtual winding. The
limitation to lower nominal currents and the optional communication currents processed by the device for
(10 mA, for example). Where interface. Using this information this winding are a summation of the
sufficient output relays are interface, the MiCOM P63x series inputs from the two appropriate sets
available, a freely selected differential protection devices can of CT inputs.
measured variable can be output in be integrated with substation control
BCD-coded form via contacts. systems or telecontrol systems.

Models available

P631 P632 P633 P634


Main functions ANSI Device Number
• Differential protection 87 2 wind. 2 wind. 3 wind. 4 wind.
• Ground differential protection 87G – 2 3 3
• Definite-time overcurrent protection 50P, 50Q, 50N/G 2 2 3 3
• Inverse-time overcurrent protection 51P, 51Q, 51N/G 2 2 3 3
• Thermal overload protection 49 1 1 2 2
• Over/underfrequency protection 81O, 81U, 81U-R – 1 1 1
• Over/undervoltage protection 27, 59 – 1 1 1
• Limit value monitoring 2 2 3 3
• Programmable logic 1 1 1 1
Measuring inputs
• Phase current 2x3 2x3 3x3 4x3
• Residual current or neutral-point current – 2 3 3
• Voltage – 1 1 1
Binary inputs and outputs
• Optical coupler inputs (per order) 4 4 to 34 4 to 40 4 to 34
• Output relays (per order) 8 to 14 8 to 22 8 to 30 8 to 22
Analogue inputs & outputs (optional)
• 0 to 20 mA input – 1 1 1
• PT 100 input – 1 1 1
• 0 to 20 mA outputs – 2 2 2

3
Main functions 8.00

Main functions are autonomous


function groups and can be Id /I ref
individually configured or disabled Tripping area
to suit a particular application. 6.00

Function groups that are not


required and have been disabled
by the user are masked completely

tic
(except for the configuration 4.00

fee cteris
parameter) and functional support is

ra
7

d
0.

le-s cha
withdrawn from such groups. =

sing ent
ide
m 2

This concept permits an extensive

for lt curr
scope of functions and universal 2.00

Fau
Blocking area
application of the protection device 0.3
m1=
in a single design version, while at

12200e.DS4
I R,m2 /I ref = 4.0
the same time providing for a clear Id> / I ref = 0.2
and straight-forward setting
0.00 2.00 4.00 6.00 8.00
procedure and adaptation to the IR /I ref
protection task under consideration.
Figure 1: Tripping characteristics of differential protection
Differential protection for three-phase symmetrical infeed

Amplitude matching Tripping characteristics Overfluxing restraint


On the basis of the primary The tripping characteristics of the For stabilization under overfluxing
transformer currents, the differential protection device has conditions, the ratio of the fifth
MiCOM P63x series differential two knees (see Figure 1). The first harmonic to the fundamental for the
protection devices can be flexibly knee is dependent on the setting of differential currents is used. Tripping
adapted to the reference currents of the basic threshold value Id> and is is blocked on a per measuring
the protected object. Amplitude on the fault line for single-side feed. system basis. For differential current
matching is by means of a straight- The second knee of the tripping levels of 4·Iref or higher, the
forward input of the reference characteristic is defined by a blocking criterion is no longer taken
power common to all windings, plus setting. Above the user-selected into account.
the nominal voltages and the differential current level Id>>>, the The overfluxing restraint function
nominal transformer currents for restraining current is no longer may be deactivated.
each winding. The resulting taken into account.
reference currents and matching
Through stabilization
factors are automatically deduced Harmonic restraint
by the device and checked for Up to a certain limit, stability in the
Stabilization under inrush event of external faults is ensured
compatibility with the internally
conditions is based on the by means of the bias. Due to the
allowed value ranges.
presence of second harmonic triple-slope tripping characteristic,
Vector group matching and components in the differential the stabilization is particularly
zero-sequence filtering currents. The ratio of the second effective for high currents. However,
harmonic component to the as an additional safeguard for
Matching of the MiCOM P63x
fundamental wave for the through-currents with transformer
series differential protection devices
differential currents of the saturation, the MiCOM P63x series
to the vector group of the protected
measuring system serves as the differential protection devices are
object is via a straight-forward input
criterion. Optionally, tripping is provided with a saturation detector.
of the relevant vector group
blocked either across all three Particularly the start-up of direct on-
identification number. The
measuring systems or selectively line starting induction motors
mathematical formula to be applied
for one measuring system. represents a problem in differential
to the measured currents is
However, from a user-selected protection due to transient
automatically selected internally
differential current level Id>>, the transformer saturation caused by a
according to the relevant vector
blocking criterion is no longer displacement of the start-up current
group and zero-sequence filtering is
taken into account. For application for relatively high primary time
taken into account simultaneously.
as a differential protection device constants. Even under such
For special applications, zero-
for motors or generators, the unfavorable measurement
sequence filtering may be
harmonic restraint can be conditions, the MiCOM P63x series
deactivated separately for each
deactivated. differential protection devices
winding.
perform with excellent stability.

4
Ground differential 8.00

protection
The ground differential protection Id,N /I ref Tripping area rs
r me
(UK: Restricted earth fault 6.00 n sfo
protection, REF) mode can be tra
nt
rre
applied to transformer windings cu
in
with grounded neutral point where ma
the
the neutral point/ground connection of
4.00 n
io
is fitted with a current transformer. 0 05 ur
at
1. t
sa
= nt
m ie
ns
Ground differential protection ra
rt
fo
(UK: Restricted earth fault ic
2.00 rist
protection, REF) is based on a cte Blocking area
ar
ch
comparing the vector sum of the en
t
rr
phase currents of the relevant cu

12201e.DS4
lt
Fau
transformer winding to the neutral I d,N > /I ref = 0.2
point current. The vector sum of the 0.00 2.00 4.00 6.00 8.00
phase currents can be generated, I R,N /I ref
for example, by residual connection
Figure 2: Tripping characteristics of ground differential protection
of the three main current (UK: Restricted earth fault protection, REF)
transformers.
The advantage of ground For the optimum performance of the Inverse-time
differential protection (UK: differential protection function under overcurrent protection
Restricted earth fault protection, inrush conditions of the protected The inverse-time overcurrent
REF) resides in the linear transformer, starting of the phase protection operates on the basis of
dependence of the sensitivity on the current stage I> and the negative- one measuring system each for the
distance between the fault and the sequence current stage Ineg> can three phase currents, the negative-
neutral point. be stabilized, if desired. sequence current and the residual
(Notes : REF is applicable for wye- The blocking signals of the inrush current just as the definite-time
connected windings. Balanced REF stabilization function of differential overcurrent protection does.
for delta windings is in protection are selective to the However, the three measuring
development). measuring system. These signals are systems operate with single-stage
Definite-time linked by OR operators to obtain evaluation for this function. The
overcurrent protection the criterion for stabilization. As a timer stage of the phase-current-
consequence, stabilization is always related measuring system operates
The definite-time overcurrent
effective across all three phases. with phase-selective starting.
protection function operates with
Neither the phase current stages The effect on the general starting
separate measuring systems for the
I>> and I>>> nor the negative- signal of the stages measuring in
evaluation of the three phase
sequence current stages Ineg>> and the residual path and in the
currents, the negative-sequence Ineg>>> are affected by the negative-sequence system
current and the residual current. The stabilization. respectively, can be suppressed if
negative-sequence current is desired.
Additionally, the operate values of
determined from the filtered
all overcurrent stages can be set as For the individual measuring
fundamental component of the three
dynamic parameters. For a settable systems, the user can select from a
phase currents. The residual current
hold time, switching to the dynamic multitude of tripping characteristics
is obtained either from the fourth
operate values can be done via an (see Table 1, page 6).
current input or from the internal
external signal. Starting of the phase current stage
vector addition of the three phase
The hold time is selected to can be stabilized under inrush
currents, depending on the user’s
implement a cold load pick-up conditions if desired. The blocking
choice. Three stages each are
function, assuring stability when signals from the harmonic restraint
provided for the three phases. Each
increased loading is present. Once function of differential protection,
stage of the phase current-related
the hold time has elapsed, the static formed selectively for each
measuring system operates with
operate values are reinstated. measuring system, are linked by an
phase-selective starting. The effect
on the general starting signal of the OR operator to serve as the
stages measuring in the negative- criterion. Consequently, this
sequence system and in the residual stabilization is always effective
across all three phases.
path, respectively, can be
suppressed if preferred.

5
• Over/underfrequency monitoring
No. Tripping time characteristic Constants and formulae (t in s)
(k = 0.01 to 10.00) a b c R • Over/underfrequency monitoring
combined with differential
0 Definite time t=k frequency gradient monitoring
Per IEC 60255-3 (df/dt) for system decoupling
1 Normally inverse 0.14 0.02 applications
a • Over/underfrequency monitoring
2 Very inverse 13.5 1.00 t =k
2 Extremely inverse 80 2.00
I b combined with medium frequency
4 Long time inverse 120 1.00
Iref – 1 gradient monitoring (∆f/∆t) for
load shedding applications.
Per ANSI/IEEE C37.112 Trip Release
5 Moderately inverse 0.0515 0.0200 0.1140 4.85 Over/undervoltage
6 Very inverse 19.6100 2.0000 0.4910 21.60 protection
7 Extremely inverse 28.2000 2.0000 0.1217 29.10
The over/undervoltage protection
function evaluates the fundamental
Per ANSI Trip Release
component of the voltage by way of
8 Normally inverse 8.9341 2.0938 0.17966 9.00
two definite-time overvoltage and
9 Short time inverse 0.2663 1.2969 0.03393 0.50
undervoltage stages each.
10 Long time inverse 5.6143 1.0000 2.18592 15.75
a R Limit value monitoring
t =k +c tr =k 2
I b I
Iref – 1 Iref – 1 The highest of the three phase
currents is the basis of evaluation
by a definite-time overcurrent stage
Not per standard 1 with adjustable operate value and
11 RI type inverse t =k
0.236 time delay. Thereby these measured
0.339 –
I values are monitored for exceeding
Iref the set limit.

Not per standard Programmable logic


12 RXIDG type inverse =k 5.8 – 1.35 ln
I
t
Iref User-configurable logic enables the
user to set up logic operations on
binary signals within a framework
Table 1: Tripping time characteristics of inverse-time overcurrent protection
of Boolean equations. By means of
Intermittent startings of the phase, a straightforward configuration
level ∆ϑtrip and depends on the procedure, any of the signals of the
negative sequence or residual accumulated thermal load ∆ϑ0:
current stage can be accumulated protection device can be linked by
I 2– ∆ϑ logic ‘OR’ or ‘AND’ operations with
on the basis of the set tripping Iref 0

characteristic by means of a t = τ.ln the possibility of additional


I 2– ∆ϑ negation operations.
settable hold time. Tripping is also trip
Iref
performed in accordance with the The output signal of an equation
relevant tripping characteristic. The temperature of the cooling can be fed into a further, higher-
medium can be taken into account order equation as an input signal,
Additionally, the operate values of
in the thermal replica using the thus leading to a set of interlinked
all overcurrent stages can be set as Boolean equations.
optional PT 100 input or the
dynamic parameters. For a settable
0 to 20 mA input. The user has a The output signal of each equation
hold time, switching to the dynamic
choice of using a thermal replica on is fed to a separate timer stage with
operate values can be done via an
the basis of either absolute or two timer elements each and a
external signal. The hold time is
relative temperature. choice of operating modes. Thus the
selected to implement a cold load
An alarm signal can be issued in output signal of each equation can
pick-up function, assuring stability
accordance with the set warning be assigned a freely configurable
when increased loading is present. time characteristic.
Once the hold time has elapsed, level ∆ϑwarning. As an alternative
the static operate values are method of generating an alarm, the The two output signals of each
reinstated. cyclically updated measured equation can be configured to each
operating value of the predicted available input signal after logic OR
Thermal overload protection time remaining before tripping is linking. The user-configurable logic
monitored to check whether it is function is then able to influence the
Using this function, thermal individual functions without external
overload protection can be falling below a set threshold.
wiring (block, reset, trigger, for
realized. The highest of the three Over/underfrequency example).
phase currents serves to track a first- protection Via non-storable continuous signals,
order thermal replica according to
Over/underfrequency protection monostable trigger signals and
IEC 60255-8. bistable setting/resetting signals,
The tripping time is determined by has four stages.
Each of these can be operated in the Boolean equations can be
the set thermal time constant τ of controlled externally via any of the
the protected object, the set tripping one of the following modes:
device’s interfaces.

6
Global functions Operating data recording Fault recording

Functions operating globally allow For the continuous recording of While a fault condition persists in
processes in system operation or of the power system, the relevant
the adaptation of the device’s
events, a non-volatile ring memory signals, each fully tagged with date
interfaces to the protected power
is provided. The relevant signals, and time at signal start and end,
system, offer support during
each fully tagged with date and are entered into a non-volatile
commissioning and testing, provide
time at signal start and end, are memory in chronological sequence.
continuously updated information
entered in chronological sequence. The measured fault data, fully
on the operation, as well as
Included are control actions such as tagged with the date and time of
valuable analysis results following
the enabling or disabling of acquisition, are also entered.
events in the protected system.
functions as well as local control Furthermore, the sampled values of
Clock synchronization triggering for testing and resetting. all analogue input variables, such
The onset and end of events in the as phase currents and neutral-point
The devices incorporates an internal
network, as far as these represent a currents, are recorded during a
clock with a resolution of 1ms.
deviation from normal operation fault.
All events are time-tagged based on (overload, ground fault or short-
this clock, entered in the recording circuit, for example) are recorded. Up to 8 faults can be recorded. If
memory appropriate to their more than 8 faults occur without
significance and signaled via the Overload data acquisition interim memory clearance then the
communication interface. oldest fault recording is overwritten.
Overload situations in the network
Alternatively two external
represent a deviation from normal Self-monitoring
synchronisation signals can be used
system operation and can be
according to the selected Comprehensive self-monitoring
permitted for a brief period only.
communication protocol: using one procedures within the devices
The overload protection functions
of the protocols Modbus, DNP3, ensure that internal hardware or
enabled in the protective devices
IEC 60870-5-103, IEC 60870-5- software errors are detected and do
recognize overload situations in the
101 the device will be not cause malfunctions of the
system and provide for acquisition
synchronized by a time telegram protective devices.
of overload data such as the
from a higher-level substation magnitude of the overload current, As the auxiliary voltage is turned
control system or in any other case the relative heating during the on, a functional test is carried out.
it will be synchronized using the overload situation and its duration. Cyclic self-monitoring tests are run
IRIG-B signal input. The internal during operation. If test results
clock will then be adjusted Overload recording deviate from the default value then
accordingly and operate with an the corresponding signal is entered
While an overload condition
accuracy of ±10 ms if synchronized into the non-volatile monitoring
persists in the network, the relevant
via protocol and ±1ms if signals, each fully tagged with date signal memory. The result of the
synchronized via IRIG-B signal. and time at signal start and end, fault diagnosis determines whether
are entered into a non-volatile a blocking of the protection device
Parameter subset selection will occur or whether a warning
memory in chronological sequence.
The function parameters for setting The measured overload data, fully only is issued.
the protection functions are, to a tagged with the date and time of
large extent, stored in four acquisition, are also entered.
parameter subsets. Switching
between these subsets is readily Up to 8 overload situations can be
achieved via local control or binary recorded. If more than 8 overload
input. situations occur without interim
memory clearance then the oldest
overload recording is overwritten.

Fault data acquisition


A short-circuit within the network is
described as a fault. The short-
circuit protection functions enabled
in the devices recognize short-
circuits within the system and
trigger acquisition of the associated
measured fault data such as the
magnitude of the short-circuit current
and the fault duration.

7
Display
1 (1) The integrated local control
5 panel has an LCD display with
4x20 alphanumeric characters.
17 LED indicators are provided
for signal display.
(2) 5 LED indicators are
permanently assigned to signals.

3 (3) The remaining 12 LED indicators


are available for free
assignment by the user. A
separate adhesive label is
2 provided for user-defined
labeling of these LED indicators
according to the chosen
configuration.

Menu tree
(4) By pressing the
cursor keys and guided by the
6 7 4 LCD display, the user moves
within a plain text menu. All
setting parameters and
Figure 3: Local control panel measured variables as well as
all local control functions are
arranged in this menu which is
Control standardized for all devices of
Measured value panels the system. Changes to the
All data required for operation of
The configuration of the local settings can be prepared and
the protection and control unit are
confirmed by means of the
entered from the integrated local control panel allows the installation
ENTER key which also
control panel. Data important for of measured value ‘Panels’ on
serves to trigger local control
system management is also read out the LCD display. The Panels are
functions. In the event of
from here. The following tasks can automatically displayed for certain
erroneous entries, exit from the
be handled via the local control operation conditions of the
EDIT MODE with rejection of the
panel: system. Priority increases from entries is possible at any time by
• Readout and modification of normal operation to operation means of the CLEAR key C .
settings under overload conditions and When the EDIT MODE is not
finally to operation following a activated, pressing the CLEAR
• Readout of cyclically updated short-circuit in the system. key has the effect of resetting
measured operating data and
The protection device thus the indications.
state signals
provides the measured value Pressing the READ key G
• Readout of operating data logs data relevant for the prevailing provides direct access to a
and monitoring signal logs conditions. preselected point in the menu.
• Readout of event logs (after Type label and PC interface
overload situations, ground faults
(5) The upper covering flap is
or short-circuits in the power
labelled with the device type
system)
designation. Located under the
• Resetting of the unit and flap is the type identification
triggering of further control label with information of order
functions designed to support number, serial number and the
testing and commissioning tasks nominal electrical values.
Password protection
The local control panel shown in (6) Located under the lower
Access barriers protect the enter
Figure 3 comprises the local control covering flap is the serial
mode in order to guard against
elements and functions described interface for connecting a PC.
inadvertent or unauthorized
below. changing of parameters or (7) To prevent unauthorized
triggering of control functions. opening of the lower flap, the
attached eyelets can be sealed.

8
Mechanical design Transformer module T Bus modules B
The devices are supplied in two The transformer modules convert the Bus modules are printed circuit
case designs. measured currents and voltages to boards (PCBs), providing the
the internal processing levels and electrical connection between the
• Surface-mounted
provides for electrical isolation. other modules. Two types of bus
• Flush-mounted modules are used, namely the
Processor module P
analogue and digital-bus PCB.
With both case designs, connection
The processor module performs the
is via threaded terminal ends with Binary modules X
analogue/digital conversion of the
the option of either pin or ring-
measured variables as well as all The binary modules are equipped
terminal connections.
digital processing tasks. with optical couplers for binary
Two 40TE flush mounted cases can signal input and/or output relays
Local control module L
be combined to form a complete for the output of signals and
19" mounting rack. The local control module commands.
encompasses all control and display
Figure 4 shows the modular
elements as well as a PC interface. Analogue module Y
hardware structure of the devices.
The local control module is located The analogue module is fitted with
The plug-in modules can be
behind the front panel and a PT 100 input, a 20 mA input and
combined to suit individual
connected to the processor module two 20 mA outputs. One output
requirements. The device itself can
via a ribbon cable. relay each is assigned to two
identify the fitted modules. During
each startup, the number and type Communication module A 20 mA outputs. Additionally, four
of fitted modules are identified and optical coupler inputs are available.
The optional communication module
checked for compliance with the
provides a serial information Power Supply module V
permissible configurations. As a
interface for the integration of the
function of the components actually The power supply module ensures
protection device into a substation
fitted, the corresponding the electrical isolation of the device
control system.
configuration parameters are then as well as providing the power
The communication module is
enabled for application. supply. Depending on the chosen
plugged into the processor module.
design version, optical coupler
inputs and output relays are
provided in addition.

PC Interface Communication Interface

A
MiCOM

TRIP

L
ALARM
OUT OF SERVICE
HEALTHY
EDIT MODE

CLEAR
CG G
C
G
G
READ
ENTER
G G
G

P
µP

T X Y V

Currents / Voltages Binary Signals / Measured Data / Commands Power Supply

Figure 4: Hardware structure

9
Technical Data
General Data

Case Design Other Inputs and Outputs Electrical Fast Transient or


Threaded terminals for pin-terminal Burst Requirements
Surface-mounted case suitable for wall
connection: Per IEC 60255-22-4,
installation or flush-mounted case for
• Threaded terminal ends M3, Test severity levels 4,
19" cabinets and control panels self-centering with wire protection for • Rise time of one pulse: 5 ns,
conductor cross sections of • Impulse duration (50% value): 50 ns,
Installation Position
0.2 to 2.5 mm2 • Amplitude: 4 kV / 2 kV, resp.,
Vertical ±30° or • Burst duration: 15 ms,
Degree of Protection Threaded terminals for ring-terminal • Burst period: 300 ms,
connection: • Burst frequency: 2.5 kHz,
Per DIN VDE 0470 and EN 60529 or
• Source impedance: 50 Ω
IEC 60529. • In preparation
IP 52; IP 20 for the rear connection Creepage Distances and Surge Immunity Test
area of the flush-mounted case.
Clearances Per EN 61000-4-5 or
Weight Per EN 61010-1 and IEC 60664-1 IEC 61000-4-5, Level 4,
• Case 40 TE: approx. 7 kg • Pollution degree 3, Testing of power supply circuits,
• Case 84 TE: approx. 11 kg • Working voltage 250 V, unsymmetrically/ symmetrically
• Overvoltage category III, operated lines,
Dimensions • Impulse test voltage 5 kV • Open-circuit voltage front time/time
See: Dimensions to half-value: 1.2 / 50 µs,
Tests • Short-circuit current front time/time
Terminal connection to half-value: 8 / 20 µs,
Type Test • Amplitude: 4 / 2 kV,
diagrams Tests according to • Pulse frequency: > 5/min,
See: Location and Connections EN 60255-6 or IEC 60255-6 • Source impedance: 12 / 42 Ω

Terminals EMC Immunity to Conducted


Interference Suppression Disturbances Induced by
PC Interface (X6) Radio Frequency Fields
Per EN 55022 or IEC CISPR 22,
DIN 41652 connector, type D-Sub, 9pin. Per EN 61000-4-6 or
Class A
IEC 61000-4-6, Level 3,
Communication Interface 1 MHz Burst Disturbance Test • Disturbing test voltage: 10 V
Optical fibre (X7 and X8):
Per IEC 60255-22-1, Class III,
• F-SMA connector Power Frequency Magnetic
• Common-mode test voltage: 2.5 kV,
per IEC 60874-2 or DIN 47258 for
• Differential test voltage: 1.0 kV, Field Immunity
plastic fibre connection Per EN 61000-4-8 or
• Test duration: > 2 s,
or IEC 61000-4-8 , Level 4,
• Source impedance: 200 Ω
• BFOC (ST®) connector 2.5 • Frequency: 50 Hz,
per DIN 47254-1 or IEC 60874-10 • Test field strength: 30 A/m
for glass fibre connection Immunity to Electrostatic
or Discharge Alternating Component
Leads (X9, X10): Per EN 60255-22-2 or (Ripple) in DC Auxiliary
• Threaded terminal ends M2 for wire IEC 60255-22-2, Level 3, Energizing Quantity
cross-sections up to 1.5 mm2 • Contact discharge,
Per IEC 60255-11, 12 %
IRIG-B Interface (X11) single discharges: > 10,
BNC plug • Holding time: > 5 s, Insulation
• Test voltage: 6 kV,
• Test generator: 50 to 100 MΩ, Voltage Test
Current-Measuring Inputs 150 pF / 330 Ω Per IEC 60255-5 or EN 61010,
Threaded terminals for pin-terminal 2 kV AC, 60 s
Immunity to Radiated
connection: For the voltage test of the power supply
• Threaded terminal ends M5, Electromagnetic Energy
inputs, direct voltage
self-centering with wire protection for Per EN 61000-4-3 and (2.8 kV DC) must be used.
conductor cross sections of ≤ 4 mm2 ENV 50204, Level 3, The PC interface must not be subjected
or • Antenna distance to tested device:
to the voltage test.
Threaded terminals for ring-terminal > 1 m on all sides,
connection: • Test field strength, frequ. band
Impulse Voltage Withstand Test
80 to 1000 MHz: 10 V/m,
• In preparation • Test using AM: 1 kHz / 80%, Per IEC 60255-5,
• Single test at 900 MHz: • Front time: 1.2 µs,
AM 200 Hz / 100% • Time to half-value: 50 µs,
• Peak value: 5 kV,
Source impedance: 500 Ω

10
Mechanical Robustness Current Power Supply
Vibration Test • Nominal current Inom: Nominal Auxiliary Voltage
1 and 5 A (settable) • VA,nom: 48 to 250 V DC and
Per EN 60255-21-1 or
• Nominal consumption per phase: 100 to 230 V AC, or
IEC 60255-21-1, Test severity class 1,
< 0.1 VA at Inom • VA,nom: 24 to 36 V DC (per order)
• Frequency range in operation:
• Load rating: continuous 4 Inom
10 to 60 Hz, 0.035 mm, Operating Range
for 10 s: 30 Inom
60 to 150 Hz, 0.5 g, • for direct voltage: 0.8 to 1.1 VA,nom with a
for 1 s; 100 Inom
• Frequency range during transport: residual ripple of up to 12% of VA,nom
• Nominal surge current: 250 Inom
10 to 150 Hz, 1 g • for alternating voltage:
Shock Response and Voltage 0.9 to 1.1 VA,nom
Withstand Test, Bump Test • Nominal voltage Vnom: Nominal Burden
Per EN 60255-21-2 or 50 to 130 V AC (settable) • At VA = 220 V DC /
IEC 60255-21-2, Test severity class 1, • Nominal consumption per phase: maximum number of modules fitted:
• Acceleration: 5 g/15 g, < 0.3 VA at Vnom = 130 V AC • In case 40TE:
• Pulse duration: 11 ms • Load rating: continuous 150 V AC Initial position approx.: 12.6 W
Seismic Test Binary Signal Inputs Active position approx.: 34.1 W
Per EN 60255-21-3 or • In case 84TE:
• Nominal auxiliary voltage Vin,nom:
IEC 60255-21-3, Initial position approx.: 14.5 W
24 to 250 V DC
Test procedure A, Class 1, Active position approx.: 42.3 W
• Operating range: 0.8 to 1.1 Vin,nom
• Frequency range: with a residual ripple of up to 12% Start-Up Peak Current
5 to 8 Hz, 3.5 mm / 1.5 mm of Vin,nom • < 3 A, duration 0.25 ms
8 to 35 Hz, 10/5 m/s2, • Power consumption per input: Stored-Energy Time
• 3 x 1 cycle Vin = 19 to 110 V DC: 0.5 W ± 30% • ∅ 50 ms for interruption of VA ∅ 220 DC
Routine Test Vin > 110 V DC: Vin x 5 mA ± 30%
Tests per EN 60255-6 or PC Interface
Output Relays
IEC 60255-6 • Transmission rate: 300 to 115,200
• Rated voltage: 250 V DC, 250 V AC baud (settable)
Voltage Test • Continuous current: 5 A
Per IEC 60255-5, 2.2 kV AC, 1 s • Short-duration current: 30 A for 0.5 s Communication Interface
For the voltage test of the power • Making capacity: • Protocol can be switched between:
supply inputs, direct voltage (2.8 kV 1000 W (VA) at L/R = 40 ms IEC 60870-5-103, IEC 60870-5-
DC) must be used. The PC interface • Breaking capacity: 101, Modbus, DNP 3.0
must not be subjected to the voltage test. 0.2 A at 220 V DC and L/R = 40 ms • Transmission rate:
4 A at 230 V AC and cos ϕ = 0.4 300 to 64000 baud (settable)
Additional Thermal Test
100% controlled thermal endurance Analogue inputs and outputs Wire Leads
test, inputs loaded Direct current input Per RS 485 or RS 422, 2kV-isolation,
Distance to be bridged:
• Input current: 0 to 26 mA
• peer-to-peer link: max. 1200 m
Environmental Conditions • Value range: 0.00 to 1.20 Idc,nom
• multi-endpoint link: max. 100 m
(Idc,nom = 20 mA)
Ambient Temperature Range • Maximum permissible continuous Plastic Fibre Connection
current: 50 mA • Optical wavelength: typ. 660 nm
• Recommended temperature range: • Optical output: min. -7.5 dBm
• Maximum permissible input voltage:
-5°C to +55°C or • Optical sensitivity: min. -20 dBm
17V
+23°F to +131°F
• Input load: 100 Ω • Optical input: max. -5 dBm
• Limit temperature range: • Distance to be bridged: max. 45 m (1)
• Open circuit monitoring:
-25°C to +70°C or
0 to 10 mA (adjustable) Glass Fibre Connection G 50/125
-13°F to +158°F
• Overload monitoring: > 24.8 mA • Optical wavelength: typ. 820 nm
Ambient Humidity Range • Zero suppression: 0.000 to 0.200 • Optical output: min. -19.8 dBm
≤ 75 % relative humidity (annual
Idc,nom (adjustable) • Optical sensitivity: min. -24 dBm
mean), up to 56 days at ≤ 95% Resistance thermometer: • Optical input: max. -10 dBm
relative humidity and 40 °C, • Only PT 100 permitted, mapping • Distance to be bridged: max. 400 m (1)
condensation not permissible curve per IEC 60751 Glass Fibre Connection G 62,5/125
• Value range: –40 to +215 °C • Optical wavelength: typ. 820 nm
Solar Radiation (equivalent to –40 to +419 °F) • Optical output: min. -16 dBm
Avoid exposure of the front panel to • 3 wire configuration: • Optical sensitivity: min. -24 dBm
direct solar radiation. max. 20 Ω per conductor. • Optical input: max. -10 dBm
• Open and short circuited input • Distance to be bridged: max. 1400 m (1)
permitted.
Ratings • Open circuit monitoring: IRIG-B Interface
Measurement Inputs Θ > +215 °C (or Θ > +419 °F) and • Format B122,
• Nominal frequency fnom:
Θ < –40 °C (or Θ < –40 °F) • Amplitude modulated, 1 kHz carrier signal,
50 and 60 Hz (settable) Direct current output • BCD time-of-year code
• Operating range: 0.95 to 1.05 fnom • Output current: 0 to 20 mA (1) Distance to be bridged for optical outputs
• Over/Underfrequency Protection: • Maximum permissible load: 500 Ω and inputs that are equal on both ends,
40...70 Hz • Maximum output voltage: 15 V taking into account a system reserve of 3
dB and typical fiber attenuation.

11
Typical Characteristic Data

Main Function Deviations of the Resolution in Fault Data


• Minimum output pulse for a trip Timer Stages Acquisition
command: 0.1 to 10 s (settable)
• Output pulse for a close command: Reference Conditions Time Resolution
0.1 to 10 s (settable) • Sinusoidal signals with nominal 20 sampled values per period
frequency fnom, total harmonic
Differential Protection distortion ≤ 2 %, Phase Currents and Residual
• Shortest tripping time: • ambient temperature 20 °C and Currents or Neutral-Point
approx. 19 ms • nominal auxiliary voltage VA,nom Currents resp.
Deviation • Dynamic range: 33 Inom
Overcurrent-Time • Amplitude resolution
Protection Deviation relative to the setting under at Inom = 1 A: 2.0 mA r.m.s.
reference conditions at Inom = 5 A: 10.1 mA r.m.s.
• Operate time inclusive of output
relay (measured variable Definite-Time Stages Voltage
from 0 to 2-fold operate value):
± 1% + 20 to 40 ms • Dynamic range: 150 V
≤ 40 ms, approx. 30 ms
• Reset time (measured variable • Amplitude resolution: 9.2 mV r.m.s.
Inverse-Time Stages
from 2-fold operate value to 0): • ± 5 % + 10 to 25 ms (measured
≤ 40 ms, approx. 30 ms variable greater than 2 Iref)
• Starting resetting ratio: ca. 0.95 for IEC characteristic extremely
inverse and
Deviations of the • for thermal overload protection:
Operate Values ± 7.5 % + 10 to 20 ms

Reference Conditions Deviations in Measured


• Sinusoidal signals with nominal Data Acquisition
frequency fnom, total harmonic
distortion ≤ 2 %, Reference Conditions
• ambient temperature 20 °C and • Sinusoidal signals with nominal
• nominal auxiliary voltage VA,nom frequency fnom , total harmonic
Deviation distortion ≤ 2 %,
• ambient temperature 20 °C and
Deviation relative to the set value • nominal auxiliary voltage VA,nom
under reference conditions
Deviation’
Differential Protection
Deviation relative to the relevant
• Measuring system:
nominal value under reference
± 5 % at Id ∅ 0.2 Iref
conditions
• Harmonic restraint: ± 10 %
Operating Data
Ground Differential Protection
• Currents / measuring inputs: ± 1 %
Measuring system:
• Voltages / measuring input: ± 0.5 %
± 5 % at Id ∅ 0.2 Iref • Currents formed internally (restraining
Overcurrent-Time Protection and differential currents): ± 2 %
• Frequency: ± 10 mHz
Operate values: ± 5 %
Fault Data
Thermal Overload Protection
• Short-circuit current and voltage:
Operate value Θ: ± 5 % ±3%
Over/Underfrequency • Restraining and differential currents:
Protection ±5%
Operate values: ± 3 % Internal Clock
Over/Undervoltage Protection With free running internal clock:
Operate values: ± 3 % • < 1 min. / month

With external synchronization,


• via protocol, synch. interval
≤ 1 min: < 10 ms
• via IRIG-B signal input: ± 1 ms

12
Address List - Function Parameters

Global Functions Parameter Subset Selection • Matching fact. kam,b:


(PSS): 0.0000...5.0000
PC Link (PC): • Matching fact. kam,c:
• Control via USER: No/Yes
• Command blocking: No/Yes 0.0000...5.0000
• Param.subs.sel. USER:
• Sig./meas.val.block.: No/Yes • Matching fact. kam,d:
Parameter subset 1
0.0000...5.0000
Communication Link 1 Parameter subset 2 • Vector grp. ends a-b: 0...11
(COMM1): Parameter subset 3 • Vector grp. ends a-c: 0...11
• Command block. USER: No/Yes Parameter subset 4 • Vector grp. ends a-d: 0...11
• Sig./meas.block.USER: No/Yes • Keep time: • Meas. value rel. Id: 0.00...0.20 Iref
0.000...65.000 s /Blocked • Meas. value rel. IR: 0.00...0.20 Iref
Binary Output (OUTP):
• Outp.rel.block USER: No/Yes Ground Differential Protection
Self-Monitoring (SFMON):
(REF_1, REF_2, REF_3):
Main Function (MAIN): Fct. assign. warning: see selection
• Enabled USER: No/Yes
• Protection enabled: table • Select. meas. input:
No (= off)/Yes (= on)
Fault Recording (FT_RC): End a
• Test mode USER: No/Yes End b
• Fct. assig. trigger: see selection
• Nominal frequ. fnom: 50 Hz/60 Hz End c
table
• Rotary field: Clockwise • Reference power Sref:
• Id>: 0.01...30.00 Iref / Blocked
rotation/Anti-clockwise rot. 0.1...5000.0 MVA
• IR>: 0.01...30.00 Iref /Blocked
• Inom C.T.prim.,end a: 1...50000 A • Ref. curr. Iref: 0.000...50.000 kA
• Pre-fault time: 1...50 Periods
• Inom C.T.prim.,end b: 1...50000 A • Matching fact. kam,N:
• Post-fault time: 1...50 Periods
• Inom C.T.prim.,end c: 1...50000 A 0.0000...5.0000
• Max. recording time:
• Inom C.T.prim.,end d: 1...50000 A • Matching fact.kam,Y:
5...300 Periods 0.0000...5.0000
• Inom C.T.Yprim,end a: 1...50000 A
• Inom C.T.Yprim,end b: 1...50000 A • Meas. value rel. Id: 0.00...0.20 Iref
• Inom C.T.Yprim,end c: 1...50000 A Main Functions • Meas. value rel. IR: 0.00...0.20 Iref
• Vnom V.T. prim.: 0.1...1500.0 kV Definite-Time
• Inom device, end a: 1.0 A/5.0 A Main Function (MAIN):
Overcurrent Protection
• Inom device, end b: 1.0 A/5.0 A • Vnom prim., end a:
(DTOC1, DTOC2, DTOC3):
• Inom device, end c: 1.0 A/5.0 A 0.1...1500.0 kV
• Inom device, end d 1.0 A/5.0 A • Enabled USER: No/Yes
• Vnom prim., end b:
• Select. meas. input:
• Vnom V.T. sec.: 50...130 V 0.1...1500.0 kV
End a
• Meas. value rel. IP: • Vnom prim., end c:
End b
0.00...0.20 Inom 0.1...1500.0 kV End c
• Meas. value rel. IN: • Vnom prim., end d: End d
0.000...0.200 Inom 0.1...1500.0 kV Current summation
• Meas. value rel. IY: • Evaluation IN, end a:
0.000...0.200 IN,nom Calculated/Measured Inverse-Time Overcurrent
• Meas. value rel. V: • Evaluation IN, end b: Protection (IDMT1, IDMT2, IDMT3):
0.00...0.20 Vnom Calculated/Measured • Enabled USER: No/Yes
• Fct.assign. block. 1: Evaluation IN, end c: • Select. meas. input:
see selection table Calculated/Measured End a
• Fct.assign. block. 2: • Current summation: End b
see selection table Without End c
• Fct.assign. block. 3: End a + end b End d
see selection table End a + end c Current summation
• Fct.assign. block. 4: End a + end d Thermal Overload Protection
see selection table End b + end c (THRM1, THRM2):
• Trip cmd.block. USER: No/Yes End b + end d • Enabled USER: No/Yes
• Fct.assig.trip cmd.1: • Hold time dyn.param.: • Select. meas. input:
see selection table 0.00...100.00 s /Blocked End a
• Fct.assig.trip cmd.2: End b
Differential Protection (DIFF):
see selection table End c
• Fct.assig.trip cmd.3: • Enabled USER: No/Yes
End d
see selection table • Reference power Sref:
Current summation
• Fct.assig.trip cmd.4: 0.1...5000.0 MVA • Operating mode:
see selection table • Ref. curr. Iref,a: Absolute replica/Relative replica
• Min.dur. trip cmd. 1: 0.10...10.00 s 0.000...50.000 kA /Not measured
• Ref. curr. Iref,b: Over/Underfrequency
• Min.dur. trip cmd. 2: 0.10...10.00 s
0.000...50.000 kA /Not measured Protection (f<>):
• Min.dur. trip cmd. 3: 0.10...10.00 s
• Min.dur. trip cmd. 4: 0.10...10.00 s • Ref. curr. Iref,c: • Enabled USER: No/Yes
0.000...50.000 kA /Not measured • Evaluation time: 3...6 Periods
• Latching trip cmd. 1: No/Yes
• Ref. curr. Iref,d: • Undervolt. block.
• Latching trip cmd. 2: No/Yes V<: 0.20...1.00 Vnom(/3)
• Latching trip cmd. 3: No/Yes 0.000...50.000 kA /Not measured
• Latching trip cmd. 4: No/Yes • Matching fact. kam,a: Over/Undervoltage Protection
• Fct. assign. fault: see selection table 0.0000...5.0000 (V<>) : Enabled USER: No/Yes

13
Limit Value Monitoring Parameter Subset Inverse-Time Overcurrent
(LIMIT): valid for parameter subsets x = ‘1’ to ‘4’ Protection
• Enabled USER: No/Yes (IDMT1, IDMT2, IDMT3):
• IDC,Iin>: Differential Protection (DIFF):
• Enable PSx: No/Yes
0.100...1.100 IDC,nom /Blocked • Enable PSx: No/Yes
• Bl. tim.st. IN,n PSx:
• IDC,Iin>>: • Idiff> PSx: 0.10...2.50 Iref Without
0.100...1.100 IDC,nom /Blocked • Idiff>> PSx: 5...30 Iref
• Idiff>>> PSx: 5...30 Iref For single-ph. start
• tIDC,Iin>: 0.00...20.00 s /Blocked For multi-ph. start.
• m1 PSx: 0.2...1.5
• tIDC,Iin>>: 0.00...20.00 s/Blocked • Gen.starting modePSx:
• m2 PSx: 0.4...1.5
• IDC,Iin<: • IR,m2 PSx: 1.5...10.0 Iref W/o start. IN, Ineg/With starting
0.100...1.100 IDC,nom /Blocked • Op.mode harm.bl. PSx: IN, Ineg
• IDC,Iin<<: Without • tGS PSx: 0.00 ... 100.00 s/Blocked
0.100...1.100 IDC,nom /Blocked Not phase-selective • Rush restr.enabl PSx: No/Yes
• tIDC,Iin<: 0.00...20.00 s /Blocked Phase-selective • Iref,P PSx: 0.10...4.00 Inom
• tIDC,Iin<<: 0.00...20.00 s /Blocked • RushI(2f0)/I(f0) PSx: 10...50 % /Blocked
• T>: -20...200 °C • 0-seq. filt.a en.PSx: No/Yes • Iref,P dynamic PSx:
• T>>: -20...200 °C • 0-seq. filt.b en.PSx: No/Yes 0.10...4.00 Inom /Blocked
• tT>: 0...1000 s /Blocked • 0-seq. filt.c en.PSx: No/Yes • Characteristic P PSx:
• tT>>: 0...1000 s /Blocked • 0-seq. filt.d en.PSx: No/Yes Definite Time
• T<: -20...200 °C • Overflux.bl. en. PSx: No/Yes IEC Standard Inverse
• T<<: -20...200 °C • Over I(5f0)/(f0) PSx: 10...80 % IEC Very Inverse
• tT<: 0...1000 s /Blocked Ground Differential Protection IEC Extr. Inverse
• tT<<: 0...1000 s /Blocked IEC Long Time Inv.
(REF_1, REF_2, REF_3):
Limit Value Monitoring • Enable PSx: No/Yes IEEE Moderately Inv.
(LIM_1, LIM_2, LIM_3): • Idiff> PSx: 0.10...1.00 Iref IEEE Very Inverse
• Idiff>>> PSx: 5...10 Iref IEEE Extremely Inv.
• Enabled USER: No/Yes
ANSI Normally Inv.
• Select. meas. input: Definite-Time Overcurrent ANSI Short Time Inv.
End a Protection ANSI Long Time Inv.
End b
(DTOC1, DTOC2, DTOC3): RI-Type Inverse
End c
• Enable PSx: No/Yes RXIDG-Type Inverse
End d
• Bl. tim.st. IN,n PSx: • Factor kt,P PSx: 0.05...10.00
Current summation
Without • Min. trip t. P PSx: 0.00...10.00 s
• I>: 0.10...5.00 Inom /Blocked
For single-ph. start • Hold time P PSx: 0.00...600.00 s
• I>>: 0.10...5.00 Inom /Blocked
For multi-ph. start. • Reset P PSx: Without delay/Delayed
• tI>: 0.5...1000.0 s /Blocked • Gen.starting modePSx: W/o start. as per char.
• tI>>: 0.5...1000.0 s /Blocked IN, Ineg/With starting IN, Ineg valid for y = ‚neg‘ or ‚N‘:
Programmable Logic (LOGIC): • tGS PSx: 0.00 ... 100.00 s/Blocked • Iref,y PSx:
• Enabled USER: No/Yes • Rush restr.enabl PSx: No/Yes 0.01...0.80 Inom /Blocked
• Set 1 USER: No/Yes • I> PSx: 0.10...30.00 Inom /Blocked • Iref,y dynamic PSx:
to • I>> PSx: 0.10...30.00 Inom /Blocked 0.01...0.80 Inom /Blocked
Set 8 USER: No/Yes • I>>> PSx: 0.10...30.00 Inom/Blocked • Characteristic y PSx:
valid for y = ‚1‘ to ‚32‘: • I> dynamic PSx: Definite Time
• Fct.assignm. outp. y: see selection 0.10...30.00 Inom /Blocked IEC Standard Inverse
table • I>> dynamic PSx: IEC Very Inverse
Op. mode t output y: 0.10...30.00 Inom /Blocked IEC Extr. Inverse
• I>>> dynamic PSx: IEC Long Time Inv.
Without timer stage
0.10...30.00 Inom /Blocked
Oper./releas.delay IEEE Moderately Inv.
• tI> PSx: 0.00...100.00 s /Blocked
Oper.del./puls.dur. IEEE Very Inverse
• tI>> PSx: 0.00...100.00 s /Blocked
Op./rel.delay,retrig IEEE Extremely Inv.
• tI>>> PSx: 0.00...100.00 s /Blocked
Op.del./puls.dur.,rt ANSI Normally Inv.
valid for y = ‚neg‘ or ‚N‘:
Minimum time ANSI Short Time Inv.
• Iy> PSx:
• Time t1 output y: 0.00...600.00 s 0.10...8.00 Inom /Blocked ANSI Long Time Inv.
• Time t2 output y: 0.00...600.00 s • Iy>> PSx: RI-Type Inverse
• Sig.assig. outp. y: 0.10...8.00 Inom /Blocked RXIDG-Type Inverse
see selection table • Iy>>> PSx: • Factor kt,y PSx: 0.05...10.00
• Sig.assig.outp. y(t): 0.10...8.00 Inom /Blocked • Min. trip t. y PSx: 0.00...10.00 s
see selection table • Iy> dynamic PSx: • Hold time y PSx: 0.00...600.00 s
0.10...8.00 Inom /Blocked • Reset y PSx:
• Iy>> dynamic PSx: Without delay/Delayed as per char.
0.10...8.00 Inom /Blocked
• Iy>>> dynamic PSx:
0.10...8.00 Inom /Blocked
• tIy> PSx:
0.00...100.00 s /Blocked
• tIy>> PSx:
0.00...100.00 s /Blocked
• tIy>>> PSx:
0.00...100.00 s /Blocked

14
Thermal Overload Protection Measured Operating Current IN,d p.u.: 0.000...25.000 Inom
(THRM1, THRM2): Voltage V p.u.: 0.00...25.00 Vnom
Data Angle phi AB, end a: -180...180 °
• Enable PSx: No/Yes
• Iref PSx: 0.10...4.00 Inom Measured Data Input (MEASI): Angle phi BC, end a: -180...180 °
• Factor kP PSx: 1.05...1.50 • Current IDC: 0.00...24.00 mA Angle phi CA, end a: -180...180 °
• Tim.const.1,>Ibl PSx: • Current IDC p.u.: Angle phi AB, end b: -180...180 °
1.0...1000.0 min 0.00...1.20 IDC,nom Angle phi BC, end b: -180...180 °
• Tim.const.2,<Ibl PSx: • Curr. IDC,Iin. p.u.: Angle phi CA, end b: -180...180 °
1.0...1000.0 min 0.00...1.20 IDC,nom Angle phi AB, end c: -180...180 °
• Max.object temp. PSx: 0...300 °C • Scaled value IDC, Iin: Angle phi BC, end c: -180...180 °
• Max. cool. temp. PSx: 0...70 °C -32000...32000 Angle phi CA, end c: -180...180 °
• Select CTA PSx: • Temperature: -40.0...215.0 °C Angle phi AB, end d: -180...180 °
Default temp. value Angle phi BC, end d -180...180 °
Measured Data Output Angle phi CA, end d: -180...180 °
From PT100
From 20 mA input (MEASO): Angle phi NY, end a: -180...180 °
• Coolant temp. PSx: -40...70 °C • Current A-1: 0.00...20.00 mA Angle phi NY, end b: -180...180 °
• Bl. f. CTA fault PSx: No/Yes • Current A-2: 0.00...20.00 mA Angle phi NY, end c: -180...180 °
• ∆ϑ warning PSx: 50...200 % Angle phi A, end a-b: -180...180 °
Main Function (MAIN):
• ∆ϑ trip PSx: 50...200 % Angle phi B, end a-b: -180...180 °
Date:01.01.1997...31.12.2096 dd.mm.yy Angle phi C, end a-b: -180...180 °
• Hysteres. ∆ϑ,trip PSx: 2...30 % Time: 00:00:00...23:59:59 hh:mm:ss
• Warning pre-trip PSx: Angle phi A, end a-c: -180...180 °
Time switching: Angle phi B, end a-c: -180...180 °
0.0...1000.0 min /Blocked Standard time/Daylight saving time Angle phi C, end a-c: -180...180 °
Over/Underfrequency Frequency f: 40.00...70.00 Hz Angle phi A, end a-d: -180...180 °
Protection (f<>): Current Imax,a prim.: 0...25000 A Angle phi B, end a-d: -180...180 °
• Enable PSx: No/Yes Current Imax,b prim.: 0...25000 A Angle phi C, end a-d: -180...180 °
• Oper. mode f1 PSx: Current Imax,c prim.: 0...25000 A
Current Imax,d prim.: 0...25000 A Differential Protection (DIFF):
f
Current IA,a prim.: 0...25000 A Diff. current 1:
f with df/dt
Current IB,a prim.: 0...25000 A 0.000...40.000Iref
f w. Delta f/Delta t
Current IC,a prim.: 0...25000 A Restrain. current 1:
• f1 PSx: 40.00...70.00 Hz /Blocked
Current IA,b prim.: 0...25000 A 0.000...40.000 Iref
• tf1 PSx: 0.00...10.00 s /Blocked
Current IB,b prim.: 0...25000 A Diff. current 2:
• df1/dt PSx: 0.1...10.0 Hz/s /Blocked
Current IC,b prim.: 0...25000 A 0.000...40.000 Iref
• Delta f1 PSx: 0.01...5.00 Hz /Blocked
Current IA,c prim.: 0...25000 A Restrain. current 2:
• Delta t1 PSx: 0.04...3.00 s
Current IB,c prim.: 0...25000 A 0.000...40.000 Iref
to
Current IC,c prim.: 0...25000 A Diff. current 3:
• Oper. mode f4 PSx:
Current IA,d prim.: 0...25000 A 0.000...40.000 Iref
f
Current IB,d prim.: 0...25000 A Restrain. current 3:
f with df/dt
Current IC,d prim.: 0...25000 A 0.000...40.000 Iref
f w. Delta f/Delta t
• f4 PSx: 40.00...70.00 Hz /Blocked Current IN,a prim.: 0...25000 A Ground Differential Protection
• tf4 PSx: 0.00...10.00 s /Blocked Current IY,a prim.: 0...25000 A
(REF_1, REF_2, REF_3):
• df4/dt PSx: 0.1...10.0 Hz/s /Blocked Current IN,b prim.: 0...25000 A
Current IY,b prim.: 0...25000 A Diff. current: 0.00...20.00 Iref
• Delta f4 PSx: 0.01...5.00 Hz /Blocked Restrain.current: 0.00...20.00 Iref
• Delta t4 PSx: 0.04...3.00 s Current IN,c prim.: 0...25000 A
Current IY,c prim.: 0...25000 A Thermal Overload Protection
Over/Undervoltage Protection Current IN,d prim.: 0...25000 A (THRM1, THRM2):
(V<>): Voltage V prim.: 0.0...2500.0 kV Object temperature: -40...300 °C
• Enable PSx: No/Yes Current Imax,a p.u.: 0.00...25.00 Inom Coolant temperature: -40...200 °C
• V> PSx: Current Imax,b p.u.: 0.00...25.00 Inom Pre-trip time left: 0.0...1000.0 min
0.20...1.50 Vnom /Blocked Current Imax,c p.u.: 0.00...25.00 Inom Therm. replica vers.:
• V>> PSx: Current Imax,d p.u.: 0.00...25.00 Inom -25000...25000 %
0.20...1.50 Vnom /Blocked Current IA,a p.u.: 0.00...25.00 Inom Temp. offset replica:
• tV> PSx: Current IB,a p.u.: 0.00...25.00 Inom -25000...25000 %
0.00...100.00 s /Blocked Current IC,a p.u.: 0.00...25.00 Inom
• tV>> PSx: Current IA,b p.u.: 0.00...25.00 Inom
0.00...100.00 s /Blocked Current IB,b p.u.: 0.00...25.00Inom
• V< PSx: Current IC,b p.u.: 0.00...25.00 Inom
0.20...1.50 Vnom /Blocked Current IA,c p.u.: 0.00...25.00 Inom
• V<< PSx: Current IB,c p.u.: 0.00...25.00 Inom
0.20...1.50 Vnom /Blocked Current IC,c p.u.: 0.00...25.00 Inom
• Vmin> PSx: Current IA,d p.u.: 0.00...25.00 Inom
0.00...0.60 Vnom /Blocked Current IB,d p.u.: 0.00...25.00 Inom
• tV< PSx: Current IC,d p.u.: 0.00...25.00 Inom
0.00...100.00 s /Blocked Current IN,a p.u.: 0.000...25.000 Inom
• tV<< PSx: Current IY,a p.u.: 0.000...25.000 Inom
0.00...100.00 s /Blocked Current IN,b p.u.: 0.000...25.000 Inom
• tTransient PSx: Current IY,b p.u.: 0.000...25.000 Inom
0.00...100.00 s /Blocked Current IN,c p.u.: 0.000...25.000 Inom
• Hyst. V<> meas. PSx: 1...10 % Current IY,c p.u.: 0.000...25.000 Inom

15
Dimensions

Surface-mounted case 40 TE

147.5
177.5
184.5
C G
C
G

X6

213.4 257.1
242.6
260.2

Flush-mounted case 40 TE with panel cutout


177.5

C G
C
G

X6

227.9
213.4 253.6

203
155.4
159
168

181.3

Figure 5: Dimensional drawings for case 40 TE

16
Surface-mounted case 84 TE

147.5
177.5
184.5
C G
C
G

X6

434.8 257.1
464
481.6

Flush-mounted case 84 TE with panel cutout


177.5

C G
C
G

X6

434.8 227.9
253.6

284.9
259
25.9
159
168

5.0

5.0
410.0

Figure 6: Dimensional drawings for case 84 TE

17
Location and Connections

P631 in case 40 TE for ring-terminal connection P631 in case 40 TE for pin-terminal connection
01 02 03 04 05 06 07 08 09 10 01 02 03 04 05 06 07 08 09 10

P A T X V P A T X V
6J 4I 6J 4I
6O 8O 6O 8O

01 02 03 04 05 06 07 08 09 10 01 02 03 04 05 06 07 08 09 10

P632 in case 84 TE for ring-terminal connection P632 in case 40 TE for pin-terminal connection
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 01 02 03 04 05 06 07 08 09 10

P A T T X X X V P A T T X X V X
4J 4J 24I 6I 4I 4J 4J 6I 24I 4I
1U 8O 6O 8O 1U 8O 8O 6O
alt. alt.

Y Y
4I 4I

01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 01 02 03 04 05 06 07 08 09 10

P633 in case 40 TE for pin-terminal connection


01 02 03 04 05 06 07 08 09 10

P A T T T V X
4J 4J 4J 4I
1U 8O 6O

01 02 03 04 05 06 07 08 09 10

P633 in case 84 TE for ring-terminal connection P633 in case 84 TE for pin-terminal connection
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21

P A T T T X Y X X X V P A T T T X Y X X X V
4J 4J 4J 6I 4I 24I 6I 4I 4J 4J 4J 6I 4I 24I 6I 4I
1U 8O 8O 6O 8O 1U 8O 8O 6O 8O

01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21

P634 in case 84 TE for ring-terminal connection P634 in case 84 TE for pin-terminal connection
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21

P A T T T T Y X X X V P A T T T T Y X X X V
4J 4J 4J 3J 4I 24I 6I 4I 4J 4J 4J 3J 4I 24I 6I 4I
1U 8O 6O 8O 1U 8O 6O 8O

01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21

Figure 7: Location diagrams

18
Transformer Type T Transformer Type T Transformer Type T Transformer Type T Communication Type A
module 6J module 4J 1U module 4J module 3J module

Per order
Ring Pin Current measuring Ring Pin Voltage measuring
X031 X032 inputs X031 X031 input COMM1
1 1 1IA T11 Mounting variation optical fibre link
2 2 13 1 1U T5 X7
3 3 1IB T12 16 4 2U 1
X//Y U17
4 4
5 5 1IC T13 X8
6 6 1
X//Y U18

or wire link
X9
Ring Pin Ring Pin X//Y
Current measuring Current measuring Current measuring 1
X042 X032 inputs X_2 inputs X092 inputs 2 D2 [R ]
7 1 2IA T21 1 1 xI A Tx1 1 1 xI A Tx1 1 1 xI A Tx1 3
8
U19
2 2 2 2 2 2 2 4
9 3 2IB T22 3 3 xIB Tx2 3 3 xIB Tx2 3 3 xIB Tx2 5 D1 [T ]
10 4 4 4 4 4 4 4
11 5 2IC T23 5 5 xIC Tx3 5 5 xIC Tx3 5 5 xIC Tx3 RS 485
12 6 6 6 6 6 6 6

COMM2
wire link only
(in preparation)
7 7 xIN Tx4 7 7 xIN Tx4 X10
X//Y
8 8 8 8 1
2 D2 [R ]
3
U20
4
5 D1 [T ]

RS 485

IRIG-B
time synchronization
X11
1 # U21
#

Analogue Type Y Binary Type X Binary Type X Binary Type X Power supply Type V
module 4I module 24I module 6I 8O module 6O module

Ring Pin Ring pin Ring Pin Ring Pin Ring Pin
X_1 X_1 Meas. outputs Signal inputs X_1 X_1 Output relays X_1 X_1 Output relays X_1 X_1 Output relays
1 1 X_1 X_1 1 1 1 1 1 1
Vin
2 2 K_1 1 1 2 2 K_1 2 2 K_1 2 2 K_1
valid U_1
3 3 2 2 3 3 3 3 3 3
U_2
3 3 4 4 4 4 4 4
U U_3
4 4 4 4 5 5 5 5 5 5
U_4
5 5 5 5 6 6 K_2 6 6 6 6 K_2
# U_5
6 6 6 6 7 7 7 7 7 7
0..20 mA U_8 U_6 K_2
7 7 8 8 8 8 8 8
U_7 K_3 K_3
7 7 8 8 9 9 9 9 9 9
K_2 U_8
8 8 9 9
9 9 valid X_2 X_2
10 1 X_2 10 1
X_2 X_2 11 2 K_4 10 1 11 2 K_4
Vin
10 1
U 10 1 12 3 K_5 11 2 12 3 K_5
U_9
11 2 11 2 13 4 K_6 12 3 13 4 K_6
# U_10
12 3 12 3 14 5 K_7 13 4 14 5 K_7
U_11
0..20 mA U_9 13 4 15 6 14 5 K_3 15 6
U_12
14 5 15 7 K_8 15 6 15 7 K_8
U_13
15 6 17 8 15 7 17 8
Signal and meas. U_14
15 7 17 8
inputs U_15 Signal inputs Signal inputs
17 8 18 9
U_16
13 4 18 9 18 9 18 9
Vin U _1 Vin Vin
14 5 U _1 U _1
15 6 X_3 X_3 X_3
Vin U_2
15 7 X_3 19 1 19 1 19 1
Vin
17 8 19 1 20 2
Vin 20 2 K_4 20 2
Vin
Vin U_3 U_18
20 2 21 3 U_2 21 3 21 3 U_2
U_18
18 9 21 3 22 4
Vin 22 4 22 4
Vin U_4 U_19 Vin
22 4 U_3 23 5 K_5 U_3
U_20
X_3 23 5 23 5
Vin 24 6 23 5
U_21 Vin
19 1 24 6 24 6 U_4 25 7 24 6 U_4
20 2
U U_22 K_6
U _5 25 7 25 7
Vin 26 8
21 3 0..20 mA U_23 U_5 27 9 Power supply
26 8
# U_24
22 4 U U_6 27 9 26 8 Vin 25 7 VAux
23 5 27 9 U_6 26 8
24 6 PT100
# 27 9
U100

'_' is used as a wildcard for the location according to figure 7

Figure 8: Terminal connection diagrams of the modules

19
Connection Examples

A
B
C

Transformer Type T
module 6J

Ring Pin Current measuring


X031 X032 inputs
1 1 1IA T11
2 2
3 3 1IB T12
4 4
5 5 1IC T13
6 6

X042
7 1 2I A T21
8 2
9 3 2IB T22
10 4
11 5 2IC T23
12 6

A B C

Figure 9: Connection example for P631

20
A
B
Transformer Type T
C module 4J 1U

Ring Pin Voltage measuring


X031 X031 input

13 1 1U T5
16 4 2U

Current measuring
X032 inputs
1 1 xIA Tx1
2 2
3 3 xIB Tx2
4 4
5 5 xIC Tx3
6 6

7 7 xIN Tx4
8 8

b c

Transformer Type T
module 4J

Ring Pin Current measuring


X051 X052 inputs
1 1 xIA Tx1
2 2
3 3 xIB Tx2
4 4
5 5 xIC Tx3
6 6

7 7 xIN Tx4
8 8

Transformer Type T
module 4J

Ring Pin Current measuring


X071 X072 inputs
1 1 xIA Tx1
2 2
3 3 xIB Tx2
4 4
5 5 xIC Tx3
6 6

A B C A B C 7
8
7
8
xIN Tx4

Figure 10: Connection example for P633

21
Information required with order:

Variants Order No.


P631 Differential protection P631- 9 0 0 0 0
Basic device 40TE, pin terminal connection 3 -401
Basic device 40TE, ring terminal connection 4 -402
Basic complement 4 binary inputs and 8 output relays

P632 Differential protection P632- 9 0 1


Basic device 40TE, pin terminal connection 3 -401
Basic device 84TE, ring terminal connection 8 -402
Basic complement 4 binary inputs and 8 output relays

P633 Differential protection P633- 9 9 1


Basic device 40TE, pin terminal connection 3 0 0 -401
Basic device 84TE, pin terminal connection 7 -402
Basic device 84TE, ring terminal connection 8 -403
Basic complement 4 binary inputs and 8 output relays

P634 Differential protection P634- 9 9 1


Basic device 84TE, pin terminal connection -401
Basic device 84TE, ring terminal connection -402
Basic complement 4 binary inputs and 8 output relays

Case design:
Surface mounted, local control panel with text display 3
Flush mounted, local control panel with text display 4

Additional options: [not possible for P633 40TE]


Without 0
With 1 binary module (6 binary inputs/8 output relays) [P632/P633/P634 only] 1
With 2 binary modules (12 binary inputs/16 output relays) [P633 only] 2

Power supply and additional option:


VA,nom = 24 to 36 VDC 3
VA,nom = 48 to 250VDC/100 to 230VAC 4
VA,nom = 24 to 36 VDC and binary module (6 output relays) 8
VA,nom = 48 to 250VDC/100 to 230VAC and binary module (6 output relays) 9

Additional options: [not possible for P633 40TE]


Without 0
With analogue module [P632/P633/P634 only] 2
With binary module (24 binary inputs) [P632/P633/P634 only] 4
With binary module (24 binary inputs) and analogue module [P633 only] 6

Interfaces:
With communication interface -451 9 1
protocol: IEC 60870-5-103

With communication interface -456 9


only IRIG-B input for clock synchronisation 0 0

protocol can be switched between: 2


IEC 60870-5-101/-103, MODBUS, DNP 3.0
and IRIG-B input for clock synchronisation

for connection to wire, RS485, isolated 1


for connection to plastic fibre, FSMA connector 2
for connection to glass fibre, ST connector 4

Language:
English (German)
German (English) -801
French (English) -802
Spanish (English) -803

22

S-ar putea să vă placă și