Sunteți pe pagina 1din 15

JOHN DEERE

WORLDWIDE COMMERCIAL & CONSUMER


EQUIPMENT DIVISION

N pr
Portable Generator
ot o
Models LP030344-0, LP030345-0, LP030419-0
R

279598
fo du
e

Service and Troubleshooting


r ct
Manual
io
n

WARNING
Failure to read and follow the
Service Manual and all operating
instructions can result in death, bodily
injury, and/or equipment damage.
Save this manual for future reference.

North American Edition


Litho in USA
Safety Important Safety Information
The manufacturer cannot anticipate every possible
Equipment Description
circumstance that might involve a hazard. The
warnings in this manual, and the tags and decals
Read this manual carefully and become
affixed to the unit are, therefore, not all-inclusive. If you
familiar with your generator. Know its
use a procedure, work method or operating technique
applications, its limitations and any hazards
that the manufacturer does not specifically
involved.
recommend, you must satisfy yourself that it is safe for
This generator is engine-driven, revolving field, you and others. You must also make sure that the
alternating current (AC) generator. It was designed to procedure, work method or operating technique that
supply electrical power for operating compatible you choose does not render the generator unsafe.
electrical lighting, appliances, tools and motor loads.
The generator’s revolving field is driven at about 3,600
rpm by a single-cylinder engine.
Safety Symbols and Meanings
1
NOTICE: Exceeding generator’s wattage/amperage
capacity could damage generator and/or electrical
devices connected to it.
• DO NOT exceed the generator’s wattage/
amperage capacity.
N pr
TOXIC KICKBACK ELECTRICAL
FUMES SHOCK
Every effort has been made to ensure that the
ot o
information in this manual is both accurate and current.
However, the manufacturer reserves the right to
R

change, alter, or otherwise improve the generator and


this documentation at any time without prior notice.
fo du
FIRE EXPLOSION READ
e

The Emission Control System for this generator is


warranted for standards set for the Environmental MANUAL
Protection Agency and the California Air Resources
r ct
Board.

MOVING FLYING HOT


PARTS OBJECTS SURFACE

Signal Words in Safety Messages


io

The safety alert symbol is used to identify safety


information about hazards that can result in personal
n

injury.
A signal word (DANGER, WARNING, or CAUTION) is
used with the alert symbol to indicate the likelihood and
the potential severity of injury. In addition, a hazard
symbol may be used to represent the type of hazard.

DANGER indicates a hazard which, if not avoided,


will result in death or serious injury.

WARNING indicates a hazard, which, if not


avoided, could result in death or serious injury.

CAUTION indicates a hazard which, if not avoided,


could result in minor or moderate injury.

NOTICE address practices not related to personal


injury.

1
WARNING Starter cord kickback (rapid
retraction) will pull hand and arm toward
engine faster than you can let go which could
cause broken bones, fractures, bruises, or
sprains resulting in serious injury.
• When starting engine, pull cord slowly until resistance
is felt and then pull rapidly to avoid kickback.
• NEVER start or stop engine with electrical devices
plugged in and turned on.

WARNING Fuel and its vapors are extremely


flammable and explosive which could cause
1 burns, fire, or explosion resulting in death,
serious injury and/or property damage.
WARNING Engines emit carbon monoxide, an
odorless, colorless, poison gas. Breathing WHEN ADDING OR DRAINNG FUEL
carbon monoxide could result in death, serious • Turn generator engine OFF and let it cool at
injury, headache, fatigue, dizziness, vomiting, least 2 minutes before removing fuel cap.
confusion, seizures, nausea or fainting. Loosen cap slowly to relieve pressure in tank.
• Operate this product ONLY outdoors. • Fill or drain tank outdoors.
N pr
• Install a battery operated carbon monoxide alarm
• DO NOT overfill tank. Allow space for fuel
near the bedrooms.
• Keep exhaust gas from entering a confined area
expansion.
ot o
through windows, doors, ventilation intakes, or other • If fuel spills, wait until it evaporated before
openings. starting engine.
R

• DO NOT operate this product inside any building, • Keep fuel away from sparks, open flames, pilot
carport, porch, mobile equipment, marine lights, heat, and other ignition sources.
fo du
applications, or enclosure, even if windows and doors • Check fuel lines, tank, cap, and fittings
e

are open. frequently for cracks or leaks. Replace if


necessary.
r ct
• DO NOT light a cigarette or smoke.
WARNING The engine exhaust from this WHEN STARTING EQUIPMENT
product contains chemicals known to the State of • Ensure spark plug, muffler, fuel cap, and air
California to cause cancer, birth defects, or other cleaner are in place.
reproductive harm. • DO NOT crank engine with spark plug
removed.
WHEN OPERATING EQUIPMENT
WARNING Battery posts, terminals, and related • DO NOT operate this product inside any
accessories contain lead and lead compounds, building, carport, porch, mobile equipment,
chemicals known to the State of California to cause marine applications, or enclosure.
cancer and reproductive harm. Wash hands after • DO NOT tip engine or equipment at angle
io

handling. which causes fuel to spill.


• DO NOT stop engine by moving choke to
“CHOKE” position.
n

WARNING Certain components in this product WHEN TRANSPORTING, MOVING OR


and related accessories contain chemicals known to REPAIRING EQUIPMENT
the State of California to cause cancer, birth defects • Transport/move/repair with fuel tank EMPTY or
or other reproductive harm. Wash hands after with fuel shutoff valve OFF.
handling. • DO NOT tip engine or equipment at angle
which causes fuel to spill.
• Disconnect spark plug wire.
WARNING WHEN STORING FUEL OR EQUIPMENT WITH
• This generator does not meet U.S. Coast Guard FUEL IN TANK
Regulation 33CFR-183 and should not be used on • Store away from furnaces, stoves, water
marine applications. heaters, clothes dryers, or other appliances that
• Failure to use the appropriate U.S. Coast Guard have pilot light or other ignition source because
approved generator could result in death or serious they could ignite fuel vapors.
injury and/or property damage.

2
WARNING Generator voltage could cause WARNING Starter and other rotating parts
electrical shock or burn resulting in death or could entangle hands, hair clothing, or
serious injury. accessories resulting in serious injury.
• Use approved transfer equipment to prevent • NEVER operate generator without protective housing
backfeed by isolating generator from electric utility or covers.
workers. • DO NOT wear loose clothing, jewelry or anything that
• When using generator for backup power, notify utility could be caught in the starter or other rotating parts.
company. • Tie up long hair and remove jewelry.
• Use a ground fault circuit interrupter (GFCI) in any
damp or highly conductive area, such as metal
decking or steel work.
• DO NOT touch bare wires or receptacles.
• DO NOT use generator with electrical cords which
are worn, frayed, bare, or otherwise damaged. CAUTION Excessively high operating speeds


DO NOT operate generator in the rain or wet weather.
DO NOT handle generator or electrical cords while
could result in minor injury and/or generator
damage. Excessively low speeds impose a heavy
1
standing in water, while barefoot, or while hands and load.
feet are wet. • DO NOT tamper with governor spring, links, or other
• DO NOT allow unqualified persons or children to parts to increase engine speed. Generator supplies
operate or service generator. correct rated frequency and voltage when running at
governed speed.
• DO NOT modify generator in any way.
N pr
WARNING Exhaust heat/gases could ignite
combustibles, structures or damage fuel tank
NOTICE: Exceeding generator’s wattage/amperage
causing a fire, resulting in death, serious injury
ot o
capacity could damage generator and/or electrical
and/or property damage. Contact with muffler
devices connected to it.
R

area could cause burns resulting in serious


injury. • DO NOT exceed the generator’s wattage/
amperage capacity. See Don’t Overload
fo du
• DO NOT touch hot parts and AVOID hot exhaust
e

gases. Generator in the Operator’s Manual.


• Allow equipment to cool before touching. • Start generator and let engine stabilize
• Keep at least 5 feet (152 cm) of clearance on all side before connecting electrical loads.
r ct
of generator including overhead.
• Connect electrical loads in OFF position,
• It is a violation of California Public Resource Code,
Section 4442, to use or operate the engine on nay
then turn ON for operation.
forest-covered, brush-covered, or grass-covered land • Turn electrical loads OFF and disconnect
unless the exhaust system is equipped with a spark from generator before stopping generator.
arrester, as defined in Section 4442, maintained in
effective working order. Other states or federal
NOTICE: Improper treatment of generator can damage
jurisdictions may have similar laws. Contact the
original equipment manufacturer, retailer, or dealer to
and shorten its life.
obtain a spark arrester designed for the exhaust • Use generator only for intended uses.
system installed on this engine. • If you have questions about intended use,
io

• Replacement parts must be the same and installed in contact your authorized dealer.
the same position as the original parts.
• Operate generator only on level surfaces.
• DO NOT expose generator to excessive
n

moisture, dust, dirt, lint, or corrosive vapors.


WARNING Unintentional sparking could
cause fire or electric shock resulting in death • DO NOT start engine with air cleaner or air
or serious injury. cleaner cover removed.
• DO NOT insert any objects through cooling
WHEN ADJUSTING OR MAKING REPAIRS TO YOUR slots.
GENERATOR • If connected devices overheat, turn them off
• Disconnect the spark plug wire from the spark plug and disconnect them from generator.
and place the wire where it cannot contact spark
plug. • Shut off generator if electrical output is lost, if
WHEN TESTING FOR ENGINE SPARK equipment sparks, smokes, or emits flames,
• Use approved spark plug tester or if unit vibrates excessively.
• DO NOT check for spark with spark plug removed.

3
Generator Components

1 N pr
ot o
R

fo du
e

r ct

A - 120/240Volt AC, 30 Amp Locking Receptacle — H - Air Cleaner — Protects engine by filtering dust and
May be used to supply electrical power for the debris out of intake air.
operation of 120 and/or 240 Volt AC, 30 Amp, J - Recoil Starter — Used to start the engine.
single phase, 60 Hz electrical, lighting, appliance, K - Identification Label — Provides model, revision,
tool, and motor loads. and serial number of generator. Please have these
B - 120 Volt AC, 20 Amp, Duplex Receptacles — readily available when calling for assistance.
io

May be used to supply electrical power for the L - Oil Drain Plug — Drain engine oil here.
operation of 120 Volt AC, 20 Amp, single phase, 60 M - Oil Fill Cap — Check and fill engine with oil here.
Hz electrical, lighting, appliance, tool, and motor N - Fuel Tank — Capacity of seven (7_ U.S. gallons
n

loads. (26.5 L).


C - Double Pole Circuit Breaker (AC) — A double P - Spark Arrester Muffler — Exhaust muffler lowers
pole circuit breaker is provided to protect the 30A engine noise and is equipped with a spark arrestor
receptacle and generator against electrical screen.
overload. R - Engine Identification — Provides model, type,
D - Circuit Breakers (AC) — Push-to-reset circuit and code of engine. Please have these readily
breakers are provided to protect the generator available if calling for assistance.
against electrical overload.
E - Grounding Fastener — Consult your local agency
having jurisdiction for grounding requirements in
your area.
F - Choke Lever — Used when starting a cold engine.
G - Rocker Switch — Set this switch to “On” before
using recoil starter. Set switch to “off” to stop
engine.

4
Alternator Components

H - Air Cleaner —
J - Recoil Starter —

N pr 1
ot o
R

fo du
e

r ct

A - Four (4) screws for Rear Bearing Cover


B - Rear Bearing Cover
C - Two (2) screws for Brush Assembly
D - Brush Assembly
E - Automatic Voltage Regulator
io

F - Rear Bearing Carrier


G - Stator
n

H - Rotor Slip Rings


J - Rotor

5
Automatic Voltage Regulator (AVR)
The voltage regulator acts to increase or decrease
current flow to the rotor windings based on the
demands of the load connected to the generator. The
increase or decrease in current flow through the rotor
results in a proportional increase or decrease in the
rotor’s magnetic field strength, which is what induces
(AC) current in the power windings of the stator.
The operating sequence for this type of voltage
regulator is as follows:

1 N pr
ot o
R

fo du
e

r ct
Figure 1

• The rotor turns at a pre-determined speed. • Excitation winding output is delivered


through wires 2 and 6 to the voltage
• Voltage is induced into the stator windings
regulator at excitation terminals 2 (C) and 6
by residual magnetism in the rotor.
(D). If the excitation wire connections are
• Voltage from the 120VAC stator power reversed, the voltage regulator will shut off.
windings are available through wires 11,22,
• The voltage regulator converts the (AC)
33, and 44 to the circuit breaker. Any
excitation winding output to (DC) and
electrical load connected to the generator
delivers the (DC) output to the rotor via the
will complete the circuit.
io

red wire (+) (E), brush, and slip ring. Then it


• 120 VAC and frequency signals are moves throughout the rotor winding, the slip
delivered from the stator winding via wires ring and the (-) brush and through the black
n

11A and 22A, to the voltage regulator at wire (F). The (DC) output from the voltage
sensing terminals 11(A, Figure 1) and 22 regulator to the rotor is based on the voltage
(B). If for any reason sensing or frequency is and frequency signals received from sensing
lost, the voltage regulator will turn off, and it wires 11A and 22A.
will only turn back on when the generator is
shut down and restarted.

6
Troubleshooting
Refer to Figure 2 for wire identification and locations
when performing the following tests.

N pr 1
ot o
R

fo du
e

r ct

Figure 2
io
n

7
TEST 1 - Check Voltage and Frequency Output output voltage that will remain at zero. This usually
1. Disconnect any electrical loads. occurs if the unit is out of use for a long period of time. If
2. Check all circuit breakers and verify they are residual magnetism is lost, it can usually be restored by
ON. “flashing the field” with a simple process involving a
3. Set meter to measure AC volts. (DC) battery.
4. Connect the meter test leads into a 120 VAC 1. Obtain a 12VDC battery and two jumper leads
generator receptacle. with alligator clip ends.
5. Connect a frequency meter into a generator 2. Remove the four screws and remove the rear
receptacle. bearing cover.
6. Start the generator engine, let it stabilize and 3. Gain access to the AVR and disconnect the
warm up. brush wires.
NOTICE: Isolate brush leads from each other and do
7. Read the “no-load” voltage and frequency, and
not allow them to touch grounded parts.
analyze the results as follows:
1 • If zero volts or less than 1VAC is indicated
4. Connect the battery positive (+), to the positive
brush, which will be the brush closest to the
proceed to Test 2 - Flash the Field.
rotor bearing.
• If low voltage is indicated, but readings is
5. Connect the battery negative (-), to the negative
above 1VAC and AC frequency is normal
brush, which is the brush farthest away from the
proceed to Test 3 - Isolate the Control Panel.
rotor bearing (Figure 3).
• If low voltage is indicated, but reading is
above 6VAC and AC frequency is low the
N pr
engine governor may need adjustment.
Refer to the appropriate engine manual for
ot o
further governor troubleshooting.
R

TEST 2 - Flash the Field


fo du
e

WARNING Battery posts, terminals, and related


r ct
accessories contain lead and lead compounds,
chemicals known to the State of California to cause
cancer and reproductive harm. Wash hands after
handling.

WARNING Starter and other rotating parts Figure 3


could entangle hands, hair clothing, or
accessories resulting in serious injury. 6. Start the engine and allow it to stabilize at
• DO NOT touch rotating parts. running speed.
• DO NOT wear loose clothing, jewelry or anything that 7. After about 5 seconds, shut the engine down.
io

could be caught in the starter or other rotating parts. 8. Disconnect the battery wires from the
• Tie up long hair and remove jewelry. brushes.(Disconnect negative (-) battery wire
• DO NOT allow unqualified persons to service
n

last).
generator.
9. Restart the unit and check once again for
proper (AC) output voltage.
WARNING Generator voltage could cause • If output voltage is within specifications,
electrical shock or burn resulting in death or troubleshooting is complete.
serious injury. • If output voltage is not within specifications,
• DO NOT touch bare wires or receptacles. proceed to Test 3- Isolate Control Panel.
• DO NOT allow unqualified persons to service
generator. TEST 3 - Isolate Control Panel
A “No Output” condition may or may not be related to
the alternator windings. To help isolate where the issue
is, follow these steps:
In normal generator operation, upon startup there is
1. With the engine OFF, disconnect the power
some “residual” magnetism in the rotor to get the
lead harness from the back of the control panel.
generating process started. Residual magnetism is
what is left in the rotor after the unit has shut down. 2. Set meter to measure AC volts.
When residual magnetism is lost, the unit will have an

8
3. Connect the test leads to the stator wires #11
and #22 located in the control panel connector.
Polarity does not matter (Figure 4).
4. Start the engine and measure the voltage
output.
5. Shut off the engine.
• A voltage output of 120VAC indicates the
alternator is functioning, and the no output
condition is likely in the control panel.
Disassemble the control panel and inspect
for any indication of what may cause no
output. Refer to the unit wiring diagram to
verify connections.
• A low voltage output indicates the alternator
needs to be tested. Proceed to Check
1
Alternator.

Figure 4
Check Alternator
N pr
Alternator Disassembly
ot o
There are two methods of testing the alternator
The alternator can be diagnosed without complete
R

windings:
disassembly. To access the power winding, disconnect
1. Measuring the winding resistance and
the connector from the back of the control panel. The
fo du
comparing them to the specifications.
e

Automatic Voltage Regulator (AVR) is mounted inside


the rear bearing carrier (F, Figure 4). To access the 2. Bypassing the Automatic Voltage Regulator
AVR, remove the four screws (A) and remove the (AVR).
r ct
plastic, rear bearing cover (B). The AVR (E) slides in The tests can be performed individually or in
two grooves cast into the rear bearing carrier. To conjunction with each other.
remove the AVR, slide it out and disconnect the wiring.

The brushes (D) are also mounted to the rear bearing


carrier. Remove the two screws (C) and carefully pull
out the brushes.
Once removed, the rotor slip rings can be accessed
through the area where the brushes were mounted.
io

NOTICE: The brushes are made of a carbon material


and can easily break. Use care when removing and
installing the brushes.
n

9
Measure Winding Resistance
Test Stator AC Power Winding Resistance
1. Set meter to measure Ohms.
2. Connect the test leads to stator wires #11 and
#22 located in the harness going to the control
panel connector (Figures 2 and 5).

1 N pr
ot o
Figure 6
R

5. Measure the resistance and compare it to the


nominal resistance listed in the back of this
fo du
e

manual.
• A reading within the specifications listed is
acceptable.
r ct
• A reading of infinity or high resistance
Figure 5
indicates an opening in the power winding.
3. Measure the resistance and compare it the Replace the stator.
nominal resistance from the specifications • A low reading indicates a shorted stator
listed in the back of this manual. winding. Replace the stator.
4. Connect the test leads to stator wires #33 and 6. Connect one meter test lead to a proper ground
#44 located in the control panel connector on alternator. Connect the other test lead to the
(Figures 2 and 6). stator power winding.
• A reading of infinity should be measured. If a
reading of infinity is measured and the stator
io

resistance is within specifications, the stator


is functioning properly.
n

• A reading other than infinity indicates a


stator winding shorted to ground. Replace
the stator.

10
Test Stator Excitation Winding Resistance • A reading other than infinity indicates a
The excitation wires may be colored (red and blue) or power winding shorted to an excitation
numbered (#2 and #6). Colored excitation wires must winding. Replace the stator.
not be confused with the colored power wires. The 5. Connect one test lead to an excitation wire.
excitation wires were disconnect earlier from the Connect the other test lead to a proper metal
voltage regulator earlier in Measuring Winding ground.
Resistance.
• A reading of infinity should be measured.
1. Set meter to measure Ohms.
• A reading other than infinity indicates a
2. Connect the test lead to the stator excitation winding shorted to ground. Replace the
wires #2 and #6 (Figure 7). These wires were stator.
previously disconnected from the AVR.

Check Rotor Resistance 1


1. Set meter to measure Ohms.
2. Connect one test lead to each rotor slip ring
(Figure 8). The slip rings can be accessed
through the area where the brushes were
removed. Polarity does not matter.
N pr
NOTICE: Do not connect the test lead terminals.
Ensure that each test lead makes a connection to each
ot o
slip ring.
R

fo du
e

r ct

Figure 8

3. Measure the rotor resistance. Compare it to the


Figure 7 nominal resistance from the specifications
listed in the back of this manual.
3. Measure the resistance and compare it to the
io

• A reading of infinity or a very high resistance


nominal resistance listed in the back of this indicates an open circuit or a partially open
manual. condition of the rotor windings. Before
n

• A reading within the specifications listed is replacing the rotor, proceed to Bypass the
acceptable. Automatic Voltage Regulator.
• A reading of infinity or high resistance • A very low resistance indicates a shorted
indicates an opening in the power winding. rotor. Replace the rotor.
Replace the stator. • If resistance is within specifications, proceed
• A low reading indicates a shorted winding. to Step 4.
Replace the stator. 4. Connect one test lead to a proper metal ground
4. Connect one test lead to a stator power wire. on the engine or alternator and the other test
Connect the other test lead to one of the stator lead to either slip ring.
excitation wires. • A reading of infinity should be measured. If a
• A reading of infinity should be measured. If a reading of infinity is measured and the rotor
reading of infinity is measured and the stator resistance is within specifications, the rotor
resistance is within specifications, the stator is functioning properly.
is functioning properly. • A reading other than infinity indicates a rotor
winding shorted to the rotor shaft. Replace
the rotor.

11
Bypass the Automatic Voltage
Regulator
Bypassing the Automatic Voltage Regulator (AVR) will
test all wiring and windings within the alternator without
disassembly of the generator. There are three AC
Voltage checks and one DC Amperage test to be
performed. The exact readings may very depending on
ambient temperature, battery voltage, meter
calibration, etc.

An open in the rotor could cause lowered voltage


readings during these tests. Check and record all the
voltage readings first, then check and record the
1 amperage draw on the rotor. This test requires a fully
charged 12V battery. Using a battery that is not fully
charged will give inaccurate readings.

WARNING Starter and other rotating parts


could entangle hands, hair clothing, or
accessories resulting in serious injury.
N pr
• DO NOT touch rotating parts.
• DO NOT wear loose clothing, jewelry or anything that
ot o
could be caught in the starter or other rotating parts.
• Tie up long hair and remove jewelry.
R

• DO NOT allow unqualified persons to service


generator. Figure 9
fo du
e

WARNING Generator voltage could cause


r ct
electrical shock or burn resulting in death or
serious injury. WARNING Battery posts, terminals, and related
• DO NOT touch bare wires or receptacles. accessories contain lead and lead compounds,
• DO NOT allow unqualified persons to service chemicals known to the State of California to cause
generator. cancer and reproductive harm. Wash hands after
handling.

1. Disconnect Wires #1, #4, #11A, #22A, #2, and 4. Connect a jumper wire from battery positive (+)
#6 from the AVR. Set AVR aside. to the positive brush terminal. Then connect
another jumper wire from battery negative (-) to
negative brush terminal (Figure 10).
io

NOTICE: Isolate wire terminals from each other and do


not allow them to touch grounded parts.
n

2. Disconnect the power wire harness from the


back of the control panel.
3. Set meter to measure AC Voltage. Connect one
test lead to wire #2 and the other test lead to
wire #6. Wires #2 and #6 were previously
disconnected from the voltage regulator
(Figure 9).

Figure 10

12
5. Manually start the unit. The AC voltage measured across Wire #2 and Wire #6
6. Measure AC voltage across Wire #2 and Wire should be higher that the AC Voltage measured across
#6. A minimum of 60VAC should be measured. Wire #11A and Wire #22A. Refer to Figure 13 when
7. Shut the unit OFF. performing the following test.
There is one DC Amperage test to perform. The exact
8. Connect one test lead to Wire #11 and the other
amperage readings may vary depending on ambient
lead to Wire #22. Wires #11 and #22 are
temperature, battery voltage, meter calibration, etc.
located in the control panel connector (Figure
11).
1. Set meter to read DC Amperage.
2. Connect the meter in series between battery
positive (+) and wire #4 (Figure 13). Refer to the
operation/instruction manual for the meter you
are using for correct test lead locations and
meter settings.
3. Connect the meter in series between the 12V
1
battery negative (-) and Wire #1.
4. Manually start the unit and measure DC
Amperage. Reading should be 1.0 - 1.5 Amps.
N pr
ot o
R

Figure 11
fo du
e

9. Manually start the unit and measure AC voltage


across Wire #11A and Wire #22A. A minimum
of 60VAC should be measured.
r ct
10. Shut unit OFF.
11. Connect one test lead to Wire #33 and the
other test lead to Wire #44 (Figure 12). Wires
#33 and #44 are located in the control panel
connector. Figure 13

5. Disconnect the battery from Wire #1 and Wire


#4.
6. Analyze test results as follows:
• If all readings are within the specification, the
io

alternator is good and the voltage regulator


is suspect.
n

• If amperage reading in within the range, and


one or more of the voltage readings are low,
the stator is suspect.
• High amperage indicates a short in the rotor.
Verify battery voltage, wiring, and
connections. Repair as necessary, then
retest. If the reading is still high, replace the
rotor.
• Low or no amperage, indicates an open in
the rotor. Verify the meter’s fuse is good and
Figure 12 check the battery voltage, wiring, and
connections. Repair as necessary, then
12. Manually start the unit and measure AC voltage
retest. If reading is still low, replace the rotor.
across Wire #33 and Wire #44. A minimum of
60VAC should be measured. 7. Restore wiring harness to the control panel and
the AVR.
13. Shut unit OFF.

13
GENERATOR SPECIFICATIONS

NO LOAD VOLTAGE 228-246

NO LOAD FREQUENCY (RPM) 62.0 - 62.5 Hertz (3720 - 3750 RPM)

1
RESISTANCE VALUES

Winding Resistance 030344 030345 030419

Rotor (at the slip rings) 7.7 - 9.6 OHM 6.3 - 7.6 OHM 6.3 - 7.6 OHM
N pr
Power (wires 11-22 & 33-44) 0.16 - 0.19 / 0.16 - 0.19 0.26 - 0.31 / 0.26 - 0.31 0.26 - 0.31 / 0.26 - 0.31
OHM OHM OHM
ot o
R

Excitation (wires 2-6) 2.01 - 2.39 OHM 1.53 - 1.81 OHM 1.53 - 1.81 OHM
fo du
e

r ct
io
n

14

S-ar putea să vă placă și