Documente Academic
Documente Profesional
Documente Cultură
Chapter 10
Load Transfer
10.1 Introduction
Load will be transferred through a structure and to its foundation. Thus
the load imposed from a roof structure must, somehow, be transferred
through other structural elements until it is finally resisted by the earth
supporting the foundations. In order to design the roof members , we will
first need to determine how much load they are to carry. Having designed
the roof, we might then consider the design of the walls supporting the
roof structure and, as such, we must determine how much of the roof
load will be transferred to the wall. We might then consider the floor or
other structural member. Whatever member we decide to design, we
must first determine how much load it will be required to carry. This will
be based on its position in the structure and on how the loads are
transferred from part to part. To demonstrate the problem, consider the
simple structure of Example 10.1, shown in Figure 1.
For the structure shown in Figure 1, determine the unfactored total load,
per metre depth of the building, at the base of the foundations across the
section A-A using the loads indicated in table 1.
Chapter 10 Page 1
Unit 14: Structural Mechanics in Construction and Civil Engineering
Flat Roof
A A
Wall
200 mm
6000 mm 10000 mm
Floor
600 mm Foundation
400 mm
Section A-A
5000 mm
Plan
Figure 1: Simple Structure - Example 1
Answer
First it is important to note that we will be calculating the load per metre
depth of the building. Secondly, the dead load induced by the foundation
is given for the structure in Table 1. Often, only the density of the
concrete is known, in which case we will need to calculate the force per
metre from the volume of the foundation. Finally, there is no imposed
load on the wall. This is because, in this case, the imposed loads have
been included in the load-carrying floor and roof elements and, as we are
only calculating vertical imposed loads, the wind effects need not be
considered here. This will simplify the analysis of the structure.
Chapter 10 Page 2
Unit 14: Structural Mechanics in Construction and Civil Engineering
It can be seen from Table 2 that the total dead load at the underside of
the foundation is 30.43 kN/m run of building and the total imposed load is
5.325 kN/m run of building. The total unfactored load is therefore:
We can now follow this simple procedure to calculate the loads at various
points on any structure. However, it is important to note that not all
distributed loads will be of a simple rectangular or uniform nature. Also,
certain simplifications are made in our analysis, some of which will be
considered in the garage structure shown in Figure 2 of Example 2.
Chapter 10 Page 3
Unit 14: Structural Mechanics in Construction and Civil Engineering
1.40 m
1.25 m
Details of Garage
2.20 m
Structure
5.50 m
(Not to Scale)
B B Side Elevation
2.00 m
Roof trusses at 450 mm
centres
2.50 m
Lintel ‘A’ Lintel ‘B’
A
Plan
Section A-A
I-Beam
150 mm
300 mm
Front Elevation Rear Elevation
For the given loading, calculate the total unfactored load carried by the
lintels A and B and the load per metre depth of the building just above
the foundation at point C.
Chapter 10 Page 4
Unit 14: Structural Mechanics in Construction and Civil Engineering
Answer
Before commencing our analysis of loading for the lintels A and B, let us
consider the pitched roof and its effect on the openings. Although the roof
spans from side to side on the garage and is supported on the walls, in
practice some roof load will be transmitted to the lintels. This is because,
in this case, when constructing the roof, an overhanging section will be
formed. This section can transfer load to the end (or gable) walls. Also
some load will be transmitted because the trusses do not tightly abut the
end walls. In making this allowance some ‘engineering judgement’ must
be used. In this example we will consider the end walls support one span
(i.e. 450mm) of roof. A detail of the lintel loads is shown in figure 3.
Y = 1120 mm
X = 280 mm
150 mm
2000 mm
250 mm
2500 mm
Y = 700 mm
X = 700 mm
150 mm
1250 mm
625 mm
2500 mm
Chapter 10 Page 5
Unit 14: Structural Mechanics in Construction and Civil Engineering
each lintel. To calculate the total load we multiply the area by the value
for dead and imposed load given in Figure 3 plus an allowance for the roof
load hence:
Therefore the total load at point C, per metre depth of the building, will
be:
Total load per metre depth of building at point
C = 8.426 + 2.863
= 11.289 kN/m run (of side wall)
Chapter 10 Page 6
Unit 14: Structural Mechanics in Construction and Civil Engineering
12 000 mm
Pitched
Roof
Cavity Wall
2500 mm
Floor 2
Brick wall
2500 mm
Floor 1
750 mm
5700 mm 5700 mm
300 mm
Chapter 10 Page 7
Unit 14: Structural Mechanics in Construction and Civil Engineering
Answer
Imposed Load Total Load (kN/
Dead Load (kN/m2)
(kN/ m2 m2)
Pitched roof 0.90 1.00 1.90
Cavity wall 4.00 4.00
Brick wall 2.00 2.00
Floor 1.00 1.50 2.50
Table 7: Total loads for building –Example 3
TOTAL 52.98 kN/m run 32.21 kN/m run 45.85 kN/m run
Table 8: Total loads at the base of the foundations A,B and C for building – Example 3
Chapter 10 Page 8
Unit 14: Structural Mechanics in Construction and Civil Engineering
Given the dead and imposed loads in table 9 calculate the factored loads,
per metre depth of building, at beam A and the top of the points B and C,
as shown in Figure 5. Assume that the dead loads are to be factored by
1.4 and all imposed loads by 1.6.
Cavity Wall
3 000 mm
Floor 2
Beam A
Block Wall
3500 mm
5800 mm
Floor 1
800 mm 6000 mm
Point C Point B
Chapter 10 Page 9
Unit 14: Structural Mechanics in Construction and Civil Engineering
Answer
Dead Load Imposed Factored Factored Total Load
(kN/m2) Load Dead Load Imposed (Factored)
(kN/m2) Load
(1) (2) ((1) x 1.4) ((2) x 1.6) (kN/m2)
Flat roof 0.85 075 1.19 1.20 2.39
Cavity wall 3.50 4.90 4.90
Block wall 2.50 3.50 3.50
Floor 1 1.50 1.50 2.10 2.40 4.50
Floor2 0.85 1.50 1.19 2.40 3.59
Table 10: Total loads for building – Example 4
TOTAL 37.06 kN/m run 61.22 kN/m run 38.96 kN/m run
Table 11: Total loads on beam A and at point B and C for building - Example 4
Chapter 10 Page 10
Unit 14: Structural Mechanics in Construction and Civil Engineering
Chapter 10 Page 11
Unit 14: Structural Mechanics in Construction and Civil Engineering
Exercise 10.1
1. Figure 6 shows a section through a building. Below is a table
indicating the loads imposed by each of the structural elements.
Assuming a load factor for dead loads of 1.4 and for imposed loads
of 1.6, calculate the total factored loads at beam B and foundations
A and C. The self-weight of beam B can be ignored in this case.
13 000 mm
Pitched Pitched
Roof (1) Roof (2)
Cavity Wall
Brick wall
3500 mm
Floor 2
Beam B
6750 mm 5750 mm
2700 mm
Cavity Wall
Floor 1
1000 mm
300 mm
600 mm 600 mm
Figure 6: Question 1
Foundation A Foundation C
Chapter 10 Page 12
Unit 14: Structural Mechanics in Construction and Civil Engineering
Figure 7: Question 2
Chapter 10 Page 13
Unit 14: Structural Mechanics in Construction and Civil Engineering
Flat Roof
10 m
Cavity Wall
3m Floor
0.5 m
Concrete Beam
Solid Wall
6m
0.3 m
Figure 8: Question 3
Chapter 10 Page 14