Psychrometric Chart

Content
• The Psychrometric Chart
The Psychrometric Chart
• Dry Air
• Dry air is a gas mixture having a typical volumetric 
analysis of 20.99% O2, 78.03% N2, 0.94% Ar, 0.03% 
CO2,and 0.01% H2.
• For engineering purposes, it is sufficiently accurate 
to consider dry air with 21% O2 and 79% inert gases 
taken as N2.
• The humidity in the ambient air varies according to 
content of water vapor in the vapor‐dry air mixture.
The Psychrometric Chart
• The Psychrometric Chart 
• The Psychrometric Chart graphically represents the steam tables for moisture 
in air at conditions we encounter in HVAC work.  
• The Psychrometric Chart allows complex problems to be worked out easily, 
and provides a feel for common HVAC processes that we are interested in.
• The standard ASHRAE Psychrometric Chart has a horizontal axis for dry bulb 
temperature, and a vertical axis for humidity ratio in kg of moisture per kg of 
dry air.  
• Other parameters on the chart are: relative humidity, wet bulb temperature, 
enthalpy, specific volume, and saturation temperature.
The Psychrometric Chart
• Psychrometric properties:
• Dry‐bulb temperature (Tdb). The dry‐bulb temperature is the temperature indicated 
by a thermometer exposed to the air in a place sheltered from direct solar radiation. 
(°C)
• Wet‐bulb temperature (Twb). The wet‐bulb temperature represents the temperature 
of the moisture in the air (humidity). (°C)
• Dew point temperature(Tdp).  The dew point temperature is defined as the 
temperature at which the vapor changes into liquid (condensation). (°C)
• Relative humidity (RH). Relative humidity is the ratio of the partial pressure of water 
vapor in an air‐water mixture to the saturated vapor pressure of water at a 
prescribed temperature. (%)
• Specific Humidity or Humidity Ratio (W). Specific humidity is defined as the 
proportion of the mass of water vapor per unit mass of the moist air sample (dry air 
plus the water vapor). (ghumidity/kgdry air)
The Psychrometric Chart
• Psychrometric properties (cont.):
• Specific volume (v). It is the total volume of both the dry air and water vapor 
per kilogram of dry air. (m3/kgda)
• Air Density (). It is the inverse of the specific volume. (kgda/m3)
• Specific Enthalpy (h). It is the sum of the internal (heat) energy of the moist 
air in question, including the heat of the air and water vapor within. Also 
called heat content per unit mass. (kJ/kg)
Example
Dry bulb temperature (Tdb) = 24°C
Relative Humidity (RH) = 50 %
Find:
Wet bulb temperature (Twb)
Dew point temperature (Tdp)
Humidity ratio (W)
Specific volume (v)
Enthalpy (h)
Air density ()
RH = 50 %

Tdb = 24°C
Twb = 17°C

T = 17°C
Tdp = 13°C

T = 13°C
W = 9.4 gH2O/kgda
1

1
0.854 m3/kg
. / v = 0.86 m3/kg

v = 0.85 m3/kg
v = 0.854 m3/kg
h = 48 kJ/kg
Homework 2c
Problems from the textbook (Thermodynamics, Yunus, 8th ed.):
• Answer the following conceptual problems:
• Chapter 14, problems: 33, 34, 35, 36
• Answer the following problems:
• Chapter 14, problems: 37, 39, 41, 43
Psychrometric Chart