Sunteți pe pagina 1din 28

Design, Function and Operation of On-Load Tap-Changers

Uwe Seltsam

Maschinenfabrik Reinhausen GmbH

TRANSFORM Partner
About the Author

Uwe Seltsam

Maschinenfabrik Reinhausen GmbH, Regensburg / Germany

– Manager Technical Specialists –

Scientific Background

Dipl.-Ing. (FH) Electrical Engineering

Professional Background

10 years at Maschinenfabrik Reinhausen

GmbH Technical Service / Troubleshooting

Uwe Seltsam, Maschinenfabrik Reinhausen GmbH 07.06.2013 Page 2


Agenda

1. On-load tap-changer in regulating transformer


2. On-load tap-changer – Design types
3. Switching sequence of tap selector and diverter switch insert
4. Maintenance
® ®
Intervals for OILTAP and VACUTAP
Parameter contact wear
Parameter replacement of parts
Parameter oil carbonization
Checks after maintenance
Checks between maintenances
5. Oil change criteria
6. Influence of humidity on dielectric strength
7. Avoiding carbon deposits or their effects
8. On-load tap-changer – Protective devices
9. Diagnostics
Uwe Seltsam, Maschinenfabrik Reinhausen GmbH 07.06.2013 Page 3
1. On-load tap-changer in regulating transformer

On-load tap-changers (OLTCs) are used for changing the transmission ratio under load
110 kV 16%
U1 Transformer: / 21 kV
Mwg = Main winding 40 MVA, 110 kV 17.6 kV

Cwg = Coarse winding OLTC: M III 350 Y – 123/C – 10 19 1G


Mwg Rwg = Regulating winding Step voltage: 17.6 kV : 9 steps ≙ 1.955 kV/step ≙ 1.78 %

555 wdgs LU = Diverter switch insert


U2
Cwg - 21 kV
120 wdgs + 129 wdgs

Rwg 9 LU
108 wdgs 2
U1 = N1
12 wdgs/step 1
U2 N2

Nominal: U2 = 21 kV = constant
Example 1: U1 = 110 kV
N1 = 110 kV • 129 wdgs / 21 kV = 675 wdgs
U2 = 110 kV • 129 wdgs / 675 wdgs = 21.02 kV
Example 2: U1 = 116 kV
N1 = 116 kV • 129 wdgs / 21 kV = 711 wdgs
U = 116 kV • 129 wdgs / 711 wdgs = 21.05 kV
2
Uwe Seltsam, Maschinenfabrik Reinhausen GmbH 07.06.2013 Page 4
2. On-load tap-changer – Design types
Tap-change operation Vectorial diagram Contact movement

® A,B

OILTAP Main contacts


(only for V III 350
Y/Δ, V III 500 Y / Δ,
Type M since 1972 V I 350, V I 700)

a,b
Main switching
e. g. M III 600 9 contacts

steps a 1, b 1
Transition contacts
3-pole Ra, Rb
Star connection Transition resistors

Insulation to ground Ua, Ub


Voltages of tappings
Um = 123 kV U
st
Step voltage

U, I
Voltage, current of tap-
changer terminals

Uwe Seltsam, Maschinenfabrik Reinhausen GmbH 07.06.2013 Page 5


2. On-load tap-changer – Design types
Operation Vectorial diagram Contact movement

® A,B

OILTAP Main contacts


(only V III 350 Y/Δ,
V III 500 Y/ Δ,
Type V since 1979 V I 350, V I 700)

a,b
Main switching
e. g. V III 200 10 steps conttacts

3-pole a 1, b 1
Transition contacts
Star connection R
Insulation to ground Transition resistor

Um = 76 kV Ua, Ub
Voltages of tappings
U
st
Step voltage

U, I
Voltage, current of
tap-changer terminals

Uwe Seltsam, Maschinenfabrik Reinhausen GmbH 07.06.2013 Page 6


2. On-load tap-changer – Design types

®
VACUTAP
®
Type VR since 2004

e. g. VRF III 1300 10 steps


3-pole
Star connection
Insulation to ground
Um = 76 kV

Switching sequence


Switching direction n n+1
MSV Main switching contact
(vacuum interrupter), main path

MTF Transfer contact, main path

TTV Main switching contact (vacuum


interrupter), transition path

TTF Transfer contact, transition path

MCA Main contact side A

MCB Main contact side B

ZnO ZNO varistor

R Transition resistor

Uwe Seltsam, Maschinenfabrik Reinhausen GmbH 07.06.2013 Page 7


2. On-load tap-changer – Design types

®
VACUTAP
Type VV since 2000

e. g. VV III 400 10 steps

MTS Tap-selector contact, main path


MSV Main switching contact (vacuum interrupter), main path
TTS Tap-selector contact, transition path
TTV Transition contact (vacuum interrupter), transition path
STC Sliding take-off contact
R Transition resistor
I Circulating current
C

Uwe Seltsam, Maschinenfabrik Reinhausen GmbH 07.06.2013 Page 8


3. Switching sequence of tap selector and diverter switch

IB

Tap pre-selection without current Diverter switch insert operation type M

Switching principle of diverter switch insert: Flag switching cycle


Operation switching time approx. 40 – 50 ms
Load period of transition resistors approx. 30 ms
IB = Operating through-current
IK = Circulating current
Link to movie
R = Transition resistor

Uwe Seltsam, Maschinenfabrik Reinhausen GmbH 07.06.2013 Page 9


®
4.1 Maintenance – Intervals for OILTAP and
®
VACUTAP

®
OILTAP - Regular maintenance, depending on
time of service or no. of operations
(whichever comes first)

Neutral-point application
after every 5 – 7 years
after every 50,000 – 150,000 operations

Delta application
after every 2 – 4 years
after every 20,000 – 100,000 operations
Maintenance of tap selector
after every 1 to 1.2 million operations

Diverter switch insert type M


Service life 800,000 operations
For OLTC-specific maintenance intervals, refer to the respective
operating instructions or the label on the motor-drive unit.

Uwe Seltsam, Maschinenfabrik Reinhausen GmbH 07.06.2013 Page 10


®
4.1 Maintenance – Intervals for OILTAP and
®
VACUTAP

®
VACUTAP - Regular maintenance, only depending
on the number of operations

Neutral-point or phase application


after every 300,000 operations
Tap selector maintenance
after every 1.2 million operations

Reason for time-independent maintenance:


No oil carbonization since arcs do not occur in insulating oil

®
For network applications, the VACUTAP is more or less
maintenance-free. Diverter switch insert type VR
®

Example: Service life 1.2 million operations


Switching frequency 5,000 operations per year
 maintenance after 60 years.

Uwe Seltsam, Maschinenfabrik Reinhausen GmbH 07.06.2013 Page 11


®
4.1 Maintenance – Intervals for OILTAP and
®
VACUTAP
®
Monitoring – TM100, Tapguard 260
Maintenance depending on condition
Maintenance criterion Calculation
Parts subject to wear No. of ops. specification for parts change
Oil change and cleaning Calculation algorithm for oil carbonization
Contact wear Calculation algorithm for single and difference wear

Maintenance time
Visual presentation
Present condition 0 ... 100 %
Prediction for 100 % moment
Semaphore function green/yellow/red

Red signal prevents additional operations


by the motor-drive unit, but it is not
integrated into the tripping circuit for the
circuit breaker.
®
Front panel Tapguard 260
Uwe Seltsam, Maschinenfabrik Reinhausen GmbH 07.06.2013 Page 12
4.2 Maintenance – Parameter contact wear
MSCB TCB TCA MCA

®
Criteria for OILTAP :
Single wear and MCB MCA

Difference in wear between switching and transition


contact
Parameters for contact wear: MSCA MSCB

TCA TCB
Number of operations: variable value Contact system of diverter switch type M
Arcing current: variable value
Medium arc duration: approx. 6 ms
Step voltage
Arc voltage: 25 – 30 V
Contact material: Cu or CuW sintered material U
st

Wear on main switching contact: SG

proportional to operating through-current


MCA MSCATCA TCBSCBMCB
Wear on resistor contact: MC = Main contact
independent of operating current, but proportional
to circulating current Ic (Ic = Ust / Rres) MSC = Main switching contact
TC = Transition contact
Exceeding the wear differences influences the switching R = Transition resistor
sequence – a short circuit between taps may occur. SG = Spark gap
Max. permissible single wear = 4 mm
Max. permissible difference in wear = 2.5 mm
Uwe Seltsam, Maschinenfabrik Reinhausen GmbH 07.06.2013 Page 13
4.3 Maintenance – Parameter replacement of parts

Depending on no. of ops.


Springs, leads, etc.
Depending on wear
Arc contacts, etc.
Preventively
Cover gasket, etc.
E.g. Energy accumulator spring for type
Up-dating M: 400,000 – 500,000 ops.
Measure for increasing operating reliability
Adjustment to current state of manufacture
Diverter switch insert:
®
Replacement after 800,000 operations (OILTAP )
®
Replacement after 1.2 million ops. (VACUTAP )
Tap selector:
Maintenance after every 1.0 to 1.2 million operations, E.g. Braided lead for type M:
depending on OLTC type 250,000 operations

MR original parts are the basis for safe operation.

Uwe Seltsam, Maschinenfabrik Reinhausen GmbH 07.06.2013 Page 14


4.4 Maintenance – Parameters oil carbonization

Criterion:
Heat removal from the transition resistors must
not be restricted by oil carbonization.
Determining factors for degree of carbonization:
Number of operations
Arc energy
Type of oil: Little difference between naphthenic-base
or paraffin-base oil

Drying of a sooted tap-changer leads to baking of


carbon deposits on the surfaces and to a reduction of
the dielectric strength.

Use only transformer oil for cleaning. Electrical cleaners


evaporate on the surface of the insulating material and
lead to humidity.
Diverter switch type insert T Diverter switch type insert T
before cleaning after cleaning

Uwe Seltsam, Maschinenfabrik Reinhausen GmbH 07.06.2013 Page 15


4.5 Maintenance – Checks after maintenance

The following checks have to be performed:


Identical indication of positions between on-load tap-changer and motor-drive unit
Functional check of final positions
If protective relay is in position “OFF“, it must not be possible to put the circuit breaker in
the circuit
Transformer ratio test during major modification work on the on-load tap-changer (e. g.,
replacement of motor-drive unit, or after connecting or disconnecting tap-selector leads)

1) Diverter switch with oil compartment


2) Motor-drive unit
3) Protective relay
4) Drive shafts

Uwe Seltsam, Maschinenfabrik Reinhausen GmbH 07.06.2013 Page 16


4.6 Maintenance – Checks between maintenances

Motor-drive unit Visual check


Heater in operation
Door closed

Protective relay Functional check


together with transformer
protection test

Drying agent OLTC Reliability (effectiveness)


oil conservator together with transformer test

Oil monitoring Oil exchange criteria, see section 5

Disconnected OLTC maintenance before re-commissioning of transformer


transformer if operating time and downtime exceed maintenance interval
®
of on-load tap-changer (OILTAP )
Uwe Seltsam, Maschinenfabrik Reinhausen GmbH 07.06.2013 Page 17
5. Oil change criteria

® Dielectric strength* Water content


OLTC application of OILTAP
Neutral-point application Minimum 30 kV / 2.5 mm Maximum 40 ppm

Use in auto-transformer or Minimum 40 kV / 2.5 mm Maximum 30 ppm


regulation in delta winding

®
OLTC application of VACUTAP
All Minimum 30 kV / 2.5 mm Maximum 30 ppm

*Dielectric strength, measured in accordance with IEC 60156

The temperature of the oil sample must be measured at the time when the oil was taken.
The values specified for dielectric strength apply to oil temperatures of 20 ± 5 °C at the time
of evaluating the oil sample.

Recommendation:
Dielectric strength of > 50 kV / 2.5 mm for new insulating oil that must be filled in after maintenance.

Uwe Seltsam, Maschinenfabrik Reinhausen GmbH 07.06.2013 Page 18


5. Oil change criteria

Time of oil sample test:


It is up to the user of the transformer to check the insulating oil, and the test should
be done at the same time when an oil sample of the transformer is taken
Class 1 in accordance with IEC 60214-1: after every 5 years (use in neutral-point)
Class 2 in accordance with IEC 60214-1: after every 2 years (use in auto-transformer,…)
Whenever it is suspected that humidity is absorbed (drying agent ineffective etc.)

Ask the OLTC manufacturer if other insulating liquids (ester liquids, etc.) are used.

Uwe Seltsam, Maschinenfabrik Reinhausen GmbH 07.06.2013 Page 19


6. Influence of humidity on dielectric strength

Facts:
®
Diverter switch oil of OILTAP is a mixture of oil,
carbon deposits and humidity
Water absorption of carbon deposits is several times
as high as water absorption of oil
Carbonized oil with inadmissibly high water content puts
insulation distances at risk which are exposed to
voltage stress

Effects:
Electrical-field distortion with local discharges
Thermal decomposition of surface of insulating material
Creepage paths
Breakdown of insulating distance with flashover

Switching shaft
Example of creepage paths

Uwe Seltsam, Maschinenfabrik Reinhausen GmbH 07.06.2013 Page 20


7. Avoiding carbon deposits or their effects

®
Vacuum technology in the VACUTAP
No carbon deposits since arcs do not occur in insulating oil

Vacuum interrupter

Oil filter unit, filter cartridge


with paper filter: absorbs carbon particles (6 – 9 microns); in use
for annual number of > 15,000 operations / year
with paper filter and drying agent (4 kg granulate):
absorbs carbon particles and water (approx. 420 g)

The effectiveness of the drying agent of the filter cartridge must be


determined by oil sample and water content analysis.

Oil filter unit – OF100


Uwe Seltsam, Maschinenfabrik Reinhausen GmbH 07.06.2013 Page 21
8. On-load tap-changer – Protective devices

Protective relay = flow-controlled relay type RS2001


(standard equipment)
Response value, e. g. for M III 600: 1.2 m/sec ± 20% bei 20°C
Pressure relief (burst membrane) in OLTC cover
Static response pressure about 4 – 5 bar
RS2001
®
Pressure relief valve type MPreC (instead of burst membrane)
Response value about 1.3 – 1.8 bar, depending on OLTC type
Monitoring of drive shafts, e. g., for multiple-column OLTC design

The above-mentioned protective devices must be integrated in the


tripping circuit of the circuit breaker of the transformer.

Burst membrane
End position limiting device in OLTC and/or motor-drive unit

Find out the cause after a protective device has responded!

®
MPreC
07.06.2013 Page 22
Uwe Seltsam, Maschinenfabrik Reinhausen GmbH
9. Diagnostics

Increased tap selector contact resistance


if contacts are not silver-plated:
Signs of impurity layer
Resistance measurement in accordance with
CIGRE report 12-205/1994 rounds off gas-
in-oil analysis;

Extract from CIGRE report

Tap-selector contacts colored to “black-grey“:


Signs of silver-sulfide (impurity layer)
Check for corrosive sulfur (oil, etc.)

Separated silver-sulfide layer may lead to flashovers.


Tap selector contact with silver-sulfide

Uwe Seltsam, Maschinenfabrik Reinhausen GmbH 07.06.2013 Page 23


9. Diagnostics

®
Gas-in-oil analysis for diverter switch insert oil in OILTAP :
No informative value with respect to arcing on main switching
contacts and transition contacts.

Oil
No. of ops. temp. H2 CH4 C2H6 C2H4 C2H2 CO CO2 O2 N2
[°C]
0 16 127 31 3 70 359 10 344 17500 39400
29000 50 17796 12205 3642 36170 102172 330 3032 10800 48100
50000 22 13553 13000 4200 50000 103000 317 7733 4900 25300

Example for OLTC type M

®
Gas-in-oil analysis for diverter switch insert oil in VACUTAP :
An evaluation pattern is currently being developed.

Uwe Seltsam, Maschinenfabrik Reinhausen GmbH 07.06.2013 Page 24


9. Diagnostics

Torque measurement:
Integral part of monitoring TM100 and
®
TG260 , including assessment
(semaphore function). Online procedure.
Torque measurement directly on OLTC head
with mobile measuring device.

Example of torque progress

Tap-change operation sequence assessment:


Indirect assessment of tap-change operation
sequence of diverter switch by measuring
®
the contact wear (OILTAP ).
Measurement of tap changes of diverter switch
insert operation using direct current.

Diverter switch insert type G


Uwe Seltsam, Maschinenfabrik Reinhausen GmbH 07.06.2013 Page 25
Summary

• On-load tap-changers are available in/with different


switching principles: high-speed resistor and reactor principle
types: non-vacuum and vacuum

• On-load tap-changers are available for different applications


power transformers for transmission and distribution
transformer for industrial use (e.g. arc-furnace or ladle furnace transformers)
HVDC transformers
phase-shifting-transformers
transformers for operation at explosion-prone sites (e.g. offshore platform)

• Maintenance
maintenance intervals of the respective on-load tap-changer shall be observed at any time to
ensure trouble-free operation of the transformer. Original spare parts and trained service
staff have also be seen as mandatory.

Uwe Seltsam, Maschinenfabrik Reinhausen GmbH 07.06.2013 Page 26


About MR

Maschinenfabrik Reinhausen GmbH


 Founded in 1868
 Family ownership since 1891
 Brand name since1901
 World market leader in transformer switching
 2,850 employees in 7 business areas
 30 locations – world-wide
 Doing business in 190 countries
 Company sales: 630 million EUR

 www.reinhausen.com

Uwe Seltsam, Maschinenfabrik Reinhausen GmbH 07.06.2013 Page 27

S-ar putea să vă placă și