Guided Wave Radar
Liquid-Liquid Interface Transmitter
DESCRIPTION
Measures level and interface – 2 wire
The Eclipse® 707 Transmitter is a loop-powered, 24 V DC
liquid-level transmitter based on the revolutionary Guided
Wave Radar (GWR) technology. Encompassing a number
of significant engineering accomplishments, this leading
edge level transmitter is designed to provide both liquid level
and liquid-liquid level measurement performance.
The innovative enclosure is a first in the industry, orienting
dual compartments (wiring and electronics) in the same
plane, and angled to maximize ease of wiring, configuration,
set-up and data display.
F E AT U R E S
* Measures accurately liquid-liquid interface (min. differ-
ence dielectric between upper and lower liquid ≥ 10; eg.
water and oil).
* 4-20 mA output (as per Namur NE 43) for interface level.
* Level and interface read out over Hart /AMS digital com-
® ®
munication.
* Two-wire, intrinsically safe loop powered level transmitter.
* Measurement not affected by media variables eg.
dielectrics, pressure, density, pH, viscosity, ...
* Easy bench configuration - no need for level simulation.
* Two-line, 8-character LCD and 3-button keypad.
* Integral or remote electronics.
* 360° rotatable housing can be dismantled without depres-
surizing the vessel via “Quick connect/disconnect” probe
coupling.
Interface
E M U L S I O N L AY E R S level signal
high dielectric medium
As emulsion layers can decrease the strength of the reflect- < 12 mm (eg. water, εr = 80)
(0,47")
ed signal, the Eclipse® Model 707 should only be utilized in
those applications that have clean, distinct layers. Contact
the factory for application assistance. Time
CAGES AURORA™
Eclipse can be built into cages as small as Aurora® is the innovative combination of the Eclipse®
DN 50 / 2". When a new cage is needed, it can Guided Wave Radar and a Magnetic Level Indicator
be ordered together with the Eclipse. Magnetrol (MLI). The MLI indicator rail offers the Eclipse a high-
has a long tradition in offering cost effective ly visible level indication that may obsolete the need
cages. Magnetrol cages comply with PED regu- for local indicators. The integration of these two inde-
lations and are available with a wide variety of pendent technologies provides an excellent redun-
options. dancy in one integrated design. With Aurora® it is even
possible to plan maintenance ahead. Maintenance
Measuring span 30-610 cm (12-240") ➀ becomes needed when build up in an installation has
Carbon steel or surpassed the allowable limit. Build up on the float
Materials of construction
316 (1.4401) stainless steel inside the MLI cage will force it to sink deeper in the
Process connection sizes 3/4", 1", 1 1/2", 2" liquid while the measurement of the Eclipse will not
Process connection ratings 150#-2500# ANSI see any build up until its both lead elements are com-
pletely clugged. In this way, the float will indicate a
Configurations Side-Side and Side-Bottom
lower level versus the real level measured by the
Process pressures Up to 345 bar (5000 psig) ➀
Eclipse. The degree of deviation between both read
Process temperatures Up to +400 °C (+750 °F) ➀ outs is a worthwhile tool to determine the real need
➀
Limitations are defined per selected GWR probe (see probe specifi- for maintenance.
cations in the various Eclipse® 705/707/708 bulletins.
For more details – consult bulletin 57-138.
2
REPLACEMENT OF DISPLACER TRANSMITTER
Eclipse® has proven to be the perfect replacement for existing torque tube transmitters. In hundreds of applications around the
globe, customers have found Eclipse® Guided Wave Radar superior to torque tube transmitters:
• Cost:
A new Eclipse® costs only slightly more than rebuilding an
aging torque tube.
Non-ANSI
• Installation: proprietary Non-ANSI
flange proprietary flange
No field calibration is necessary; it can be configured in
minutes with no level movement. Pre-configuration from
factory is free of charge.
• Performance:
Eclipse® is not affected by changes in specific gravity or
dielectric.
• Ease of replacement:
Proprietary flanges are offered so existing chamber/
cages can be used.
100 %
GWR probe
Displacer Length
Length
0%
min 25 mm (1")
Recommended to confirm this distance
3
S E L E C T I O N D ATA
A complete measuring system consists of:
1. Eclipse® transmitter head/electronics
2. Eclipse® 707 GWR probe
3. OPTION: HART® communicator
Magnetrol P/N 089-5213-012 (EURO plug)/089-5213-013 (UK plug)
POWER
5 24 V DC, two wire
SIGNAL OUTPUT
1 4-20 mA with HART® communication
0 4-20 mA only (requires local display and keypad - Accessories code A)
ACCESSORIES
A Digital display and keypad
0 Blind transmitter (no display/keypad) – only for units with HART® communication
MATERIAL OF CONSTRUCTION
1 Cast aluminium dual compartiment housing
2 Stainless steel dual compartiment housing
CABLE ENTRY
1 M20 x 1.5 (2 entries - one plugged)
0 3/4" NPT (2 entries - one plugged)
2 PG 13.5 (2 entries - one plugged) – not available for explosion proof version
3 PG 16 (2 entries - one plugged) – not available for explosion proof version
4
2. Order code for ECLIPSE® 707 Coaxial GWR probe
MATERIAL OF CONSTRUCTION - wetted parts (including process connection flange when applicable)
A 316/316L (1.4401/1.4404) stainless steel
ANSI flanges
2 3 1" 150 lbs. ANSI RF 4 5 2" 600 lbs. ANSI RF
2 4 1" 300 lbs. ANSI RF 5 3 3" 150 lbs. ANSI RF
3 3 1 1/2" 150 lbs. ANSI RF 5 4 3" 300 lbs. ANSI RF
3 4 1 1/2" 300 lbs. ANSI RF 5 5 3" 600 lbs. ANSI RF
3 5 1 1/2" 600 lbs. ANSI RF 6 3 4" 150 lbs. ANSI RF
4 3 2" 150 lbs. ANSI RF 6 4 4" 300 lbs. ANSI RF
4 4 2" 300 lbs. ANSI RF 6 5 4" 600 lbs. ANSI RF
DIN flanges
B A DN 25, PN 16 DIN 2527 form B E A DN 80, PN 16 DIN 2527 form B
B B DN 25, PN 25/40 DIN 2527 form B E B DN 80, PN 25/40 DIN 2527 form B
B C DN 25, PN 64/100 DIN 2527 form E E D DN 80, PN 64 DIN 2527 form E
C A DN 40, PN 16 DIN 2527 form B E E DN 80, PN 100 DIN 2527 form E
C B DN 40, PN 25/40 DIN 2527 form B F A DN 100, PN 16 DIN 2527 form B
C C DN 40, PN 64/100 DIN 2527 form E F B DN 100, PN 25/40 DIN 2527 form B
D A DN 50, PN 16 DIN 2527 form B F D DN 100, PN 64 DIN 2527 form E
D B DN 50, PN 25/40 DIN 2527 form B F E DN 100, PN 100 DIN 2527 form E
D D DN 50, PN 64 DIN 2527 form E
D E DN 50, PN 100 DIN 2527 form E
Top Hat (Modulevel type) flanges in carbon steel Top Hat (Modulevel type) flanges in stainless steel
4 R 2" 150 lbs ANSI Raised Face flange 4 W 2" 150 lbs ANSI Raised Face flange
4 S 2" 300 lbs ANSI Raised Face flange 4 Y 2" 300 lbs ANSI Raised Face flange
5 R 3" 150 lbs ANSI Raised Face flange 5 W 3" 150 lbs ANSI Raised Face flange
5 S 3" 300 lbs ANSI Raised Face flange 5 Y 3" 300 lbs ANSI Raised Face flange
Torque tube mating flanges with top hat Torque tube mating flanges
T V 600 lbs Fisher (249B/259B) with top hat in carbon steel T T 600 lbs Fisher (249B/259B) in carbon steel
T W 600 lbs Fisher (249C) with top hat in stainless steel T U 600 lbs Fisher (249C) in stainless steel
U V 600 lbs Masoneilan flange with top hat in carbon steel U T 600 lbs Masoneilan flange in carbon steel
U W 600 lbs Masoneilan flange with top hat in stainless steel U U 600 lbs Masoneilan flange in stainless steel
5
T R A N S M I T T E R S P E C I F I C AT I O N S
FUNCTIONAL/PHYSICAL
Description Specification
Power (at terminals) General Purpose / ATEX Intrinsically Safe: 11 to 28,6 V DC
ATEX Explosion Proof (with Intrinsically Safe electronics) 13,5 to 36 V DC
Signal Output Interface 4-20 mA or 4-20 mA with HART®/AMS®
3,8 to 20,5 mA useable (meets NAMUR NE 43)
Level and interface HART®/AMS® digital communication
Span 150 to 3600 mm (6" to 120")
Resolution Analog: 0,01 mA
Display: 0,1 cm (inch)
Loop Resistance Intrinsically Safe/General Purpose: 620 Ω @ 20,5 mA - 24 V DC
(see tables at page 12) Explosion Proof (with Intrinsically Safe probe): 510 Ω @ 20,5 mA - 24 V DC
Damping Adjustable 0-45 s
Diagnostic Alarm Adjustable 3,6 mA, 22 mA, HOLD (3,6 mA is not valid if unit includes both digital display and HART®)
User Interface 3-button keypad and/or HART® communicator
Display 2-line x 8-character LCD
Menu Language English/Spanish/French/German
Housing Material IP 66/Aluminium A356T6 (< 0.25% copper) or stainless steel
Approvals ATEX II 1G EEx ia II C T4, ATEX II 1/2G EEx d[ia] II C T6,➀
ATEX II 3G EEx nA II T6, FM and CSA
Electrical Data Ui = 28,6 V, li = 140 mA, Pi = 1 W
Equivalent Data Ci = 2,1 nF, Li = 385 µH
Shock/Vibration Class ANSI/ISA-571.03 SA1 (Shock), ANSI/ISA-571.03 VC2 (Vibration)
Net and Gross Weight 2,70 kg net; 3,20 kg gross
Overall Dimensions H 214 mm (8.43") x W 111 mm (4.38") x D 188 mm (7.40")
➀ ATEX, explosion proof units use EEx d bushing material BARTEC (part n° 03-3200-0001)
PERFORMANCE
Description Specification
Reference Conditions Reflection from liquid, with dielectric in center of selected range,
with a 1,8 m (72") coaxial type GWR probe at +20 °C (70 °F) with CFD threshold➀
Linearity < 13 mm (0.5")
Measured error Upper liquid: ± 25 mm (1") – Lower liquid ± 25 mm (1")
Resolution ± 2,5 mm (0.1")
Repeatability < 13 mm (0.5")
Hysteresis < 13 mm (0.5")
Response Time < 1 second
Warm-up Time < 5 seconds
Ambient Temp. -40 °C to +80 °C (-40 °F to +175 °F) – blind transmitter
-20 °C to +70 °C (-5 °F to +160 °F) – with digital display
-40 °C to +70 °C (-40 °F to +160 °F) – for EEx ia and EEx d[ia] with blind transmitter
-20 °C to +70 °C (-5 °F to +160 °F) – for EEx ia and EEx d[ia] with digital display
Operating Temp. Effect Approx. +0,02 % of probe length/°C for probes ≥ 2,5 m (8')➁
Humidity 0-99 %, non-condensing
Electromagnetic Compatibility Meets CE requirements (EN-61000-6-4, EN 61000-6-2) and NAMUR NE 21
(Twin-Rod probe must be used in metallic vessel or stillwell)
➀ May degrade for 7MD probe or with fixed threshold. ➁ Accuracy may degrade slightly < 2,5 m (8')
ELECTRICAL WIRING
Power supply
GP / intrinsically safe: min 11 V DC
Explosion proof: min 13,5 V DC 0% 100 %
Standard shielded
twisted cable Galvanic Barrier
max 28,6 V DC @ 140 mA
for intrinsically safe units
Ex Non Ex
6
P R O B E S P E C I F I C AT I O N S
Description 7MT: coaxial GWR probe for interface
Materials Probe 316/316L (1.4401/1.4404)
Process seal TFE with Viton GFLT, EPDM or Kalrez 4079 (Consult factory for alternatives)
Probe diameter Inside rod: 8 mm (0.3125") – Outer tube: 22 mm (0.875")
Mounting In-tank mounting / external cage mounting – overfill safe
Process Connection Threaded: 3/4" NPT or 1" BSP (G1)
Flanged: Various ANSI, DIN or torque tube mating flanges
Probe length From 600 mm to 3600 mm (24" to 144")
Transition Zone➀ Top 0 mm (0")
Bottom εr: 1,4 = 150 mm (6")/εr: 80 = 25 mm (1")
Process Temp max +200 °C @ 18 bar (+400 °F @ 270 psi)
min -40 °C @ 70 bar (-40 °F @ 1000 psi)
Process Pressure max 70 bar @ +20 °C (1000 psi @ +70 °F) – see table at page 12
min vacuum service (not hermetic) @ +200 °C (+ 400 °F)
Max. Viscosity 500 cP
Dielectric Range 1,4 to 5,0 upper liquid – 15 to 100 lower liquid
Upper layer thickness min 50 mm (2")
Emulsion layer thickness max 12 mm (0.47")
DIMENSIONS in mm (inches)
83 105
(3.28) (4.12) 45° View
Proprietary flanges
Ø 229 Ø 184
102 (9.0) (7.25)
(4.00)
45°
60 2 cable
(2.37) entries
45° 214
95 (8.43) Ø 22
76 840 (.875)
51 (3.00) (3.75) (33.00)
(2.00)
32
89 2 holes 108 126 (1.125)
(3.50) (4.25) (4.94)
133
(5.23) 6
(.22)
Fisher 249B/259B (600 lbs), carbon steel
Ø 143 Ø 121
111 (5.625) (4.750)
(4.38)
(45° View)
Ø 11
(.438)
29
(1.125)
86
(3.375) 5
83 105 83 105 83 105
(.188)
(3.28) (4.12) (3.28) (4.12) (3.28) (4.12)
Fisher 249C (600 lbs), 316 stainless steel
143 (5.62)
Probe Insertion
Probe Insertion Length Probe Ø 22 O.D.
Length 1" BSP (G1) Insertion (0.88)
3/4" NPT Process Conn. Length
Process Conn. Add 143 (5.62)
for complete
Ø 8 (0.31")
probe insertion
length
7MR 7MR
with threaded with flanged connection
connection 7MR
with top hat flanged Coaxial GWR Probe,
connection End View
7
T E M P E R AT U R E - P R E S S U R E R AT I N G F O R E C L I P S E ® P R O B E S E A L S
70
50
40
30
20
10
0
-40 -20 0 20 40 60 80 100 120 140 160 180 200
L O O P R E S I S TA N C E
1200 1200
1000
20 mA
1000
20 mA
23 mA
800 800
Ω 650
Ω
600 600
525
23 mA
400 400
200 200
24 Vdc 24 Vdc
0 0
11
13,5
0 10 20 30 40 Vdc 0 10 20 30 40 Vdc
GENERAL PURPOSE (GP) EXPLOSION PROOF (XP)
INTRINSICALLY SAFE (IS)
PRODUCT WARRANTY
ALL MAGNETROL ELECTRONIC AND ULTRASONIC LEVEL CONTROLS ARE WARRANTED FREE OF DEFECTS IN MATERIALS AND WORK-
MANSHIP FOR ONE FULL YEAR FROM THE DATE OF ORIGINAL FACTORY SHIPMENT. IF RETURNED WITHIN THE WARRANTY PERIOD; AND, UPON FACTORY INSPEC-
TION OF THE CONTROL, THE CAUSE OF THE CLAIM IS DETERMINED TO BE COVERED UNDER THE WARRANTY; THEN, MAGNETROL INTERNATIONAL WILL REPAIR OR
REPLACE THE CONTROL AT NO COST TO THE PURCHASER (OR OWNER) OTHER THAN TRANSPORTATION.
MAGNETROL SHALL NOT BE LIABLE FOR MISAPPLICATION, LABOR CLAIMS, DIRECT OR CONSEQUENTIAL DAMAGE OR EXPENSE ARISING FROM THE INSTALLATION
OR USE OF THE EQUIPMENT. THERE ARE NO OTHER WARRANTIES EXPRESSED OR IMPLIED, EXCEPT, SPECIAL WRITTEN WARRANTIES COVERING SOME MAGNETROL
PRODUCTS.