Service Alert
Fan coils
ZN regulation improvement
UNT-SVB08A-E4
ZN regulation improvement
1. Introduction
Control of fan coils equipped with a ZN control and a thermal actuator valve can
be improved through the following modification.
3. Discussion
The following abnormal operations may occur:
The first two points only affect comfort while the third one has an impact on energy
consumption. Since none of them concern safety or performance of the unit, the
modification must be done only when required by the customer.
4. Action
First of all, download from http://stadoc/menupublic/IndexTechnicalService.asp
(Software download/ Fan Coils) the 6 configuration files onto your laptop where
ROVER is installed.
You should only use ROVER versions 4 or 5 with the last Service Pack and
relating Patch (you can download them from the following page:
http://tranenetlax1s/GCC_Downloads/Home/Downloads/Rover.asp).
2- UNT-SVB08A-E4
ZN regulation improvement
Re Replace thermal motor by 3 point motor and modify the cabling in accordance with
the diagram provided with the KIT.
Program to
Coil type Drawing #
download
23094218 (UNITRANE or HF*)
2 pipes cooling 23094114 (UNITRANE or HF*) PG51
23094110 (UNITRANE or HF*)
23091220 (UNITRANE)
2 pipes cooling with heater 23094116 (UNITRANE) PG53
23094112 (HF*)
Connect ROVER to the unit (or network when available) using your ROVER
Service Pack.
In the Active Group tree, click the device. The Active Device View appears in the
workspace.
Click the Configuration Button in the Active Device View. The Configuration dialog
box appears.
From the File menu of the Configuration dialog box, choose Save. The Save As
dialog box appears.
Select the location and type a file name in the Save dialog box.
Click Save. The configuration file (.RCF) is saved in the location you specified.
From the Configuration dialog box, select the Unit tab. The Unit Configuration view
appears.
Compare this view to the ones of the Annex 1 in order to determine which program
you need to download on the device.
3- UNT-SVB08A-E4
ZN regulation improvement
Please find attached in Annex 2 the form to note down the values.
From the File menu of the Configuration dialog box, choose Open. The Open
dialog box appears.
Select the location and file name in the Open dialog box.
Click Open and then Download on the Configuration dialog box. A message box
appears to confirm the download.
From the File menu of the Configuration dialog box, choose Save. The Save As
dialog box appears.
Select the location and type a file name in the Save dialog box.
Click Save. The configuration file (.RCF) is saved in the location you specified.
Click Close.
NB: If some units have the same customized parameters and the same program,
you can follow the here above procedure for the first one and download its file to
the following instead of points d) and e).
5. Part
Order one KIT1095E per unit, it contains:
1 three point actuator
1 seven wire connector
2 lead connections
revised electrical diagram (sticker to cut and place on the unit diagram)
6. Labor coverage
Motor replacement: 30 minutes per unit
4- UNT-SVB08A-E4
ZN regulation improvement
Appendix 1
a) PG51 (2 pipes cooling only)
5- UNT-SVB08A-E4
ZN regulation improvement
6- UNT-SVB08A-E4
ZN regulation improvement
f) PG58 (4 pipes)
7- UNT-SVB08A-E4
6. Appendix 2
Unit Values
Default
Configuration Menu
Values Unit ………………… Unit ………………… Unit ………………… Unit …………………
Occupied Heating 20 °C
Generic yes
Not Used
Generic Temperature
8- UNT-SVB08A-E4
Unit Values
Default
Configuration Menu
Values
Unit ………………… Unit ………………… Unit ………………… Unit …………………
Medium
High
Auto yes
Default Fan Off
Speed, Heating
Low
Medium
High
Auto yes
Enable Zone Sensor Fan Switch yes
Other Space Effective Value
Temperature
Sensor Offset 0 °C
Hardwired Setpoint Effective Value
Offset 0 °C
Timers Fan Run Time
Maintenance Required Time
300 h
Setpoint
Occupied Bypass Time 120 mn
9- UNT-SVB08A-E4
Literature Order Number UNT-SVB08A-E4
Date 06-04
New
www.trane.com Stocking Location Europe
Trane has a policy of continuous product and product data improvement and reserves the right to change
For more information contact design and specifications without notice. Only qualified technicians should perform the installation and
your local sales office servicing of equipment referred to in this publication.
or e-mail us at comfort@trane.com
10 - UNT-SVB08A-E4
American Standard Europe BVBA
Registered Office: 1789 Chaussée de Wavre, 1160 Brussels - Belgium