1. Assembly Occupancy
1.1 Fire Protection
1. All rooms used for storage of combustible materials shall be
located away from staircases and properly secluded from assembly
areas.
2. The stage area including any proscenium opening shall be separated
from the seating area by a firm wall of 3-hour fire resistance
rating.
1.2 Fire & Smoke Venting
1. Automatic smoke vents, with an area not less than 2% of the total
floor area of the building shall be installed and actuated by
smoke detectors.
2. Vents shall be located in a sheltered position at the highest
point of the area to be served.
3. The position of vents shall take into consideration the direction
of the prevailing wind to provide the required suction.
1.3 Fire Fighting
1. A separate fire fighting staircase shall be provided in buildings
more than 2 storeys high.
2. A fire fighting staircase and a fire fighting lift into a
separate fire fighting lobby shall be provided in buildings more
than 4 storeys high.
2. Buisness Occupancy
2.1 Fire Protection
1. Access corridors on all floors shall be fire protected with
walls of 2-hours fire resistive construction.
2. Doors opening into access corridors shall be fire doors with a
1-hour fire resistant rating.
4. Dwelling Occupancy
5. Educational Occupancy