Electrical Discrimination Study


For

Mace
155 Moorgate
London
EC2M 6XB

Ref: 4366/KAL/WF/RPT01.Rev11

February 2016
Electrical Discrimination Study
5 Broadgate

Issue Register
Rev Issue Date Issued By Checked by

10 Formal Issue 16th February 2016 KAL PC

Rev Issue Date Issued By Checked by

11 Formal Issue 25th February 2016 KAL PC

This document has been checked by: This document has been checked by:

(Associate Director) (Director)

Long and Partners Ltd


Rev 11 QA-R06-1 2 of 14
Electrical Discrimination Study
5 Broadgate

Contents
1.0 Executive Summary .............................................................................................................................................. 4

2.0 Introduction ............................................................................................................................................................ 5

2.1 Scope .................................................................................................................................................................... 5

2.2 Method .................................................................................................................................................................. 7

2.3 Description of System ........................................................................................................................................... 8

3.0 UKPN Fault Levels ................................................................................................................................................ 9

4.0 Network Layout ................................................................................................................................................... 10

5.0 33 kV Network Analysis ...................................................................................................................................... 11

6.0 11kV Network Analysis ....................................................................................................................................... 12

7.0 Generator - Network Analysis ............................................................................................................................. 13

8.0 400 V Network Analysis ...................................................................................................................................... 14

Long and Partners Ltd


Rev 11 QA-R06-1 3 of 14
Electrical Discrimination Study
5 Broadgate

1.0 Executive Summary

The electrical protection study demonstrates that all over-current fault and earth fault conditions achieve full
discrimination.

The report attachments provide full transparency between theoretical modeling and the field settings.

Long and Partners Ltd


Rev 11 QA-R06-1 4 of 14
Electrical Discrimination Study
5 Broadgate

2.0 Introduction
2.1 Scope

The 5 Broadgate Development was constructed by Mace on a traditional contract basis and completed in 2015.

The building, commissioned by British Land for their Tenant UBS, with the electrical design produced by British Land’s
appointed Consulting Engineers WPP.

The nature of UBS business dictates resilient electrical power infrastructure to meet the requirements of their trading
activities.

The incoming power is delivered at 33kV by UKPN, the District Network Operator (DNO). The electrical network is
extensive with down-stream networks comprising of 11kV and 400V, LV distribution, together with 8 number 2.5 MVA
11kV parallel operation standby generators and a 400V, 1MVA standby generator set for life safety load support.

Each section of distribution networks are provided with circuit breakers designed to distribute and manage power in
both normal operating conditions and to automatically disconnect power under fault conditions. The circuit breakers
are provided with electronic protection modules that require site specific commissioning to ensure that the
arrangement remains stable under transient conditions and further operate within logical sequential zones minimizing
disruption during power loss as a result of fault conditions.

The building engineering specification prepared by Consulting Engineer WPP dictated that the contractor produce
these protection settings to ensure the system is configured to meet these requirements.

The protection settings are set to achieve full discrimination and operate with the systems varying fault levels through
the network, dependent on the respective circuit impedance. Discrimination is targeted to ensure that under fault
conditions the protection module and associated circuit breaker closest to the fault opens first or as is the case, in
agreed zones.

Long & Partners Ltd Consulting Engineers were appointed by Mace to produce the discrimination and protection study
to model the protection curves and establish the optimum protection settings of each adjustable device. This then
reviewed by the professional client team, including technical lead, WPP Consulting Engineers.

The Tenant, UBS has employed Consulting Engineer Hurley Palmer Flatt who are engaged to offer technical insight
and offer comments on behalf of UBS. The actual protection module settings, taken from this study are applied onsite
by Mardix and Schneider, the manufacturers of the equipment, under the control of Mace MEP (the contractor).
During input or these setting onsite chronological records and witnessing of the design give a comprehensive record.

Long and Partners Ltd


Rev 11 QA-R06-1 5 of 14
Electrical Discrimination Study
5 Broadgate

The electrical protection system is required to operate under all required conditions, and (equally important) refrain
from operating when so required (including, where appropriate, being restrained from operating for faults external to
the zone being protected). Settings must be selected which will ensure that the system protective devices achieve the
following general objectives:

 Operate positively for the full range of fault levels experienced by the network

 Operate with the minimum time delay to provide optimum protection to both plant & personnel

 Clear faults selectively so that minimum disruption occurs to the healthy part of the network

 Allow maximum load currents to flow through the network under normal and abnormal plant operating
conditions without unnecessary tripping of devices

 Allow normal short time & transient overload currents to flow in the network without unnecessary tripping of
devices i.e. motor starting/ transformer in-rush

The main protection is graded, with back-up protection that allows the devices nearest the fault to operate first.
If the main protection fails to operate the back-up protection is capable of clearing the fault.
Within the design consideration has been given to the nature, frequency and duration of faults likely to be experienced
along with all relevant parameters of the power system, these include the characteristics of the supply source,
methods of operation and the type of protection equipment used.

This study is to be read in conjunction with the following parameters and operating conditions:

• The scheme includes the use of zone selective interlocking (Blocking) between the 11kV bus links referenced
H3 and H5, linking HVBS-1XX01 to HVSB-1XX02 and between HVSB13XX01 to HVSB13XX02 respectively.
This is illustrated in section 4 network layout graphically and within section 6, 11kV network analysis, detailed
within the setting sheets for H3 and H5 devices.

 Breaker fail signal to UKPN for 33kV feeders.

Long and Partners Ltd


Rev 11 QA-R06-1 6 of 14
Electrical Discrimination Study
5 Broadgate

2.2 Method

In order to provide discrimination for circuit protective devices, HVCB's, ACB's, MCCB's or fuses there are five main
principles, which can be employed.

 Current Discrimination, utilized on the LV system network where two LV Protective devices having similar
Long Time (LT) tripping curves are set at differing current settings when the difference in setting is large
enough to ensure that discrimination is achieved.

 Time Discrimination - is used to provide discrimination between the Short Time (ST) settings of two devices.
The minimum delay time between tripping is determined by the device employed, an industry standard delay
is employed for HV systems, whilst for LV systems values are provided by the device manufacturer.

2
 Energy Discrimination - uses the principle that the downstream device not only limits the I t energy value into
the fault, but also the fault energy seen by the upstream device. This principle is also used where there is a
step change in fault current, e.g. across a transformer.

 Unit Protection - uses the principle of measuring the current entering a zone of protection and comparing it
with the current leaving. The comparison is vectorial and is based on Kirchoff's Laws. This protection is only
used in specialist cases such as for Restricted Earth Fault, to provide high speed high sensitivity fault
protection in a defined zone.

The first three methods have been employed to provide discrimination between HV & LV devices. The delay setting
achieved is within the industry norm. CB breaking time and 'safety factors', at maximum fault current have been used
for the HV devices and the LV setting values to obtain discrimination by using preparatory software, Amtech
PROTECT.

In calculating the LV device settings one outgoing device for each rating has been coordinated with the upstream
devices using tables and data supplied by the manufacturer. The settings have also been reproduced graphically
using preparatory software, Amtech PROTECT.

On the HV system both settings for over current and earth fault have been considered as dedicated protection
elements and have been provided for each mode of protection.

At LV level, protective devices include a mix of both over current and earth fault elements respectively.
Within the studies LV protection schedules, devices having combined over current and earth fault elements have
identical settings applied.

Unit protection, in the form of REF, has been provided for the Transformer LV windings. Values for relays and stability
resistors have been calculated to ensure resilient operation in through fault conditions.

The results for each case above are shown in the sections below with associated results summarized in schedules
below.

Long and Partners Ltd


Rev 11 QA-R06-1 7 of 14
Electrical Discrimination Study
5 Broadgate

2.3 Description of System

The simplified network is shown on HV Schematic Drawing 4366/E/1000/C1 in section 3 of this document.

The following calculation is typically applied to determine the minimum discrimination time that can be achieved
between devices to allow for errors:-

T = t[2Er + Ect]+ tCB + to + ts (secs)


100

where: Er = relay timing error (IEC 60255-4)


Ect = allowance for CT ratio error (%)
t= operating time of relay nearer fault (s)
tCB = CB interrupting time (s)
to = relay overshoot time (s)
ts = safety margin (s)

Typical values applied are:-

Er = 3%
Ect = 5%
t = 400ms
tCB = 100ms (HV CB’s, LV ACB’s) & 30ms (LV MCCB’s)
to = 30ms
ts = 75ms

For this study the nominal grading time is:-

T = [2x3 + 5] 0.4 + (0.1 + 0.030 + 0.075) = 249ms for HV CB’s


100

T = [2x3 + 5] 0.4 + (0.030 + 0.030 + 0.075) = 179ms for LV MCCB’s


100

Therefore, the nominal discrimination time that will be applied to this protection will be:
• 250ms for HV Circuit Breakers and
• 179ms for LV MCCB’s.

These nominal discrimination times are the minimum value that will be accepted as achieving discrimination for
devices of differing manufacturers/ devices without known characteristics, any discrimination below the nominal value
will be reported as a compromise if a suitable solution cannot be found.

The majority of the protective devices utilized on the project were made by Schneider.

The UKPN incoming default protection settings that this study are calculated on are as follows:

• Over current: 600A at 0.3TMS


• Earth Fault: 200A at 0.225TMS

Long and Partners Ltd


Rev 11 QA-R06-1 8 of 14
Electrical Discrimination Study
5 Broadgate

3.0 UKPN Fault Levels

Long and Partners Ltd


Rev 11 QA-R06-1 9 of 14
UKPN EARTH FAULT

Table 1a Table 1b
A @ BACK, B @ FINF A @ BACK, B @ FINF
Normal running B2 outage
5 Broadgate 5 Broadgate
Name Ik" A Ik' A ip A Ib A ib A Name Ik" A Ik' A ip A Ib A ib A
kA kA kA kA kA kA kA kA kA kA
BB1 1.943 1.929 2.804 1.932 2.732 BB1 1.809 1.796 2.611 1.799 2.544

Table 2a Table 2b
A @ FINF, B @ BACK A @ FINF, B @ BACK
Normal running B2 outage
5 Broadgate 5 Broadgate
Name Ik" A Ik' A ip A Ib A ib A Name Ik" A Ik' A ip A Ib A ib A
kA kA kA kA kA kA kA kA kA kA
BB1 1.867 1.855 2.695 1.858 2.627 BB1 1.799 1.788 2.597 1.790 2.532

Table 3a Table 3b
A and B @ BACK A and B @ BACK
Normal running B2 outage
5 Broadgate 5 Broadgate
Name Ik" A Ik' A ip A Ib A ib A Name Ik" A Ik' A ip A Ib A ib A
kA kA kA kA kA kA kA kA kA kA
BB1 1.851 1.836 2.672 1.839 2.601 BB1 1.785 1.770 2.576 1.774 2.508

Table 4a Table 4b
A and B @ FINF A and B @ FINF
Normal running B2 outage
5 Broadgate 5 Broadgate
Name Ik" A Ik' A ip A Ib A ib A Name Ik" A Ik' A ip A Ib A ib A
kA kA kA kA kA kA kA kA kA kA
BB1 1.913 1.896 2.761 1.900 2.687 BB1 1.784 1.767 2.574 1.771 2.504
UKPN 3-PH SHORT CIRCUIT

Table 1a
A @ BACK, B @ FINF
Normal running
Back Hill
Peak Breaking
Name Ik" ip Ik' Ib Current
kA kA kA kA kA
BB1.1 15.22 39.38 13.19 13.64 27.83
Finsbury Market
Peak Breaking
Name Ik" ip Ik' Ib Current
kA kA kA kA kA
BB2.1 13.52 33.01 11.75 12.15 20.37
5 Broadgate
Peak Breaking
Name Ik" ip Ik' Ib Current
kA kA kA kA kA
BB1 16.27 41.57 14.29 14.73 27.79

Table 2a
A @ FINF, B @ BACK
Normal running
Back Hill
Peak Breaking
Name Ik" ip Ik' Ib Current
kA kA kA kA kA
BB1.1 14.52 34.97 12.70 13.10 21.15
Finsbury Market
Peak Breaking
Name Ik" ip Ik' Ib Current
kA kA kA kA kA
BB2.1 16.73 43.13 14.47 14.98 29.45
5 Broadgate
Peak Breaking
Name Ik" ip Ik' Ib Current
kA kA kA kA kA
BB1 14.44 36.50 12.70 13.09 24.15
Table 3a
A and B @ BACK
Normal running
Back Hill
Peak Breaking
Name Ik" ip Ik' Ib Current
kA kA kA kA kA
BB1.1 17.02 44.04 13.96 14.64 30.26
Finsbury Market
Peak Breaking
Name Ik" ip Ik' Ib Current
kA kA kA kA kA
BB2.1 14.88 36.13 12.35 12.91 21.51
5 Broadgate
Peak Breaking
Name Ik" ip Ik' Ib Current
kA kA kA kA kA
BB1 15.87 39.88 13.12 13.73 25.30

Table 4a
A and B @ FINF
Normal running
Back Hill
Peak Breaking
Name Ik" ip Ik' Ib Current
kA kA kA kA kA
BB1.1 15.74 37.71 13.21 13.77 22.11
Finsbury Market
Peak Breaking
Name Ik" ip Ik' Ib Current
kA kA kA kA kA
BB2.1 18.44 47.56 15.17 15.90 31.68
5 Broadgate
Peak Breaking
Name Ik" ip Ik' Ib Current
kA kA kA kA kA
BB1 17.86 45.46 14.76 15.46 29.22
Electrical Discrimination Study
5 Broadgate

4.0 Network Layout

Long and Partners Ltd


Rev 11 QA-R06-1 10 of 14
1250A 1250A

Rev Date Description Drawn

buildin service consultants


Fifth Floor, 120 Old Broad Street, London,
EC2N 1AR
T +44 (0)20 7920 4850
F +44 (0)20 7920 4851
E info@longandpartners.co.uk
W www.longandpartners.co.uk
Electrical Discrimination Study
5 Broadgate

5.0 33 kV Network Analysis

Long and Partners Ltd


Rev 11 QA-R06-1 11 of 14
ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 33 kV FEEDER, UKPN 1 Circuit EH1


Device SOLKOR 7SG18 N
Select
CT Ratio 800/400/1A on 400A Range
SETTINGS GROUP G MENU ONLY
SCREEN FUNCTION MENU ENTRY
Active Settings Group Group that the relay will act upon G1
Settings Group Edit/View Group to be displayed on the LCD G1
Local P/F Rating Local relay’s phase fault CT rating 1A
Local E/F Rating Local relay’s earth fault CT rating 1A
Local P/F CT Ratio relay’s phase input CT ratio 400:1
Local E/F CT Ratio relay’s earth input CT ratio 400:1
Remote P/F Rating Remote relay’s phase fault CT rating 400:1
Remote P/F CT Ratio Remote relay’s earth fault CT rating 400:1
Current Display display mode to use for the relay xIn
Set Identifier 16 character alphanumeric code UKPN 1 SOLKOR
Set Alarm 1 ALARM 1
Calendar – Set Date DD/MM/YY Todays Date
Clock - Set Time HH:MM:SS Actual Time
Clock Sync. From Status Seconds or Minutes Minutes
Default Screen Timer 10sec, 60sec, 5min, 1hour 5 min
Change Password 4 alphanumeric characters NONE

DIFF' PROTECTION MENU ONLY


SCREEN FUNCTION MENU ENTRY
Gn P/F Diff. Setting* setting for the differential element 0.3 x In
Gn P/F Bias Slope 1* 1st bias slope differential element 30%
Gn P/F Bias Slope 2* 2nd bias slope differential element 150%
Gn Bias Break Point* bias slope break point 1 to 2 2.00 x In
Gn Differential Delay trip time differential element/ intertrip 0.0s
P/F CT Ratio Correction CT ratio correction 1
Remote P/F Ratio Correction CT ratio correction 1
Gn Internal Intertrip enables / disables internal intertrips OFF
Gn Int Intertrip Delay internal intertrip elements 0.00s
Gn External Intertrip enables / disables external intertrips ON
Gn Ext Intertrip Delay external intertrip elements 0.00s

O/C PROTECTION MENU ONLY


SCREEN FUNCTION MENU ENTRY
Gn P/F Charact. Setting phase fault O/C pick-up level 0.95 x In
Gn P/F Charact. phase fault O/C characteristic NI
Gn P/F Charact. Time Mult phase fault TMS 0.275
Gn P/F Charact. Delay phase fault delay DTL
Gn P/F Lowset Setting phase fault lowset pick-up OFF
Gn P/F Lowset Delay phase fault lowset delay
Gn P/F Highset1 Setting phase fault highset 1 pick-up 10.5 x In
Gn P/F Highset1 Delay phase fault highset 1 delay 0s
Gn P/F Highset2 Setting phase fault highset 2 pick-up OFF
Gn P/F Highset2 Delay phase fault highset 2 delay
Gn E/F Charact. Setting earth fault O/C pick-up level 0.2 x In
Gn E/F Charact. earth fault O/C characteristic NI
Gn E/F Charact. Time Mult earth fault TMS 0.05
Gn E/F Charact. Delay earth fault delay DTL
Gn E/F Lowset Setting earth fault lowset pick-up OFF
Gn E/F Lowset Delay earth fault lowset delay
Gn E/F Highset1 Setting earth fault highset 1 pick-up OFF
Gn E/F Highset1 Delay earth fault highset 1 delay
Gn E/F Highset2 Setting earth fault highset 2 pick-up OFF
Gn E/F Highset2 Delay earth fault highset 2 delay
Gn CB Fail Time Delay 1 1st time delay for CB Fail 0.2s
Gn CB Fail Time Delay2 2nd time delay for CB Fail 0s
Gn P/F CB Fail Setting sets over current CB Fail level OFF
Gn E/F CB Fail Setting sets earth fault current CB Fail level OFF
Gn CT Failure Setting sets CT Failure level OFF
Gn CT Failure Delay sets delay for CT Failure 1s
Gn Relay Reset Delay OC reset characteristic INST
O/P RELAY CONFIG MENU ONLY
Gn Prot. Healthy RL1
Gn P/F Diff. RL4

5 Broadgate Protective Device Settings 33SB-1XX01 Rev 4 4 of 4 UKPN 1 SOLKOR


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 33 kV INCOMER, CB 1 Circuit EH1


Device SEPAM S20
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 800/400/1A on 400A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 450A Is = 125A
50N/51N - 1 Trip CB P T = 1100ms T = 460ms
Group A ON Curve = IEC SIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 9 kA ON
50/51 - 2 Latching P Is = 1000A
50N/51N - 2 Trip CB P T = 730ms
SWITCHED OFF
Group A ON Curve = IAC INV
2nd Harmonic Restraint Restraint Threshold 17% Icc = 9 kA
50/51 - 1 Latching P
50N/51N - 1 Trip CB P SWITCHED OFF SWITCHED OFF
Group B OFF
50/51 - 2 Latching P
50N/51N - 2 Trip CB P SWITCHED OFF SWITCHED OFF
Group B OFF
46 negative sequence / unbalance
79 Re-closer

5 Broadgate Protective Device Settings 33SB-1XX01 Rev 4 2 of 4 CB 1


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 33 kV FEEDER, CB 1 & 2 Circuit EH1


Device SOLKOR 7SG18 N
Select
CT Ratio 800/400/1A on 400A Range
SETTINGS GROUP G MENU ONLY
SCREEN FUNCTION MENU ENTRY
Active Settings Group Group that the relay will act upon G1
Settings Group Edit/View Group to be displayed on the LCD G1
Local P/F Rating Local relay’s phase fault CT rating 1A
Local E/F Rating Local relay’s earth fault CT rating 1A
Local P/F CT Ratio relay’s phase input CT ratio 400:1
Local E/F CT Ratio relay’s earth input CT ratio 400:1
Remote P/F Rating Remote relay’s phase fault CT rating 400:1
Remote P/F CT Ratio Remote relay’s earth fault CT rating 400:1
Current Display display mode to use for the relay xIn
Set Identifier 16 character alphanumeric code CB1_CB2 SOLKOR
Set Alarm 1 ALARM 1
Calendar – Set Date DD/MM/YY Todays Date
Clock - Set Time HH:MM:SS Actual Time
Clock Sync. From Status Seconds or Minutes Minutes
Default Screen Timer 10sec, 60sec, 5min, 1hour 5 min
Change Password 4 alphanumeric characters NONE

DIFF' PROTECTION MENU ONLY


SCREEN FUNCTION MENU ENTRY
Gn P/F Diff. Setting* setting for the differential element 0.3 x In
Gn P/F Bias Slope 1* 1st bias slope differential element 30%
Gn P/F Bias Slope 2* 2nd bias slope differential element 150%
Gn Bias Break Point* bias slope break point 1 to 2 2.00 x In
Gn Differential Delay trip time differential element/ intertrip 0.0s
P/F CT Ratio Correction CT ratio correction 1
Remote P/F Ratio Correction CT ratio correction 1
Gn Internal Intertrip enables / disables internal intertrips OFF
Gn Int Intertrip Delay internal intertrip elements 0.00s
Gn External Intertrip enables / disables external intertrips ON
Gn Ext Intertrip Delay external intertrip elements 0.00s

O/C PROTECTION MENU ONLY


SCREEN FUNCTION MENU ENTRY
Gn P/F Charact. Setting phase fault O/C pick-up level 0.95 x In
Gn P/F Charact. phase fault O/C characteristic NI
Gn P/F Charact. Time Mult phase fault TMS 0.275
Gn P/F Charact. Delay phase fault delay DTL
Gn P/F Lowset Setting phase fault lowset pick-up OFF
Gn P/F Lowset Delay phase fault lowset delay
Gn P/F Highset1 Setting phase fault highset 1 pick-up 10.5 x In
Gn P/F Highset1 Delay phase fault highset 1 delay 0s
Gn P/F Highset2 Setting phase fault highset 2 pick-up OFF
Gn P/F Highset2 Delay phase fault highset 2 delay
Gn E/F Charact. Setting earth fault O/C pick-up level 0.2 x In
Gn E/F Charact. earth fault O/C characteristic NI
Gn E/F Charact. Time Mult earth fault TMS 0.05
Gn E/F Charact. Delay earth fault delay DTL
Gn E/F Lowset Setting earth fault lowset pick-up OFF
Gn E/F Lowset Delay earth fault lowset delay
Gn E/F Highset1 Setting earth fault highset 1 pick-up OFF
Gn E/F Highset1 Delay earth fault highset 1 delay
Gn E/F Highset2 Setting earth fault highset 2 pick-up OFF
Gn E/F Highset2 Delay earth fault highset 2 delay
Gn CB Fail Time Delay 1 1st time delay for CB Fail 0.2s
Gn CB Fail Time Delay2 2nd time delay for CB Fail 0s
Gn P/F CB Fail Setting sets over current CB Fail level OFF
Gn E/F CB Fail Setting sets earth fault current CB Fail level OFF
Gn CT Failure Setting sets CT Failure level OFF
Gn CT Failure Delay sets delay for CT Failure 1s
Gn Relay Reset Delay OC reset characteristic INST
O/P RELAY CONFIG MENU ONLY
Gn Prot. Healthy RL1
Gn P/F Diff. RL4

5 Broadgate Protective Device Settings 33SB-1XX01 Rev 4 3 of 4 CB1_CB2 SOLKOR


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 33 kV FEEDER, UKPN 2 Circuit EH2


Device SOLKOR 7SG18 N
Select
CT Ratio 800/400/1A on 400A Range
SETTINGS GROUP G MENU ONLY
SCREEN FUNCTION MENU ENTRY
Active Settings Group Group that the relay will act upon G1
Settings Group Edit/View Group to be displayed on the LCD G1
Local P/F Rating Local relay’s phase fault CT rating 1A
Local E/F Rating Local relay’s earth fault CT rating 1A
Local P/F CT Ratio relay’s phase input CT ratio 400:1
Local E/F CT Ratio relay’s earth input CT ratio 400:1
Remote P/F Rating Remote relay’s phase fault CT rating 400:1
Remote P/F CT Ratio Remote relay’s earth fault CT rating 400:1
Current Display display mode to use for the relay xIn
Set Identifier 16 character alphanumeric code UKPN 2 SOLKOR
Set Alarm 1 ALARM 1
Calendar – Set Date DD/MM/YY Todays Date
Clock - Set Time HH:MM:SS Actual Time
Clock Sync. From Status Seconds or Minutes Minutes
Default Screen Timer 10sec, 60sec, 5min, 1hour 5 min
Change Password 4 alphanumeric characters NONE

DIFF' PROTECTION MENU ONLY


SCREEN FUNCTION MENU ENTRY
Gn P/F Diff. Setting* setting for the differential element 0.3 x In
Gn P/F Bias Slope 1* 1st bias slope differential element 30%
Gn P/F Bias Slope 2* 2nd bias slope differential element 150%
Gn Bias Break Point* bias slope break point 1 to 2 2.00 x In
Gn Differential Delay trip time differential element/ intertrip 0.0s
P/F CT Ratio Correction CT ratio correction 1
Remote P/F Ratio Correction CT ratio correction 1
Gn Internal Intertrip enables / disables internal intertrips OFF
Gn Int Intertrip Delay internal intertrip elements 0.00s
Gn External Intertrip enables / disables external intertrips ON
Gn Ext Intertrip Delay external intertrip elements 0.00s

O/C PROTECTION MENU ONLY


SCREEN FUNCTION MENU ENTRY
Gn P/F Charact. Setting phase fault O/C pick-up level 0.95 x In
Gn P/F Charact. phase fault O/C characteristic NI
Gn P/F Charact. Time Mult phase fault TMS 0.275
Gn P/F Charact. Delay phase fault delay DTL
Gn P/F Lowset Setting phase fault lowset pick-up OFF
Gn P/F Lowset Delay phase fault lowset delay
Gn P/F Highset1 Setting phase fault highset 1 pick-up 10.5 x In
Gn P/F Highset1 Delay phase fault highset 1 delay 0s
Gn P/F Highset2 Setting phase fault highset 2 pick-up OFF
Gn P/F Highset2 Delay phase fault highset 2 delay
Gn E/F Charact. Setting earth fault O/C pick-up level 0.2 x In
Gn E/F Charact. earth fault O/C characteristic NI
Gn E/F Charact. Time Mult earth fault TMS 0.05
Gn E/F Charact. Delay earth fault delay DTL
Gn E/F Lowset Setting earth fault lowset pick-up OFF
Gn E/F Lowset Delay earth fault lowset delay
Gn E/F Highset1 Setting earth fault highset 1 pick-up OFF
Gn E/F Highset1 Delay earth fault highset 1 delay
Gn E/F Highset2 Setting earth fault highset 2 pick-up OFF
Gn E/F Highset2 Delay earth fault highset 2 delay
Gn CB Fail Time Delay 1 1st time delay for CB Fail 0.2s
Gn CB Fail Time Delay2 2nd time delay for CB Fail 0s
Gn P/F CB Fail Setting sets over current CB Fail level OFF
Gn E/F CB Fail Setting sets earth fault current CB Fail level OFF
Gn CT Failure Setting sets CT Failure level OFF
Gn CT Failure Delay sets delay for CT Failure 1s
Gn Relay Reset Delay OC reset characteristic INST
O/P RELAY CONFIG MENU ONLY
Gn Prot. Healthy RL1
Gn P/F Diff. RL4

5 Broadgate Protective Device Settings 33SB-1XX02 Rev 4 4 of 4 UKPN 2 SOLKOR


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 33 kV FEEDER, CB 2 Circuit EH1A, from 33SB-1XX01 to TX33-1XX01


Device SEPAM T87
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 800/400/1A on 400A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 380A Is = 80A
50N/51N - 1 Trip CB P T = 820ms T = 130ms
Group A ON Curve = IEC SIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 9 kA ON
50/51 - 2 Latching P Is = 4200A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group A ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 9 kA
50/51 - Elements 3~8
50N/51N - Elements 2~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - Elements 1~8
50N/51N - Elements 1~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
50BF - 1 Latching P Is = 400A
Trip CB P T = 130ms
46 negative sequence / unbalance
49RMS Thermal Overload
64 REF Restricted Earth Fault
64 REF - 1 Latching P Main channels (I, I0)
Trip CB P 50A
64 REF - 2 OFF
87T Transformer Differential
87T - 1 Latching P Ids Threshold 30%
Trip CB P Id/It Threshold 29%
67 Directional Overcurrent
67N Directional Earth Fault
32P Active Power
24 Overfluxing
`
27R Remnant Undervoltage
27 Undervoltage
59 Overvoltage
59N Neutral Voltage Displacement
Latching P 1 2
59N - 1
Trip CB P Unp = 15% Unp = 20%
Latching P T = 2s T = 100ms
59N - 2
Trip CB P Curve = IDMT Curve = DT
47 Negative Sequence Over Voltage
38/49T Temperature Monitoring
81H over frequency
81L under frequency
38/49T Temperature Monitoring
25 Synchro Check

5 Broadgate Protective Device Settings 33SB-1XX01 Rev 4 1 of 4 CB 2


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 33 kV INCOMER, CB 73 Circuit EH2


Device SEPAM S20
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 800/400/1A on 400A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 450A Is = 125A
50N/51N - 1 Trip CB P T = 1100ms T = 460ms
Group A ON Curve = IEC SIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 9 kA ON
50/51 - 2 Latching P Is = 1000A
50N/51N - 2 Trip CB P T = 730ms
SWITCHED OFF
Group A ON Curve = IAC INV
2nd Harmonic Restraint Restraint Threshold 17% Icc = 9 kA
50/51 - 1 Latching P
50N/51N - 1 Trip CB P SWITCHED OFF SWITCHED OFF
Group B OFF
50/51 - 2 Latching P
50N/51N - 2 Trip CB P SWITCHED OFF SWITCHED OFF
Group B OFF
46 negative sequence / unbalance
79 Re-closer

5 Broadgate Protective Device Settings 33SB-1XX02 Rev 4 1 of 4 CB 73


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 33 kV FEEDER, CB 74 Circuit EH2A, from 33SB-1XX02 to TX33-1XX02


Device SEPAM T87
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 800/400/1A on 400A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 380A Is = 80A
50N/51N - 1 Trip CB P T = 820ms T = 130ms
Group A ON Curve = IEC SIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 9 kA ON
50/51 - 2 Latching P Is = 4200A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group A ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 9 kA
50/51 - Elements 3~8
50N/51N - Elements 2~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - Elements 1~8
50N/51N - Elements 1~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
50BF - 1 Latching P Is = 400A
Trip CB P T = 130ms
46 negative sequence / unbalance
49RMS Thermal Overload
64 REF Restricted Earth Fault
64 REF - 1 Latching P Main channels (I, I0)
Trip CB P 50A
64 REF - 2 OFF
87T Transformer Differential
87T - 1 Latching P Ids Threshold 30%
Trip CB P Id/It Threshold 29%
67 Directional Overcurrent
67N Directional Earth Fault
32P Active Power
24 Overfluxing
`
27R Remnant Undervoltage
27 Undervoltage
59 Overvoltage
59N Neutral Voltage Displacement
Latching P 1 2
59N - 1
Trip CB P Unp = 15% Unp = 20%
Latching P T = 2s T = 100ms
59N - 2
Trip CB P Curve = IDMT Curve = DT
47 Negative Sequence Over Voltage
47 - 1 Latching P
OFF
47 - 2 Trip CB P
38/49T Temperature Monitoring
81H over frequency
81L under frequency
38/49T Temperature Monitoring
25 Synchro Check

5 Broadgate Protective Device Settings 33SB-1XX02 Rev 4 2 of 4 CB 74


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 33 kV FEEDER, CB 73 & 74 Circuit EH2


Device SOLKOR 7SG18 N
Select
CT Ratio 800/400/1A on 400A Range
SETTINGS GROUP G MENU ONLY
SCREEN FUNCTION MENU ENTRY
Active Settings Group Group that the relay will act upon G1
Settings Group Edit/View Group to be displayed on the LCD G1
Local P/F Rating Local relay’s phase fault CT rating 1A
Local E/F Rating Local relay’s earth fault CT rating 1A
Local P/F CT Ratio relay’s phase input CT ratio 400:1
Local E/F CT Ratio relay’s earth input CT ratio 400:1
Remote P/F Rating Remote relay’s phase fault CT rating 400:1
Remote P/F CT Ratio Remote relay’s earth fault CT rating 400:1
Current Display display mode to use for the relay xIn
Set Identifier 16 character alphanumeric code CB73_CB74 SOLKOR
Set Alarm 1 ALARM 1
Calendar – Set Date DD/MM/YY Todays Date
Clock - Set Time HH:MM:SS Actual Time
Clock Sync. From Status Seconds or Minutes Minutes
Default Screen Timer 10sec, 60sec, 5min, 1hour 5 min
Change Password 4 alphanumeric characters NONE

DIFF' PROTECTION MENU ONLY


SCREEN FUNCTION MENU ENTRY
Gn P/F Diff. Setting* setting for the differential element 0.3 x In
Gn P/F Bias Slope 1* 1st bias slope differential element 30%
Gn P/F Bias Slope 2* 2nd bias slope differential element 150%
Gn Bias Break Point* bias slope break point 1 to 2 2.00 x In
Gn Differential Delay trip time differential element/ intertrip 0.0s
P/F CT Ratio Correction CT ratio correction 1
Remote P/F Ratio Correction CT ratio correction 1
Gn Internal Intertrip enables / disables internal intertrips OFF
Gn Int Intertrip Delay internal intertrip elements 0.00s
Gn External Intertrip enables / disables external intertrips ON
Gn Ext Intertrip Delay external intertrip elements 0.00s

O/C PROTECTION MENU ONLY


SCREEN FUNCTION MENU ENTRY
Gn P/F Charact. Setting phase fault O/C pick-up level 0.95 x In
Gn P/F Charact. phase fault O/C characteristic NI
Gn P/F Charact. Time Mult phase fault TMS 0.275
Gn P/F Charact. Delay phase fault delay DTL
Gn P/F Lowset Setting phase fault lowset pick-up OFF
Gn P/F Lowset Delay phase fault lowset delay
Gn P/F Highset1 Setting phase fault highset 1 pick-up 10.5 x In
Gn P/F Highset1 Delay phase fault highset 1 delay 0s
Gn P/F Highset2 Setting phase fault highset 2 pick-up OFF
Gn P/F Highset2 Delay phase fault highset 2 delay
Gn E/F Charact. Setting earth fault O/C pick-up level 0.2 x In
Gn E/F Charact. earth fault O/C characteristic NI
Gn E/F Charact. Time Mult earth fault TMS 0.05
Gn E/F Charact. Delay earth fault delay DTL
Gn E/F Lowset Setting earth fault lowset pick-up OFF
Gn E/F Lowset Delay earth fault lowset delay
Gn E/F Highset1 Setting earth fault highset 1 pick-up OFF
Gn E/F Highset1 Delay earth fault highset 1 delay
Gn E/F Highset2 Setting earth fault highset 2 pick-up OFF
Gn E/F Highset2 Delay earth fault highset 2 delay
Gn CB Fail Time Delay 1 1st time delay for CB Fail 0.2s
Gn CB Fail Time Delay2 2nd time delay for CB Fail 0s
Gn P/F CB Fail Setting sets over current CB Fail level OFF
Gn E/F CB Fail Setting sets earth fault current CB Fail level OFF
Gn CT Failure Setting sets CT Failure level OFF
Gn CT Failure Delay sets delay for CT Failure 1s
Gn Relay Reset Delay OC reset characteristic INST
O/P RELAY CONFIG MENU ONLY
Gn Prot. Healthy RL1
Gn P/F Diff. RL4

5 Broadgate Protective Device Settings 33SB-1XX02 Rev 4 3 of 4 CB73_CB74 SOLKOR


COMMISSIONING REPORT
AMTECH Protect - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision Created 26/01/2016 18:23:16
Job ID Last Saved 31/01/2016 13:45:52
Engineer
UTILITY Mode EF 5 Broadgate_H1_EH1_UKPN1 - Earth Fault Settings
UKPN 1 33kV Feeder, Reyrolle, Argus DCD
ICT 600 Curve NI IHS1 OFF IHS2 OFF ILS1 OFF
Is 0.35 tHS1 0.10 tHS2 0.05 tLS1 0.00
tm 0.225

CB1 33kV Incomer, 600A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve IAC INV Curve Curve
Iso 125.0 Iso 999000 Iso Iso
T 0.46 T 0.44 T T

CB 2 33kV Feeder, 600A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve IAC VI Curve Curve
Iso 80.0 Iso 999000 Iso Iso
T 0.13 T 0.44 T T

15/02/2016 12:09:22 Amtech Protect HV Version 2013.0.0 Page 1 of 3


UTILITY Mode EF 5 Broadgate_H1_EH1_UKPN1.prs17
Earth Fault-Time/Current Analysis, Voltage Base: 33000V, 15/02/2016 12:09:38
10000s

1 hour

1000s
UKPN 1 33kV Feeder
CB1 33kV Incomer
CB 2 33kV Feeder

100s

1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
10mA 100mA 1A 10A 100A 1kA 10kA 100kA 1MA

15/02/2016 12:09:22 Amtech Protect HV Version 2013.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
UTILITY Mode EF 5 Broadgate_H1_EH1_UKPN1 - Earth Fault Analysis

UKPN Earth Fault - 33000V


~

UKPN 1 33kV Feeder - 33000V


Reyrolle - Argus DCD
Ief is 1.78kA, Icu is Unknown

CB1 33kV Incomer - 600A@33000V


Merlin Gerin MV - Sepam S1000+
Ief is 1.7kA, Icu is Unknown

CB 2 33kV Feeder - 600A@33000V


Merlin Gerin MV - Sepam S1000+
Ief is 1.7kA, Icu is Unknown

Ief Exceeds Fault Capacity.

15/02/2016 12:09:22 Amtech Protect HV Version 2013.0.0 Page 3 of 3


COMMISSIONING REPORT
AMTECH Protect - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision Created 26/01/2016 18:23:16
Job ID Last Saved 31/01/2016 14:09:48
Engineer
UTILITY Mode OC 5 Broadgate_H1_EH1_UKPN1 - Overcurrent Settings
UKPN 1 33kV Feeder, Reyrolle, Argus DCD
ICT 600 Curve NI IHS1 OFF IHS2 OFF ILS1 OFF
Is 1.00 tHS1 0.10 tHS2 0.05 tLS1 0.00
tm 0.300

CB1 33kV Incomer, 600A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve IAC INV Curve Curve
Is 450.0 Is 1000.0 Is Is
T 1.10 T 0.73 T T

CB 2 33kV Feeder, 600A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve DT Curve Curve
Is 380.0 Is 4200.0 Is Is
T 0.82 T 0.05 T T

CB 16 Incomer HVSB-1XX01, 1250A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve DT Curve Curve
Is 945.0 Is 999000 Is Is
T 0.67 T 1.05 T T

15/02/2016 11:59:50 Amtech Protect HV Version 2013.0.0 Page 1 of 3


UTILITY Mode OC 5 Broadgate_H1_EH1_UKPN1.prs17
Overcurrent-Time/Current Analysis, Voltage Base: 33000V, 15/02/2016 12:00:03
10000s
Pscc Src Pscc
7.800kA 15.8kA

1 hour

1000s
UKPN 1 33kV Feeder
CB1 33kV Incomer
CB 2 33kV Feeder
CB 16 Incomer HVSB-1XX01

100s

1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

15/02/2016 11:59:50 Amtech Protect HV Version 2013.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
UTILITY Mode OC 5 Broadgate_H1_EH1_UKPN1 - Overcurrent Analysis

UKPN - 33000V, Pscc is 15.8kA


~

UKPN 1 33kV Feeder - 33000V


Reyrolle - Argus DCD
Pscc is 15kA, Icu is Unknown

CB1 33kV Incomer - 600A@33000V


Merlin Gerin MV - Sepam S1000+
Pscc is 15kA, Icu is Unknown

CB 2 33kV Feeder - 600A@33000V


Merlin Gerin MV - Sepam S1000+
Pscc is 15kA, Icu is Unknown

Transformer 33000/11000 - 33000V/11000V, 18000kVA

CB 16 Incomer HVSB-1XX01 - 1250A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 7.8kA, Icu is Unknown

Pscc Exceeds Fault Capacity.

15/02/2016 11:59:50 Amtech Protect HV Version 2013.0.0 Page 3 of 3


Electrical Discrimination Study
5 Broadgate

6.0 11kV Network Analysis

Long and Partners Ltd


Rev 11 QA-R06-1 12 of 14
ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 4 Spare Circuit


Device SEPAM T81
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 200/100/1A on 200A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 60A Is = 30A
50N/51N - 1 Trip CB P T = 400ms T = 120ms
Group A ON Curve = IEC EIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 2000A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group A ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 60A Is = 30A
50N/51N - 1 Trip CB P T = 140ms T = 100ms
Group B ON Curve = IEC SIT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 2000A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group B ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
49RMS Thermal Overload
64 REF Restricted Earth Fault
67N Directional Earth Fault
32P Active Power
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
81R Rate of change of frequency
38/49T Temperature Monitoring
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-1XX01 Rev 4 2 of 21 CB 4


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 5 Circuit H4


Device SEPAM S80
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 1250/800/1A on 800A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 800A Is = 80A
50N/51N - 1 Trip CB P T = 450ms T = 710ms
Group A ON Curve = IEC SIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P
SWITCHED OFF SWITCHED OFF
Group A OFF
2nd Harmonic Restraint
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 700A Is = 80A
50N/51N - 1 Trip CB P T = 600ms T = 370ms
Group B ON Curve = RI Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P
SWITCHED OFF SWITCHED OFF
Group B OFF
2nd Harmonic Restraint
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
79 Re-closer
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-1XX01 Rev 4 3 of 21 CB 5


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 5 Circuit H4


Device SOLKOR 7SG18 N
Select
CT Ratio 1000/1A on 1000A Range
SETTINGS GROUP G MENU ONLY
SCREEN FUNCTION MENU ENTRY
Active Settings Group Group that the relay will act upon G1
Settings Group Edit/View Group to be displayed on the LCD G1
Local P/F Rating Local relay’s phase fault CT rating 1A
Local E/F Rating Local relay’s earth fault CT rating 1A
Local P/F CT Ratio relay’s phase input CT ratio 1000:1
Local E/F CT Ratio relay’s earth input CT ratio 1000:1
Remote P/F Rating Remote relay’s phase fault CT rating 1A
Remote P/F CT Ratio Remote relay’s earth fault CT rating 1000:1
Current Display display mode to use for the relay xIn
Set Identifier 16 character alphanumeric code CB5 SOLKOR
Set Alarm 1 ALARM 1
Calendar – Set Date DD/MM/YY Todays Date
Clock - Set Time HH:MM:SS Actual Time
Clock Sync. From Status Seconds or Minutes Minutes
Default Screen Timer 10sec, 60sec, 5min, 1hour 5 min
Change Password 4 alphanumeric characters NONE

DIFF' PROTECTION MENU ONLY


SCREEN FUNCTION MENU ENTRY
Gn P/F Diff. Setting* setting for the differential element 0.3 x In
Gn P/F Bias Slope 1* 1st bias slope differential element 30%
Gn P/F Bias Slope 2* 2nd bias slope differential element 150%
Gn Bias Break Point* bias slope break point 1 to 2 2.00 x In
Gn Differential Delay trip time differential element/ intertrip 0.0s
P/F CT Ratio Correction CT ratio correction 1
Remote P/F Ratio Correction CT ratio correction 1
Gn Internal Intertrip enables / disables internal intertrips OFF
Gn Int Intertrip Delay internal intertrip elements 0.00s
Gn External Intertrip enables / disables external intertrips ON
Gn Ext Intertrip Delay external intertrip elements 0.00s

O/C PROTECTION MENU ONLY


SCREEN FUNCTION MENU ENTRY
Gn P/F Charact. Setting phase fault O/C pick-up level OFF
Gn P/F Charact. phase fault O/C characteristic
Gn P/F Charact. Time Mult phase fault TMS
Gn P/F Charact. Delay phase fault delay DTL
Gn P/F Lowset Setting phase fault lowset pick-up OFF
Gn P/F Lowset Delay phase fault lowset delay
Gn P/F Highset1 Setting phase fault highset 1 pick-up OFF
Gn P/F Highset1 Delay phase fault highset 1 delay
Gn P/F Highset2 Setting phase fault highset 2 pick-up OFF
Gn P/F Highset2 Delay phase fault highset 2 delay
Gn E/F Charact. Setting earth fault O/C pick-up level OFF
Gn E/F Charact. earth fault O/C characteristic
Gn E/F Charact. Time Mult earth fault TMS
Gn E/F Charact. Delay earth fault delay DTL
Gn E/F Lowset Setting earth fault lowset pick-up OFF
Gn E/F Lowset Delay earth fault lowset delay
Gn E/F Highset1 Setting earth fault highset 1 pick-up OFF
Gn E/F Highset1 Delay earth fault highset 1 delay
Gn E/F Highset 2 Setting earth fault highset 2 pick-up OFF
Gn E/F Highset 2 Delay earth fault highset 2 delay
Gn CB Fail Time Delay 1 1st time delay for CB Fail OFF
Gn CB Fail Time Delay2 2nd time delay for CB Fail OFF
Gn P/F CB Fail Setting sets over current CB Fail level OFF
Gn E/F CB Fail Setting sets earth fault current CB Fail level OFF
Gn CT Failure Setting sets CT Failure level OFF
Gn CT Failure Delay sets delay for CT Failure 1s
Gn Relay Reset Delay OC reset characteristic INST
O/P RELAY CONFIG MENU ONLY
Gn Prot. Healthy RL1
Gn P/F Diff. RL4

5 Broadgate Protective Device Settings HVSB-1XX01 Rev 4 4 of 21 CB5 SOLKOR


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 6 Spare Circuit


Device SEPAM T81
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 200/100/1A on 200A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 60A Is = 30A
50N/51N - 1 Trip CB P T = 400ms T = 120ms
Group A ON Curve = IEC EIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 2000A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group A ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 60A Is = 30A
50N/51N - 1 Trip CB P T = 140ms T = 100ms
Group B ON Curve = IEC SIT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 2000A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group B ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
49RMS Thermal Overload
64 REF Restricted Earth Fault
67N Direction Earth Fault
32P Active Power
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
81R Rate of change of frequency
38/49T Temperature Monitoring
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-1XX01 Rev 4 5 of 21 CB 6


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 7 Spare Circuit


Device SEPAM T81
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 600/300/1A on 300A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 60A Is = 30A
50N/51N - 1 Trip CB P T = 400ms T = 120ms
Group A ON Curve = IEC EIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 2000A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group A ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 60A Is = 30A
50N/51N - 1 Trip CB P T = 140ms T = 100ms
Group B ON Curve = IEC SIT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 2000A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group B ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
49RMS Thermal Overload
64 REF Restricted Earth Fault
67N Direction Earth Fault
32P Active Power
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
81R Rate of change of frequency
38/49T Temperature Monitoring
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-1XX01 Rev 4 6 of 21 CB 7


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 8 Spare Circuit


Device SEPAM T81
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 600/300/1A on 300A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 60A Is = 30A
50N/51N - 1 Trip CB P T = 400ms T = 120ms
Group A ON Curve = IEC EIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 2000A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group A ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 60A Is = 30A
50N/51N - 1 Trip CB P T = 140ms T = 100ms
Group B ON Curve = IEC SIT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 2000A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group B ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
49RMS Thermal Overload
64 REF Restricted Earth Fault
67N Direction Earth Fault
32P Active Power
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
81R Rate of change of frequency
38/49T Temperature Monitoring
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-1XX01 Rev 4 7 of 21 CB 8


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 9 Circuit H19


Device SOLKOR 7SG18 N
Select
CT Ratio 1000/1A on 1000A Range
SETTINGS GROUP G MENU ONLY
SCREEN FUNCTION MENU ENTRY
Active Settings Group Group that the relay will act upon G1
Settings Group Edit/View Group to be displayed on the LCD G1
Local P/F Rating Local relay’s phase fault CT rating 1A
Local E/F Rating Local relay’s earth fault CT rating 1A
Local P/F CT Ratio relay’s phase input CT ratio 1000:1
Local E/F CT Ratio relay’s earth input CT ratio 1000:1
Remote P/F Rating Remote relay’s phase fault CT rating 1A
Remote P/F CT Ratio Remote relay’s earth fault CT rating 1000:1
Current Display display mode to use for the relay xIn
Set Identifier 16 character alphanumeric code CB9 SOLKOR
Set Alarm 1 ALARM 1
Calendar – Set Date DD/MM/YY Todays Date
Clock - Set Time HH:MM:SS Actual Time
Clock Sync. From Status Seconds or Minutes Minutes
Default Screen Timer 10sec, 60sec, 5min, 1hour 5 min
Change Password 4 alphanumeric characters NONE

DIFF' PROTECTION MENU ONLY


SCREEN FUNCTION MENU ENTRY
Gn P/F Diff. Setting* setting for the differential element 0.3 x In
Gn P/F Bias Slope 1* 1st bias slope differential element 30%
Gn P/F Bias Slope 2* 2nd bias slope differential element 150%
Gn Bias Break Point* bias slope break point 1 to 2 2.00 x In
Gn Differential Delay trip time differential element/ intertrip 0.0s
P/F CT Ratio Correction CT ratio correction 1
Remote P/F Ratio Correction CT ratio correction 1
Gn Internal Intertrip enables / disables internal intertrips OFF
Gn Int Intertrip Delay internal intertrip elements 0.00s
Gn External Intertrip enables / disables external intertrips ON
Gn Ext Intertrip Delay external intertrip elements 0.00s

O/C PROTECTION MENU ONLY


SCREEN FUNCTION MENU ENTRY
Gn P/F Charact. Setting phase fault O/C pick-up level OFF
Gn P/F Charact. phase fault O/C characteristic
Gn P/F Charact. Time Mult phase fault TMS
Gn P/F Charact. Delay phase fault delay DTL
Gn P/F Lowset Setting phase fault lowset pick-up OFF
Gn P/F Lowset Delay phase fault lowset delay
Gn P/F Highset1 Setting phase fault highset 1 pick-up OFF
Gn P/F Highset1 Delay phase fault highset 1 delay
Gn P/F Highset 2 Setting phase fault highset 2 pick-up OFF
Gn P/F Highset 2 Delay phase fault highset 2 delay
Gn E/F Charact. Setting earth fault O/C pick-up level OFF
Gn E/F Charact. earth fault O/C characteristic
Gn E/F Charact. Time Mult earth fault TMS
Gn E/F Charact. Delay earth fault delay DTL
Gn E/F Lowset Setting earth fault lowset pick-up OFF
Gn E/F Lowset Delay earth fault lowset delay
Gn E/F Highset1 Setting earth fault highset 1 pick-up OFF
Gn E/F Highset1 Delay earth fault highset 1 delay
Gn E/F Highset2 Setting earth fault highset 2 pick-up OFF
Gn E/F Highset2 Delay earth fault highset 2 delay
Gn CB Fail Time Delay 1 1st time delay for CB Fail OFF
Gn CB Fail Time Delay2 2nd time delay for CB Fail OFF
Gn P/F CB Fail Setting sets over current CB Fail level OFF
Gn E/F CB Fail Setting sets earth fault current CB Fail level OFF
Gn CT Failure Setting sets CT Failure level OFF
Gn CT Failure Delay sets delay for CT Failure 1s
Gn Relay Reset Delay OC reset characteristic INST
O/P RELAY CONFIG MENU ONLY
Gn Prot. Healthy RL1
Gn P/F Diff. RL4

5 Broadgate Protective Device Settings HVSB-1XX01 Rev 4 8 of 21 CB9 SOLKOR


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV INCOMER, CB 9 Circuit H19


Device SEPAM S80
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 1250/800/1A on 800A range
Logic Discrimination ON 200ms
MES 120 I/O Card I103 Blocking Reception 1 from CB 20, CB 21
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 800A Is = 80A
50N/51N - 1 Trip CB P T = 220ms T = 700ms
Group A ON Curve = IEC SIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P
SWITCHED OFF SWITCHED OFF
Group A OFF
2nd Harmonic Restraint
50/51 - 3 Latching P Is = 800A Is = 80A
50N/51N - 3 Trip CB P T = 220ms T = 700ms
Group A OFF Curve = IEC SIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - Elements 4~8
50N/51N - Elements 4~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 780A Is = 95A
50N/51N - 1 Trip CB P T = 2000ms T = 620ms
Group B ON Curve = DT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P
SWITCHED OFF SWITCHED OFF
Group B OFF
2nd Harmonic Restraint
50/51 - 3 Latching P Is = 780A Is = 95A
50N/51N - 3 Trip CB P T = 2250ms T = 870ms
Group B OFF Curve = DT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - Elements 4~8
50N/51N - Elements 4~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
79 Re-closer
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-1XX01 Rev 4 9 of 21 CB 9


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 10 Spare Circuit


Device SEPAM T81
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 600/300/1A on 300A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 60A Is = 30A
50N/51N - 1 Trip CB P T = 400ms T = 120ms
Group A ON Curve = IEC EIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 2000A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group A ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 60A Is = 30A
50N/51N - 1 Trip CB P T = 140ms T = 100ms
Group B ON Curve = IEC SIT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 2000A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group B ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
49RMS Thermal Overload
64 REF Restricted Earth Fault
67N Direction Earth Fault
32P Active Power
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
81R Rate of change of frequency
38/49T Temperature Monitoring
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-1XX01 Rev 4 10 of 21 CB 10


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 11 Spare Circuit


Device SEPAM T81
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 600/300/1A on 300A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 60A Is = 30A
50N/51N - 1 Trip CB P T = 400ms T = 120ms
Group A ON Curve = IEC EIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 2000A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group A ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 60A Is = 30A
50N/51N - 1 Trip CB P T = 140ms T = 100ms
Group B ON Curve = IEC SIT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 2000A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group B ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
49RMS Thermal Overload
64 REF Restricted Earth Fault
67N Direction Earth Fault
32P Active Power
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
81R Rate of change of frequency
38/49T Temperature Monitoring
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-1XX01 Rev 4 11 of 21 CB 11


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 12 Circuit H20


Device SOLKOR 7SG18 N
Select
CT Ratio 1000/1A on 1000A Range
SETTINGS GROUP G MENU ONLY
SCREEN FUNCTION MENU ENTRY
Active Settings Group Group that the relay will act upon G1
Settings Group Edit/View Group to be displayed on the LCD G1
Local P/F Rating Local relay’s phase fault CT rating 1A
Local E/F Rating Local relay’s earth fault CT rating 1A
Local P/F CT Ratio relay’s phase input CT ratio 1000:1
Local E/F CT Ratio relay’s earth input CT ratio 1000:1
Remote P/F Rating Remote relay’s phase fault CT rating 1A
Remote P/F CT Ratio Remote relay’s earth fault CT rating 1000:1
Current Display display mode to use for the relay xIn
Set Identifier 16 character alphanumeric code CB12 SOLKOR
Set Alarm 1 ALARM 1
Calendar – Set Date DD/MM/YY Todays Date
Clock - Set Time HH:MM:SS Actual Time
Clock Sync. From Status Seconds or Minutes Minutes
Default Screen Timer 10sec, 60sec, 5min, 1hour 5 min
Change Password 4 alphanumeric characters NONE

DIFF' PROTECTION MENU ONLY


SCREEN FUNCTION MENU ENTRY
Gn P/F Diff. Setting* setting for the differential element 0.3 x In
Gn P/F Bias Slope 1* 1st bias slope differential element 30%
Gn P/F Bias Slope 2* 2nd bias slope differential element 150%
Gn Bias Break Point* bias slope break point 1 to 2 2.00 x In
Gn Differential Delay trip time differential element/ intertrip 0.0s
P/F CT Ratio Correction CT ratio correction 1
Remote P/F Ratio Correction CT ratio correction 1
Gn Internal Intertrip enables / disables internal intertrips OFF
Gn Int Intertrip Delay internal intertrip elements 0.00s
Gn External Intertrip enables / disables external intertrips ON
Gn Ext Intertrip Delay external intertrip elements 0.00s

O/C PROTECTION MENU ONLY


SCREEN FUNCTION MENU ENTRY
Gn P/F Charact. Setting phase fault O/C pick-up level OFF
Gn P/F Charact. phase fault O/C characteristic
Gn P/F Charact. Time Mult phase fault TMS
Gn P/F Charact. Delay phase fault delay DTL
Gn P/F Lowset Setting phase fault lowset pick-up OFF
Gn P/F Lowset Delay phase fault lowset delay
Gn P/F Highset1 Setting phase fault highset 1 pick-up OFF
Gn P/F Highset1 Delay phase fault highset 1 delay
Gn P/F Highset 2 Setting phase fault highset 2 pick-up OFF
Gn P/F Highset 2 Delay phase fault highset 2 delay
Gn E/F Charact. Setting earth fault O/C pick-up level OFF
Gn E/F Charact. earth fault O/C characteristic
Gn E/F Charact. Time Mult earth fault TMS
Gn E/F Charact. Delay earth fault delay DTL
Gn E/F Lowset Setting earth fault lowset pick-up OFF
Gn E/F Lowset Delay earth fault lowset delay
Gn E/F Highset1 Setting earth fault highset 1 pick-up OFF
Gn E/F Highset1 Delay earth fault highset 1 delay
Gn E/F Highset2 Setting earth fault highset 2 pick-up OFF
Gn E/F Highset2 Delay earth fault highset 2 delay
Gn CB Fail Time Delay 1 1st time delay for CB Fail OFF
Gn CB Fail Time Delay2 2nd time delay for CB Fail OFF
Gn P/F CB Fail Setting sets over current CB Fail level OFF
Gn E/F CB Fail Setting sets earth fault current CB Fail level OFF
Gn CT Failure Setting sets CT Failure level OFF
Gn CT Failure Delay sets delay for CT Failure 1s
Gn Relay Reset Delay OC reset characteristic INST
O/P RELAY CONFIG MENU ONLY
Gn Prot. Healthy RL1
Gn P/F Diff. RL4

5 Broadgate Protective Device Settings HVSB-1XX01 Rev 4 12 of 21 CB12 SOLKOR


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV INCOMER, CB 12 Circuit H20


Device SEPAM S80
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 1250/800/1A on 800A range
Logic Discrimination ON 200ms
MES 120 I/O Card I103 Blocking Reception 1 from CB 20, CB 21
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 800A Is = 80A
50N/51N - 1 Trip CB P T = 220ms T = 700ms
Group A ON Curve = IEC SIT Curve = IEC SIT
2nd Harmonic Restraint OFF Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P
SWITCHED OFF SWITCHED OFF
Group A OFF
2nd Harmonic Restraint
50/51 - 3 Latching P Is = 800A Is = 80A
50N/51N - 3 Trip CB P T = 220ms T = 700ms
Group A OFF Curve = IEC SIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - Elements 4~8
50N/51N - Elements 4~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 780A Is = 95A
50N/51N - 1 Trip CB P T = 2000ms T = 620ms
Group B ON Curve = DT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P
SWITCHED OFF SWITCHED OFF
Group B OFF
2nd Harmonic Restraint
50/51 - 3 Latching P Is = 780A Is = 95A
50N/51N - 3 Trip CB P T = 2250ms T = 870ms
Group B OFF Curve = DT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - Elements 4~8
50N/51N - Elements 4~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
79 Re-closer
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-1XX01 Rev 4 13 of 21 CB 12


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 13 Spare Circuit


Device SEPAM T81
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 600/300/1A on 300A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 60A Is = 30A
50N/51N - 1 Trip CB P T = 400ms T = 120ms
Group A ON Curve = IEC EIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 2000A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group A ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 60A Is = 30A
50N/51N - 1 Trip CB P T = 140ms T = 100ms
Group B ON Curve = IEC SIT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 2000A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group B ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
49RMS Thermal Overload
64 REF Restricted Earth Fault
67N Direction Earth Fault
32P Active Power
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
81R Rate of change of frequency
38/49T Temperature Monitoring
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-1XX01 Rev 4 14 of 21 CB 13


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 14 Spare Circuit


Device SEPAM T81
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 600/300/1A on 300A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 60A Is = 30A
50N/51N - 1 Trip CB P T = 400ms T = 120ms
Group A ON Curve = IEC EIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 2000A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group A ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 60A Is = 30A
50N/51N - 1 Trip CB P T = 140ms T = 100ms
Group B ON Curve = IEC SIT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 2000A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group B ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
49RMS Thermal Overload
64 REF Restricted Earth Fault
67N Direction Earth Fault
32P Active Power
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
81R Rate of change of frequency
38/49T Temperature Monitoring
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-1XX01 Rev 4 15 of 21 CB 14


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 15 Circuit H7 TX-2XX01


Device SEPAM T81
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 600/300/1A on 300A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 250A Is = 50A
50N/51N - 1 Trip CB P T = 400ms T = 120ms
Group A ON Curve = IEC EIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 4200A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group A ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 250A Is = 50A
50N/51N - 1 Trip CB P T = 120ms T = 100ms
Group B ON Curve = IEC SIT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 4200A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group B ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
SWITCHED OFF
50N/51N - Elements 3~8 SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
49RMS Thermal Overload
64 REF Restricted Earth Fault
67N Directional Earth Fault
32P Active Power
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
81R Rate of change of frequency
38/49T Temperature Monitoring
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-1XX01 Rev 4 17 of 21 CB 15


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV INCOMER, CB 16 Circuit H11


Device SEPAM S81
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 1250/800/1A on 1250A range
Logic Discrimination ON 200ms
MES 120 I/O Card I103 Blocking Reception 1 from CB 20, CB 21
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 945A Is = 200A
50N/51N - 1 Trip CB P T = 670ms T = 800ms
Group A ON Curve = IEC SIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P
SWITCHED OFF SWITCHED OFF
Group A OFF
2nd Harmonic Restraint
50/51 - 3 Latching P Is = 945A Is = 200A
50N/51N - 3 Trip CB P T = 920ms T = 1050ms
Group A ON Curve = IEC SIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - Elements 4~8
50N/51N - Elements 4~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 945A Is = 200A
50N/51N - 1 Trip CB P T = 670ms T = 800ms
Group B ON Curve = IEC SIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P
SWITCHED OFF SWITCHED OFF
Group B OFF
2nd Harmonic Restraint
50/51 - 3 Latching P Is = 945A Is = 200A
50N/51N - 3 Trip CB P T = 920ms T = 1050ms
Group B ON Curve = IEC SIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - Elements 4~8
50N/51N - Elements 4~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50BF Breaker Failure
50BF - 1 Latching P Is = 1.25kA
Trip CB P T = 130ms
46 negative sequence / unbalance
49RMS Thermal Overload
67N Direction Earth Fault
32P Active Power
27D Positive sequence undercurrent
27R Remnant undervoltage
To align with Generator Operation Philosophy & Initiate Change Over?
27 Under voltage
If not OFF
(Phase to Phase & Phase to Neutral) Tripping Curve = DT
Unit 1 & 2 ON P Mode = Phase to Phase
Unit 3 & 4 OFF Voltage = 80%, Delay = 2s
To align with Generator Operation Philosophy & Initiate Change Over?
59 overvoltage
If not OFF
(Phase to Phase & Phase to Neutral) Mode = Phase to Phase
Unit 1 & 2 ON P Voltage = 110%
Unit 3 & 4 OFF Delay = 2s
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
To align with Generator Operation Philosophy & Initiate Change Over?
81H over frequency
If not OFF
Unit 1 ON P Threshold = 52Hz
Unit 2 OFF Delay = 200ms
To align with Generator Operation Philosophy & Initiate Change Over?
81L under frequency
If not OFF
Unit 1 ON Threshold = 48Hz
Unit 2 OFF Delay = 200ms
79 Re-closer
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-1XX01 Rev 4 1 of 21 CB 16


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 17 Circuit H8 TX-2XX02


Device SEPAM T81
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 200/100/1A on 200A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 60A Is = 20A
50N/51N - 1 Trip CB P T = 400ms T = 120ms
Group A ON Curve = IEC EIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 2000A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group A ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 60A Is = 20A
50N/51N - 1 Trip CB P T = 140ms T = 100ms
Group B ON Curve = IEC SIT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 2000A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group B ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
49RMS Thermal Overload
64 REF Restricted Earth Fault
67N Directional Earth Fault
32P Active Power
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
81R Rate of change of frequency
38/49T Temperature Monitoring
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-1XX01 Rev 4 16 of 21 CB 17


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 18 Circuit H9 TX-2XX03


Device SEPAM T81
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 600/300/1A on 300A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 200A Is = 40A
50N/51N - 1 Trip CB P T = 400ms T = 120ms
Group A ON Curve = IEC EIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 3800A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group A ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 200A Is = 40A
50N/51N - 1 Trip CB P T = 140ms T = 100ms
Group B ON Curve = IEC SIT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 3800A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group B ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
SWITCHED OFF
50N/51N - Elements 3~8 SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
49RMS Thermal Overload
64 REF Restricted Earth Fault
67N Directional Earth Fault
32P Active Power
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
81R Rate of change of frequency
38/49T Temperature Monitoring
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-1XX01 Rev 4 18 of 21 CB 18


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 19 Circuit H10 TX-2XX04


Device SEPAM T81
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 200/100/1A on 200A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 125A Is = 25A
50N/51N - 1 Trip CB P T = 400ms T = 120ms
Group A ON Curve = IEC EIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 3000A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group A ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 125A Is = 25A
50N/51N - 1 Trip CB P T = 140ms T = 100ms
Group B ON Curve = IEC SIT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 3000A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group B ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
SWITCHED OFF
50N/51N - Elements 3~8 SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
49RMS Thermal Overload
64 REF Restricted Earth Fault
67N Directional Earth Fault
32P Active Power
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
81R Rate of change of frequency
38/49T Temperature Monitoring
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-1XX01 Rev 4 19 of 21 CB 19


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 12.02.16
23.02.16 4

Description 11 kV FEEDER, CB 20 Circuit H3


Device SEPAM S80
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 1250/800/1A on 800A range
Logic Discrimination ON 200ms
MES 120 I/O Card Block Out O102:CB 25,29,32 O103: CB 16,9,12
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 No Latching Is = 3kA Is = 500A
50N/51N - 1 No Trip CB T = 0ms T = 0ms
Group A ON Curve = DT Curve = DT
2nd Harmonic Restraint OFF
50/51 - 2 Latching P
50N/51N - 2 Trip CB P
SWITCHED OFF SWITCHED OFF
Group A OFF
2nd Harmonic Restraint
50/51 - 3 Latching Is = 945A Is = 100A
50N/51N - 3 Trip CB T = 670ms T = 900ms
Group A ON Curve = IEC SIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - Elements 4~8
50N/51N - Elements 4~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 No Latching Is = 400A Is = 50A
50N/51N - 1 No Trip CB T = 0ms T = 0ms
Group B ON Curve = DT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P
SWITCHED OFF SWITCHED OFF
Group B OFF
2nd Harmonic Restraint
50/51 - 3 Latching P Is = 780A Is = 95A
50N/51N - 3 Trip CB P T = 1750ms T = 620ms
Group B ON Curve = DT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - Elements 4~8
50N/51N - Elements 4~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
79 Re-closer
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-1XX01 Rev 4 20 of 21 CB 20


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 20 Circuit H3


Device SOLKOR 7SG18 N
Select
CT Ratio 1000/1A on 1000A Range
SETTINGS GROUP G MENU ONLY
SCREEN FUNCTION MENU ENTRY
Active Settings Group Group that the relay will act upon G1
Settings Group Edit/View Group to be displayed on the LCD G1
Local P/F Rating Local relay’s phase fault CT rating 1A
Local E/F Rating Local relay’s earth fault CT rating 1A
Local P/F CT Ratio relay’s phase input CT ratio 1000:1
Local E/F CT Ratio relay’s earth input CT ratio 1000:1
Remote P/F Rating Remote relay’s phase fault CT rating 1A
Remote P/F CT Ratio Remote relay’s earth fault CT rating 1000:1
Current Display display mode to use for the relay xIn
Set Identifier 16 character alphanumeric code CB20 SOLKOR
Set Alarm 1 ALARM 1
Calendar – Set Date DD/MM/YY Todays Date
Clock - Set Time HH:MM:SS Actual Time
Clock Sync. From Status Seconds or Minutes Minutes
Default Screen Timer 10sec, 60sec, 5min, 1hour 5 min
Change Password 4 alphanumeric characters NONE

DIFF' PROTECTION MENU ONLY


SCREEN FUNCTION MENU ENTRY
Gn P/F Diff. Setting* setting for the differential element 0.3 x In
Gn P/F Bias Slope 1* 1st bias slope differential element 30%
Gn P/F Bias Slope 2* 2nd bias slope differential element 150%
Gn Bias Break Point* bias slope break point 1 to 2 2.00 x In
Gn Differential Delay trip time differential element/ intertrip 0.0s
P/F CT Ratio Correction CT ratio correction 1
Remote P/F Ratio Correction CT ratio correction 1
Gn Internal Intertrip enables / disables internal intertrips OFF
Gn Int Intertrip Delay internal intertrip elements 0.00s
Gn External Intertrip enables / disables external intertrips ON
Gn Ext Intertrip Delay external intertrip elements 0.00s

O/C PROTECTION MENU ONLY


SCREEN FUNCTION MENU ENTRY
Gn P/F Charact. Setting phase fault O/C pick-up level OFF
Gn P/F Charact. phase fault O/C characteristic
Gn P/F Charact. Time Mult phase fault TMS
Gn P/F Charact. Delay phase fault delay DTL
Gn P/F Lowset Setting phase fault lowset pick-up OFF
Gn P/F Lowset Delay phase fault lowset delay
Gn P/F Highset1 Setting phase fault highset 1 pick-up OFF
Gn P/F Highset1 Delay phase fault highset 1 delay
Gn P/F Highset 2 Setting phase fault highset 2 pick-up OFF
Gn P/F Highset 2 Delay phase fault highset 2 delay
Gn E/F Charact. Setting earth fault O/C pick-up level OFF
Gn E/F Charact. earth fault O/C characteristic
Gn E/F Charact. Time Mult earth fault TMS
Gn E/F Charact. Delay earth fault delay DTL
Gn E/F Lowset Setting earth fault lowset pick-up OFF
Gn E/F Lowset Delay earth fault lowset delay
Gn E/F Highset1 Setting earth fault highset 1 pick-up OFF
Gn E/F Highset1 Delay earth fault highset 1 delay
Gn E/F Highset2 Setting earth fault highset 2 pick-up OFF
Gn E/F Highset2 Delay earth fault highset 2 delay
Gn CB Fail Time Delay 1 1st time delay for CB Fail OFF
Gn CB Fail Time Delay2 2nd time delay for CB Fail OFF
Gn P/F CB Fail Setting sets over current CB Fail level OFF
Gn E/F CB Fail Setting sets earth fault current CB Fail level OFF
Gn CT Failure Setting sets CT Failure level OFF
Gn CT Failure Delay sets delay for CT Failure 1s
Gn Relay Reset Delay OC reset characteristic INST
O/P RELAY CONFIG MENU ONLY
Gn Prot. Healthy RL1
Gn P/F Diff. RL4

5 Broadgate Protective Device Settings HVSB-1XX01 Rev 4 21 of 21 CB20 SOLKOR


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV INCOMER, CB 21 Circuit H3


Device SEPAM S80
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 1250/800/1A on 800A range
Logic Discrimination ON 200ms
MES 120 I/O Card Block Out O102:CB 25,29,32 O103: CB 16,9,12
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 No Latching Is = 3kA Is = 500A
50N/51N - 1 No Trip CB T = 0ms T = 0ms
Group A ON Curve = DT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P
SWITCHED OFF SWITCHED OFF
Group A OFF
2nd Harmonic Restraint
50/51 - 3 Latching P Is = 945A Is = 100A
50N/51N - 3 Trip CB P T = 670ms T = 900ms
Group A ON Curve = IEC SIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 4 Latching P
50N/51N - 4 Trip CB P
SWITCHED OFF SWITCHED OFF
Group A OFF
2nd Harmonic Restraint
50/51 - Elements 4~8
50N/51N - Elements 4~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 No Latching Is = 400A Is = 50A
50N/51N - 1 No Trip CB T = 0ms T = 0ms
Group B ON Curve = DT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P
SWITCHED OFF SWITCHED OFF
Group B OFF
2nd Harmonic Restraint
50/51 - 3 Latching P Is = 780A Is = 95A
50N/51N - 3 Trip CB P T = 1750ms T = 620ms
Group B ON Curve = DT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - Elements 4~8
50N/51N - Elements 4~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
79 Re-closer
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-1XX02 Rev 4 20 of 21 CB 21


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 21 Circuit H3


Device SOLKOR 7SG18 N
Select
CT Ratio 1000/1A on 1000A Range
SETTINGS GROUP G MENU ONLY
SCREEN FUNCTION MENU ENTRY
Active Settings Group Group that the relay will act upon G1
Settings Group Edit/View Group to be displayed on the LCD G1
Local P/F Rating Local relay’s phase fault CT rating 1A
Local E/F Rating Local relay’s earth fault CT rating 1A
Local P/F CT Ratio relay’s phase input CT ratio 1000:1
Local E/F CT Ratio relay’s earth input CT ratio 1000:1
Remote P/F Rating Remote relay’s phase fault CT rating 1A
Remote P/F CT Ratio Remote relay’s earth fault CT rating 1000:1
Current Display display mode to use for the relay xIn
Set Identifier 16 character alphanumeric code CB21 SOLKOR
Set Alarm 1 ALARM 1
Calendar – Set Date DD/MM/YY Todays Date
Clock - Set Time HH:MM:SS Actual Time
Clock Sync. From Status Seconds or Minutes Minutes
Default Screen Timer 10sec, 60sec, 5min, 1hour 5 min
Change Password 4 alphanumeric characters NONE

DIFF' PROTECTION MENU ONLY


SCREEN FUNCTION MENU ENTRY
Gn P/F Diff. Setting* setting for the differential element 0.3 x In
Gn P/F Bias Slope 1* 1st bias slope differential element 30%
Gn P/F Bias Slope 2* 2nd bias slope differential element 150%
Gn Bias Break Point* bias slope break point 1 to 2 2.00 x In
Gn Differential Delay trip time differential element/ intertrip 0.0s
P/F CT Ratio Correction CT ratio correction 1
Remote P/F Ratio Correction CT ratio correction 1
Gn Internal Intertrip enables / disables internal intertrips OFF
Gn Int Intertrip Delay internal intertrip elements 0.00s
Gn External Intertrip enables / disables external intertrips ON
Gn Ext Intertrip Delay external intertrip elements 0.00s

O/C PROTECTION MENU ONLY


SCREEN FUNCTION MENU ENTRY
Gn P/F Charact. Setting phase fault O/C pick-up level OFF
Gn P/F Charact. phase fault O/C characteristic
Gn P/F Charact. Time Mult phase fault TMS
Gn P/F Charact. Delay phase fault delay DTL
Gn P/F Lowset Setting phase fault lowset pick-up OFF
Gn P/F Lowset Delay phase fault lowset delay
Gn P/F Highset1 Setting phase fault highset 1 pick-up OFF
Gn P/F Highset1 Delay phase fault highset 1 delay
Gn P/F Highset2 Setting phase fault highset 2 pick-up OFF
Gn P/F Highset2 Delay phase fault highset 2 delay
Gn E/F Charact. Setting earth fault O/C pick-up level OFF
Gn E/F Charact. earth fault O/C characteristic
Gn E/F Charact. Time Mult earth fault TMS
Gn E/F Charact. Delay earth fault delay DTL
Gn E/F Lowset Setting earth fault lowset pick-up OFF
Gn E/F Lowset Delay earth fault lowset delay
Gn E/F Highset 1 Setting earth fault highset 1 pick-up OFF
Gn E/F Highset 1 Delay earth fault highset 1 delay
Gn E/F Highset 2 Setting earth fault highset 2 pick-up OFF
Gn E/F Highset 2 Delay earth fault highset 2 delay
Gn CB Fail Time Delay 1 1st time delay for CB Fail OFF
Gn CB Fail Time Delay2 2nd time delay for CB Fail OFF
Gn P/F CB Fail Setting sets over current CB Fail level OFF
Gn E/F CB Fail Setting sets earth fault current CB Fail level OFF
Gn CT Failure Setting sets CT Failure level OFF
Gn CT Failure Delay sets delay for CT Failure 1s
Gn Relay Reset Delay OC reset characteristic INST
O/P RELAY CONFIG MENU ONLY
Gn Prot. Healthy RL1
Gn P/F Diff. RL4

5 Broadgate Protective Device Settings HVSB-1XX02 Rev 4 21 of 21 CB21 SOLKOR


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 22 Circuit H11 TX-1XX04


Device SEPAM T81
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 200/100/1A on 200A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 125A Is = 25A
50N/51N - 1 Trip CB P T = 400ms T = 120ms
Group A ON Curve = IEC EIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 3000A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group A ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 125A Is = 25A
50N/51N - 1 Trip CB P T = 140ms T = 100ms
Group B ON Curve = IEC SIT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 3000A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group B ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
49RMS Thermal Overload
64 REF Restricted Earth Fault
67N Directional Earth Fault
32P Active Power
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
81R Rate of change of frequency
38/49T Temperature Monitoring
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-1XX02 Rev 4 19 of 21 CB 22


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 23 Circuit H12 TX-1XX03


Device SEPAM T81
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 600/300/1A on 300A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching  Is = 200A Is = 40A
50N/51N - 1 Trip CB  T = 400ms T = 120ms
Group A ON Curve = IEC EIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching  Is = 3800A
50N/51N - 2 Trip CB  T = 0ms
SWITCHED OFF
Group A ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching  Is = 200A Is = 40A
50N/51N - 1 Trip CB  T = 140ms T = 100ms
Group B ON Curve = IEC SIT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching  Is = 3800A
50N/51N - 2 Trip CB  T = 0ms
SWITCHED OFF
Group B ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
49RMS Thermal Overload
64 REF Restricted Earth Fault
67N Directional Earth Fault
32P Active Power
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
81R Rate of change of frequency
38/49T Temperature Monitoring
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-1XX02 Rev 4 1 of 1 CB 23


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 24 Circuit H13 TX-1XX02


Device SEPAM T81
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 200/100/1A on 200A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 60A Is = 20A
50N/51N - 1 Trip CB P T = 400ms T = 120ms
Group A ON Curve = IEC EIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 2000A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group A OFF Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 60A Is = 20A
50N/51N - 1 Trip CB P T = 140ms T = 100ms
Group B ON Curve = IEC SIT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 2000A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group B OFF Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
49RMS Thermal Overload
64 REF Restricted Earth Fault
67N Directional Earth Fault
32P Active Power
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
81R Rate of change of frequency
38/49T Temperature Monitoring
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-1XX02 Rev 4 16 of 21 CB 24


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV INCOMER, CB 25 Circuit H2


Device SEPAM S81
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 1250/800/1A on 1250A range
Logic Discrimination ON 200ms
MES 120 I/O Card I103 Blocking Reception 1 from CB 20, CB 21
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 945A Is = 200A
50N/51N - 1 Trip CB P T = 670ms T = 800ms
Group A ON Curve = IEC SIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P
SWITCHED OFF SWITCHED OFF
Group A OFF
2nd Harmonic Restraint
50/51 - 3 Latching P Is = 945A Is = 200A
50N/51N - 3 Trip CB P T = 920ms T = 1050ms
Group A ON Curve = IEC SIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - Elements 4~8
50N/51N - Elements 4~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 945A Is = 200A
50N/51N - 1 Trip CB P T = 670ms T = 800ms
Group B ON Curve = IEC SIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P
SWITCHED OFF SWITCHED OFF
Group B OFF
2nd Harmonic Restraint
50/51 - 3 Latching P Is = 945A Is = 200A
50N/51N - 3 Trip CB P T = 920ms T = 1050ms
Group B ON Curve = IEC SIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - Elements 4~8
50N/51N - Elements 4~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50BF Breaker Failure
50BF - 1 Latching P Is = 1.25kA
Trip CB P T = 130ms
46 negative sequence / unbalance
49RMS Thermal Overload
67N Direction Earth Fault
32P Active Power
27D Positive sequence undercurrent
27R Remnant undervoltage
To align with Generator Operation Philosophy & Initiate Change Over?
27 Under voltage
If not OFF
(Phase to Phase & Phase to Neutral) Tripping Curve = DT
Unit 1 & 2 ON P Mode = Phase to Phase
Unit 3 & 4 OFF Voltage = 80%, Delay = 2s
To align with Generator Operation Philosophy & Initiate Change Over?
59 overvoltage
If not OFF
(Phase to Phase & Phase to Neutral) Mode = Phase to Phase
Unit 1 & 2 ON P Voltage = 110%
Unit 3 & 4 OFF Delay = 2s
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
To align with Generator Operation Philosophy & Initiate Change Over?
81H over frequency
If not OFF
Unit 1 ON P Threshold = 52Hz
Unit 2 OFF Delay = 200ms
To align with Generator Operation Philosophy & Initiate Change Over?
81L under frequency
If not OFF
Unit 1 ON Threshold = 48Hz
Unit 2 OFF Delay = 200ms
79 Re-closer
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-1XX02 Rev 4 1 of 21 CB 25


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 26 Circuit H14 TX-1XX01


Device SEPAM T81
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 600/300/1A on 300A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 250A Is = 50A
50N/51N - 1 Trip CB P T = 400ms T = 120ms
Group A ON Curve = IEC EIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 4200A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group A ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 250A Is = 50A
50N/51N - 1 Trip CB P T = 120ms T = 100ms
Group B ON Curve = IEC SIT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 4200A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group B ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
49RMS Thermal Overload
64 REF Restricted Earth Fault
67N Directional Earth Fault
32P Active Power
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
81R Rate of change of frequency
38/49T Temperature Monitoring
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-1XX02 Rev 4 17 of 21 CB 26


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 27 Spare Circuit


Device SEPAM T81
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 200/100/1A on 200A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 60A Is = 30A
50N/51N - 1 Trip CB P T = 400ms T = 120ms
Group A ON Curve = IEC EIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 2000A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group A ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 60A Is = 30A
50N/51N - 1 Trip CB P T = 400ms T = 100ms
Group B ON Curve = IEC EIT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 2000A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group B ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group B OFF
46 negative sequence / unbalance
49RMS Thermal Overload
64 REF Restricted Earth Fault
67N Direction Earth Fault
32P Active Power
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
81R Rate of change of frequency
38/49T Temperature Monitoring
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-1XX02 Rev 4 15 of 21 CB 27


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 28 Spare Circuit


Device SEPAM T81
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 200/100/1A on 200A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 60A Is = 30A
50N/51N - 1 Trip CB P T = 400ms T = 120ms
Group A ON Curve = IEC EIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 2000A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group A ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 60A Is = 30A
50N/51N - 1 Trip CB P T = 400ms T = 100ms
Group B ON Curve = IEC EIT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 2000A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group B ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group B OFF
46 negative sequence / unbalance
49RMS Thermal Overload
64 REF Restricted Earth Fault
67N Direction Earth Fault
32P Active Power
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
81R Rate of change of frequency
38/49T Temperature Monitoring
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-1XX02 Rev 4 14 of 21 CB 28


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV INCOMER, CB 29 Circuit H21


Device SEPAM S80
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 1250/800/1A on 800A range
Logic Discrimination ON 200ms
MES 120 I/O Card I103 Blocking Reception 1 from CB 20, CB 21
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 800A Is = 80A
50N/51N - 1 Trip CB P T = 220ms T = 700ms
Group A ON Curve = IEC SIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P
SWITCHED OFF SWITCHED OFF
Group A OFF
2nd Harmonic Restraint
50/51 - 3 Latching P Is = 800A Is = 80A
50N/51N - 3 Trip CB P T = 220ms T = 700ms
Group A ON Curve = IEC SIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - Elements 4~8
50N/51N - Elements 4~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 780A Is = 95A
50N/51N - 1 Trip CB P T = 2000ms T = 620ms
Group B ON Curve = DT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P
SWITCHED OFF SWITCHED OFF
Group B OFF
2nd Harmonic Restraint
50/51 - 3 Latching P Is = 780A Is = 95A
50N/51N - 3 Trip CB P T = 2250ms T = 870ms
Group B ON Curve = DT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - Elements 4~8
50N/51N - Elements 4~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
79 Re-closer
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-1XX02 Rev 4 12 of 21 CB 29


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 29 Circuit H21


Device SOLKOR 7SG18 N
Select
CT Ratio 1000/1A on 1000A Range
SETTINGS GROUP G MENU ONLY
SCREEN FUNCTION MENU ENTRY
Active Settings Group Group that the relay will act upon G1
Settings Group Edit/View Group to be displayed on the LCD G1
Local P/F Rating Local relay’s phase fault CT rating 1A
Local E/F Rating Local relay’s earth fault CT rating 1A
Local P/F CT Ratio relay’s phase input CT ratio 1000:1
Local E/F CT Ratio relay’s earth input CT ratio 1000:1
Remote P/F Rating Remote relay’s phase fault CT rating 1A
Remote P/F CT Ratio Remote relay’s earth fault CT rating 1000:1
Current Display display mode to use for the relay xIn
Set Identifier 16 character alphanumeric code CB29 SOLKOR
Set Alarm 1 ALARM 1
Calendar – Set Date DD/MM/YY Todays Date
Clock - Set Time HH:MM:SS Actual Time
Clock Sync. From Status Seconds or Minutes Minutes
Default Screen Timer 10sec, 60sec, 5min, 1hour 5 min
Change Password 4 alphanumeric characters NONE

DIFF' PROTECTION MENU ONLY


SCREEN FUNCTION MENU ENTRY
Gn P/F Diff. Setting* setting for the differential element 0.3 x In
Gn P/F Bias Slope 1* 1st bias slope differential element 30%
Gn P/F Bias Slope 2* 2nd bias slope differential element 150%
Gn Bias Break Point* bias slope break point 1 to 2 2.00 x In
Gn Differential Delay trip time differential element/ intertrip 0.0s
P/F CT Ratio Correction CT ratio correction 1
Remote P/F Ratio Correction CT ratio correction 1
Gn Internal Intertrip enables / disables internal intertrips OFF
Gn Int Intertrip Delay internal intertrip elements 0.00s
Gn External Intertrip enables / disables external intertrips ON
Gn Ext Intertrip Delay external intertrip elements 0.00s

O/C PROTECTION MENU ONLY


SCREEN FUNCTION MENU ENTRY
Gn P/F Charact. Setting phase fault O/C pick-up level OFF
Gn P/F Charact. phase fault O/C characteristic
Gn P/F Charact. Time Mult phase fault TMS
Gn P/F Charact. Delay phase fault delay DTL
Gn P/F Lowset Setting phase fault lowset pick-up OFF
Gn P/F Lowset Delay phase fault lowset delay
Gn P/F Highset1 Setting phase fault highset 1 pick-up OFF
Gn P/F Highset1 Delay phase fault highset 1 delay
Gn P/F Highset2 Setting phase fault highset 2 pick-up OFF
Gn P/F Highset2 Delay phase fault highset 2 delay
Gn E/F Charact. Setting earth fault O/C pick-up level OFF
Gn E/F Charact. earth fault O/C characteristic
Gn E/F Charact. Time Mult earth fault TMS
Gn E/F Charact. Delay earth fault delay DTL
Gn E/F Lowset Setting earth fault lowset pick-up OFF
Gn E/F Lowset Delay earth fault lowset delay
Gn E/F Highset 1 Setting earth fault highset 1 pick-up OFF
Gn E/F Highset 1 Delay earth fault highset 1 delay
Gn E/F Highset 2 Setting earth fault highset 2 pick-up OFF
Gn E/F Highset 2 Delay earth fault highset 2 delay
Gn CB Fail Time Delay 1 1st time delay for CB Fail OFF
Gn CB Fail Time Delay2 2nd time delay for CB Fail OFF
Gn P/F CB Fail Setting sets over current CB Fail level OFF
Gn E/F CB Fail Setting sets earth fault current CB Fail level OFF
Gn CT Failure Setting sets CT Failure level OFF
Gn CT Failure Delay sets delay for CT Failure 1s
Gn Relay Reset Delay OC reset characteristic INST
O/P RELAY CONFIG MENU ONLY
Gn Prot. Healthy RL1
Gn P/F Diff. RL4

5 Broadgate Protective Device Settings HVSB-1XX02 Rev 4 13 of 21 CB29 SOLKOR


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 30 Spare Circuit


Device SEPAM T81
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 200/100/1A on 200A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 60A Is = 30A
50N/51N - 1 Trip CB P T = 400ms T = 120ms
Group A ON Curve = IEC EIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 2000A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group A ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 60A Is = 30A
50N/51N - 1 Trip CB P T = 400ms T = 100ms
Group B ON Curve = IEC EIT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 2000A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group B ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group B OFF
46 negative sequence / unbalance
49RMS Thermal Overload
64 REF Restricted Earth Fault
67N Direction Earth Fault
32P Active Power
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
81R Rate of change of frequency
38/49T Temperature Monitoring
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-1XX02 Rev 4 11 of 21 CB 30


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 31 Spare Circuit


Device SEPAM T81
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 200/100/1A on 200A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 60A Is = 30A
50N/51N - 1 Trip CB P T = 400ms T = 120ms
Group A ON Curve = IEC EIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 2000A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group A ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 60A Is = 30A
50N/51N - 1 Trip CB P T = 400ms T = 100ms
Group B ON Curve = IEC EIT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 2000A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group B ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group B OFF
46 negative sequence / unbalance
49RMS Thermal Overload
64 REF Restricted Earth Fault
67N Direction Earth Fault
32P Active Power
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
81R Rate of change of frequency
38/49T Temperature Monitoring
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-1XX02 Rev 4 10 of 21 CB 31


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV INCOMER, CB 32 Circuit H22


Device SEPAM S80
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 1250/800/1A on 800A range
Logic Discrimination ON 200ms
MES 120 I/O Card I103 Blocking Reception 1 from CB 20, CB 21
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 800A Is = 80A
50N/51N - 1 Trip CB P T = 220ms T = 700ms
Group A ON Curve = IEC SIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P
SWITCHED OFF SWITCHED OFF
Group A OFF
2nd Harmonic Restraint
50/51 - 3 Latching P Is = 800A Is = 80A
50N/51N - 3 Trip CB P T = 220ms T = 700ms
Group A ON Curve = IEC SIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - Elements 4~8
50N/51N - Elements 4~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 780A Is = 95A
50N/51N - 1 Trip CB P T = 2000ms T = 620ms
Group B ON Curve = DT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P
SWITCHED OFF SWITCHED OFF
Group B OFF
2nd Harmonic Restraint
50/51 - 3 Latching P Is = 780A Is = 95A
50N/51N - 3 Trip CB P T = 2250ms T = 870ms
Group B ON Curve = DT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - Elements 4~8
50N/51N - Elements 4~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
79 Re-closer
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-1XX02 Rev 4 8 of 21 CB 32


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 32 Circuit H22


Device SOLKOR 7SG18 N
Select
CT Ratio 1000/1A on 1000A Range
SETTINGS GROUP G MENU ONLY
SCREEN FUNCTION MENU ENTRY
Active Settings Group Group that the relay will act upon G1
Settings Group Edit/View Group to be displayed on the LCD G1
Local P/F Rating Local relay’s phase fault CT rating 1A
Local E/F Rating Local relay’s earth fault CT rating 1A
Local P/F CT Ratio relay’s phase input CT ratio 1000:1
Local E/F CT Ratio relay’s earth input CT ratio 1000:1
Remote P/F Rating Remote relay’s phase fault CT rating 1A
Remote P/F CT Ratio Remote relay’s earth fault CT rating 1000:1
Current Display display mode to use for the relay xIn
Set Identifier 16 character alphanumeric code CB32 SOLKOR
Set Alarm 1 ALARM 1
Calendar – Set Date DD/MM/YY Todays Date
Clock - Set Time HH:MM:SS Actual Time
Clock Sync. From Status Seconds or Minutes Minutes
Default Screen Timer 10sec, 60sec, 5min, 1hour 5 min
Change Password 4 alphanumeric characters NONE

DIFF' PROTECTION MENU ONLY


SCREEN FUNCTION MENU ENTRY
Gn P/F Diff. Setting* setting for the differential element 0.3 x In
Gn P/F Bias Slope 1* 1st bias slope differential element 30%
Gn P/F Bias Slope 2* 2nd bias slope differential element 150%
Gn Bias Break Point* bias slope break point 1 to 2 2.00 x In
Gn Differential Delay trip time differential element/ intertrip 0.0s
P/F CT Ratio Correction CT ratio correction 1
Remote P/F Ratio Correction CT ratio correction 1
Gn Internal Intertrip enables / disables internal intertrips OFF
Gn Int Intertrip Delay internal intertrip elements 0.00s
Gn External Intertrip enables / disables external intertrips ON
Gn Ext Intertrip Delay external intertrip elements 0.00s

O/C PROTECTION MENU ONLY


SCREEN FUNCTION MENU ENTRY
Gn P/F Charact. Setting phase fault O/C pick-up level OFF
Gn P/F Charact. phase fault O/C characteristic
Gn P/F Charact. Time Mult phase fault TMS
Gn P/F Charact. Delay phase fault delay DTL
Gn P/F Lowset Setting phase fault lowset pick-up OFF
Gn P/F Lowset Delay phase fault lowset delay
Gn P/F Highset1 Setting phase fault highset 1 pick-up OFF
Gn P/F Highset1 Delay phase fault highset 1 delay
Gn P/F Highset2 Setting phase fault highset 2 pick-up OFF
Gn P/F Highset2 Delay phase fault highset 2 delay
Gn E/F Charact. Setting earth fault O/C pick-up level OFF
Gn E/F Charact. earth fault O/C characteristic
Gn E/F Charact. Time Mult earth fault TMS
Gn E/F Charact. Delay earth fault delay DTL
Gn E/F Lowset Setting earth fault lowset pick-up OFF
Gn E/F Lowset Delay earth fault lowset delay
Gn E/F Highset 1 Setting earth fault highset 1 pick-up OFF
Gn E/F Highset 1 Delay earth fault highset 1 delay
Gn E/F Highset 2 Setting earth fault highset 2 pick-up OFF
Gn E/F Highset 2 Delay earth fault highset 2 delay
Gn CB Fail Time Delay 1 1st time delay for CB Fail OFF
Gn CB Fail Time Delay2 2nd time delay for CB Fail OFF
Gn P/F CB Fail Setting sets over current CB Fail level OFF
Gn E/F CB Fail Setting sets earth fault current CB Fail level OFF
Gn CT Failure Setting sets CT Failure level OFF
Gn CT Failure Delay sets delay for CT Failure 1s
Gn Relay Reset Delay OC reset characteristic INST
O/P RELAY CONFIG MENU ONLY
Gn Prot. Healthy RL1
Gn P/F Diff. RL4

5 Broadgate Protective Device Settings HVSB-1XX02 Rev 4 9 of 21 CB32 SOLKOR


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 33 Spare Circuit


Device SEPAM T81
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 200/100/1A on 200A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 60A Is = 30A
50N/51N - 1 Trip CB P T = 400ms T = 120ms
Group A ON Curve = IEC EIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 2000A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group A ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 60A Is = 30A
50N/51N - 1 Trip CB P T = 400ms T = 100ms
Group B ON Curve = IEC EIT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 2000A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group B ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group B OFF
46 negative sequence / unbalance
49RMS Thermal Overload
64 REF Restricted Earth Fault
67N Direction Earth Fault
32P Active Power
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
81R Rate of change of frequency
38/49T Temperature Monitoring
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-1XX02 Rev 4 7 of 21 CB 33


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 34 Spare Circuit


Device SEPAM T81
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 200/100/1A on 200A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 60A Is = 30A
50N/51N - 1 Trip CB P T = 400ms T = 120ms
Group A ON Curve = IEC EIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 2000A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group A ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 60A Is = 30A
50N/51N - 1 Trip CB P T = 400ms T = 100ms
Group B ON Curve = IEC EIT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 2000A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group B ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group B OFF
46 negative sequence / unbalance
49RMS Thermal Overload
64 REF Restricted Earth Fault
67N Direction Earth Fault
32P Active Power
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
81R Rate of change of frequency
38/49T Temperature Monitoring
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-1XX02 Rev 4 6 of 21 CB 34


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 35 Spare Circuit


Device SEPAM T81
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 200/100/1A on 200A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 60A Is = 30A
50N/51N - 1 Trip CB P T = 400ms T = 120ms
Group A ON Curve = IEC EIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 2000A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group A ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 60A Is = 30A
50N/51N - 1 Trip CB P T = 140ms T = 100ms
Group B ON Curve = IEC SIT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 2000A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group B ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
49RMS Thermal Overload
64 REF Restricted Earth Fault
67N Directional Earth Fault
32P Active Power
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
81R Rate of change of frequency
38/49T Temperature Monitoring
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-1XX02 Rev 4 5 of 21 CB 35


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 36 Circuit H6


Device SEPAM S80
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 1250/800/1A on 800A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching  Is = 800A Is = 80A
50N/51N - 1 Trip CB  T = 450ms T = 710ms
Group A ON Curve = IEC SIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching 
50N/51N - 2 Trip CB 
SWITCHED OFF SWITCHED OFF
Group A OFF
2nd Harmonic Restraint
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching  Is = 700A Is = 80A
50N/51N - 1 Trip CB  T = 600ms T = 370ms
Group B ON Curve = RI Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching 
50N/51N - 2 Trip CB 
SWITCHED OFF SWITCHED OFF
Group B OFF
2nd Harmonic Restraint
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
79 Re-closer
25 Synchro Check

Copy of 5 Broadgate Protective Device Settings HVSB-1XX02 Rev 4 1 of 1 CB 36


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 36 Circuit H6


Device SOLKOR 7SG18 N
Select
CT Ratio 1000/1A on 1000A Range
SETTINGS GROUP G MENU ONLY
SCREEN FUNCTION MENU ENTRY
Active Settings Group Group that the relay will act upon G1
Settings Group Edit/View Group to be displayed on the LCD G1
Local P/F Rating Local relay’s phase fault CT rating 1A
Local E/F Rating Local relay’s earth fault CT rating 1A
Local P/F CT Ratio relay’s phase input CT ratio 1000:1
Local E/F CT Ratio relay’s earth input CT ratio 1000:1
Remote P/F Rating Remote relay’s phase fault CT rating 1A
Remote P/F CT Ratio Remote relay’s earth fault CT rating 1000:1
Current Display display mode to use for the relay xIn
Set Identifier 16 character alphanumeric code CB36 SOLKOR
Set Alarm 1 ALARM 1
Calendar – Set Date DD/MM/YY Todays Date
Clock - Set Time HH:MM:SS Actual Time
Clock Sync. From Status Seconds or Minutes Minutes
Default Screen Timer 10sec, 60sec, 5min, 1hour 5 min
Change Password 4 alphanumeric characters NONE

DIFF' PROTECTION MENU ONLY


SCREEN FUNCTION MENU ENTRY
Gn P/F Diff. Setting* setting for the differential element 0.3 x In
Gn P/F Bias Slope 1* 1st bias slope differential element 30%
Gn P/F Bias Slope 2* 2nd bias slope differential element 150%
Gn Bias Break Point* bias slope break point 1 to 2 2.00 x In
Gn Differential Delay trip time differential element/ intertrip 0.0s
P/F CT Ratio Correction CT ratio correction 1
Remote P/F Ratio Correction CT ratio correction 1
Gn Internal Intertrip enables / disables internal intertrips OFF
Gn Int Intertrip Delay internal intertrip elements 0.00s
Gn External Intertrip enables / disables external intertrips ON
Gn Ext Intertrip Delay external intertrip elements 0.00s

O/C PROTECTION MENU ONLY


SCREEN FUNCTION MENU ENTRY
Gn P/F Charact. Setting phase fault O/C pick-up level OFF
Gn P/F Charact. phase fault O/C characteristic
Gn P/F Charact. Time Mult phase fault TMS
Gn P/F Charact. Delay phase fault delay DTL
Gn P/F Lowset Setting phase fault lowset pick-up OFF
Gn P/F Lowset Delay phase fault lowset delay
Gn P/F Highset1 Setting phase fault highset 1 pick-up OFF
Gn P/F Highset1 Delay phase fault highset 1 delay
Gn P/F Highset2 Setting phase fault highset 2 pick-up OFF
Gn P/F Highset2 Delay phase fault highset 2 delay
Gn E/F Charact. Setting earth fault O/C pick-up level OFF
Gn E/F Charact. earth fault O/C characteristic
Gn E/F Charact. Time Mult earth fault TMS
Gn E/F Charact. Delay earth fault delay DTL
Gn E/F Lowset Setting earth fault lowset pick-up OFF
Gn E/F Lowset Delay earth fault lowset delay
Gn E/F Highset 1 Setting earth fault highset 1 pick-up OFF
Gn E/F Highset 1 Delay earth fault highset 1 delay
Gn E/F Highset 2 Setting earth fault highset 2 pick-up OFF
Gn E/F Highset 2 Delay earth fault highset 2 delay
Gn CB Fail Time Delay 1 1st time delay for CB Fail OFF
Gn CB Fail Time Delay2 2nd time delay for CB Fail OFF
Gn P/F CB Fail Setting sets over current CB Fail level OFF
Gn E/F CB Fail Setting sets earth fault current CB Fail level OFF
Gn CT Failure Setting sets CT Failure level OFF
Gn CT Failure Delay sets delay for CT Failure 1s
Gn Relay Reset Delay OC reset characteristic INST
O/P RELAY CONFIG MENU ONLY
Gn Prot. Healthy RL1
Gn P/F Diff. RL4

5 Broadgate Protective Device Settings HVSB-1XX02 Rev 4 4 of 21 CB36 SOLKOR


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 37 Spare Circuit


Device SEPAM T81
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 200/100/1A on 200A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 60A Is = 30A
50N/51N - 1 Trip CB P T = 400ms T = 120ms
Group A ON Curve = IEC EIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 2000A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group A ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 60A Is = 30A
50N/51N - 1 Trip CB P T = 140ms T = 100ms
Group B ON Curve = IEC SIT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 2000A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group B ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
49RMS Thermal Overload
64 REF Restricted Earth Fault
67N Directional Earth Fault
32P Active Power
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
81R Rate of change of frequency
38/49T Temperature Monitoring
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-1XX02 Rev 4 2 of 21 CB 37


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV INCOMER, CB 38 Circuit H4


Device SEPAM S80
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 1250/800/1A on 800A range
Logic Discrimination ON 200ms
MES 120 I/O Card I103 Blocking Reception 1 from CB 42,43
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 800A Is = 80A
50N/51N - 1 Trip CB P T = 450ms T = 710ms
Group A ON Curve = IEC SIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P
SWITCHED OFF SWITCHED OFF
Group A OFF
2nd Harmonic Restraint
50/51 - 3 Latching P Is = 800A Is = 80A
50N/51N - 3 Trip CB P T = 700ms T = 960ms
Group A ON Curve = IEC SIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - Elements 4~8
50N/51N - Elements 4~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 700A Is = 80A
50N/51N - 1 Trip CB P T = 600ms T = 370ms
Group B ON Curve = RI Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P
SWITCHED OFF SWITCHED OFF
Group B OFF
2nd Harmonic Restraint
50/51 - 3 Latching P Is = 700A Is = 80A
50N/51N - 3 Trip CB P T = 850ms T = 610ms
Group B ON Curve = RI Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - Elements 4~8
50N/51N - Elements 4~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
79 Re-closer
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-13XX01 Rev 4 2 of 7 CB38


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 38 Circuit H4


Device SOLKOR 7SG18 N
Select
CT Ratio 1000/1A on 1000A Range
SETTINGS GROUP G MENU ONLY
SCREEN FUNCTION MENU ENTRY
Active Settings Group Group that the relay will act upon G1
Settings Group Edit/View Group to be displayed on the LCD G1
Local P/F Rating Local relay’s phase fault CT rating 1A
Local E/F Rating Local relay’s earth fault CT rating 1A
Local P/F CT Ratio relay’s phase input CT ratio 1000:1
Local E/F CT Ratio relay’s earth input CT ratio 1000:1
Remote P/F Rating Remote relay’s phase fault CT rating 1A
Remote P/F CT Ratio Remote relay’s earth fault CT rating 1000:1
Current Display display mode to use for the relay xIn
Set Identifier 16 character alphanumeric code CB38 SOLKOR
Set Alarm 1 ALARM 1
Calendar – Set Date DD/MM/YY Todays Date
Clock - Set Time HH:MM:SS Actual Time
Clock Sync. From Status Seconds or Minutes Minutes
Default Screen Timer 10sec, 60sec, 5min, 1hour 5 min
Change Password 4 alphanumeric characters NONE

DIFF' PROTECTION MENU ONLY


SCREEN FUNCTION MENU ENTRY
Gn P/F Diff. Setting* setting for the differential element 0.3 x In
Gn P/F Bias Slope 1* 1st bias slope differential element 30%
Gn P/F Bias Slope 2* 2nd bias slope differential element 150%
Gn Bias Break Point* bias slope break point 1 to 2 2.00 x In
Gn Differential Delay trip time differential element/ intertrip 0.0s
P/F CT Ratio Correction CT ratio correction 1
Remote P/F Ratio Correction CT ratio correction 1
Gn Internal Intertrip enables / disables internal intertrips OFF
Gn Int Intertrip Delay internal intertrip elements 0.00s
Gn External Intertrip enables / disables external intertrips ON
Gn Ext Intertrip Delay external intertrip elements 0.00s

O/C PROTECTION MENU ONLY


SCREEN FUNCTION MENU ENTRY
Gn P/F Charact. Setting phase fault O/C pick-up level OFF
Gn P/F Charact. phase fault O/C characteristic
Gn P/F Charact. Time Mult phase fault TMS
Gn P/F Charact. Delay phase fault delay DTL
Gn P/F Lowset Setting phase fault lowset pick-up OFF
Gn P/F Lowset Delay phase fault lowset delay
Gn P/F Highset1 Setting phase fault highset 1 pick-up OFF
Gn P/F Highset1 Delay phase fault highset 1 delay
Gn P/F Highset2 Setting phase fault highset 2 pick-up OFF
Gn P/F Highset2 Delay phase fault highset 2 delay
Gn E/F Charact. Setting earth fault O/C pick-up level OFF
Gn E/F Charact. earth fault O/C characteristic
Gn E/F Charact. Time Mult earth fault TMS
Gn E/F Charact. Delay earth fault delay DTL
Gn E/F Lowset Setting earth fault lowset pick-up OFF
Gn E/F Lowset Delay earth fault lowset delay
Gn E/F Highset 1 Setting earth fault highset 1 pick-up OFF
Gn E/F Highset 1 Delay earth fault highset 1 delay
Gn E/F Highset 2 Setting earth fault highset 2 pick-up OFF
Gn E/F Highset 2 Delay earth fault highset 2 delay
Gn CB Fail Time Delay 1 1st time delay for CB Fail OFF
Gn CB Fail Time Delay2 2nd time delay for CB Fail OFF
Gn P/F CB Fail Setting sets over current CB Fail level OFF
Gn E/F CB Fail Setting sets earth fault current CB Fail level OFF
Gn CT Failure Setting sets CT Failure level OFF
Gn CT Failure Delay sets delay for CT Failure 1s
Gn Relay Reset Delay OC reset characteristic INST
O/P RELAY CONFIG MENU ONLY
Gn Prot. Healthy RL1
Gn P/F Diff. RL4

5 Broadgate Protective Device Settings HVSB-13XX01 Rev 4 1 of 7 CB38 SOLKOR


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 39 Circuit H15 TX-13XX01


Device SEPAM T81
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 200/100/1A on 200A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 125A Is = 25A
50N/51N - 1 Trip CB P T = 400ms T = 120ms
Group A ON Curve = IEC EIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 3000A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group A ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 125A Is = 10A
50N/51N - 1 Trip CB P T = 140ms T = 110ms
Group B ON Curve = IEC SIT Curve = RI
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 3000A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group B ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
49RMS Thermal Overload
64 REF Restricted Earth Fault
67N Directional Earth Fault
32P Active Power
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
81R Rate of change of frequency
38/49T Temperature Monitoring
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-13XX01 Rev 4 4 of 7 CB 39


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 40 Circuit H16 TX-13XX02


Device SEPAM T81
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 600/300/1A on 300A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 250A Is = 50A
50N/51N - 1 Trip CB P T = 400ms T = 120ms
Group A ON Curve = IEC EIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 4200A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group A ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 250A Is = 10A
50N/51N - 1 Trip CB P T = 120ms T = 110ms
Group B ON Curve = IEC SIT Curve = RI
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 4200A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group B ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
49RMS Thermal Overload
64 REF Restricted Earth Fault
67N Directional Earth Fault
32P Active Power
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
81R Rate of change of frequency
38/49T Temperature Monitoring
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-13XX01 Rev 4 5 of 7 CB 40


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 41 Spare Circuit


Device SEPAM T81
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 600/300/1A on 300A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 60A Is = 30A
50N/51N - 1 Trip CB P T = 400ms T = 120ms
Group A ON Curve = IEC EIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 2000A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group A ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 60A Is = 10A
50N/51N - 1 Trip CB P T = 140ms T = 110ms
Group B ON Curve = IEC SIT Curve = RI
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 2000A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group B ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
49RMS Thermal Overload
64 REF Restricted Earth Fault
67N Directional Earth Fault
32P Active Power
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
81R Rate of change of frequency
38/49T Temperature Monitoring
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-13XX01 Rev 4 3 of 7 CB 41


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 42 Circuit H5


Device SEPAM S80
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 1250/800/1A on 800A range
Logic Discrimination ON 200ms
MES 120 I/O Card Block Out O102:CB 38,47
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 No Latching Is = 2kA Is = 500A
50N/51N - 1 No Trip CB T = 0ms T = 0ms
Group A ON Curve = DT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching 
50N/51N - 2 Trip CB 
SWITCHED OFF SWITCHED OFF
Group A OFF
2nd Harmonic Restraint
50/51 - 3 Latching  Is = 800A Is = 80A
50N/51N - 3 Trip CB  T = 450ms T = 710ms
Group A OFF Curve = IEC SIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - Elements 4~8
50N/51N - Elements 4~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 No Latching Is = 350A Is = 50A
50N/51N - 1 No Trip CB T = 0ms T = 0ms
Group B ON Curve = DT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching 
50N/51N - 2 Trip CB 
SWITCHED OFF SWITCHED OFF
Group B OFF
2nd Harmonic Restraint
50/51 - 3 Latching  Is = 700A Is = 80A
50N/51N - 3 Trip CB  T = 330ms T = 370ms
Group B ON Curve = RI Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - Elements 4~8
50N/51N - Elements 4~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
79 Re-closer
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-13XX01 Rev 4 1 of 1 CB 42


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 42 Circuit H5


Device SOLKOR 7SG18 N
Select
CT Ratio 1000/1A on 1000A Range
SETTINGS GROUP G MENU ONLY
SCREEN FUNCTION MENU ENTRY
Active Settings Group Group that the relay will act upon G1
Settings Group Edit/View Group to be displayed on the LCD G1
Local P/F Rating Local relay’s phase fault CT rating 1A
Local E/F Rating Local relay’s earth fault CT rating 1A
Local P/F CT Ratio relay’s phase input CT ratio 1000:1
Local E/F CT Ratio relay’s earth input CT ratio 1000:1
Remote P/F Rating Remote relay’s phase fault CT rating 1A
Remote P/F CT Ratio Remote relay’s earth fault CT rating 1000:1
Current Display display mode to use for the relay xIn
Set Identifier 16 character alphanumeric code CB42 SOLKOR
Set Alarm 1 ALARM 1
Calendar – Set Date DD/MM/YY Todays Date
Clock - Set Time HH:MM:SS Actual Time
Clock Sync. From Status Seconds or Minutes Minutes
Default Screen Timer 10sec, 60sec, 5min, 1hour 5 min
Change Password 4 alphanumeric characters NONE

DIFF' PROTECTION MENU ONLY


SCREEN FUNCTION MENU ENTRY
Gn P/F Diff. Setting* setting for the differential element 0.3 x In
Gn P/F Bias Slope 1* 1st bias slope differential element 30%
Gn P/F Bias Slope 2* 2nd bias slope differential element 150%
Gn Bias Break Point* bias slope break point 1 to 2 2.00 x In
Gn Differential Delay trip time differential element/ intertrip 0.0s
P/F CT Ratio Correction CT ratio correction 1
Remote P/F Ratio Correction CT ratio correction 1
Gn Internal Intertrip enables / disables internal intertrips OFF
Gn Int Intertrip Delay internal intertrip elements 0.00s
Gn External Intertrip enables / disables external intertrips ON
Gn Ext Intertrip Delay external intertrip elements 0.00s

O/C PROTECTION MENU ONLY


SCREEN FUNCTION MENU ENTRY
Gn P/F Charact. Setting phase fault O/C pick-up level OFF
Gn P/F Charact. phase fault O/C characteristic
Gn P/F Charact. Time Mult phase fault TMS
Gn P/F Charact. Delay phase fault delay DTL
Gn P/F Lowset Setting phase fault lowset pick-up OFF
Gn P/F Lowset Delay phase fault lowset delay
Gn P/F Highset1 Setting phase fault highset 1 pick-up OFF
Gn P/F Highset1 Delay phase fault highset 1 delay
Gn P/F Highset2 Setting phase fault highset 2 pick-up OFF
Gn P/F Highset2 Delay phase fault highset 2 delay
Gn E/F Charact. Setting earth fault O/C pick-up level OFF
Gn E/F Charact. earth fault O/C characteristic
Gn E/F Charact. Time Mult earth fault TMS
Gn E/F Charact. Delay earth fault delay DTL
Gn E/F Lowset Setting earth fault lowset pick-up OFF
Gn E/F Lowset Delay earth fault lowset delay
Gn E/F Highset 1 Setting earth fault highset 1 pick-up OFF
Gn E/F Highset 1 Delay earth fault highset 1 delay
Gn E/F Highset 2 Setting earth fault highset 2 pick-up OFF
Gn E/F Highset 2 Delay earth fault highset 2 delay
Gn CB Fail Time Delay 1 1st time delay for CB Fail OFF
Gn CB Fail Time Delay2 2nd time delay for CB Fail OFF
Gn P/F CB Fail Setting sets over current CB Fail level OFF
Gn E/F CB Fail Setting sets earth fault current CB Fail level OFF
Gn CT Failure Setting sets CT Failure level OFF
Gn CT Failure Delay sets delay for CT Failure 1s
Gn Relay Reset Delay OC reset characteristic INST
O/P RELAY CONFIG MENU ONLY
Gn Prot. Healthy RL1
Gn P/F Diff. RL4

5 Broadgate Protective Device Settings HVSB-13XX01 Rev 4 7 of 7 CB42 SOLKOR


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 43 Circuit H5


Device SEPAM S80
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 1250/800/1A on 800A range
Logic Discrimination ON 200ms
MES 120 I/O Card Block Out O102:CB 25,29,32 O103: CB16,9,12
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 No Latching Is = 2kA Is = 500A
50N/51N - 1 No Trip CB T = 0ms T = 0ms
Group A ON Curve = DT Curve = DT
2nd Harmonic Restraint OFF
50/51 - 2 Latching P
50N/51N - 2 Trip CB P
SWITCHED OFF SWITCHED OFF
Group A OFF
2nd Harmonic Restraint
50/51 - 3 Latching P Is = 800A Is = 80A
50N/51N - 3 Trip CB P T = 450ms T = 710ms
Group A ON Curve = IEC SIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - Elements 4~8
50N/51N - Elements 4~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 No Latching Is = 350A Is = 40A
50N/51N - 1 No Trip CB T = 0ms T = 0ms
Group B ON Curve = DT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P
SWITCHED OFF SWITCHED OFF
Group B OFF
2nd Harmonic Restraint
50/51 - 3 Latching P Is = 700A Is = 80A
50N/51N - 3 Trip CB P T = 330ms T = 370ms
Group B ON Curve = RI Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - Elements 4~8
50N/51N - Elements 4~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
79 Re-closer
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-13XX02 Rev 4 6 of 7 CB 43


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 43 Circuit H5


Device SOLKOR 7SG18 N
Select
CT Ratio 1000/1A on 1000A Range
SETTINGS GROUP G MENU ONLY
SCREEN FUNCTION MENU ENTRY
Active Settings Group Group that the relay will act upon G1
Settings Group Edit/View Group to be displayed on the LCD G1
Local P/F Rating Local relay’s phase fault CT rating 1A
Local E/F Rating Local relay’s earth fault CT rating 1A
Local P/F CT Ratio relay’s phase input CT ratio 1000:1
Local E/F CT Ratio relay’s earth input CT ratio 1000:1
Remote P/F Rating Remote relay’s phase fault CT rating 1A
Remote P/F CT Ratio Remote relay’s earth fault CT rating 1000:1
Current Display display mode to use for the relay xIn
Set Identifier 16 character alphanumeric code CB43 SOLKOR
Set Alarm 1 ALARM 1
Calendar – Set Date DD/MM/YY Todays Date
Clock - Set Time HH:MM:SS Actual Time
Clock Sync. From Status Seconds or Minutes Minutes
Default Screen Timer 10sec, 60sec, 5min, 1hour 5 min
Change Password 4 alphanumeric characters NONE

DIFF' PROTECTION MENU ONLY


SCREEN FUNCTION MENU ENTRY
Gn P/F Diff. Setting* setting for the differential element 0.3 x In
Gn P/F Bias Slope 1* 1st bias slope differential element 30%
Gn P/F Bias Slope 2* 2nd bias slope differential element 150%
Gn Bias Break Point* bias slope break point 1 to 2 2.00 x In
Gn Differential Delay trip time differential element/ intertrip 0.0s
P/F CT Ratio Correction CT ratio correction 1
Remote P/F Ratio Correction CT ratio correction 1
Gn Internal Intertrip enables / disables internal intertrips OFF
Gn Int Intertrip Delay internal intertrip elements 0.00s
Gn External Intertrip enables / disables external intertrips ON
Gn Ext Intertrip Delay external intertrip elements 0.00s

O/C PROTECTION MENU ONLY


SCREEN FUNCTION MENU ENTRY
Gn P/F Charact. Setting phase fault O/C pick-up level OFF
Gn P/F Charact. phase fault O/C characteristic
Gn P/F Charact. Time Mult phase fault TMS
Gn P/F Charact. Delay phase fault delay DTL
Gn P/F Lowset Setting phase fault lowset pick-up OFF
Gn P/F Lowset Delay phase fault lowset delay
Gn P/F Highset1 Setting phase fault highset 1 pick-up OFF
Gn P/F Highset1 Delay phase fault highset 1 delay
Gn P/F Highset2 Setting phase fault highset 2 pick-up OFF
Gn P/F Highset2 Delay phase fault highset 2 delay
Gn E/F Charact. Setting earth fault O/C pick-up level OFF
Gn E/F Charact. earth fault O/C characteristic
Gn E/F Charact. Time Mult earth fault TMS
Gn E/F Charact. Delay earth fault delay DTL
Gn E/F Lowset Setting earth fault lowset pick-up OFF
Gn E/F Lowset Delay earth fault lowset delay
Gn E/F Highset1 Setting earth fault highset 1 pick-up OFF
Gn E/F Highset1 Delay earth fault highset 1 delay
Gn E/F Highset 2 Setting earth fault highset 2 pick-up OFF
Gn E/F Highset 2 Delay earth fault highset 2 delay
Gn CB Fail Time Delay 1 1st time delay for CB Fail OFF
Gn CB Fail Time Delay2 2nd time delay for CB Fail OFF
Gn P/F CB Fail Setting sets over current CB Fail level OFF
Gn E/F CB Fail Setting sets earth fault current CB Fail level OFF
Gn CT Failure Setting sets CT Failure level OFF
Gn CT Failure Delay sets delay for CT Failure 1s
Gn Relay Reset Delay OC reset characteristic INST
O/P RELAY CONFIG MENU ONLY
Gn Prot. Healthy RL1
Gn P/F Diff. RL4

5 Broadgate Protective Device Settings HVSB-13XX02 Rev 4 7 of 7 CB43 SOLKOR


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 44 Circuit H17 TX-13XX03


Device SEPAM T81
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 600/300/1A on 300A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 250A Is = 50A
50N/51N - 1 Trip CB P T = 400ms T = 120ms
Group A ON Curve = IEC EIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 4200A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group A ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 250A Is = 50A
50N/51N - 1 Trip CB P T = 120ms T = 100ms
Group B ON Curve = IEC SIT Curve = RI
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 4200A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group B ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
49RMS Thermal Overload
64 REF Restricted Earth Fault
67N Directional Earth Fault
32P Active Power
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
81R Rate of change of frequency
38/49T Temperature Monitoring
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-13XX02 Rev 4 5 of 7 CB 44


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 45 Circuit H18 TX-13XX04


Device SEPAM T81
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 200/100/1A on 200A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 125A Is = 25A
50N/51N - 1 Trip CB P T = 400ms T = 120ms
Group A ON Curve = IEC EIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 3000A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group A ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 125A Is = 25A
50N/51N - 1 Trip CB P T = 120ms T = 100ms
Group B ON Curve = IEC SIT Curve = RI
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 3000A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group B ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
49RMS Thermal Overload
64 REF Restricted Earth Fault
67N Directional Earth Fault
32P Active Power
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
81R Rate of change of frequency
38/49T Temperature Monitoring
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-13XX02 Rev 4 4 of 7 CB 45


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 46 Spare Circuit


Device SEPAM T81
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 600/300/1A on 300A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 60A Is = 30A
50N/51N - 1 Trip CB P T = 400ms T = 120ms
Group A ON Curve = IEC EIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 2000A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group A ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 60A Is = 30A
50N/51N - 1 Trip CB P T = 140ms T = 110ms
Group B ON Curve = IEC SIT Curve = RI
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P Is = 2000A
50N/51N - 2 Trip CB P T = 0ms
SWITCHED OFF
Group B ON Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
49RMS Thermal Overload
64 REF Restricted Earth Fault
67N Directional Earth Fault
32P Active Power
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
81R Rate of change of frequency
38/49T Temperature Monitoring
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-13XX02 Rev 4 3 of 7 CB 46


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV INCOMER, CB 47 Circuit H6


Device SEPAM S80
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 1250/800/1A on 800A range
Logic Discrimination ON 200ms
MES 120 I/O Card I103 Blocking Reception 1 from CB 42,43
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 800A Is = 80A
50N/51N - 1 Trip CB P T = 450ms T = 710ms
Group A ON Curve = IEC SIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P
SWITCHED OFF SWITCHED OFF
Group A OFF
2nd Harmonic Restraint
50/51 - 3 Latching P Is = 800A Is = 80A
50N/51N - 3 Trip CB P T = 700ms T = 960ms
Group A ON Curve = IEC SIT Curve = IEC SIT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - Elements 4~8
50N/51N - Elements 4~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 700A Is = 80A
50N/51N - 1 Trip CB P T = 600ms T = 370ms
Group B ON Curve = RI Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P
SWITCHED OFF SWITCHED OFF
Group B OFF
2nd Harmonic Restraint
50/51 - 3 Latching P Is = 700A Is = 80A
50N/51N - 3 Trip CB P T = 850ms T = 610ms
Group B ON Curve = RI Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 7 kA ON
50/51 - Elements 4~8
50N/51N - Elements 4~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
79 Re-closer
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-13XX02 Rev 4 2 of 7 CB 47


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 47 Circuit H6


Device SOLKOR 7SG18 N
Select
CT Ratio 1000/1A on 1000A Range
SETTINGS GROUP G MENU ONLY
SCREEN FUNCTION MENU ENTRY
Active Settings Group Group that the relay will act upon G1
Settings Group Edit/View Group to be displayed on the LCD G1
Local P/F Rating Local relay’s phase fault CT rating 1A
Local E/F Rating Local relay’s earth fault CT rating 1A
Local P/F CT Ratio relay’s phase input CT ratio 1000:1
Local E/F CT Ratio relay’s earth input CT ratio 1000:1
Remote P/F Rating Remote relay’s phase fault CT rating 1A
Remote P/F CT Ratio Remote relay’s earth fault CT rating 1000:1
Current Display display mode to use for the relay xIn
Set Identifier 16 character alphanumeric code CB47 SOLKOR
Set Alarm 1 ALARM 1
Calendar – Set Date DD/MM/YY Todays Date
Clock - Set Time HH:MM:SS Actual Time
Clock Sync. From Status Seconds or Minutes Minutes
Default Screen Timer 10sec, 60sec, 5min, 1hour 5 min
Change Password 4 alphanumeric characters NONE

DIFF' PROTECTION MENU ONLY


SCREEN FUNCTION MENU ENTRY
Gn P/F Diff. Setting* setting for the differential element 0.3 x In
Gn P/F Bias Slope 1* 1st bias slope differential element 30%
Gn P/F Bias Slope 2* 2nd bias slope differential element 150%
Gn Bias Break Point* bias slope break point 1 to 2 2.00 x In
Gn Differential Delay trip time differential element/ intertrip 0.0s
P/F CT Ratio Correction CT ratio correction 1
Remote P/F Ratio Correction CT ratio correction 1
Gn Internal Intertrip enables / disables internal intertrips OFF
Gn Int Intertrip Delay internal intertrip elements 0.00s
Gn External Intertrip enables / disables external intertrips ON
Gn Ext Intertrip Delay external intertrip elements 0.00s

O/C PROTECTION MENU ONLY


SCREEN FUNCTION MENU ENTRY
Gn P/F Charact. Setting phase fault O/C pick-up level OFF
Gn P/F Charact. phase fault O/C characteristic
Gn P/F Charact. Time Mult phase fault TMS
Gn P/F Charact. Delay phase fault delay DTL
Gn P/F Lowset Setting phase fault lowset pick-up OFF
Gn P/F Lowset Delay phase fault lowset delay
Gn P/F Highset1 Setting phase fault highset 1 pick-up OFF
Gn P/F Highset1 Delay phase fault highset 1 delay
Gn P/F Highset2 Setting phase fault highset 2 pick-up OFF
Gn P/F Highset2 Delay phase fault highset 2 delay
Gn E/F Charact. Setting earth fault O/C pick-up level OFF
Gn E/F Charact. earth fault O/C characteristic
Gn E/F Charact. Time Mult earth fault TMS
Gn E/F Charact. Delay earth fault delay DTL
Gn E/F Lowset Setting earth fault lowset pick-up OFF
Gn E/F Lowset Delay earth fault lowset delay
Gn E/F Highset1 Setting earth fault highset 1 pick-up OFF
Gn E/F Highset1 Delay earth fault highset 1 delay
Gn E/F Highset 2 Setting earth fault highset 2 pick-up OFF
Gn E/F Highset 2 Delay earth fault highset 2 delay
Gn CB Fail Time Delay 1 1st time delay for CB Fail OFF
Gn CB Fail Time Delay2 2nd time delay for CB Fail OFF
Gn P/F CB Fail Setting sets over current CB Fail level OFF
Gn E/F CB Fail Setting sets earth fault current CB Fail level OFF
Gn CT Failure Setting sets CT Failure level OFF
Gn CT Failure Delay sets delay for CT Failure 1s
Gn Relay Reset Delay OC reset characteristic INST
O/P RELAY CONFIG MENU ONLY
Gn Prot. Healthy RL1
Gn P/F Diff. RL4

5 Broadgate Protective Device Settings HVSB-13XX02 Rev 4 1 of 7 CB47 SOLKOR


COMMISSIONING REPORT
AMTECH Protect - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision Created 26/01/2016 18:23:16
Job ID Last Saved 19/02/2016 15:31:07
Engineer
UTILITY Mode EF 5 Broadgate_H1_H7 - Earth Fault Settings
CB 16 Incomer HVSB-1XX01, 1250A, Merlin Gerin MV, Sepam S1000+
Group A Curve IEC SIT Curve DT Curve Curve
Iso 200.0 Iso 999000 Iso Iso
T 0.80 T 1.05 T T

CB 15 Feeder TX-2XX01, 300A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve DT Curve Curve
Iso 50.0 Iso 999000 Iso Iso
T 0.12 T 0.10 T T

LVSB -2XX01, 6300A, Schneider, Masterpact NW63 H1 Micrologic 5.0A standard

19/02/2016 15:31:14 Amtech Protect HV Version 2013.0.0 Page 1 of 3


UTILITY Mode EF 5 Broadgate_H1_H7.prs17
Earth Fault-Time/Current Analysis, Voltage Base: 110000V, 19/02/2016 15:31:22
10000s
1ph EF Ief
115A 1.000kA

1 hour

1000s
CB 16 Incomer HVSB-1XX01
CB 15 Feeder TX-2XX01
LVSB -2XX01

100s

1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
10mA 100mA 1A 10A 100A 1kA 10kA 100kA 1MA

19/02/2016 15:31:14 Amtech Protect HV Version 2013.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
UTILITY Mode EF 5 Broadgate_H1_H7 - Earth Fault Analysis

10MVA Transformer Earth - 110000V


~

CB 16 Incomer HVSB-1XX01 - 1250A@110000V


Merlin Gerin MV - Sepam S1000+
Ief is 1kA, Icu is Unknown

CB 15 Feeder TX-2XX01 - 300A@110000V


Merlin Gerin MV - Sepam S1000+
Ief is 1kA, Icu is Unknown

TX-2XX01 - 110000V/400V, 4000kVA

LVSB -2XX01 - 6300A@400V


Schneider - Masterpact NW63 H1 Micrologic 5.0A standard
Ief is 0kA, Icu is 100kA

No Earth Fault Protection. Overcurrent Protection is Operational.


Ief Exceeds Fault Capacity.

19/02/2016 15:31:14 Amtech Protect HV Version 2013.0.0 Page 3 of 3


COMMISSIONING REPORT
AMTECH Protect - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision Created 26/01/2016 18:23:16
Job ID Last Saved 17/02/2016 19:17:27
Engineer
UTILITY Mode OC 5 Broadgate_H1_H7 rev 1 - Overcurrent Settings
UKPN 1 33kV Feeder, Reyrolle, Argus DCD
ICT 600 Curve NI IHS1 OFF IHS2 OFF ILS1 OFF
Is 1.00 tHS1 0.10 tHS2 0.05 tLS1 0.00
tm 0.300

CB1 33kV Incomer, 600A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve IAC INV Curve Curve
Is 450.0 Is 1000.0 Is Is
T 1.10 T 0.73 T T

CB 2 33kV Feeder, 600A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve DT Curve Curve
Is 380.0 Is 4200.0 Is Is
T 0.82 T 0.05 T T

CB 16 Incomer HVSB-1XX01, 1250A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve DT Curve Curve
Is 945.0 Is 999000 Is Is
T 0.67 T 1.05 T T

CB 15 Feeder TX-2XX01, 300A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC EIT Curve DT Curve Curve
Is 250.0 Is 4200.0 Is Is
T 0.40 T 0.05 T T

Device 1, 6300A, Schneider, Masterpact NW63 H1 Micrologic 5.0A standard


Ir 1.00 Isd 5.00 Iinst OFF
tr 1.0 tsd 0.1

19/02/2016 14:22:01 Amtech Protect HV Version 2013.0.0 Page 1 of 3


UTILITY Mode OC 5 Broadgate_H1_H7 rev 1.prs17
Overcurrent-Time/Current Analysis, Voltage Base: 33000V, 19/02/2016 14:22:33
10000s
Device 1 - 300A@11000V Primary 3ph Pscc Src Pscc
Merlin Gerin MV 210A 2999A 7.800kA 15.8kA
Sepam S1000+

1 hour

1000s
UKPN 1 33kV Feeder
CB1 33kV Incomer
CB 2 33kV Feeder
CB 16 Incomer HVSB-1XX01
CB 15 Feeder TX-2XX01
Device 1

100s

1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

19/02/2016 14:22:01 Amtech Protect HV Version 2013.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
UTILITY Mode OC 5 Broadgate_H1_H7 rev 1 - Overcurrent Analysis

UKPN - 33000V, Pscc is 15.8kA


~

UKPN 1 33kV Feeder - 33000V


Reyrolle - Argus DCD
Pscc is 15kA, Icu is Unknown

CB1 33kV Incomer - 600A@33000V


Merlin Gerin MV - Sepam S1000+
Pscc is 15kA, Icu is Unknown

CB 2 33kV Feeder - 600A@33000V


Merlin Gerin MV - Sepam S1000+
Pscc is 15kA, Icu is Unknown

Transformer 33000/11000 - 33000V/11000V, 18000kVA

CB 16 Incomer HVSB-1XX01 - 1250A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 7.8kA, Icu is Unknown

CB 15 Feeder TX-2XX01 - 300A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 7.8kA, Icu is Unknown

TX-2XX01 - 11000V/400V, 4000kVA

Device 1 - 6300A@400V
Schneider - Masterpact NW63 H1 Micrologic 5.0A standard
Pscc is 56kA, Icu is 100kA

Pscc Exceeds Fault Capacity.

19/02/2016 14:22:01 Amtech Protect HV Version 2013.0.0 Page 3 of 3


COMMISSIONING REPORT
AMTECH Protect - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision Created 26/01/2016 18:23:16
Job ID Last Saved 19/02/2016 15:26:00
Engineer
UTILITY Mode EF 5 Broadgate_H1_H8 - Earth Fault Settings
CB 16 Incomer HVSB-1XX01, 1250A, Merlin Gerin MV, Sepam S1000+
Group A Curve IEC SIT Curve DT Curve Curve
Iso 200.0 Iso 999000 Iso Iso
T 0.80 T 1.05 T T

CB 17 Feeder TX-2XX02, 200A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve DT Curve Curve
Iso 20.0 Iso 999000 Iso Iso
T 0.12 T 1.05 T T

Device 1, 1600A, Schneider, Masterpact NW16 H1 Micrologic 5.0A standard

19/02/2016 15:26:05 Amtech Protect HV Version 2013.0.0 Page 1 of 3


UTILITY Mode EF 5 Broadgate_H1_H8.prs17
Earth Fault-Time/Current Analysis, Voltage Base: 11000V, 19/02/2016 15:26:08
10000s
1ph EF Ief
404A 1.000kA

1 hour

1000s
CB 16 Incomer HVSB-1XX01
CB 17 Feeder TX-2XX02
Device 1

100s

1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
10mA 100mA 1A 10A 100A 1kA 10kA 100kA 1MA

19/02/2016 15:26:05 Amtech Protect HV Version 2013.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
UTILITY Mode EF 5 Broadgate_H1_H8 - Earth Fault Analysis

10MVA Transformer Earth - 11000V


~

CB 16 Incomer HVSB-1XX01 - 1250A@11000V


Merlin Gerin MV - Sepam S1000+
Ief is 1kA, Icu is Unknown

CB 17 Feeder TX-2XX02 - 200A@11000V


Merlin Gerin MV - Sepam S1000+
Ief is 1kA, Icu is Unknown

TX-2XX02 - 11000V/400V, 1000kVA

Device 1 - 1600A@400V
Schneider - Masterpact NW16 H1 Micrologic 5.0A standard
Ief is 0kA, Icu is 65kA

No Earth Fault Protection. Overcurrent Protection is Operational.


Ief Exceeds Fault Capacity.

19/02/2016 15:26:05 Amtech Protect HV Version 2013.0.0 Page 3 of 3


COMMISSIONING REPORT
AMTECH Protect - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision Created 26/01/2016 18:23:16
Job ID Last Saved 19/02/2016 14:26:32
Engineer
UTILITY Mode OC 5 Broadgate_H1_H8 rev 1 - Overcurrent Settings
UKPN 1 33kV Feeder, Reyrolle, Argus DCD
ICT 600 Curve NI IHS1 OFF IHS2 OFF ILS1 OFF
Is 1.00 tHS1 0.10 tHS2 0.05 tLS1 0.00
tm 0.300

CB1 33kV Incomer, 600A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve IAC INV Curve Curve
Is 450.0 Is 1000.0 Is Is
T 1.10 T 0.73 T T

CB 2 33kV Feeder, 600A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve DT Curve Curve
Is 380.0 Is 4200.0 Is Is
T 0.82 T 0.05 T T

CB 16 Incomer HVSB-1XX01, 1250A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve DT Curve Curve
Is 945.0 Is 999000 Is Is
T 0.67 T 1.05 T T

CB 17 Feeder TX-2XX02, 300A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC EIT Curve DT Curve Curve
Is 60.0 Is 2000.0 Is Is
T 0.40 T 0.05 T T

Device 1, 1600A, Schneider, Masterpact NW16 H1 Micrologic 5.0A standard


Ir 1.00 Isd 3.00 Iinst OFF
tr 1.0 tsd 0.1

19/02/2016 14:26:58 Amtech Protect HV Version 2013.0.0 Page 1 of 3


UTILITY Mode OC 5 Broadgate_H1_H8 rev 1.prs17
Overcurrent-Time/Current Analysis, Voltage Base: 33000V, 19/02/2016 14:27:01
10000s
Primary 3ph Pscc Src Pscc
52A 1050A 7.800kA 15.8kA

1 hour

1000s
UKPN 1 33kV Feeder
CB1 33kV Incomer
CB 2 33kV Feeder
CB 16 Incomer HVSB-1XX01
CB 17 Feeder TX-2XX02
Device 1

100s

1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

19/02/2016 14:26:58 Amtech Protect HV Version 2013.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
UTILITY Mode OC 5 Broadgate_H1_H8 rev 1 - Overcurrent Analysis

UKPN - 33000V, Pscc is 15.8kA


~

UKPN 1 33kV Feeder - 33000V


Reyrolle - Argus DCD
Pscc is 15kA, Icu is Unknown

CB1 33kV Incomer - 600A@33000V


Merlin Gerin MV - Sepam S1000+
Pscc is 15kA, Icu is Unknown

CB 2 33kV Feeder - 600A@33000V


Merlin Gerin MV - Sepam S1000+
Pscc is 15kA, Icu is Unknown

Transformer 33000/11000 - 33000V/11000V, 18000kVA

CB 16 Incomer HVSB-1XX01 - 1250A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 7.8kA, Icu is Unknown

CB 17 Feeder TX-2XX02 - 300A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 7.8kA, Icu is Unknown

TX-2XX03 - 11000V/400V, 1000kVA

Device 1 - 1600A@400V
Schneider - Masterpact NW16 H1 Micrologic 5.0A standard
Pscc is 0kA, Icu is 65kA

Pscc Exceeds Fault Capacity.

19/02/2016 14:26:58 Amtech Protect HV Version 2013.0.0 Page 3 of 3


COMMISSIONING REPORT
AMTECH Protect - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision Created 26/01/2016 18:23:16
Job ID Last Saved 15/02/2016 12:06:02
Engineer
UTILITY Mode EF 5 Broadgate_H1_H9 - Earth Fault Settings
CB 16 Incomer HVSB-1XX01, 1250A, Merlin Gerin MV, Sepam S1000+
Group A Curve IEC SIT Curve DT Curve Curve
Iso 200.0 Iso 999000 Iso Iso
T 0.80 T 1.05 T T

CB 18 Feeder TX-2XX03, 300A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve DT Curve Curve
Iso 40.0 Iso 999000 Iso Iso
T 0.12 T 0.10 T T

LVSB-2XX03, 5000A, Schneider, Masterpact NW50 H1 Micrologic 5.0A standard

15/02/2016 12:12:50 Amtech Protect HV Version 2013.0.0 Page 1 of 3


UTILITY Mode EF 5 Broadgate_H1_H9.prs17
Earth Fault-Time/Current Analysis, Voltage Base: 11000V, 15/02/2016 12:12:53
10000s
Ief
18.00kA

1 hour

1000s
CB 16 Incomer HVSB-1XX01
CB 18 Feeder TX-2XX03
LVSB-2XX03

100s

1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
10mA 100mA 1A 10A 100A 1kA 10kA 100kA 1MA

15/02/2016 12:12:50 Amtech Protect HV Version 2013.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
UTILITY Mode EF 5 Broadgate_H1_H9 - Earth Fault Analysis

10MVA Transformer Earth - 11000V


~

CB 16 Incomer HVSB-1XX01 - 1250A@11000V


Merlin Gerin MV - Sepam S1000+
Ief is 1kA, Icu is Unknown

CB 18 Feeder TX-2XX03 - 300A@11000V


Merlin Gerin MV - Sepam S1000+
Ief is 1kA, Icu is Unknown

TX-2XX03 - 11000V/400V, 3150kVA

LVSB-2XX03 - 5000A@400V
Schneider - Masterpact NW50 H1 Micrologic 5.0A standard
Ief is 18kA, Icu is 100kA

No Earth Fault Protection. Overcurrent Protection is Operational.


Ief Exceeds Fault Capacity.

15/02/2016 12:12:50 Amtech Protect HV Version 2013.0.0 Page 3 of 3


COMMISSIONING REPORT
AMTECH Protect - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision Created 26/01/2016 18:23:16
Job ID Last Saved 15/02/2016 11:44:26
Engineer
UTILITY Mode OC 5 Broadgate_H1_H9 - Overcurrent Settings
UKPN 1 33kV Feeder, Reyrolle, Argus DCD
ICT 600 Curve NI IHS1 OFF IHS2 OFF ILS1 OFF
Is 1.00 tHS1 0.10 tHS2 0.05 tLS1 0.00
tm 0.300

CB1 33kV Incomer, 600A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve IAC INV Curve Curve
Is 450.0 Is 1000.0 Is Is
T 1.10 T 0.73 T T

CB 2 33kV Feeder, 600A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve DT Curve Curve
Is 380.0 Is 4200.0 Is Is
T 0.82 T 0.05 T T

CB 16 Incomer HVSB-1XX01, 1250A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve DT Curve Curve
Is 945.0 Is 999000 Is Is
T 0.67 T 1.05 T T

CB 18 Feeder TX-2XX03, 300A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC EIT Curve DT Curve Curve
Is 200.0 Is 3800.0 Is Is
T 0.40 T 0.05 T T

LVSB-2XX03, 5000A, Schneider, Masterpact NW50 H1 Micrologic 5.0A standard


Ir 1.00 Isd 5.00 Iinst OFF
tr 1.0 tsd 0.1

15/02/2016 12:01:16 Amtech Protect HV Version 2013.0.0 Page 1 of 3


UTILITY Mode OC 5 Broadgate_H1_H9.prs17
Overcurrent-Time/Current Analysis, Voltage Base: 33000V, 15/02/2016 12:01:20
10000s
Src Pscc
15.8kA

1 hour

1000s
UKPN 1 33kV Feeder
CB1 33kV Incomer
CB 2 33kV Feeder
CB 16 Incomer HVSB-1XX01
CB 18 Feeder TX-2XX03
LVSB-2XX03

100s

1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

15/02/2016 12:01:16 Amtech Protect HV Version 2013.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
UTILITY Mode OC 5 Broadgate_H1_H9 - Overcurrent Analysis

UKPN - 33000V, Pscc is 15.8kA


~

UKPN 1 33kV Feeder - 33000V


Reyrolle - Argus DCD
Pscc is 15kA, Icu is Unknown

CB1 33kV Incomer - 600A@33000V


Merlin Gerin MV - Sepam S1000+
Pscc is 15kA, Icu is Unknown

CB 2 33kV Feeder - 600A@33000V


Merlin Gerin MV - Sepam S1000+
Pscc is 15kA, Icu is Unknown

Transformer 33000/11000 - 33000V/11000V, 18000kVA

CB 16 Incomer HVSB-1XX01 - 1250A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 7.8kA, Icu is Unknown

CB 18 Feeder TX-2XX03 - 300A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 7.8kA, Icu is Unknown

TX-2XX03 - 11000V/400V, 3150kVA

LVSB-2XX03 - 5000A@400V
Schneider - Masterpact NW50 H1 Micrologic 5.0A standard
Pscc is 46kA, Icu is 100kA

Pscc Exceeds Fault Capacity.

15/02/2016 12:01:16 Amtech Protect HV Version 2013.0.0 Page 3 of 3


COMMISSIONING REPORT
AMTECH Protect - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision Created 26/01/2016 18:23:16
Job ID Last Saved 19/02/2016 15:22:46
Engineer
UTILITY Mode EF 5 Broadgate_H1_H10 - Earth Fault Settings
CB 16 Incomer HVSB-1XX01, 1250A, Merlin Gerin MV, Sepam S1000+
Group A Curve IEC SIT Curve DT Curve Curve
Iso 200.0 Iso 999000 Iso Iso
T 0.80 T 1.05 T T

CB 19 Feeder TX-2XX04, 200A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve DT Curve Curve
Iso 25.0 Iso 999000 Iso Iso
T 0.12 T 1.05 T T

LVSB-2XX04, 3200A, Schneider, Masterpact NW32 H1 Micrologic 5.0A standard

19/02/2016 15:22:52 Amtech Protect HV Version 2013.0.0 Page 1 of 3


UTILITY Mode EF 5 Broadgate_H1_H10.prs17
Earth Fault-Time/Current Analysis, Voltage Base: 11000V, 19/02/2016 15:22:56
10000s
Ief
1.000kA
1ph EF
1 hour 808A

1000s
CB 16 Incomer HVSB-1XX01
CB 19 Feeder TX-2XX04
LVSB-2XX04

100s

1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
10mA 100mA 1A 10A 100A 1kA 10kA 100kA 1MA

19/02/2016 15:22:52 Amtech Protect HV Version 2013.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
UTILITY Mode EF 5 Broadgate_H1_H10 - Earth Fault Analysis

10MVA Transformer Earth - 11000V


~

CB 16 Incomer HVSB-1XX01 - 1250A@11000V


Merlin Gerin MV - Sepam S1000+
Ief is 1kA, Icu is Unknown

CB 19 Feeder TX-2XX04 - 200A@11000V


Merlin Gerin MV - Sepam S1000+
Ief is 1kA, Icu is Unknown

TX-2XX03 - 11000V/400V, 2000kVA

LVSB-2XX04 - 3200A@400V
Schneider - Masterpact NW32 H1 Micrologic 5.0A standard
Ief is 0kA, Icu is 65kA

No Earth Fault Protection. Overcurrent Protection is Operational.


Ief Exceeds Fault Capacity.

19/02/2016 15:22:52 Amtech Protect HV Version 2013.0.0 Page 3 of 3


COMMISSIONING REPORT
AMTECH Protect - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision Created 26/01/2016 18:23:16
Job ID Last Saved 19/02/2016 14:27:55
Engineer
UTILITY Mode OC 5 Broadgate_H1_H10 rev 1 - Overcurrent Settings
UKPN 1 33kV Feeder, Reyrolle, Argus DCD
ICT 600 Curve NI IHS1 OFF IHS2 OFF ILS1 OFF
Is 1.00 tHS1 0.10 tHS2 0.05 tLS1 0.00
tm 0.300

CB1 33kV Incomer, 600A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve IAC INV Curve Curve
Is 450.0 Is 1000.0 Is Is
T 1.10 T 0.73 T T

CB 2 33kV Feeder, 600A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve DT Curve Curve
Is 380.0 Is 4200.0 Is Is
T 0.82 T 0.05 T T

CB 16 Incomer HVSB-1XX01, 1250A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve DT Curve Curve
Is 945.0 Is 999000 Is Is
T 0.67 T 1.05 T T

CB 19 Feeder TX-2XX04, 300A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC EIT Curve DT Curve Curve
Is 125.0 Is 3000.0 Is Is
T 0.40 T 0.05 T T

LVSB-2XX04, 3200A, Schneider, Masterpact NW32 H1 Micrologic 5.0A standard


Ir 1.00 Isd 3.00 Iinst OFF
tr 1.0 tsd 0.1

19/02/2016 14:28:06 Amtech Protect HV Version 2013.0.0 Page 1 of 3


UTILITY Mode OC 5 Broadgate_H1_H10 rev 1.prs17
Overcurrent-Time/Current Analysis, Voltage Base: 33000V, 19/02/2016 14:28:11
10000s
Pscc Src Pscc
43.00kA 15.8kA

1 hour

1000s
UKPN 1 33kV Feeder
CB1 33kV Incomer
CB 2 33kV Feeder
CB 16 Incomer HVSB-1XX01
CB 19 Feeder TX-2XX04
LVSB-2XX04

100s

1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

19/02/2016 14:28:06 Amtech Protect HV Version 2013.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
UTILITY Mode OC 5 Broadgate_H1_H10 rev 1 - Overcurrent Analysis

UKPN - 33000V, Pscc is 15.8kA


~

UKPN 1 33kV Feeder - 33000V


Reyrolle - Argus DCD
Pscc is 15kA, Icu is Unknown

CB1 33kV Incomer - 600A@33000V


Merlin Gerin MV - Sepam S1000+
Pscc is 15kA, Icu is Unknown

CB 2 33kV Feeder - 600A@33000V


Merlin Gerin MV - Sepam S1000+
Pscc is 15kA, Icu is Unknown

Transformer 33000/11000 - 33000V/11000V, 18000kVA

CB 16 Incomer HVSB-1XX01 - 1250A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 7.8kA, Icu is Unknown

CB 19 Feeder TX-2XX04 - 300A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 7.8kA, Icu is Unknown

TX-2XX03 - 11000V/400V, 2000kVA

LVSB-2XX04 - 3200A@400V
Schneider - Masterpact NW32 H1 Micrologic 5.0A standard
Pscc is 43kA, Icu is 65kA

Pscc Exceeds Fault Capacity.

19/02/2016 14:28:06 Amtech Protect HV Version 2013.0.0 Page 3 of 3


COMMISSIONING REPORT
AMTECH Protect - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision Created 26/01/2016 18:23:16
Job ID Last Saved 19/02/2016 15:19:30
Engineer
UTILITY Mode EF 5 Broadgate_H2_H3_H4_H5_H17 - Earth Fault Settings
CB 25 Incomer HVSB-1XX02, 1250A, Merlin Gerin MV, Sepam S1000+
Group A Curve IEC SIT Curve DT Curve Curve
Iso 200.0 Iso 999000 Iso Iso
T 0.80 T 1.05 T T

CB 21 Bus Link, 800A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve DT Curve Curve
Iso 100.0 Iso 999000 Iso Iso
T 0.90 T 1.05 T T

CB 5 Ring Feed, 800A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve DT Curve Curve
Iso 80.0 Iso 999000 Iso Iso
T 0.71 T 1.05 T T

CB 38 Incomer HVSB13XX01, 800A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve DT Curve Curve
Iso 80.0 Iso 999000 Iso Iso
T 0.71 T 1.05 T T

CB 42 Bus Link HVSB13XX01, 800A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve DT Curve Curve
Iso 80.0 Iso 999000 Iso Iso
T 0.38 T 1.05 T T

CB 44 Feeder TX13XX03, 300A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve DT Curve Curve
Iso 50.0 Iso 999000 Iso Iso
T 0.12 T 0.10 T T

LVSB13XX03, 6300A, Schneider, Masterpact NW63 H1 Micrologic 5.0A standard

19/02/2016 15:19:37 Amtech Protect HV Version 2013.0.0 Page 1 of 3


UTILITY Mode EF 5 Broadgate_H2_H3_H4_H5_H17.prs17
Earth Fault-Time/Current Analysis, Voltage Base: 11000V, 19/02/2016 15:19:40
10000s
1ph EF
1154A
Ief
1 hour 1.000kA

1000s
CB 25 Incomer HVSB-1XX02
CB 21 Bus Link
CB 5 Ring Feed
CB 38 Incomer HVSB13XX01
CB 42 Bus Link HVSB13XX01
CB 44 Feeder TX13XX03
LVSB13XX03

100s

1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
10mA 100mA 1A 10A 100A 1kA 10kA 100kA 1MA

19/02/2016 15:19:37 Amtech Protect HV Version 2013.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
UTILITY Mode EF 5 Broadgate_H2_H3_H4_H5_H17 - Earth Fault Analysis

10MVA Transformer Earth - 11000V


~

CB 25 Incomer HVSB-1XX02 - 1250A@11000V


Merlin Gerin MV - Sepam S1000+
Ief is 1kA, Icu is Unknown

CB 21 Bus Link - 800A@11000V


Merlin Gerin MV - Sepam S1000+
Ief is 1kA, Icu is Unknown

CB 5 Ring Feed - 800A@11000V


Merlin Gerin MV - Sepam S1000+
Ief is 1kA, Icu is Unknown

CB 38 Incomer HVSB13XX01 - 800A@11000V


Merlin Gerin MV - Sepam S1000+
Ief is 1kA, Icu is Unknown

CB 42 Bus Link HVSB13XX01 - 800A@11000V


Merlin Gerin MV - Sepam S1000+
Ief is 1kA, Icu is Unknown

CB 44 Feeder TX13XX03 - 300A@11000V


Merlin Gerin MV - Sepam S1000+
Ief is 1kA, Icu is Unknown

TX13XX03 - 11000V/400V, 4000kVA

LVSB13XX03 - 6300A@400V
Schneider - Masterpact NW63 H1 Micrologic 5.0A standard
Ief is 0kA, Icu is 100kA

No Earth Fault Protection. Overcurrent Protection is Operational.


Ief Exceeds Fault Capacity.

19/02/2016 15:19:37 Amtech Protect HV Version 2013.0.0 Page 3 of 3


COMMISSIONING REPORT
AMTECH Protect - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision Created 26/01/2016 18:23:16
Job ID Last Saved 19/02/2016 14:30:36
Engineer
UTILITY Mode OC 5 Broadgate_H2_H3_H4_H5_H17 rev1 - Overcurrent Settings
UKPN 2 33kV Feeder, Reyrolle, Argus DCD
ICT 600 Curve NI IHS1 OFF IHS2 OFF ILS1 OFF
Is 1.00 tHS1 0.10 tHS2 0.05 tLS1 0.00
tm 0.300

CB73 33kV Incomer, 600A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve IAC INV Curve Curve
Is 450.0 Is 1000.0 Is Is
T 1.10 T 0.73 T T

CB 74 33kV Feeder, 600A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve DT Curve Curve
Is 380.0 Is 4200.0 Is Is
T 0.82 T 0.05 T T

CB 25 Incomer HVSB-1XX02, 1250A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve DT Curve Curve
Is 945.0 Is 999000 Is Is
T 0.67 T 1.05 T T

CB 21 Bus Link, 800A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve DT Curve Curve
Is 945.0 Is 999000 Is Is
T 0.67 T 0.10 T T

CB 5 Ring Feed, 800A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve IEC SIT Curve Curve
Is 800.0 Is 999000 Is Is
T 0.45 T 0.19 T T

CB 38 Incomer HVSB13XX01, 800A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve DT Curve Curve
Is 800.0 Is 999000 Is Is
T 0.45 T 1.05 T T

CB 42 Bus Link HVSB13XX01, 800A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve DT Curve Curve
Is 800.0 Is 999000 Is Is
T 0.45 T 1.05 T T

CB 44 Feeder TX13XX03, 300A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC EIT Curve DT Curve Curve
Is 250.0 Is 4200.0 Is Is
T 0.40 T 0.05 T T

LVSB13XX03, 6300A, Schneider, Masterpact NW63 H1 Micrologic 5.0A standard


Ir 1.00 Isd 5.00 Iinst OFF
tr 1.0 tsd 0.1

19/02/2016 14:30:48 Amtech Protect HV Version 2013.0.0 Page 1 of 3


UTILITY Mode OC 5 Broadgate_H2_H3_H4_H5_H17 rev1.prs17
Overcurrent-Time/Current Analysis, Voltage Base: 33000V, 19/02/2016 14:30:51
10000s
Pscc Src Pscc
56.00kA 15.8kA

1 hour

1000s
UKPN 2 33kV Feeder
CB73 33kV Incomer
CB 74 33kV Feeder
CB 25 Incomer HVSB-1XX02
CB 21 Bus Link
CB 5 Ring Feed
CB 38 Incomer HVSB13XX01
CB 42 Bus Link HVSB13XX01
CB 44 Feeder TX13XX03
LVSB13XX03
100s

1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

19/02/2016 14:30:48 Amtech Protect HV Version 2013.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
UTILITY Mode OC 5 Broadgate_H2_H3_H4_H5_H17 rev1 - Overcurrent Analysis

UKPN - 33000V, Pscc is 15.8kA


~

UKPN 2 33kV Feeder - 33000V


Reyrolle - Argus DCD
Pscc is 15kA, Icu is Unknown

CB73 33kV Incomer - 600A@33000V


Merlin Gerin MV - Sepam S1000+
Pscc is 15kA, Icu is Unknown

CB 74 33kV Feeder - 600A@33000V


Merlin Gerin MV - Sepam S1000+
Pscc is 15kA, Icu is Unknown

Transformer 33000/11000 - 33000V/11000V, 18000kVA

CB 25 Incomer HVSB-1XX02 - 1250A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 7.8kA, Icu is Unknown

CB 21 Bus Link - 800A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 7.8kA, Icu is Unknown

CB 5 Ring Feed - 800A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 7.8kA, Icu is Unknown

CB 38 Incomer HVSB13XX01 - 800A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 7.8kA, Icu is Unknown

CB 42 Bus Link HVSB13XX01 - 800A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 7.8kA, Icu is Unknown

CB 44 Feeder TX13XX03 - 300A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 7.8kA, Icu is Unknown

TX13XX03 - 11000V/400V, 4000kVA

LVSB13XX03 - 6300A@400V
Schneider - Masterpact NW63 H1 Micrologic 5.0A standard
Pscc is 56kA, Icu is 100kA

Pscc Exceeds Fault Capacity.

19/02/2016 14:30:48 Amtech Protect HV Version 2013.0.0 Page 3 of 3


COMMISSIONING REPORT
AMTECH Protect - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision Created 26/01/2016 18:23:16
Job ID Last Saved 19/02/2016 15:13:35
Engineer
UTILITY Mode EF 5 Broadgate_H2_H3_H4_H15 - Earth Fault Settings
CB 25 Incomer HVSB-1XX02, 1250A, Merlin Gerin MV, Sepam S1000+
Group A Curve IEC SIT Curve DT Curve Curve
Iso 200.0 Iso 999000 Iso Iso
T 0.80 T 1.05 T T

CB 21 Bus Link, 800A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve DT Curve Curve
Iso 100.0 Iso 999000 Iso Iso
T 0.90 T 1.05 T T

CB 5 Ring Feed, 800A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve DT Curve Curve
Iso 80.0 Iso 999000 Iso Iso
T 0.71 T 1.05 T T

CB 38 Incomer HVSB13XX01, 800A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve DT Curve Curve
Iso 80.0 Iso 999000 Iso Iso
T 0.71 T 1.05 T T

CB 39 Feeder TX13XX01, 200A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve DT Curve Curve
Iso 25.0 Iso 999000 Iso Iso
T 0.12 T 1.05 T T

LVSB13XX01, 3200A, Schneider, Masterpact NW32 H1 Micrologic 5.0A standard

19/02/2016 15:13:40 Amtech Protect HV Version 2013.0.0 Page 1 of 3


UTILITY Mode EF 5 Broadgate_H2_H3_H4_H15.prs17
Earth Fault-Time/Current Analysis, Voltage Base: 11000V, 19/02/2016 15:13:53
10000s
CB 39 Feeder TX13XX01 - 200A@0V Ief
Merlin Gerin MV 1.000kA
Sepam S1000+ 1ph EF
1 hour 808A

1000s
CB 25 Incomer HVSB-1XX02
CB 21 Bus Link
CB 5 Ring Feed
CB 38 Incomer HVSB13XX01
CB 39 Feeder TX13XX01
LVSB13XX01

100s

1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
10mA 100mA 1A 10A 100A 1kA 10kA 100kA 1MA

19/02/2016 15:13:40 Amtech Protect HV Version 2013.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
UTILITY Mode EF 5 Broadgate_H2_H3_H4_H15 - Earth Fault Analysis

10MVA Transformer Earth - 11000V


~

CB 25 Incomer HVSB-1XX02 - 1250A@11000V


Merlin Gerin MV - Sepam S1000+
Ief is 1kA, Icu is Unknown

CB 21 Bus Link - 800A@11000V


Merlin Gerin MV - Sepam S1000+
Ief is 1kA, Icu is Unknown

CB 5 Ring Feed - 800A@11000V


Merlin Gerin MV - Sepam S1000+
Ief is 1kA, Icu is Unknown

CB 38 Incomer HVSB13XX01 - 800A@11000V


Merlin Gerin MV - Sepam S1000+
Ief is 1kA, Icu is Unknown

CB 39 Feeder TX13XX01 - 200A@11000V


Merlin Gerin MV - Sepam S1000+
Ief is 1kA, Icu is Unknown

TX13XX01 - 11000V/400V, 2000kVA

LVSB13XX01 - 3200A@400V
Schneider - Masterpact NW32 H1 Micrologic 5.0A standard
Ief is 0kA, Icu is 65kA

No Earth Fault Protection. Overcurrent Protection is Operational.


Ief Exceeds Fault Capacity.

19/02/2016 15:13:40 Amtech Protect HV Version 2013.0.0 Page 3 of 3


COMMISSIONING REPORT
AMTECH Protect - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision Created 26/01/2016 18:23:16
Job ID Last Saved 19/02/2016 14:39:37
Engineer
UTILITY Mode OC 5 Broadgate_H2_H3_H4_H15 rev 1 - Overcurrent Settings
UKPN 2 33kV Feeder, Reyrolle, Argus DCD
ICT 600 Curve NI IHS1 OFF IHS2 OFF ILS1 OFF
Is 1.00 tHS1 0.10 tHS2 0.05 tLS1 0.00
tm 0.300

CB73 33kV Incomer, 600A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve IAC INV Curve Curve
Is 450.0 Is 1000.0 Is Is
T 1.10 T 0.73 T T

CB 74 33kV Feeder, 600A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve DT Curve Curve
Is 380.0 Is 4200.0 Is Is
T 0.82 T 0.05 T T

CB 25 Incomer HVSB-1XX02, 1250A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve DT Curve Curve
Is 945.0 Is 999000 Is Is
T 0.67 T 1.05 T T

CB 21 Bus Link, 800A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve IEC SIT Curve Curve
Is 925.0 Is 999000 Is Is
T 0.67 T 0.42 T T

CB 5 Ring Feed, 800A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve IEC SIT Curve Curve
Is 800.0 Is 999000 Is Is
T 0.45 T 0.19 T T

CB 38 Incomer HVSB13XX01, 800A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve DT Curve Curve
Is 800.0 Is 999000 Is Is
T 0.45 T 1.05 T T

CB 39 Feeder TX13XX01, 300A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC EIT Curve DT Curve Curve
Is 125.0 Is 3000.0 Is Is
T 0.40 T 0.05 T T

LVSB13XX01, 3200A, Schneider, Masterpact NW32 H1 Micrologic 5.0A standard


Ir 1.00 Isd 3.00 Iinst OFF
tr 1.0 tsd 0.1

19/02/2016 14:39:47 Amtech Protect HV Version 2013.0.0 Page 1 of 3


UTILITY Mode OC 5 Broadgate_H2_H3_H4_H15 rev 1.prs17
Overcurrent-Time/Current Analysis, Voltage Base: 33000V, 19/02/2016 14:39:51
10000s
Pscc Src Pscc
43.00kA 15.8kA

1 hour

1000s
UKPN 2 33kV Feeder
CB73 33kV Incomer
CB 74 33kV Feeder
CB 25 Incomer HVSB-1XX02
CB 21 Bus Link
CB 5 Ring Feed
CB 38 Incomer HVSB13XX01
CB 39 Feeder TX13XX01
LVSB13XX01
100s

1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

19/02/2016 14:39:47 Amtech Protect HV Version 2013.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
UTILITY Mode OC 5 Broadgate_H2_H3_H4_H15 rev 1 - Overcurrent Analysis

UKPN - 33000V, Pscc is 15.8kA


~

UKPN 2 33kV Feeder - 33000V


Reyrolle - Argus DCD
Pscc is 15kA, Icu is Unknown

CB73 33kV Incomer - 600A@33000V


Merlin Gerin MV - Sepam S1000+
Pscc is 15kA, Icu is Unknown

CB 74 33kV Feeder - 600A@33000V


Merlin Gerin MV - Sepam S1000+
Pscc is 15kA, Icu is Unknown

Transformer 33000/11000 - 33000V/11000V, 18000kVA

CB 25 Incomer HVSB-1XX02 - 1250A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 7.8kA, Icu is Unknown

CB 21 Bus Link - 800A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 7.8kA, Icu is Unknown

CB 5 Ring Feed - 800A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 7.8kA, Icu is Unknown

CB 38 Incomer HVSB13XX01 - 800A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 7.8kA, Icu is Unknown

CB 39 Feeder TX13XX01 - 300A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 7.8kA, Icu is Unknown

TX13XX01 - 11000V/400V, 2000kVA

LVSB13XX01 - 3200A@400V
Schneider - Masterpact NW32 H1 Micrologic 5.0A standard
Pscc is 43kA, Icu is 65kA

Pscc Exceeds Fault Capacity.

19/02/2016 14:39:47 Amtech Protect HV Version 2013.0.0 Page 3 of 3


COMMISSIONING REPORT
AMTECH Protect - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision Created 26/01/2016 18:23:16
Job ID Last Saved 19/02/2016 15:06:21
Engineer
UTILITY Mode EF 5 Broadgate_H2_H3_H4_H16 - Earth Fault Settings
CB 25 Incomer HVSB-1XX02, 1250A, Merlin Gerin MV, Sepam S1000+
Group A Curve IEC SIT Curve DT Curve Curve
Iso 200.0 Iso 999000 Iso Iso
T 0.80 T 1.05 T T

CB 21 Bus Link, 800A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve DT Curve Curve
Iso 100.0 Iso 999000 Iso Iso
T 0.90 T 1.05 T T

CB 5 Ring Feed, 800A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve DT Curve Curve
Iso 80.0 Iso 999000 Iso Iso
T 0.71 T 1.05 T T

CB 38 Incomer HVSB13XX01, 800A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve DT Curve Curve
Iso 80.0 Iso 999000 Iso Iso
T 0.71 T 1.05 T T

CB 40 Feeder TX13XX02, 300A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve DT Curve Curve
Iso 50.0 Iso 999000 Iso Iso
T 0.12 T 0.10 T T

LVSB13XX02, 6300A, Schneider, Masterpact NW63 H1 Micrologic 5.0A standard

19/02/2016 15:06:28 Amtech Protect HV Version 2013.0.0 Page 1 of 3


UTILITY Mode EF 5 Broadgate_H2_H3_H4_H16.prs17
Earth Fault-Time/Current Analysis, Voltage Base: 11000V, 19/02/2016 15:06:32
10000s
1ph EF
1154A
Ief
1 hour 1.000kA

1000s
CB 25 Incomer HVSB-1XX02
CB 21 Bus Link
CB 5 Ring Feed
CB 38 Incomer HVSB13XX01
CB 40 Feeder TX13XX02
LVSB13XX02

100s

1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
10mA 100mA 1A 10A 100A 1kA 10kA 100kA 1MA

19/02/2016 15:06:28 Amtech Protect HV Version 2013.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
UTILITY Mode EF 5 Broadgate_H2_H3_H4_H16 - Earth Fault Analysis

10MVA Transformer Earth - 11000V


~

CB 25 Incomer HVSB-1XX02 - 1250A@11000V


Merlin Gerin MV - Sepam S1000+
Ief is 1kA, Icu is Unknown

CB 21 Bus Link - 800A@11000V


Merlin Gerin MV - Sepam S1000+
Ief is 1kA, Icu is Unknown

CB 5 Ring Feed - 800A@11000V


Merlin Gerin MV - Sepam S1000+
Ief is 1kA, Icu is Unknown

CB 38 Incomer HVSB13XX01 - 800A@11000V


Merlin Gerin MV - Sepam S1000+
Ief is 1kA, Icu is Unknown

CB 40 Feeder TX13XX02 - 300A@11000V


Merlin Gerin MV - Sepam S1000+
Ief is 1kA, Icu is Unknown

TX13XX02 - 11000V/400V, 4000kVA

LVSB13XX02 - 6300A@400V
Schneider - Masterpact NW63 H1 Micrologic 5.0A standard
Ief is 0kA, Icu is 100kA

No Earth Fault Protection. Overcurrent Protection is Operational.


Ief Exceeds Fault Capacity.

19/02/2016 15:06:28 Amtech Protect HV Version 2013.0.0 Page 3 of 3


COMMISSIONING REPORT
AMTECH Protect - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision Created 26/01/2016 18:23:16
Job ID Last Saved 19/02/2016 14:41:34
Engineer
UTILITY Mode OC 5 Broadgate_H2_H3_H4_H16 rev 1 - Overcurrent Settings
UKPN 2 33kV Feeder, Reyrolle, Argus DCD
ICT 600 Curve NI IHS1 OFF IHS2 OFF ILS1 OFF
Is 1.00 tHS1 0.10 tHS2 0.05 tLS1 0.00
tm 0.300

CB73 33kV Incomer, 600A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve IAC INV Curve Curve
Is 450.0 Is 1000.0 Is Is
T 1.10 T 0.73 T T

CB 74 33kV Feeder, 600A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve DT Curve Curve
Is 380.0 Is 4200.0 Is Is
T 0.82 T 0.05 T T

CB 25 Incomer HVSB-1XX02, 1250A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve DT Curve Curve
Is 945.0 Is 999000 Is Is
T 0.67 T 1.05 T T

CB 21 Bus Link, 800A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve IEC SIT Curve Curve
Is 945.0 Is 999000 Is Is
T 0.67 T 0.42 T T

CB 5 Ring Feed, 800A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve IEC SIT Curve Curve
Is 800.0 Is 999000 Is Is
T 0.45 T 0.19 T T

CB 38 Incomer HVSB13XX01, 800A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve DT Curve Curve
Is 800.0 Is 999000 Is Is
T 0.45 T 1.05 T T

CB 40 Feeder TX13XX02, 300A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC EIT Curve DT Curve Curve
Is 250.0 Is 4200.0 Is Is
T 0.40 T 0.05 T T

LVSB13XX02, 6300A, Schneider, Masterpact NW63 H1 Micrologic 5.0A standard


Ir 1.00 Isd 5.00 Iinst OFF
tr 1.0 tsd 0.1

19/02/2016 14:41:38 Amtech Protect HV Version 2013.0.0 Page 1 of 3


UTILITY Mode OC 5 Broadgate_H2_H3_H4_H16 rev 1.prs17
Overcurrent-Time/Current Analysis, Voltage Base: 33000V, 19/02/2016 14:41:41
10000s
Primary 3ph Pscc Src Pscc
210A 2999A 7.800kA 15.8kA

1 hour

1000s
UKPN 2 33kV Feeder
CB73 33kV Incomer
CB 74 33kV Feeder
CB 25 Incomer HVSB-1XX02
CB 21 Bus Link
CB 5 Ring Feed
CB 38 Incomer HVSB13XX01
CB 40 Feeder TX13XX02
LVSB13XX02
100s

1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

19/02/2016 14:41:38 Amtech Protect HV Version 2013.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
UTILITY Mode OC 5 Broadgate_H2_H3_H4_H16 rev 1 - Overcurrent Analysis

UKPN - 33000V, Pscc is 15.8kA


~

UKPN 2 33kV Feeder - 33000V


Reyrolle - Argus DCD
Pscc is 15kA, Icu is Unknown

CB73 33kV Incomer - 600A@33000V


Merlin Gerin MV - Sepam S1000+
Pscc is 15kA, Icu is Unknown

CB 74 33kV Feeder - 600A@33000V


Merlin Gerin MV - Sepam S1000+
Pscc is 15kA, Icu is Unknown

Transformer 33000/11000 - 33000V/11000V, 18000kVA

CB 25 Incomer HVSB-1XX02 - 1250A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 7.8kA, Icu is Unknown

CB 21 Bus Link - 800A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 7.8kA, Icu is Unknown

CB 5 Ring Feed - 800A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 7.8kA, Icu is Unknown

CB 38 Incomer HVSB13XX01 - 800A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 7.8kA, Icu is Unknown

CB 40 Feeder TX13XX02 - 300A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 7.8kA, Icu is Unknown

TX13XX02 - 11000V/400V, 4000kVA

LVSB13XX02 - 6300A@400V
Schneider - Masterpact NW63 H1 Micrologic 5.0A standard
Pscc is 56kA, Icu is 100kA

Pscc Exceeds Fault Capacity.

19/02/2016 14:41:38 Amtech Protect HV Version 2013.0.0 Page 3 of 3


COMMISSIONING REPORT
H7_H3 - Licenced to Long & Partners Ltd

Project Reference 5 Broadgate Modified By


Revision - Created 26/01/2016 18:23:16
Job ID Last Saved 19/02/2016 15:02:49
Engineer Mick Beck
UTILITY Mode EF 5 Broadgate_H2_H3_H7 - Earth Fault Settings
CB 25 Incomer HVSB-1XX02, 1250A, Merlin Gerin MV, Sepam S1000+
Group A Curve IEC SIT Curve DT Curve Curve
Iso 200.0 Iso 999000 Iso Iso
T 0.80 T 1.05 T T

CB 21 Bus Link, 800A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve DT Curve Curve
Iso 100.0 Iso 999000 Iso Iso
T 0.90 T 1.05 T T

CB 15 Feeder TX-2XX01, 300A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve DT Curve Curve
Iso 50.0 Iso 999000 Iso Iso
T 0.12 T 0.10 T T

LVSB-2XX01, 6300A, Schneider, Masterpact NW63 H1 Micrologic 5.0A standard

19/02/2016 15:02:54 Amtech Protect HV Version 2013.0.0 Page 1 of 3


UTILITY Mode EF 5 Broadgate_H2_H3_H7.prs17
Earth Fault-Time/Current Analysis, Voltage Base: 11000V, 19/02/2016 15:03:05
10000s
1ph EF
1154A
Ief
1 hour 1.000kA

1000s
CB 25 Incomer HVSB-1XX02
CB 21 Bus Link
CB 15 Feeder TX-2XX01
LVSB-2XX01

100s

1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
10mA 100mA 1A 10A 100A 1kA 10kA 100kA 1MA

19/02/2016 15:02:54 Amtech Protect HV Version 2013.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
UTILITY Mode EF 5 Broadgate_H2_H3_H7 - Earth Fault Analysis

10MVA Transformer Earth - 11000V


~

CB 25 Incomer HVSB-1XX02 - 1250A@11000V


Merlin Gerin MV - Sepam S1000+
Ief is 1kA, Icu is Unknown

CB 21 Bus Link - 800A@11000V


Merlin Gerin MV - Sepam S1000+
Ief is 1kA, Icu is Unknown

CB 15 Feeder TX-2XX01 - 300A@11000V


Merlin Gerin MV - Sepam S1000+
Ief is 1kA, Icu is Unknown

TX-2XX01 - 11000V/400V, 4000kVA

LVSB-2XX01 - 6300A@400V
Schneider - Masterpact NW63 H1 Micrologic 5.0A standard
Ief is 0kA, Icu is 100kA

No Earth Fault Protection. Overcurrent Protection is Operational.


Ief Exceeds Fault Capacity.

19/02/2016 15:02:54 Amtech Protect HV Version 2013.0.0 Page 3 of 3


COMMISSIONING REPORT
H7_H3 - Licenced to Long & Partners Ltd

Project Reference 5 Broadgate Modified By


Revision - Created 26/01/2016 18:23:16
Job ID Last Saved 19/02/2016 14:43:04
Engineer Mick Beck
UTILITY Mode OC 5 Broadgate_H2_H3_H7 rev 1 - Overcurrent Settings
UKPN 2 33kV Feeder, Reyrolle, Argus DCD
ICT 600 Curve NI IHS1 OFF IHS2 OFF ILS1 OFF
Is 1.00 tHS1 0.10 tHS2 0.05 tLS1 0.00
tm 0.300

CB73 33kV Incomer, 600A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve IAC INV Curve Curve
Is 450.0 Is 1000.0 Is Is
T 1.10 T 0.73 T T

CB 74 33kV Feeder, 600A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve DT Curve Curve
Is 380.0 Is 4200.0 Is Is
T 0.82 T 0.05 T T

CB 25 Incomer HVSB-1XX02, 1250A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve DT Curve Curve
Is 945.0 Is 999000 Is Is
T 0.67 T 1.05 T T

CB 21 Bus Link, 800A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve IEC SIT Curve Curve
Is 945.0 Is 999000 Is Is
T 0.67 T 0.42 T T

CB 15 Feeder TX-2XX01, 300A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC EIT Curve DT Curve Curve
Is 250.0 Is 4200.0 Is Is
T 0.40 T 0.05 T T

LVSB-2XX01, 6300A, Schneider, Masterpact NW63 H1 Micrologic 5.0A standard


Ir 1.00 Isd 5.00 Iinst OFF
tr 1.0 tsd 0.1

19/02/2016 14:43:09 Amtech Protect HV Version 2013.0.0 Page 1 of 3


UTILITY Mode OC 5 Broadgate_H2_H3_H7 rev 1.prs17
Overcurrent-Time/Current Analysis, Voltage Base: 33000V, 19/02/2016 14:43:12
10000s
Primary 3ph Pscc Src Pscc
210A 2999A 7.800kA 15.8kA

1 hour

1000s
UKPN 2 33kV Feeder
CB73 33kV Incomer
CB 74 33kV Feeder
CB 25 Incomer HVSB-1XX02
CB 21 Bus Link
CB 15 Feeder TX-2XX01
LVSB-2XX01

100s

1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

19/02/2016 14:43:09 Amtech Protect HV Version 2013.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
UTILITY Mode OC 5 Broadgate_H2_H3_H7 rev 1 - Overcurrent Analysis

UKPN - 33000V, Pscc is 15.8kA


~

UKPN 2 33kV Feeder - 33000V


Reyrolle - Argus DCD
Pscc is 15kA, Icu is Unknown

CB73 33kV Incomer - 600A@33000V


Merlin Gerin MV - Sepam S1000+
Pscc is 15kA, Icu is Unknown

CB 74 33kV Feeder - 600A@33000V


Merlin Gerin MV - Sepam S1000+
Pscc is 15kA, Icu is Unknown

Transformer 33000/11000 - 33000V/11000V, 18000kVA

CB 25 Incomer HVSB-1XX02 - 1250A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 7.8kA, Icu is Unknown

CB 21 Bus Link - 800A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 7.8kA, Icu is Unknown

CB 15 Feeder TX-2XX01 - 300A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 7.8kA, Icu is Unknown

TX-2XX01 - 11000V/400V, 4000kVA

LVSB-2XX01 - 6300A@400V
Schneider - Masterpact NW63 H1 Micrologic 5.0A standard
Pscc is 56kA, Icu is 100kA

Pscc Exceeds Fault Capacity.

19/02/2016 14:43:09 Amtech Protect HV Version 2013.0.0 Page 3 of 3


Electrical Discrimination Study
5 Broadgate

7.0 Generator - Network Analysis

Long and Partners Ltd


Rev 11 QA-R06-1 13 of 14
ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV GEN FEEDER, CB 48 Circuit GEN12XX01


Device SPEAM G87
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 200/100/1A on 200A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 150A Is = 105A
50N/51N - 1 Trip CB P T = 3100ms T = 870ms
Group A ON P Curve = DT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 2 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 150A Is = 105A
50N/51N - 1 Trip CB P T = 3100ms T = 870ms
Group B ON P Curve = DT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 2 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P SWITCHED OFF SWITCHED OFF
Group B OFF
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
49RMS thermal overload for machines
87M Machine differential
87M - 1 Latching P Is = 20A
Trip CB P
67 Directional phase overcurrent
67 - 1 Latching P 1 2
67 - 2 Trip CB P Is = 75A
Group A ON P T = 0ms
SWITCHED OFF
Curve = DT
Angle 45o Line
67 - 1 Latching P Is = 75A
67 - 2 Trip CB P T = 0ms
SWITCHED OFF
Group B ON P Curve = DT
Angle 45o Line
67N Directional earth fault
32P directional active overpower
32Q Directional reactive overpower
40 Field loss (under impedance)
78PS Pole slip
12-14 Overspeed - Underspeed
50V/ 51V Voltage-restrained overcurrent
21B Under impedance
50/27 Inadvertent energisation
24 Overfluxing (V / Hz)
27 under voltage (L-L or L-N)
27D Positive sequence undercurrent
27R Remanent undervoltage
27TN/ 64G2/ 64G 3rd harmonic undervoltage / 100% stator earth fault
59 overvoltage (L-L or L-N)
59N Neutral Voltage Displacement
Latching P 1 2
59N - 1
Trip CB P Unp = 15% Unp = 20%
Latching P T = 4s T = 100ms
59N - 2
Trip CB P Curve = IDMT Curve = DT
47 Negative Sequence Overvoltage
81H over frequency
81L under frequency
38/ 49T Temperature Monitoring (No OFF, output can be disabled)
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-13XX03 Rev 4 1 of 9 CB 48


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

11 kV INTERLINK, CB 49. Interlinking Gen boards HVSB13XX03 to


Description
HVSB13XX06
Device SEPAM S80
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 1250/800/1A on 800A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 780A Is = 95A
50N/51N - 1 Trip CB P T = 2000ms T = 620ms
Group A ON Curve = DT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 2 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - Elements 3~8
50N/51N - Elements 2~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 780A Is = 95A
50N/51N - 1 Trip CB P T = 2000ms T = 620ms
Group B ON Curve = DT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 2 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P SWITCHED OFF SWITCHED OFF
Group B OFF
50/51 - Elements 3~8
50N/51N - Elements 1~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
79 Re-closer
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-13XX03 Rev 4 2 of 9 CB 49


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV INTERLINK, CB 49. Interlinking Gen boards HVSB13XX03 to HVSB13XX06


Device SOLKOR 7SG18 N
Select
CT Ratio 1000/1A on 1000A Range
SETTINGS GROUP G MENU ONLY
SCREEN FUNCTION MENU ENTRY
Active Settings Group Group that the relay will act upon G1
Settings Group Edit/View Group to be displayed on the LCD G1
Local P/F Rating Local relay’s phase fault CT rating 1A
Local E/F Rating Local relay’s earth fault CT rating 1A
Local P/F CT Ratio relay’s phase input CT ratio 1000:1
Local E/F CT Ratio relay’s earth input CT ratio 1000:1
Remote P/F Rating Remote relay’s phase fault CT rating 1A
Remote P/F CT Ratio Remote relay’s earth fault CT rating 1000:1
Current Display display mode to use for the relay xIn
Set Identifier 16 character alphanumeric code CB49 SOLKOR
Set Alarm 1 ALARM 1
Calendar – Set Date DD/MM/YY Todays Date
Clock - Set Time HH:MM:SS Actual Time
Clock Sync. From Status Seconds or Minutes Minutes
Default Screen Timer 10sec, 60sec, 5min, 1hour 5 min
Change Password 4 alphanumeric characters NONE

DIFF' PROTECTION MENU ONLY


SCREEN FUNCTION MENU ENTRY
Gn P/F Diff. Setting* setting for the differential element 0.3 x In
Gn P/F Bias Slope 1* 1st bias slope differential element 30%
Gn P/F Bias Slope 2* 2nd bias slope differential element 150%
Gn Bias Break Point* bias slope break point 1 to 2 2.00 x In
Gn Differential Delay trip time differential element/ intertrip 0.0s
P/F CT Ratio Correction CT ratio correction 1
Remote P/F Ratio Correction CT ratio correction 1
Gn Internal Intertrip enables / disables internal intertrips OFF
Gn Int Intertrip Delay internal intertrip elements 0.00s
Gn External Intertrip enables / disables external intertrips ON
Gn Ext Intertrip Delay external intertrip elements 0.00s

O/C PROTECTION MENU ONLY


SCREEN FUNCTION MENU ENTRY
Gn P/F Charact. Setting phase fault O/C pick-up level OFF
Gn P/F Charact. phase fault O/C characteristic
Gn P/F Charact. Time Mult phase fault TMS
Gn P/F Charact. Delay phase fault delay DTL
Gn P/F Lowset Setting phase fault lowset pick-up OFF
Gn P/F Lowset Delay phase fault lowset delay
Gn P/F Highset1 Setting phase fault highset 1 pick-up OFF
Gn P/F Highset1 Delay phase fault highset 1 delay
Gn P/F Highset2 Setting phase fault highset 2 pick-up OFF
Gn P/F Highset2 Delay phase fault highset 2 delay
Gn E/F Charact. Setting earth fault O/C pick-up level OFF
Gn E/F Charact. earth fault O/C characteristic
Gn E/F Charact. Time Mult earth fault TMS
Gn E/F Charact. Delay earth fault delay DTL
Gn E/F Lowset Setting earth fault lowset pick-up OFF
Gn E/F Lowset Delay earth fault lowset delay
Gn E/F Highset1 Setting earth fault highset 1 pick-up OFF
Gn E/F Highset1 Delay earth fault highset 1 delay
Gn E/F Highset2 Setting earth fault highset 2 pick-up OFF
Gn E/F Highset 2 Delay earth fault highset 2 delay
Gn CB Fail Time Delay 1 1st time delay for CB Fail OFF
Gn CB Fail Time Delay2 2nd time delay for CB Fail OFF
Gn P/F CB Fail Setting sets over current CB Fail level OFF
Gn E/F CB Fail Setting sets earth fault current CB Fail level OFF
Gn CT Failure Setting sets CT Failure level OFF
Gn CT Failure Delay sets delay for CT Failure 1s
Gn Relay Reset Delay OC reset characteristic INST
O/P RELAY CONFIG MENU ONLY
Gn Prot. Healthy RL1
Gn P/F Diff. RL4

5 Broadgate Protective Device Settings HVSB-13XX03 Rev 4 3 of 9 CB49 SOLKOR


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 50 Circuit H19


Device SEPAM S80
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 1250/800/1A on 800A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 780A Is = 95A
50N/51N - 1 Trip CB P T = 2000ms T = 620ms
Group A ON Curve = DT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 2 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - Elements 3~8
50N/51N - Elements 2~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 780A Is = 95A
50N/51N - 1 Trip CB P T = 2000ms T = 620ms
Group B ON Curve = DT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 2 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P SWITCHED OFF SWITCHED OFF
Group B OFF
50/51 - Elements 3~8
50N/51N - Elements 1~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
79 Re-closer
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-13XX03 Rev 4 4 of 9 CB 50


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 50 Circuit H19


Device SOLKOR 7SG18 N
Select
CT Ratio 1000/1A on 1000A Range
SETTINGS GROUP G MENU ONLY
SCREEN FUNCTION MENU ENTRY
Active Settings Group Group that the relay will act upon G1
Settings Group Edit/View Group to be displayed on the LCD G1
Local P/F Rating Local relay’s phase fault CT rating 1A
Local E/F Rating Local relay’s earth fault CT rating 1A
Local P/F CT Ratio relay’s phase input CT ratio 1000:1
Local E/F CT Ratio relay’s earth input CT ratio 1000:1
Remote P/F Rating Remote relay’s phase fault CT rating 1A
Remote P/F CT Ratio Remote relay’s earth fault CT rating 1000:1
Current Display display mode to use for the relay xIn
Set Identifier 16 character alphanumeric code CB50 SOLKOR
Set Alarm 1 ALARM 1
Calendar – Set Date DD/MM/YY Todays Date
Clock - Set Time HH:MM:SS Actual Time
Clock Sync. From Status Seconds or Minutes Minutes
Default Screen Timer 10sec, 60sec, 5min, 1hour 5 min
Change Password 4 alphanumeric characters NONE

DIFF' PROTECTION MENU ONLY


SCREEN FUNCTION MENU ENTRY
Gn P/F Diff. Setting* setting for the differential element 0.3 x In
Gn P/F Bias Slope 1* 1st bias slope differential element 30%
Gn P/F Bias Slope 2* 2nd bias slope differential element 150%
Gn Bias Break Point* bias slope break point 1 to 2 2.00 x In
Gn Differential Delay trip time differential element/ intertrip 0.0s
P/F CT Ratio Correction CT ratio correction 1
Remote P/F Ratio Correction CT ratio correction 1
Gn Internal Intertrip enables / disables internal intertrips OFF
Gn Int Intertrip Delay internal intertrip elements 0.00s
Gn External Intertrip enables / disables external intertrips ON
Gn Ext Intertrip Delay external intertrip elements 0.00s

O/C PROTECTION MENU ONLY


SCREEN FUNCTION MENU ENTRY
Gn P/F Charact. Setting phase fault O/C pick-up level OFF
Gn P/F Charact. phase fault O/C characteristic
Gn P/F Charact. Time Mult phase fault TMS
Gn P/F Charact. Delay phase fault delay DTL
Gn P/F Lowset Setting phase fault lowset pick-up OFF
Gn P/F Lowset Delay phase fault lowset delay
Gn P/F Highset1 Setting phase fault highset 1 pick-up OFF
Gn P/F Highset1 Delay phase fault highset 1 delay
Gn P/F Highset2 Setting phase fault highset 2 pick-up OFF
Gn P/F Highset2 Delay phase fault highset 2 delay
Gn E/F Charact. Setting earth fault O/C pick-up level OFF
Gn E/F Charact. earth fault O/C characteristic
Gn E/F Charact. Time Mult earth fault TMS
Gn E/F Charact. Delay earth fault delay DTL
Gn E/F Lowset Setting earth fault lowset pick-up OFF
Gn E/F Lowset Delay earth fault lowset delay
Gn E/F Highset1 Setting earth fault highset 1 pick-up OFF
Gn E/F Highset1 Delay earth fault highset 1 delay
Gn E/F Highset2 Setting earth fault highset 2 pick-up OFF
Gn E/F Highset 2 Delay earth fault highset 2 delay
Gn CB Fail Time Delay 1 1st time delay for CB Fail OFF
Gn CB Fail Time Delay2 2nd time delay for CB Fail OFF
Gn P/F CB Fail Setting sets over current CB Fail level OFF
Gn E/F CB Fail Setting sets earth fault current CB Fail level OFF
Gn CT Failure Setting sets CT Failure level OFF
Gn CT Failure Delay sets delay for CT Failure 1s
Gn Relay Reset Delay OC reset characteristic INST
O/P RELAY CONFIG MENU ONLY
Gn Prot. Healthy RL1
Gn P/F Diff. RL4

5 Broadgate Protective Device Settings HVSB-13XX03 Rev 4 5 of 9 CB50 SOLKOR


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 51. To loadbank panel HVSB14XX01 (CB 76)


Device SEPAM S80
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 1250/800/1A on 800A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 140A Is = 95A
50N/51N - 1 Trip CB P T = 1105ms T = 620ms
Group A ON Curve = RI Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 2 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - Elements 3~8
50N/51N - Elements 2~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 140A Is = 95A
50N/51N - 1 Trip CB P T = 1105ms T = 620ms
Group B ON Curve = RI Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 2 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P SWITCHED OFF SWITCHED OFF
Group B OFF
50/51 - Elements 3~8
50N/51N - Elements 1~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
79 Re-closer
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-13XX03 Rev 4 6 of 9 CB 51


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV GEN FEEDER, CB 52 Circuit GEN12XX02


Device SPEAM G87
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 200/100/1A on 200A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 150A Is = 105A
50N/51N - 1 Trip CB P T = 3100ms T = 870ms
Group A ON P Curve = DT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 2 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 150A Is = 105A
50N/51N - 1 Trip CB P T = 3100ms T = 870ms
Group B ON P Curve = DT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 2 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P SWITCHED OFF SWITCHED OFF
Group B OFF
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
49RMS thermal overload for machines
87M Machine differential
87M - 1 Latching P Is = 20A
Trip CB P
67 Directional phase overcurrent
67 - 1 Latching P 1 2
67 - 2 Trip CB P Is = 75A
Group A ON P T = 0ms
SWITCHED OFF
Curve = DT
Angle 45o Line
67 - 1 Latching P Is = 75A
67 - 2 Trip CB P T = 0ms
SWITCHED OFF
Group B ON P Curve = DT
Angle 45o Line
67N Directional earth fault
32P directional active overpower
32Q Directional reactive overpower
40 Field loss (under impedance)
78PS Pole slip
12-14 Overspeed - Underspeed
50V/ 51V Voltage-restrained overcurrent
21B Under impedance
50/27 Inadvertent energisation
24 Overfluxing (V / Hz)
27 under voltage (L-L or L-N)
27D Positive sequence undercurrent
27R Remanent undervoltage
27TN/ 64G2/ 64G 3rd harmonic undervoltage / 100% stator earth fault
59 overvoltage (L-L or L-N)
59N Neutral Voltage Displacement
Latching P 1 2
59N - 1
Trip CB P Unp = 15% Unp = 20%
Latching P T = 4s T = 100ms
59N - 2
Trip CB P Curve = IDMT Curve = DT
47 Negative Sequence Overvoltage
81H over frequency
81L under frequency
38/ 49T Temperature Monitoring (No OFF, output can be disabled)
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-13XX03 Rev 4 7 of 9 CB 52


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

11 kV INTERLINK, CB 53. Interlinking Gen boards HVSB13XX03 to


Description
HVSB13XX04
Device SEPAM S80
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 1250/800/1A on 800A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 780A Is = 95A
50N/51N - 1 Trip CB P T = 2000ms T = 620ms
Group A ON Curve = DT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 2 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - Elements 3~8
50N/51N - Elements 2~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 780A Is = 95A
50N/51N - 1 Trip CB P T = 2000ms T = 620ms
Group B ON Curve = DT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 2 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P SWITCHED OFF SWITCHED OFF
Group B OFF
50/51 - Elements 3~8
50N/51N - Elements 1~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
79 Re-closer
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-13XX03 Rev 4 8 of 9 CB 53


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV INTERLINK, CB 53. Interlinking Gen boards HVSB13XX03 to HVSB13XX04


Device SOLKOR 7SG18 N
Select
CT Ratio 1000/1A on 1000A Range
SETTINGS GROUP G MENU ONLY
SCREEN FUNCTION MENU ENTRY
Active Settings Group Group that the relay will act upon G1
Settings Group Edit/View Group to be displayed on the LCD G1
Local P/F Rating Local relay’s phase fault CT rating 1A
Local E/F Rating Local relay’s earth fault CT rating 1A
Local P/F CT Ratio relay’s phase input CT ratio 1000:1
Local E/F CT Ratio relay’s earth input CT ratio 1000:1
Remote P/F Rating Remote relay’s phase fault CT rating 1A
Remote P/F CT Ratio Remote relay’s earth fault CT rating 1000:1
Current Display display mode to use for the relay xIn
Set Identifier 16 character alphanumeric code CB53 SOLKOR
Set Alarm 1 ALARM 1
Calendar – Set Date DD/MM/YY Todays Date
Clock - Set Time HH:MM:SS Actual Time
Clock Sync. From Status Seconds or Minutes Minutes
Default Screen Timer 10sec, 60sec, 5min, 1hour 5 min
Change Password 4 alphanumeric characters NONE

DIFF' PROTECTION MENU ONLY


SCREEN FUNCTION MENU ENTRY
Gn P/F Diff. Setting* setting for the differential element 0.3 x In
Gn P/F Bias Slope 1* 1st bias slope differential element 30%
Gn P/F Bias Slope 2* 2nd bias slope differential element 150%
Gn Bias Break Point* bias slope break point 1 to 2 2.00 x In
Gn Differential Delay trip time differential element/ intertrip 0.0s
P/F CT Ratio Correction CT ratio correction 1
Remote P/F Ratio Correction CT ratio correction 1
Gn Internal Intertrip enables / disables internal intertrips OFF
Gn Int Intertrip Delay internal intertrip elements 0.00s
Gn External Intertrip enables / disables external intertrips ON
Gn Ext Intertrip Delay external intertrip elements 0.00s

O/C PROTECTION MENU ONLY


SCREEN FUNCTION MENU ENTRY
Gn P/F Charact. Setting phase fault O/C pick-up level OFF
Gn P/F Charact. phase fault O/C characteristic
Gn P/F Charact. Time Mult phase fault TMS
Gn P/F Charact. Delay phase fault delay DTL
Gn P/F Lowset Setting phase fault lowset pick-up OFF
Gn P/F Lowset Delay phase fault lowset delay
Gn P/F Highset1 Setting phase fault highset 1 pick-up OFF
Gn P/F Highset1 Delay phase fault highset 1 delay
Gn P/F Highset2 Setting phase fault highset 2 pick-up OFF
Gn P/F Highset2 Delay phase fault highset 2 delay
Gn E/F Charact. Setting earth fault O/C pick-up level OFF
Gn E/F Charact. earth fault O/C characteristic
Gn E/F Charact. Time Mult earth fault TMS
Gn E/F Charact. Delay earth fault delay DTL
Gn E/F Lowset Setting earth fault lowset pick-up OFF
Gn E/F Lowset Delay earth fault lowset delay
Gn E/F Highset1 Setting earth fault highset 1 pick-up OFF
Gn E/F Highset1 Delay earth fault highset 1 delay
Gn E/F Highset2 Setting earth fault highset 2 pick-up OFF
Gn E/F Highset 2 Delay earth fault highset 2 delay
Gn CB Fail Time Delay 1 1st time delay for CB Fail OFF
Gn CB Fail Time Delay2 2nd time delay for CB Fail OFF
Gn P/F CB Fail Setting sets over current CB Fail level OFF
Gn E/F CB Fail Setting sets earth fault current CB Fail level OFF
Gn CT Failure Setting sets CT Failure level OFF
Gn CT Failure Delay sets delay for CT Failure 1s
Gn Relay Reset Delay OC reset characteristic INST
O/P RELAY CONFIG MENU ONLY
Gn Prot. Healthy RL1
Gn P/F Diff. RL4

5 Broadgate Protective Device Settings HVSB-13XX03 Rev 4 9 of 9 CB53 SOLKOR


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV GEN FEEDER, CB 54 Circuit GEN12XX03


Device SPEAM G87
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 200/100/1A on 200A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 150A Is = 105A
50N/51N - 1 Trip CB P T = 3100ms T = 870ms
Group A ON P Curve = DT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 2 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 150A Is = 105A
50N/51N - 1 Trip CB P T = 3100ms T = 870ms
Group B ON P Curve = DT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 2 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P SWITCHED OFF SWITCHED OFF
Group B OFF
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
49RMS thermal overload for machines
87M Machine differential
87M - 1 Latching P Is = 20A
Trip CB P
67 Directional phase overcurrent
67 - 1 Latching P 1 2
67 - 2 Trip CB P Is = 75A
Group A ON P T = 0ms
SWITCHED OFF
Curve = DT
Angle 45o Line
67 - 1 Latching P Is = 75A
67 - 2 Trip CB P T = 0ms
SWITCHED OFF
Group B ON P Curve = DT
Angle 45o Line
67N Directional earth fault
32P directional active overpower
32Q Directional reactive overpower
40 Field loss (under impedance)
78PS Pole slip
12-14 Overspeed - Underspeed
50V/ 51V Voltage-restrained overcurrent
21B Under impedance
50/27 Inadvertent energisation
24 Overfluxing (V / Hz)
27 under voltage (L-L or L-N)
27D Positive sequence undercurrent
27R Remanent undervoltage
27TN/ 64G2/ 64G 3rd harmonic undervoltage / 100% stator earth fault
59 overvoltage (L-L or L-N)
59N Neutral Voltage Displacement
Latching P 1 2
59N - 1
Trip CB P Unp = 15% Unp = 20%
Latching P T = 4s T = 100ms
59N - 2
Trip CB P Curve = IDMT Curve = DT
47 Negative Sequence Overvoltage
81H over frequency
81L under frequency
38/ 49T Temperature Monitoring (No OFF, output can be disabled)
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-13XX04 Rev 4 1 of 9 CB 54


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

11 kV INTERLINK, CB 55. Interlinking Gen boards HVSB13XX04 to


Description
HVSB13XX03
Device SEPAM S80
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 1250/800/1A on 800A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 780A Is = 95A
50N/51N - 1 Trip CB P T = 2000ms T = 620ms
Group A ON Curve = DT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 2 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - Elements 3~8
50N/51N - Elements 2~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 780A Is = 95A
50N/51N - 1 Trip CB P T = 2000ms T = 620ms
Group B ON Curve = DT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 2 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P SWITCHED OFF SWITCHED OFF
Group B OFF
50/51 - Elements 3~8
50N/51N - Elements 1~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
79 Re-closer
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-13XX04 Rev 4 2 of 9 CB 55


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV INTERLINK, CB 55. Interlinking Gen boards HVSB13XX04 to HVSB13XX03


Device SOLKOR 7SG18 N
Select
CT Ratio 1000/1A on 1000A Range
SETTINGS GROUP G MENU ONLY
SCREEN FUNCTION MENU ENTRY
Active Settings Group Group that the relay will act upon G1
Settings Group Edit/View Group to be displayed on the LCD G1
Local P/F Rating Local relay’s phase fault CT rating 1A
Local E/F Rating Local relay’s earth fault CT rating 1A
Local P/F CT Ratio relay’s phase input CT ratio 1000:1
Local E/F CT Ratio relay’s earth input CT ratio 1000:1
Remote P/F Rating Remote relay’s phase fault CT rating 1A
Remote P/F CT Ratio Remote relay’s earth fault CT rating 1000:1
Current Display display mode to use for the relay xIn
Set Identifier 16 character alphanumeric code CB55 SOLKOR
Set Alarm 1 ALARM 1
Calendar – Set Date DD/MM/YY Todays Date
Clock - Set Time HH:MM:SS Actual Time
Clock Sync. From Status Seconds or Minutes Minutes
Default Screen Timer 10sec, 60sec, 5min, 1hour 5 min
Change Password 4 alphanumeric characters NONE

DIFF' PROTECTION MENU ONLY


SCREEN FUNCTION MENU ENTRY
Gn P/F Diff. Setting* setting for the differential element 0.3 x In
Gn P/F Bias Slope 1* 1st bias slope differential element 30%
Gn P/F Bias Slope 2* 2nd bias slope differential element 150%
Gn Bias Break Point* bias slope break point 1 to 2 2.00 x In
Gn Differential Delay trip time differential element/ intertrip 0.0s
P/F CT Ratio Correction CT ratio correction 1
Remote P/F Ratio Correction CT ratio correction 1
Gn Internal Intertrip enables / disables internal intertrips OFF
Gn Int Intertrip Delay internal intertrip elements 0.00s
Gn External Intertrip enables / disables external intertrips ON
Gn Ext Intertrip Delay external intertrip elements 0.00s

O/C PROTECTION MENU ONLY


SCREEN FUNCTION MENU ENTRY
Gn P/F Charact. Setting phase fault O/C pick-up level OFF
Gn P/F Charact. phase fault O/C characteristic
Gn P/F Charact. Time Mult phase fault TMS
Gn P/F Charact. Delay phase fault delay DTL
Gn P/F Lowset Setting phase fault lowset pick-up OFF
Gn P/F Lowset Delay phase fault lowset delay
Gn P/F Highset1 Setting phase fault highset 1 pick-up OFF
Gn P/F Highset1 Delay phase fault highset 1 delay
Gn P/F Highset2 Setting phase fault highset 2 pick-up OFF
Gn P/F Highset2 Delay phase fault highset 2 delay
Gn E/F Charact. Setting earth fault O/C pick-up level OFF
Gn E/F Charact. earth fault O/C characteristic
Gn E/F Charact. Time Mult earth fault TMS
Gn E/F Charact. Delay earth fault delay DTL
Gn E/F Lowset Setting earth fault lowset pick-up OFF
Gn E/F Lowset Delay earth fault lowset delay
Gn E/F Highset1 Setting earth fault highset 1 pick-up OFF
Gn E/F Highset1 Delay earth fault highset 1 delay
Gn E/F Highset 2 Setting earth fault highset 2 pick-up OFF
Gn E/F Highset 2 Delay earth fault highset 2 delay
Gn CB Fail Time Delay 1 1st time delay for CB Fail OFF
Gn CB Fail Time Delay2 2nd time delay for CB Fail OFF
Gn P/F CB Fail Setting sets over current CB Fail level OFF
Gn E/F CB Fail Setting sets earth fault current CB Fail level OFF
Gn CT Failure Setting sets CT Failure level OFF
Gn CT Failure Delay sets delay for CT Failure 1s
Gn Relay Reset Delay OC reset characteristic INST
O/P RELAY CONFIG MENU ONLY
Gn Prot. Healthy RL1
Gn P/F Diff. RL4

5 Broadgate Protective Device Settings HVSB-13XX04 Rev 4 3 of 9 CB55 SOLKOR


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 56 Circuit H20


Device SEPAM S80
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 1250/800/1A on 800A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 780A Is = 95A
50N/51N - 1 Trip CB P T = 2000ms T = 620ms
Group A ON Curve = DT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 2 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - Elements 3~8
50N/51N - Elements 2~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 780A Is = 95A
50N/51N - 1 Trip CB P T = 2000ms T = 620ms
Group B ON Curve = DT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 2 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P SWITCHED OFF SWITCHED OFF
Group B OFF
50/51 - Elements 3~8
50N/51N - Elements 1~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
79 Re-closer
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-13XX04 Rev 4 4 of 9 CB 56


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 56 Circuit H20


Device SOLKOR 7SG18 N
Select
CT Ratio 1000/1A on 1000A Range
SETTINGS GROUP G MENU ONLY
SCREEN FUNCTION MENU ENTRY
Active Settings Group Group that the relay will act upon G1
Settings Group Edit/View Group to be displayed on the LCD G1
Local P/F Rating Local relay’s phase fault CT rating 1A
Local E/F Rating Local relay’s earth fault CT rating 1A
Local P/F CT Ratio relay’s phase input CT ratio 1000:1
Local E/F CT Ratio relay’s earth input CT ratio 1000:1
Remote P/F Rating Remote relay’s phase fault CT rating 1A
Remote P/F CT Ratio Remote relay’s earth fault CT rating 1000:1
Current Display display mode to use for the relay xIn
Set Identifier 16 character alphanumeric code CB56 SOLKOR
Set Alarm 1 ALARM 1
Calendar – Set Date DD/MM/YY Todays Date
Clock - Set Time HH:MM:SS Actual Time
Clock Sync. From Status Seconds or Minutes Minutes
Default Screen Timer 10sec, 60sec, 5min, 1hour 5 min
Change Password 4 alphanumeric characters NONE

DIFF' PROTECTION MENU ONLY


SCREEN FUNCTION MENU ENTRY
Gn P/F Diff. Setting* setting for the differential element 0.3 x In
Gn P/F Bias Slope 1* 1st bias slope differential element 30%
Gn P/F Bias Slope 2* 2nd bias slope differential element 150%
Gn Bias Break Point* bias slope break point 1 to 2 2.00 x In
Gn Differential Delay trip time differential element/ intertrip 0.0s
P/F CT Ratio Correction CT ratio correction 1
Remote P/F Ratio Correction CT ratio correction 1
Gn Internal Intertrip enables / disables internal intertrips OFF
Gn Int Intertrip Delay internal intertrip elements 0.00s
Gn External Intertrip enables / disables external intertrips ON
Gn Ext Intertrip Delay external intertrip elements 0.00s

O/C PROTECTION MENU ONLY


SCREEN FUNCTION MENU ENTRY
Gn P/F Charact. Setting phase fault O/C pick-up level OFF
Gn P/F Charact. phase fault O/C characteristic
Gn P/F Charact. Time Mult phase fault TMS
Gn P/F Charact. Delay phase fault delay DTL
Gn P/F Lowset Setting phase fault lowset pick-up OFF
Gn P/F Lowset Delay phase fault lowset delay
Gn P/F Highset1 Setting phase fault highset 1 pick-up OFF
Gn P/F Highset1 Delay phase fault highset 1 delay
Gn P/F Highset2 Setting phase fault highset 2 pick-up OFF
Gn P/F Highset2 Delay phase fault highset 2 delay
Gn E/F Charact. Setting earth fault O/C pick-up level OFF
Gn E/F Charact. earth fault O/C characteristic
Gn E/F Charact. Time Mult earth fault TMS
Gn E/F Charact. Delay earth fault delay DTL
Gn E/F Lowset Setting earth fault lowset pick-up OFF
Gn E/F Lowset Delay earth fault lowset delay
Gn E/F Highset1 Setting earth fault highset 1 pick-up OFF
Gn E/F Highset1 Delay earth fault highset 1 delay
Gn E/F Highset 2 Setting earth fault highset 2 pick-up OFF
Gn E/F Highset 2 Delay earth fault highset 2 delay
Gn CB Fail Time Delay 1 1st time delay for CB Fail OFF
Gn CB Fail Time Delay2 2nd time delay for CB Fail OFF
Gn P/F CB Fail Setting sets over current CB Fail level OFF
Gn E/F CB Fail Setting sets earth fault current CB Fail level OFF
Gn CT Failure Setting sets CT Failure level OFF
Gn CT Failure Delay sets delay for CT Failure 1s
Gn Relay Reset Delay OC reset characteristic INST
O/P RELAY CONFIG MENU ONLY
Gn Prot. Healthy RL1
Gn P/F Diff. RL4

5 Broadgate Protective Device Settings HVSB-13XX04 Rev 4 5 of 9 CB56 SOLKOR


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 57. To loadbank panel HVSB14XX01 (CB 75)


Device SEPAM S80
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 1250/800/1A on 800A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 140A Is = 95A
50N/51N - 1 Trip CB P T = 1105ms T = 620ms
Group A ON Curve = RI Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 2 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - Elements 3~8
50N/51N - Elements 2~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 140A Is = 95A
50N/51N - 1 Trip CB P T = 1105ms T = 620ms
Group B ON Curve = RI Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 2 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P SWITCHED OFF SWITCHED OFF
Group B OFF
50/51 - Elements 3~8
50N/51N - Elements 1~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
79 Re-closer
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-13XX04 Rev 4 6 of 9 CB 57


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

11 kV INTERLINK, CB 59. Interlinking Gen boards HVSB13XX04 to


Description
HVSB13XX05
Device SEPAM S80
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 1250/800/1A on 800A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 780A Is = 95A
50N/51N - 1 Trip CB P T = 2000ms T = 620ms
Group A ON Curve = DT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 2 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P SWITCHED OFF SWITCHED OFF
Group A ON
50/51 - Elements 3~8
50N/51N - Elements 2~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 780A Is = 95A
50N/51N - 1 Trip CB P T = 2000ms T = 620ms
Group B ON Curve = DT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 2 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P SWITCHED OFF SWITCHED OFF
Group B OFF
50/51 - Elements 3~8
50N/51N - Elements 1~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
79 Re-closer
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-13XX04 Rev 4 7 of 9 CB 59


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV INTERLINK, CB 59. Interlinking Gen boards HVSB13XX04 to HVSB13XX05


Device SOLKOR 7SG18 N
Select
CT Ratio 1000/1A on 1000A Range
SETTINGS GROUP G MENU ONLY
SCREEN FUNCTION MENU ENTRY
Active Settings Group Group that the relay will act upon G1
Settings Group Edit/View Group to be displayed on the LCD G1
Local P/F Rating Local relay’s phase fault CT rating 1A
Local E/F Rating Local relay’s earth fault CT rating 1A
Local P/F CT Ratio relay’s phase input CT ratio 1000:1
Local E/F CT Ratio relay’s earth input CT ratio 1000:1
Remote P/F Rating Remote relay’s phase fault CT rating 1A
Remote P/F CT Ratio Remote relay’s earth fault CT rating 1000:1
Current Display display mode to use for the relay xIn
Set Identifier 16 character alphanumeric code CB59 SOLKOR
Set Alarm 1 ALARM 1
Calendar – Set Date DD/MM/YY Todays Date
Clock - Set Time HH:MM:SS Actual Time
Clock Sync. From Status Seconds or Minutes Minutes
Default Screen Timer 10sec, 60sec, 5min, 1hour 5 min
Change Password 4 alphanumeric characters NONE

DIFF' PROTECTION MENU ONLY


SCREEN FUNCTION MENU ENTRY
Gn P/F Diff. Setting* setting for the differential element 0.3 x In
Gn P/F Bias Slope 1* 1st bias slope differential element 30%
Gn P/F Bias Slope 2* 2nd bias slope differential element 150%
Gn Bias Break Point* bias slope break point 1 to 2 2.00 x In
Gn Differential Delay trip time differential element/ intertrip 0.0s
P/F CT Ratio Correction CT ratio correction 1
Remote P/F Ratio Correction CT ratio correction 1
Gn Internal Intertrip enables / disables internal intertrips OFF
Gn Int Intertrip Delay internal intertrip elements 0.00s
Gn External Intertrip enables / disables external intertrips ON
Gn Ext Intertrip Delay external intertrip elements 0.00s

O/C PROTECTION MENU ONLY


SCREEN FUNCTION MENU ENTRY
Gn P/F Charact. Setting phase fault O/C pick-up level OFF
Gn P/F Charact. phase fault O/C characteristic
Gn P/F Charact. Time Mult phase fault TMS
Gn P/F Charact. Delay phase fault delay DTL
Gn P/F Lowset Setting phase fault lowset pick-up OFF
Gn P/F Lowset Delay phase fault lowset delay
Gn P/F Highset1 Setting phase fault highset 1 pick-up OFF
Gn P/F Highset1 Delay phase fault highset 1 delay
Gn P/F Highset2 Setting phase fault highset 2 pick-up OFF
Gn P/F Highset2 Delay phase fault highset 2 delay
Gn E/F Charact. Setting earth fault O/C pick-up level OFF
Gn E/F Charact. earth fault O/C characteristic
Gn E/F Charact. Time Mult earth fault TMS
Gn E/F Charact. Delay earth fault delay DTL
Gn E/F Lowset Setting earth fault lowset pick-up OFF
Gn E/F Lowset Delay earth fault lowset delay
Gn E/F Highset1 Setting earth fault highset 1 pick-up OFF
Gn E/F Highset1 Delay earth fault highset 1 delay
Gn E/F Highset 2 Setting earth fault highset 2 pick-up OFF
Gn E/F Highset 2 Delay earth fault highset 2 delay
Gn CB Fail Time Delay 1 1st time delay for CB Fail OFF
Gn CB Fail Time Delay2 2nd time delay for CB Fail OFF
Gn P/F CB Fail Setting sets over current CB Fail level OFF
Gn E/F CB Fail Setting sets earth fault current CB Fail level OFF
Gn CT Failure Setting sets CT Failure level OFF
Gn CT Failure Delay sets delay for CT Failure 1s
Gn Relay Reset Delay OC reset characteristic INST
O/P RELAY CONFIG MENU ONLY
Gn Prot. Healthy RL1
Gn P/F Diff. RL4

5 Broadgate Protective Device Settings HVSB-13XX04 Rev 4 8 of 9 CB59 SOLKOR


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV GEN FEEDER, CB 60 Circuit GEN12XX05


Device SPEAM G87
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 200/100/1A on 200A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 150A Is = 105A
50N/51N - 1 Trip CB P T = 3100ms T = 870ms
Group A ON P Curve = DT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 2 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 150A Is = 105A
50N/51N - 1 Trip CB P T = 3100ms T = 870ms
Group B ON P Curve = DT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 2 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P SWITCHED OFF SWITCHED OFF
Group B OFF
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
49RMS thermal overload for machines
87M Machine differential
87M - 1 Latching P Is = 20A
Trip CB P
67 Directional phase overcurrent
67 - 1 Latching P 1 2
67 - 2 Trip CB P Is = 75A
Group A ON P T = 0ms
SWITCHED OFF
Curve = DT
Angle 45o Line
67 - 1 Latching P Is = 75A
67 - 2 Trip CB P T = 0ms
SWITCHED OFF
Group B ON P Curve = DT
Angle 45o Line
67N Directional earth fault
32P directional active overpower
32Q Directional reactive overpower
40 Field loss (under impedance)
78PS Pole slip
12-14 Overspeed - Underspeed
50V/ 51V Voltage-restrained overcurrent
21B Under impedance
50/27 Inadvertent energisation
24 Overfluxing (V / Hz)
27 under voltage (L-L or L-N)
27D Positive sequence undercurrent
27R Remanent undervoltage
27TN/ 64G2/ 64G 3rd harmonic undervoltage / 100% stator earth fault
59 overvoltage (L-L or L-N)
59N Neutral Voltage Displacement
Latching P 1 2
59N - 1
Trip CB P Unp = 15% Unp = 20%
Latching P T = 4s T = 100ms
59N - 2
Trip CB P Curve = IDMT Curve = DT
47 Negative Sequence Overvoltage
81H over frequency
81L under frequency
38/ 49T Temperature Monitoring (No OFF, output can be disabled)
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-13XX05 Rev 4 1 of 9 CB 60


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

11 kV INTERLINK, CB 61. Interlinking Gen boards HVSB13XX05 to


Description
HVSB13XX04
Device SEPAM S80
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 1250/800/1A on 800A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 780A Is = 95A
50N/51N - 1 Trip CB P T = 2000ms T = 620ms
Group A ON Curve = DT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 2 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - Elements 3~8
50N/51N - Elements 2~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 780A Is = 95A
50N/51N - 1 Trip CB P T = 2000ms T = 620ms
Group B ON Curve = DT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 2 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P SWITCHED OFF SWITCHED OFF
Group B OFF
50/51 - Elements 3~8
50N/51N - Elements 1~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
79 Re-closer
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-13XX05 Rev 4 2 of 9 CB 61


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV INTERLINK, CB 61. Interlinking Gen boards HVSB13XX05 to HVSB13XX04


Device SOLKOR 7SG18 N
Select
CT Ratio 1000/1A on 1000A Range
SETTINGS GROUP G MENU ONLY
SCREEN FUNCTION MENU ENTRY
Active Settings Group Group that the relay will act upon G1
Settings Group Edit/View Group to be displayed on the LCD G1
Local P/F Rating Local relay’s phase fault CT rating 1A
Local E/F Rating Local relay’s earth fault CT rating 1A
Local P/F CT Ratio relay’s phase input CT ratio 1000:1
Local E/F CT Ratio relay’s earth input CT ratio 1000:1
Remote P/F Rating Remote relay’s phase fault CT rating 1A
Remote P/F CT Ratio Remote relay’s earth fault CT rating 1000:1
Current Display display mode to use for the relay xIn
Set Identifier 16 character alphanumeric code CB61 SOLKOR
Set Alarm 1 ALARM 1
Calendar – Set Date DD/MM/YY Todays Date
Clock - Set Time HH:MM:SS Actual Time
Clock Sync. From Status Seconds or Minutes Minutes
Default Screen Timer 10sec, 60sec, 5min, 1hour 5 min
Change Password 4 alphanumeric characters NONE

DIFF' PROTECTION MENU ONLY


SCREEN FUNCTION MENU ENTRY
Gn P/F Diff. Setting* setting for the differential element 0.3 x In
Gn P/F Bias Slope 1* 1st bias slope differential element 30%
Gn P/F Bias Slope 2* 2nd bias slope differential element 150%
Gn Bias Break Point* bias slope break point 1 to 2 2.00 x In
Gn Differential Delay trip time differential element/ intertrip 0.0s
P/F CT Ratio Correction CT ratio correction 1
Remote P/F Ratio Correction CT ratio correction 1
Gn Internal Intertrip enables / disables internal intertrips OFF
Gn Int Intertrip Delay internal intertrip elements 0.00s
Gn External Intertrip enables / disables external intertrips ON
Gn Ext Intertrip Delay external intertrip elements 0.00s

O/C PROTECTION MENU ONLY


SCREEN FUNCTION MENU ENTRY
Gn P/F Charact. Setting phase fault O/C pick-up level OFF
Gn P/F Charact. phase fault O/C characteristic
Gn P/F Charact. Time Mult phase fault TMS
Gn P/F Charact. Delay phase fault delay DTL
Gn P/F Lowset Setting phase fault lowset pick-up OFF
Gn P/F Lowset Delay phase fault lowset delay
Gn P/F Highset1 Setting phase fault highset 1 pick-up OFF
Gn P/F Highset1 Delay phase fault highset 1 delay
Gn P/F Highset2 Setting phase fault highset 2 pick-up OFF
Gn P/F Highset2 Delay phase fault highset 2 delay
Gn E/F Charact. Setting earth fault O/C pick-up level OFF
Gn E/F Charact. earth fault O/C characteristic
Gn E/F Charact. Time Mult earth fault TMS
Gn E/F Charact. Delay earth fault delay DTL
Gn E/F Lowset Setting earth fault lowset pick-up OFF
Gn E/F Lowset Delay earth fault lowset delay
Gn E/F Highset1 Setting earth fault highset 1 pick-up OFF
Gn E/F Highset1 Delay earth fault highset 1 delay
Gn E/F Highset2 Setting earth fault highset 2 pick-up OFF
Gn E/F Highset 2 Delay earth fault highset 2 delay
Gn CB Fail Time Delay 1 1st time delay for CB Fail OFF
Gn CB Fail Time Delay2 2nd time delay for CB Fail OFF
Gn P/F CB Fail Setting sets over current CB Fail level OFF
Gn E/F CB Fail Setting sets earth fault current CB Fail level OFF
Gn CT Failure Setting sets CT Failure level OFF
Gn CT Failure Delay sets delay for CT Failure 1s
Gn Relay Reset Delay OC reset characteristic INST
O/P RELAY CONFIG MENU ONLY
Gn Prot. Healthy RL1
Gn P/F Diff. RL4

5 Broadgate Protective Device Settings HVSB-13XX05 Rev 4 3 of 9 CB61 SOLKOR


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 62 Circuit H21


Device SEPAM S80
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 1250/800/1A on 800A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 780A Is = 95A
50N/51N - 1 Trip CB P T = 2000ms T = 620ms
Group A ON Curve = DT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 2 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - Elements 3~8
50N/51N - Elements 2~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 780A Is = 95A
50N/51N - 1 Trip CB P T = 2000ms T = 620ms
Group B ON Curve = DT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 2 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P SWITCHED OFF SWITCHED OFF
Group B OFF
50/51 - Elements 3~8
50N/51N - Elements 1~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
79 Re-closer
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-13XX05 Rev 4 4 of 9 CB 62


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 62 Circuit H21


Device SOLKOR 7SG18 N
Select
CT Ratio 1000/1A on 1000A Range
SETTINGS GROUP G MENU ONLY
SCREEN FUNCTION MENU ENTRY
Active Settings Group Group that the relay will act upon G1
Settings Group Edit/View Group to be displayed on the LCD G1
Local P/F Rating Local relay’s phase fault CT rating 1A
Local E/F Rating Local relay’s earth fault CT rating 1A
Local P/F CT Ratio relay’s phase input CT ratio 1000:1
Local E/F CT Ratio relay’s earth input CT ratio 1000:1
Remote P/F Rating Remote relay’s phase fault CT rating 1A
Remote P/F CT Ratio Remote relay’s earth fault CT rating 1000:1
Current Display display mode to use for the relay xIn
Set Identifier 16 character alphanumeric code CB62 SOLKOR
Set Alarm 1 ALARM 1
Calendar – Set Date DD/MM/YY Todays Date
Clock - Set Time HH:MM:SS Actual Time
Clock Sync. From Status Seconds or Minutes Minutes
Default Screen Timer 10sec, 60sec, 5min, 1hour 5 min
Change Password 4 alphanumeric characters NONE

DIFF' PROTECTION MENU ONLY


SCREEN FUNCTION MENU ENTRY
Gn P/F Diff. Setting* setting for the differential element 0.3 x In
Gn P/F Bias Slope 1* 1st bias slope differential element 30%
Gn P/F Bias Slope 2* 2nd bias slope differential element 150%
Gn Bias Break Point* bias slope break point 1 to 2 2.00 x In
Gn Differential Delay trip time differential element/ intertrip 0.0s
P/F CT Ratio Correction CT ratio correction 1
Remote P/F Ratio Correction CT ratio correction 1
Gn Internal Intertrip enables / disables internal intertrips OFF
Gn Int Intertrip Delay internal intertrip elements 0.00s
Gn External Intertrip enables / disables external intertrips ON
Gn Ext Intertrip Delay external intertrip elements 0.00s

O/C PROTECTION MENU ONLY


SCREEN FUNCTION MENU ENTRY
Gn P/F Charact. Setting phase fault O/C pick-up level OFF
Gn P/F Charact. phase fault O/C characteristic
Gn P/F Charact. Time Mult phase fault TMS
Gn P/F Charact. Delay phase fault delay DTL
Gn P/F Lowset Setting phase fault lowset pick-up OFF
Gn P/F Lowset Delay phase fault lowset delay
Gn P/F Highset1 Setting phase fault highset 1 pick-up OFF
Gn P/F Highset1 Delay phase fault highset 1 delay
Gn P/F Highset2 Setting phase fault highset 2 pick-up OFF
Gn P/F Highset2 Delay phase fault highset 2 delay
Gn E/F Charact. Setting earth fault O/C pick-up level OFF
Gn E/F Charact. earth fault O/C characteristic
Gn E/F Charact. Time Mult earth fault TMS
Gn E/F Charact. Delay earth fault delay DTL
Gn E/F Lowset Setting earth fault lowset pick-up OFF
Gn E/F Lowset Delay earth fault lowset delay
Gn E/F Highset1 Setting earth fault highset 1 pick-up OFF
Gn E/F Highset1 Delay earth fault highset 1 delay
Gn E/F Highset2 Setting earth fault highset 2 pick-up OFF
Gn E/F Highset 2 Delay earth fault highset 2 delay
Gn CB Fail Time Delay 1 1st time delay for CB Fail OFF
Gn CB Fail Time Delay2 2nd time delay for CB Fail OFF
Gn P/F CB Fail Setting sets over current CB Fail level OFF
Gn E/F CB Fail Setting sets earth fault current CB Fail level OFF
Gn CT Failure Setting sets CT Failure level OFF
Gn CT Failure Delay sets delay for CT Failure 1s
Gn Relay Reset Delay OC reset characteristic INST
O/P RELAY CONFIG MENU ONLY
Gn Prot. Healthy RL1
Gn P/F Diff. RL4

5 Broadgate Protective Device Settings HVSB-13XX05 Rev 4 5 of 9 CB62 SOLKOR


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 63. To loadbank panel HVSB14XX01 (CB 74)


Device SEPAM S80
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 1250/800/1A on 800A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 140A Is = 95A
50N/51N - 1 Trip CB P T = 1105ms T = 620ms
Group A ON Curve = RI Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 2 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - Elements 3~8
50N/51N - Elements 2~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 140A Is = 95A
50N/51N - 1 Trip CB P T = 1105ms T = 620ms
Group B ON Curve = RI Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 2 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P SWITCHED OFF SWITCHED OFF
Group B OFF
50/51 - Elements 3~8
50N/51N - Elements 1~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
79 Re-closer
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-13XX05 Rev 4 6 of 9 CB 63


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV GEN FEEDER, CB 64 Circuit GEN12XX06


Device SPEAM G87
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 200/100/1A on 200A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 150A Is = 105A
50N/51N - 1 Trip CB P T = 3100ms T = 870ms
Group A ON P Curve = DT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 2 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 150A Is = 105A
50N/51N - 1 Trip CB P T = 3100ms T = 870ms
Group B ON P Curve = DT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 2 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P SWITCHED OFF SWITCHED OFF
Group B OFF
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
49RMS thermal overload for machines
87M Machine differential
87M - 1 Latching P Is = 20A
Trip CB P
67 Directional phase overcurrent
67 - 1 Latching P 1 2
67 - 2 Trip CB P Is = 75A
Group A ON P T = 0ms
SWITCHED OFF
Curve = DT
Angle 45o Line
67 - 1 Latching P Is = 75A
67 - 2 Trip CB P T = 0ms
SWITCHED OFF
Group B ON P Curve = DT
Angle 45o Line
67N Directional earth fault
32P directional active overpower
32Q Directional reactive overpower
40 Field loss (under impedance)
78PS Pole slip
12-14 Overspeed - Underspeed
50V/ 51V Voltage-restrained overcurrent
21B Under impedance
50/27 Inadvertent energisation
24 Overfluxing (V / Hz)
27 under voltage (L-L or L-N)
27D Positive sequence undercurrent
27R Remanent undervoltage
27TN/ 64G2/ 64G 3rd harmonic undervoltage / 100% stator earth fault
59 overvoltage (L-L or L-N)
59N Neutral Voltage Displacement
Latching P 1 2
59N - 1
Trip CB P Unp = 15% Unp = 20%
Latching P T = 4s T = 100ms
59N - 2
Trip CB P Curve = IDMT Curve = DT
47 Negative Sequence Overvoltage
81H over frequency
81L under frequency
38/ 49T Temperature Monitoring (No OFF, output can be disabled)
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-13XX05 Rev 4 9 of 9 CB 64


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

11 kV INTERLINK, CB 65. Interlinking Gen boards HVSB13XX05 to


Description
HVSB13XX06
Device SEPAM S80
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 1250/800/1A on 800A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 780A Is = 95A
50N/51N - 1 Trip CB P T = 2000ms T = 620ms
Group A ON Curve = DT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 2 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - Elements 3~8
50N/51N - Elements 2~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 780A Is = 95A
50N/51N - 1 Trip CB P T = 2000ms T = 620ms
Group B ON Curve = DT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 2 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P SWITCHED OFF SWITCHED OFF
Group B OFF
50/51 - Elements 3~8
50N/51N - Elements 1~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
79 Re-closer
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-13XX05 Rev 4 7 of 9 CB 65


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV INTERLINK, CB 65. Interlinking Gen boards HVSB13XX05 to HVSB13XX06


Device SOLKOR 7SG18 N
Select
CT Ratio 1000/1A on 1000A Range
SETTINGS GROUP G MENU ONLY
SCREEN FUNCTION MENU ENTRY
Active Settings Group Group that the relay will act upon G1
Settings Group Edit/View Group to be displayed on the LCD G1
Local P/F Rating Local relay’s phase fault CT rating 1A
Local E/F Rating Local relay’s earth fault CT rating 1A
Local P/F CT Ratio relay’s phase input CT ratio 1000:1
Local E/F CT Ratio relay’s earth input CT ratio 1000:1
Remote P/F Rating Remote relay’s phase fault CT rating 1A
Remote P/F CT Ratio Remote relay’s earth fault CT rating 1000:1
Current Display display mode to use for the relay xIn
Set Identifier 16 character alphanumeric code CB65 SOLKOR
Set Alarm 1 ALARM 1
Calendar – Set Date DD/MM/YY Todays Date
Clock - Set Time HH:MM:SS Actual Time
Clock Sync. From Status Seconds or Minutes Minutes
Default Screen Timer 10sec, 60sec, 5min, 1hour 5 min
Change Password 4 alphanumeric characters NONE

DIFF' PROTECTION MENU ONLY


SCREEN FUNCTION MENU ENTRY
Gn P/F Diff. Setting* setting for the differential element 0.3 x In
Gn P/F Bias Slope 1* 1st bias slope differential element 30%
Gn P/F Bias Slope 2* 2nd bias slope differential element 150%
Gn Bias Break Point* bias slope break point 1 to 2 2.00 x In
Gn Differential Delay trip time differential element/ intertrip 0.0s
P/F CT Ratio Correction CT ratio correction 1
Remote P/F Ratio Correction CT ratio correction 1
Gn Internal Intertrip enables / disables internal intertrips OFF
Gn Int Intertrip Delay internal intertrip elements 0.00s
Gn External Intertrip enables / disables external intertrips ON
Gn Ext Intertrip Delay external intertrip elements 0.00s

O/C PROTECTION MENU ONLY


SCREEN FUNCTION MENU ENTRY
Gn P/F Charact. Setting phase fault O/C pick-up level OFF
Gn P/F Charact. phase fault O/C characteristic
Gn P/F Charact. Time Mult phase fault TMS
Gn P/F Charact. Delay phase fault delay DTL
Gn P/F Lowset Setting phase fault lowset pick-up OFF
Gn P/F Lowset Delay phase fault lowset delay
Gn P/F Highset1 Setting phase fault highset 1 pick-up OFF
Gn P/F Highset1 Delay phase fault highset 1 delay
Gn P/F Highset2 Setting phase fault highset 2 pick-up OFF
Gn P/F Highset2 Delay phase fault highset 2 delay
Gn E/F Charact. Setting earth fault O/C pick-up level OFF
Gn E/F Charact. earth fault O/C characteristic
Gn E/F Charact. Time Mult earth fault TMS
Gn E/F Charact. Delay earth fault delay DTL
Gn E/F Lowset Setting earth fault lowset pick-up OFF
Gn E/F Lowset Delay earth fault lowset delay
Gn E/F Highset1 Setting earth fault highset 1 pick-up OFF
Gn E/F Highset1 Delay earth fault highset 1 delay
Gn E/F Highset2 Setting earth fault highset 2 pick-up OFF
Gn E/F Highset 2 Delay earth fault highset 2 delay
Gn CB Fail Time Delay 1 1st time delay for CB Fail OFF
Gn CB Fail Time Delay2 2nd time delay for CB Fail OFF
Gn P/F CB Fail Setting sets over current CB Fail level OFF
Gn E/F CB Fail Setting sets earth fault current CB Fail level OFF
Gn CT Failure Setting sets CT Failure level OFF
Gn CT Failure Delay sets delay for CT Failure 1s
Gn Relay Reset Delay OC reset characteristic INST
O/P RELAY CONFIG MENU ONLY
Gn Prot. Healthy RL1
Gn P/F Diff. RL4

5 Broadgate Protective Device Settings HVSB-13XX05 Rev 4 8 of 9 CB65 SOLKOR


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV GEN FEEDER, CB 66 Circuit GEN13XX01


Device SPEAM G87
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 200/100/1A on 200A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 150A Is = 105A
50N/51N - 1 Trip CB P T = 3100ms T = 870ms
Group A ON P Curve = DT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 2 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 150A Is = 105A
50N/51N - 1 Trip CB P T = 3100ms T = 870ms
Group B ON P Curve = DT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 2 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P SWITCHED OFF SWITCHED OFF
Group B OFF
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
49RMS thermal overload for machines
87M Machine differential
87M - 1 Latching P Is = 20A
Trip CB P
67 Directional phase overcurrent
67 - 1 Latching P 1 2
67 - 2 Trip CB P Is = 75A
Group A ON P T = 0ms
SWITCHED OFF
Curve = DT
Angle 45o Line
67 - 1 Latching P Is = 75A
67 - 2 Trip CB P T = 0ms
SWITCHED OFF
Group B ON P Curve = DT
Angle 45o Line
67N Directional earth fault
32P directional active overpower
32Q Directional reactive overpower
40 Field loss (under impedance)
78PS Pole slip
12-14 Overspeed - Underspeed
50V/ 51V Voltage-restrained overcurrent
21B Under impedance
50/27 Inadvertent energisation
24 Overfluxing (V / Hz)
27 under voltage (L-L or L-N)
27D Positive sequence undercurrent
27R Remanent undervoltage
27TN/ 64G2/ 64G 3rd harmonic undervoltage / 100% stator earth fault
59 overvoltage (L-L or L-N)
59N Neutral Voltage Displacement
Latching P 1 2
59N - 1
Trip CB P Unp = 15% Unp = 20%
Latching P T = 4s T = 100ms
59N - 2
Trip CB P Curve = IDMT Curve = DT
47 Negative Sequence Overvoltage
81H over frequency
81L under frequency
38/ 49T Temperature Monitoring (No OFF, output can be disabled)
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-13XX06 Rev 4 1 of 9 CB 66


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

11 kV INTERLINK, CB 67. Interlinking Gen boards HVSB13XX06 to


Description
HVSB13XX05
Device SEPAM S80
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 1250/800/1A on 800A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 780A Is = 95A
50N/51N - 1 Trip CB P T = 2000ms T = 620ms
Group A ON Curve = DT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 2 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - Elements 3~8
50N/51N - Elements 2~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 780A Is = 95A
50N/51N - 1 Trip CB P T = 2000ms T = 620ms
Group B ON Curve = DT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 2 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P SWITCHED OFF SWITCHED OFF
Group B OFF
50/51 - Elements 3~8
50N/51N - Elements 1~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
79 Re-closer
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-13XX06 Rev 4 2 of 9 CB 67


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV INTERLINK, CB 67. Interlinking Gen boards HVSB13XX06 to HVSB13XX05


Device SOLKOR 7SG18 N
Select
CT Ratio 1000/1A on 1000A Range
SETTINGS GROUP G MENU ONLY
SCREEN FUNCTION MENU ENTRY
Active Settings Group Group that the relay will act upon G1
Settings Group Edit/View Group to be displayed on the LCD G1
Local P/F Rating Local relay’s phase fault CT rating 1A
Local E/F Rating Local relay’s earth fault CT rating 1A
Local P/F CT Ratio relay’s phase input CT ratio 1000:1
Local E/F CT Ratio relay’s earth input CT ratio 1000:1
Remote P/F Rating Remote relay’s phase fault CT rating 1A
Remote P/F CT Ratio Remote relay’s earth fault CT rating 1000:1
Current Display display mode to use for the relay xIn
Set Identifier 16 character alphanumeric code CB67 SOLKOR
Set Alarm 1 ALARM 1
Calendar – Set Date DD/MM/YY Todays Date
Clock - Set Time HH:MM:SS Actual Time
Clock Sync. From Status Seconds or Minutes Minutes
Default Screen Timer 10sec, 60sec, 5min, 1hour 5 min
Change Password 4 alphanumeric characters NONE

DIFF' PROTECTION MENU ONLY


SCREEN FUNCTION MENU ENTRY
Gn P/F Diff. Setting* setting for the differential element 0.3 x In
Gn P/F Bias Slope 1* 1st bias slope differential element 30%
Gn P/F Bias Slope 2* 2nd bias slope differential element 150%
Gn Bias Break Point* bias slope break point 1 to 2 2.00 x In
Gn Differential Delay trip time differential element/ intertrip 0.0s
P/F CT Ratio Correction CT ratio correction 1
Remote P/F Ratio Correction CT ratio correction 1
Gn Internal Intertrip enables / disables internal intertrips OFF
Gn Int Intertrip Delay internal intertrip elements 0.00s
Gn External Intertrip enables / disables external intertrips ON
Gn Ext Intertrip Delay external intertrip elements 0.00s

O/C PROTECTION MENU ONLY


SCREEN FUNCTION MENU ENTRY
Gn P/F Charact. Setting phase fault O/C pick-up level OFF
Gn P/F Charact. phase fault O/C characteristic
Gn P/F Charact. Time Mult phase fault TMS
Gn P/F Charact. Delay phase fault delay DTL
Gn P/F Lowset Setting phase fault lowset pick-up OFF
Gn P/F Lowset Delay phase fault lowset delay
Gn P/F Highset1 Setting phase fault highset 1 pick-up OFF
Gn P/F Highset1 Delay phase fault highset 1 delay
Gn P/F Highset2 Setting phase fault highset 2 pick-up OFF
Gn P/F Highset2 Delay phase fault highset 2 delay
Gn E/F Charact. Setting earth fault O/C pick-up level OFF
Gn E/F Charact. earth fault O/C characteristic
Gn E/F Charact. Time Mult earth fault TMS
Gn E/F Charact. Delay earth fault delay DTL
Gn E/F Lowset Setting earth fault lowset pick-up OFF
Gn E/F Lowset Delay earth fault lowset delay
Gn E/F Highset1 Setting earth fault highset 1 pick-up OFF
Gn E/F Highset1 Delay earth fault highset 1 delay
Gn E/F Highset 2 Setting earth fault highset 2 pick-up OFF
Gn E/F Highset 2 Delay earth fault highset 2 delay
Gn CB Fail Time Delay 1 1st time delay for CB Fail OFF
Gn CB Fail Time Delay2 2nd time delay for CB Fail OFF
Gn P/F CB Fail Setting sets over current CB Fail level OFF
Gn E/F CB Fail Setting sets earth fault current CB Fail level OFF
Gn CT Failure Setting sets CT Failure level OFF
Gn CT Failure Delay sets delay for CT Failure 1s
Gn Relay Reset Delay OC reset characteristic INST
O/P RELAY CONFIG MENU ONLY
Gn Prot. Healthy RL1
Gn P/F Diff. RL4

5 Broadgate Protective Device Settings HVSB-13XX06 Rev 4 3 of 9 CB67 SOLKOR


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 68 Circuit H22


Device SEPAM S80
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 1250/800/1A on 800A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 780A Is = 95A
50N/51N - 1 Trip CB P T = 2000ms T = 620ms
Group A ON Curve = DT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 2 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - Elements 3~8
50N/51N - Elements 2~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 780A Is = 95A
50N/51N - 1 Trip CB P T = 2000ms T = 620ms
Group B ON Curve = DT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 2 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P SWITCHED OFF SWITCHED OFF
Group B OFF
50/51 - Elements 3~8
50N/51N - Elements 1~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
79 Re-closer
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-13XX06 Rev 4 4 of 9 CB 68


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 68 Circuit H22


Device SOLKOR 7SG18 N
Select
CT Ratio 1000/1A on 1000A Range
SETTINGS GROUP G MENU ONLY
SCREEN FUNCTION MENU ENTRY
Active Settings Group Group that the relay will act upon G1
Settings Group Edit/View Group to be displayed on the LCD G1
Local P/F Rating Local relay’s phase fault CT rating 1A
Local E/F Rating Local relay’s earth fault CT rating 1A
Local P/F CT Ratio relay’s phase input CT ratio 1000:1
Local E/F CT Ratio relay’s earth input CT ratio 1000:1
Remote P/F Rating Remote relay’s phase fault CT rating 1A
Remote P/F CT Ratio Remote relay’s earth fault CT rating 1000:1
Current Display display mode to use for the relay xIn
Set Identifier 16 character alphanumeric code CB68 SOLKOR
Set Alarm 1 ALARM 1
Calendar – Set Date DD/MM/YY Todays Date
Clock - Set Time HH:MM:SS Actual Time
Clock Sync. From Status Seconds or Minutes Minutes
Default Screen Timer 10sec, 60sec, 5min, 1hour 5 min
Change Password 4 alphanumeric characters NONE

DIFF' PROTECTION MENU ONLY


SCREEN FUNCTION MENU ENTRY
Gn P/F Diff. Setting* setting for the differential element 0.3 x In
Gn P/F Bias Slope 1* 1st bias slope differential element 30%
Gn P/F Bias Slope 2* 2nd bias slope differential element 150%
Gn Bias Break Point* bias slope break point 1 to 2 2.00 x In
Gn Differential Delay trip time differential element/ intertrip 0.0s
P/F CT Ratio Correction CT ratio correction 1
Remote P/F Ratio Correction CT ratio correction 1
Gn Internal Intertrip enables / disables internal intertrips OFF
Gn Int Intertrip Delay internal intertrip elements 0.00s
Gn External Intertrip enables / disables external intertrips ON
Gn Ext Intertrip Delay external intertrip elements 0.00s

O/C PROTECTION MENU ONLY


SCREEN FUNCTION MENU ENTRY
Gn P/F Charact. Setting phase fault O/C pick-up level OFF
Gn P/F Charact. phase fault O/C characteristic
Gn P/F Charact. Time Mult phase fault TMS
Gn P/F Charact. Delay phase fault delay DTL
Gn P/F Lowset Setting phase fault lowset pick-up OFF
Gn P/F Lowset Delay phase fault lowset delay
Gn P/F Highset1 Setting phase fault highset 1 pick-up OFF
Gn P/F Highset1 Delay phase fault highset 1 delay
Gn P/F Highset2 Setting phase fault highset 2 pick-up OFF
Gn P/F Highset2 Delay phase fault highset 2 delay
Gn E/F Charact. Setting earth fault O/C pick-up level OFF
Gn E/F Charact. earth fault O/C characteristic
Gn E/F Charact. Time Mult earth fault TMS
Gn E/F Charact. Delay earth fault delay DTL
Gn E/F Lowset Setting earth fault lowset pick-up OFF
Gn E/F Lowset Delay earth fault lowset delay
Gn E/F Highset1 Setting earth fault highset 1 pick-up OFF
Gn E/F Highset1 Delay earth fault highset 1 delay
Gn E/F Highset 2 Setting earth fault highset 2 pick-up OFF
Gn E/F Highset 2 Delay earth fault highset 2 delay
Gn CB Fail Time Delay 1 1st time delay for CB Fail OFF
Gn CB Fail Time Delay2 2nd time delay for CB Fail OFF
Gn P/F CB Fail Setting sets over current CB Fail level OFF
Gn E/F CB Fail Setting sets earth fault current CB Fail level OFF
Gn CT Failure Setting sets CT Failure level OFF
Gn CT Failure Delay sets delay for CT Failure 1s
Gn Relay Reset Delay OC reset characteristic INST
O/P RELAY CONFIG MENU ONLY
Gn Prot. Healthy RL1
Gn P/F Diff. RL4

5 Broadgate Protective Device Settings HVSB-13XX06 Rev 4 5 of 9 CB68 SOLKOR


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV FEEDER, CB 69. To loadbank panel HVSB14XX01 (CB 73)


Device SEPAM S80
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 1250/800/1A on 800A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 140A Is = 95A
50N/51N - 1 Trip CB P T = 1105ms T = 620ms
Group A ON Curve = RI Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 2 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P SWITCHED OFF SWITCHED OFF
Group A ON
50/51 - Elements 3~8
50N/51N - Elements 2~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 140A Is = 95A
50N/51N - 1 Trip CB P T = 1105ms T = 620ms
Group B ON Curve = RI Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 2 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P SWITCHED OFF SWITCHED OFF
Group B OFF
50/51 - Elements 3~8
50N/51N - Elements 1~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
79 Re-closer
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-13XX06 Rev 4 6 of 9 CB 69


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV GEN FEEDER, CB  Circuit GEN13XX02


Device SPEAM G87
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 200/100/1A on 200A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 150A Is = 105A
50N/51N - 1 Trip CB P T = 3100ms T = 870ms
Group A ON P Curve = DT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 2 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 150A Is = 105A
50N/51N - 1 Trip CB P T = 3100ms T = 870ms
Group B ON P Curve = DT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 2 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P SWITCHED OFF SWITCHED OFF
Group B OFF
50/51 - Elements 3~8
50N/51N - Elements 3~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
49RMS thermal overload for machines
87M Machine differential
87M - 1 Latching P Is = 20A
Trip CB P
67 Directional phase overcurrent
67 - 1 Latching P 1 2
67 - 2 Trip CB P Is = 75A
Group A ON P T = 0ms
SWITCHED OFF
Curve = DT
Angle 45o Line
67 - 1 Latching P Is = 75A
67 - 2 Trip CB P T = 0ms
SWITCHED OFF
Group B ON P Curve = DT
Angle 45o Line
67N Directional earth fault
32P directional active overpower
32Q Directional reactive overpower
40 Field loss (under impedance)
78PS Pole slip
12-14 Overspeed - Underspeed
50V/ 51V Voltage-restrained overcurrent
21B Under impedance
50/27 Inadvertent energisation
24 Overfluxing (V / Hz)
27 under voltage (L-L or L-N)
27D Positive sequence undercurrent
27R Remanent undervoltage
27TN/ 64G2/ 64G 3rd harmonic undervoltage / 100% stator earth fault
59 overvoltage (L-L or L-N)
59N Neutral Voltage Displacement
Latching P 1 2
59N - 1
Trip CB P Unp = 15% Unp = 20%
Latching P T = 4s T = 100ms
59N - 2
Trip CB P Curve = IDMT Curve = DT
47 Negative Sequence Overvoltage
81H over frequency
81L under frequency
38/ 49T Temperature Monitoring (No OFF, output can be disabled)
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-13XX06 Rev 4 9 of 9 CB 70


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

11 kV INTERLINK, CB 71. Interlinking Gen boards HVSB13XX06 to


Description
HVSB13XX03
Device SEPAM S80
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 1250/800/1A on 800A range
Function Overcurrent 50/51 Earth Fault 50N/51N
50/51 - 1 Latching P Is = 780A Is = 95A
50N/51N - 1 Trip CB P T = 2000ms T = 620ms
Group A ON Curve = DT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 2 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - Elements 3~8
50N/51N - Elements 2~8 SWITCHED OFF SWITCHED OFF
Group A OFF
50/51 - 1 Latching P Is = 780A Is = 95A
50N/51N - 1 Trip CB P T = 2000ms T = 620ms
Group B ON Curve = DT Curve = DT
2nd Harmonic Restraint Restraint Threshold 17% Icc = 2 kA ON
50/51 - 2 Latching P
50N/51N - 2 Trip CB P SWITCHED OFF SWITCHED OFF
Group B OFF
50/51 - Elements 3~8
50N/51N - Elements 1~8 SWITCHED OFF SWITCHED OFF
Group B OFF
50BF Breaker Failure
46 negative sequence / unbalance
27D Positive sequence undercurrent
27R Remnant undervoltage
27 Under voltage
59 Over Voltage
59N Neutral Voltage Displacement
47 Negative Sequence Over Voltage
81H over frequency
81L under frequency
79 Re-closer
25 Synchro Check

5 Broadgate Protective Device Settings HVSB-13XX06 Rev 4 7 of 9 CB 71


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV INTERLINK, CB 71. Interlinking Gen boards HVSB13XX06 to HVSB13XX03


Device SOLKOR 7SG18 N
Select
CT Ratio 1000/1A on 1000A Range
SETTINGS GROUP G MENU ONLY
SCREEN FUNCTION MENU ENTRY
Active Settings Group Group that the relay will act upon G1
Settings Group Edit/View Group to be displayed on the LCD G1
Local P/F Rating Local relay’s phase fault CT rating 1A
Local E/F Rating Local relay’s earth fault CT rating 1A
Local P/F CT Ratio relay’s phase input CT ratio 1000:1
Local E/F CT Ratio relay’s earth input CT ratio 1000:1
Remote P/F Rating Remote relay’s phase fault CT rating 1A
Remote P/F CT Ratio Remote relay’s earth fault CT rating 1000:1
Current Display display mode to use for the relay xIn
Set Identifier 16 character alphanumeric code CB71 SOLKOR
Set Alarm 1 ALARM 1
Calendar – Set Date DD/MM/YY Todays Date
Clock - Set Time HH:MM:SS Actual Time
Clock Sync. From Status Seconds or Minutes Minutes
Default Screen Timer 10sec, 60sec, 5min, 1hour 5 min
Change Password 4 alphanumeric characters NONE

DIFF' PROTECTION MENU ONLY


SCREEN FUNCTION MENU ENTRY
Gn P/F Diff. Setting* setting for the differential element 0.3 x In
Gn P/F Bias Slope 1* 1st bias slope differential element 30%
Gn P/F Bias Slope 2* 2nd bias slope differential element 150%
Gn Bias Break Point* bias slope break point 1 to 2 2.00 x In
Gn Differential Delay trip time differential element/ intertrip 0.0s
P/F CT Ratio Correction CT ratio correction 1
Remote P/F Ratio Correction CT ratio correction 1
Gn Internal Intertrip enables / disables internal intertrips OFF
Gn Int Intertrip Delay internal intertrip elements 0.00s
Gn External Intertrip enables / disables external intertrips ON
Gn Ext Intertrip Delay external intertrip elements 0.00s

O/C PROTECTION MENU ONLY


SCREEN FUNCTION MENU ENTRY
Gn P/F Charact. Setting phase fault O/C pick-up level OFF
Gn P/F Charact. phase fault O/C characteristic
Gn P/F Charact. Time Mult phase fault TMS
Gn P/F Charact. Delay phase fault delay DTL
Gn P/F Lowset Setting phase fault lowset pick-up OFF
Gn P/F Lowset Delay phase fault lowset delay
Gn P/F Highset1 Setting phase fault highset 1 pick-up OFF
Gn P/F Highset1 Delay phase fault highset 1 delay
Gn P/F Highset2 Setting phase fault highset 2 pick-up OFF
Gn P/F Highset2 Delay phase fault highset 2 delay
Gn E/F Charact. Setting earth fault O/C pick-up level OFF
Gn E/F Charact. earth fault O/C characteristic
Gn E/F Charact. Time Mult earth fault TMS
Gn E/F Charact. Delay earth fault delay DTL
Gn E/F Lowset Setting earth fault lowset pick-up OFF
Gn E/F Lowset Delay earth fault lowset delay
Gn E/F Highset1 Setting earth fault highset 1 pick-up OFF
Gn E/F Highset1 Delay earth fault highset 1 delay
Gn E/F Highset 2 Setting earth fault highset 2 pick-up OFF
Gn E/F Highset 2 Delay earth fault highset 2 delay
Gn CB Fail Time Delay 1 1st time delay for CB Fail OFF
Gn CB Fail Time Delay2 2nd time delay for CB Fail OFF
Gn P/F CB Fail Setting sets over current CB Fail level OFF
Gn E/F CB Fail Setting sets earth fault current CB Fail level OFF
Gn CT Failure Setting sets CT Failure level OFF
Gn CT Failure Delay sets delay for CT Failure 1s
Gn Relay Reset Delay OC reset characteristic INST
O/P RELAY CONFIG MENU ONLY
Gn Prot. Healthy RL1
Gn P/F Diff. RL4

5 Broadgate Protective Device Settings HVSB-13XX06 Rev 4 8 of 9 CB71 SOLKOR


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV INCOMMER, CB 73. From HVSB13XX06 (CB 69) to loadbank panel HVSB14XX01
Device VIP 400
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 200/100/1A on 200A range
PROTECTION MENU ONLY
SCREEN FUNCTION MENU ENTRY
Frequency Network Frequency 50Hz
I> 51 Phase overcurrent I> set MI/D 126A 0.125 TMS
I>> 51 Phase overcurrent I>> OFF
I>>> 50-51 Phase overcurrent I>>> DT 16 INST
Io> 51N Earth fault overcurrent Io> set point DT 25A 0.1s
Io>> 50N-51N Earth fault overcurrent Io>> set point OFF
THERMAL 49 1 Thermal overload protection OFF
THERMAL 49 2 Thermal overload protection alarm OFF
PHASE H2 RES H2 restraint on phase protection ALL
EARTH FAULT H2 RES. H2 restraint on earth fault protection ALL
Io RANGE Selection of earth fault protection EXTENDED
PARAMETERS MENU ONLY
LANGUAGE
PEAK DEMAND
LOAD HISTORY
RESET TIME
DATE
TIME
SET PASSWORD
TRIP TEST
CONTRAST
ABOUT VIP400
OUTPUT CUST (A)
CB CUSTOM (B)
(B) Parameters menu: Display of the VIP customization to the circuit breaker
PHASE CT CUa or CUb dual core sensor rating 200A
MIN TRIP TIME Activation of minimum tripping time OFF

5 Broadgate Protective Device Settings HVSB-14XX01 Rev 4 1 of 5 CB 73


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV INCOMMER, CB 74. From HVSB13XX05 (CB 63) to loadbank panel HVSB14XX01
Device VIP 400
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 200/100/1A on 200A range
PROTECTION MENU ONLY
SCREEN FUNCTION MENU ENTRY
Frequency Network Frequency 50Hz
I> 51 Phase overcurrent I> set MI/D 126A 0.125 TMS
I>> 51 Phase overcurrent I>> OFF
I>>> 50-51 Phase overcurrent I>>> DT 16 INST
Io> 51N Earth fault overcurrent Io> set point DT 25A 0.1s
Io>> 50N-51N Earth fault overcurrent Io>> set point OFF
THERMAL 49 1 Thermal overload protection OFF
THERMAL 49 2 Thermal overload protection alarm OFF
PHASE H2 RES H2 restraint on phase protection ALL
EARTH FAULT H2 RES. H2 restraint on earth fault protection ALL
Io RANGE Selection of earth fault protection EXTENDED
PARAMETERS MENU ONLY
LANGUAGE
PEAK DEMAND
LOAD HISTORY
RESET TIME
DATE
TIME
SET PASSWORD
TRIP TEST
CONTRAST
ABOUT VIP400
OUTPUT CUST (A)
CB CUSTOM (B)
(B) Parameters menu: Display of the VIP customization to the circuit breaker
PHASE CT CUa or CUb dual core sensor rating 200A
MIN TRIP TIME Activation of minimum tripping time OFF

5 Broadgate Protective Device Settings HVSB-14XX01 Rev 4 2 of 5 CB 74


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV INCOMMER, CB 75. From HVSB13XX04 (CB 57) to loadbank panel HVSB14XX01
Device VIP 400
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 200/100/1A on 200A range
PROTECTION MENU ONLY
SCREEN FUNCTION MENU ENTRY
Frequency Network Frequency 50Hz
I> 51 Phase overcurrent I> set MI/D 126A 0.125 TMS
I>> 51 Phase overcurrent I>> OFF
I>>> 50-51 Phase overcurrent I>>> DT 16 INST
Io> 51N Earth fault overcurrent Io> set point DT 25A 0.1s
Io>> 50N-51N Earth fault overcurrent Io>> set point OFF
THERMAL 49 1 Thermal overload protection OFF
THERMAL 49 2 Thermal overload protection alarm OFF
PHASE H2 RES H2 restraint on phase protection ALL
EARTH FAULT H2 RES. H2 restraint on earth fault protection ALL
Io RANGE Selection of earth fault protection EXTENDED
PARAMETERS MENU ONLY
LANGUAGE
PEAK DEMAND
LOAD HISTORY
RESET TIME
DATE
TIME
SET PASSWORD
TRIP TEST
CONTRAST
ABOUT VIP400
OUTPUT CUST (A)
CB CUSTOM (B)
(B) Parameters menu: Display of the VIP customization to the circuit breaker
PHASE CT CUa or CUb dual core sensor rating 200A
MIN TRIP TIME Activation of minimum tripping time OFF

5 Broadgate Protective Device Settings HVSB-14XX01 Rev 4 3 of 5 CB 75


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

Description 11 kV INCOMMER, CB 76. From HVSB13XX03 (CB 51) to loadbank panel HVSB14XX01
Device VIP 400
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 200/100/1A on 200A range
PROTECTION MENU ONLY
SCREEN FUNCTION MENU ENTRY
Frequency Network Frequency 50Hz
I> 51 Phase overcurrent I> set MI/D 126A 0.125 TMS
I>> 51 Phase overcurrent I>> OFF
I>>> 50-51 Phase overcurrent I>>> DT 16 INST
Io> 51N Earth fault overcurrent Io> set point DT 25A 0.1s
Io>> 50N-51N Earth fault overcurrent Io>> set point OFF
THERMAL 49 1 Thermal overload protection OFF
THERMAL 49 2 Thermal overload protection alarm OFF
PHASE H2 RES H2 restraint on phase protection ALL
EARTH FAULT H2 RES. H2 restraint on earth fault protection ALL
Io RANGE Selection of earth fault protection EXTENDED
PARAMETERS MENU ONLY
LANGUAGE
PEAK DEMAND
LOAD HISTORY
RESET TIME
DATE
TIME
SET PASSWORD
TRIP TEST
CONTRAST
ABOUT VIP400
OUTPUT CUST (A)
CB CUSTOM (B)
(B) Parameters menu: Display of the VIP customization to the circuit breaker
PHASE CT CUa or CUb dual core sensor rating 200A
MIN TRIP TIME Activation of minimum tripping time OFF

5 Broadgate Protective Device Settings HVSB-14XX01 Rev 4 4 of 5 CB 76


ISSUE DATE REV
02.02.16 1
09.02.16 2
12.02.16 3
23.02.16 4

11 kV FEEDER, CB 77. Feeding from HVSB14XX01 to loadbank panel, LVSB 14XX01 via
Description
TX-14XX01
Device VIP 400
Select Remote Control, Group A & B Control Via SCADA
CT Ratio 200/100/1A on 200A range
PROTECTION MENU ONLY
SCREEN FUNCTION MENU ENTRY
Frequency Network Frequency 50Hz
I> 51 Phase overcurrent I> set MI/D 126A 0.125 TMS
I>> 51 Phase overcurrent I>> OFF
I>>> 50-51 Phase overcurrent I>>> DT 16 INST
Io> 51N Earth fault overcurrent Io> set point DT 25A 0.1s
Io>> 50N-51N Earth fault overcurrent Io>> set point OFF
THERMAL 49 1 Thermal overload protection OFF
THERMAL 49 2 Thermal overload protection alarm OFF
PHASE H2 RES H2 restraint on phase protection ALL
EARTH FAULT H2 RES. H2 restraint on earth fault protection ALL
Io RANGE Selection of earth fault protection EXTENDED
PARAMETERS MENU ONLY
LANGUAGE
PEAK DEMAND
LOAD HISTORY
RESET TIME
DATE
TIME
SET PASSWORD
TRIP TEST
CONTRAST
ABOUT VIP400
OUTPUT CUST (A)
CB CUSTOM (B)
(B) Parameters menu: Display of the VIP customization to the circuit breaker
PHASE CT CUa or CUb dual core sensor rating 200A
MIN TRIP TIME Activation of minimum tripping time OFF

5 Broadgate Protective Device Settings HVSB-14XX01 Rev 4 5 of 5 CB 77


COMMISSIONING REPORT
AMTECH Protect - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision Created 26/01/2016 18:23:16
Job ID Last Saved 03/02/2016 23:47:01
Engineer
2No. OC DIESEL Mode 5 Broadgate_H19_H10 - Overcurrent Settings
Diesel OC Settings, 200A, Merlin Gerin MV, Sepam S1000+
Group A Curve DT Curve DT Curve Curve
Is 150.0 Is 150.0 Is Is
T 10.00 T 10.00 T T

CB 48 Incomer HVSB13XX03, 200A, Merlin Gerin MV, Sepam S1000+


Group A Curve DT Curve DT Curve Curve
Is 150.0 Is 999000 Is Is
T 3.10 T 9.73 T T

CB 50 Feeder HVSB13XX03, 800A, Merlin Gerin MV, Sepam S1000+


Group A Curve DT Curve DT Curve Curve
Is 780.0 Is 999000 Is Is
T 2.00 T 1.05 T T

CB 9 Incomer HVSB-1XX01, 1250A, Merlin Gerin MV, Sepam S1000+


Group A Curve DT Curve DT Curve Curve
Is 780.0 Is 999000 Is Is
T 2.00 T 1.05 T T

CB 19 Feeder TX-2XX04, 300A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve DT Curve Curve
Is 125.0 Is 3000.0 Is Is
T 0.14 T 0.05 T T

LVSB13XX04, 3200A, Schneider, Masterpact NW32 H1 Micrologic 5.0A standard


Ir 1.00 Isd 3.00 Iinst OFF
tr 1.0 tsd 0.1

04/02/2016 16:45:36 Amtech Protect HV Version 2015.0.0 Page 1 of 3


2No. OC DIESEL Mode 5 Broadgate_H19_H10.prs17
Overcurrent-Time/Current Analysis, Voltage Base: 11000V, 04/02/2016 16:45:40
10000s
LVSB13XX04 - 3200A@0V Pscc 3ph
Schneider 800.0A 2099A
Masterpact NW32 H1 Micrologic 5.0A standard

1 hour

1000s
Diesel OC Settings
CB 48 Incomer HVSB13XX03
CB 50 Feeder HVSB13XX03
CB 9 Incomer HVSB-1XX01
CB 19 Feeder TX-2XX04
LVSB13XX04

100s

1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

04/02/2016 16:45:36 Amtech Protect HV Version 2015.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
2No. OC DIESEL Mode 5 Broadgate_H19_H10 - Overcurrent Analysis

2No. DIESEL - 11000V, Pscc is 0.8kA


~

Diesel OC Settings - 200A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.8kA, Icu is Unknown

CB 48 Incomer HVSB13XX03 - 200A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.8kA, Icu is Unknown

CB 50 Feeder HVSB13XX03 - 800A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.8kA, Icu is Unknown

CB 9 Incomer HVSB-1XX01 - 1250A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.8kA, Icu is Unknown

CB 19 Feeder TX-2XX04 - 300A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.8kA, Icu is Unknown

TX13XX04 - 11000V/400V, 2000kVA

LVSB13XX04 - 3200A@400V
Schneider - Masterpact NW32 H1 Micrologic 5.0A standard
Pscc is 36kA, Icu is 65kA

Pscc Exceeds Fault Capacity.

04/02/2016 16:45:36 Amtech Protect HV Version 2015.0.0 Page 3 of 3


COMMISSIONING REPORT
AMTECH Protect - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision Created 26/01/2016 18:23:16
Job ID Last Saved 19/02/2016 15:59:00
Engineer
2No. OC DIESEL Mode 5 Broadgate_H19_H3_H6_H17 - Overcurrent Settings
Diesel OC Settings, 200A, Merlin Gerin MV, Sepam S1000+
Group A Curve DT Curve DT Curve Curve
Is 150.0 Is 150.0 Is Is
T 10.00 T 10.00 T T

CB 48 Incomer HVSB13XX03, 200A, Merlin Gerin MV, Sepam S1000+


Group A Curve RI Curve DT Curve Curve
Is 150.0 Is 999000 Is Is
T 3.10 T 9.73 T T

CB 50 Feeder HVSB13XX03, 800A, Merlin Gerin MV, Sepam S1000+


Group A Curve DT Curve DT Curve Curve
Is 780.0 Is 999000 Is Is
T 2.00 T 1.05 T T

CB 9 Incomer HVSB-1XX01, 1250A, Merlin Gerin MV, Sepam S1000+


Group A Curve DT Curve DT Curve Curve
Is 780.0 Is 999000 Is Is
T 2.00 T 1.05 T T

CB 20 Bus Link, 800A, Merlin Gerin MV, Sepam S1000+


Group A Curve DT Curve IEC SIT Curve Curve
Is 780.0 Is 999000 Is Is
T 1.75 T 0.42 T T

CB 36 Ring Feed, 800A, Merlin Gerin MV, Sepam S1000+


Group A Curve RI Curve IEC SIT Curve Curve
Is 700.0 Is 999000 Is Is
T 0.60 T 0.19 T T

CB 47 Incomer HVSB13XX02, 800A, Merlin Gerin MV, Sepam S1000+


Group A Curve RI Curve DT Curve Curve
Is 700.0 Is 999000 Is Is
T 0.33 T 1.05 T T

CB 44 Feeder TX13XX03, 300A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve DT Curve Curve
Is 250.0 Is 2750.0 Is Is
T 0.12 T 0.05 T T

LVSB13XX03, 6300A, Schneider, Masterpact NW63 H1 Micrologic 5.0A standard


Ir 1.00 Isd 5.00 Iinst OFF
tr 1.0 tsd 0.1

19/02/2016 15:59:04 Amtech Protect HV Version 2013.0.0 Page 1 of 3


2No. OC DIESEL Mode 5 Broadgate_H19_H3_H6_H17 .prs17
Overcurrent-Time/Current Analysis, Voltage Base: 11000V, 19/02/2016 15:59:08
10000s
3ph
Src Pscc
2999A
4.2kA
Pscc
1 hour 780.0A

1000s
Diesel OC Settings
CB 48 Incomer HVSB13XX03
CB 50 Feeder HVSB13XX03
CB 9 Incomer HVSB-1XX01
CB 20 Bus Link
CB 36 Ring Feed
CB 47 Incomer HVSB13XX02
CB 44 Feeder TX13XX03
LVSB13XX03
100s

1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

19/02/2016 15:59:04 Amtech Protect HV Version 2013.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
2No. OC DIESEL Mode 5 Broadgate_H19_H3_H6_H17 - Overcurrent Analysis

2No. DIESEL - 11000V, Pscc is 4.2kA


~

Diesel OC Settings - 200A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.78kA, Icu is Unknown

CB 48 Incomer HVSB13XX03 - 200A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.78kA, Icu is Unknown

CB 50 Feeder HVSB13XX03 - 800A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.78kA, Icu is Unknown

CB 9 Incomer HVSB-1XX01 - 1250A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.78kA, Icu is Unknown

CB 20 Bus Link - 800A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.78kA, Icu is Unknown

CB 36 Ring Feed - 800A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.78kA, Icu is Unknown

CB 47 Incomer HVSB13XX02 - 800A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.78kA, Icu is Unknown

CB 44 Feeder TX13XX03 - 300A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.78kA, Icu is Unknown

TX13XX03 - 11000V/400V, 4000kVA

LVSB13XX03 - 6300A@400V
Schneider - Masterpact NW63 H1 Micrologic 5.0A standard
Pscc is 42kA, Icu is 100kA

Pscc Exceeds Fault Capacity.

19/02/2016 15:59:04 Amtech Protect HV Version 2013.0.0 Page 3 of 3


COMMISSIONING REPORT
AMTECH Protect - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision Created 26/01/2016 18:23:16
Job ID Last Saved 03/02/2016 23:03:41
Engineer
2No. OC DIESEL Mode 5 Broadgate_H19_H3_H6_H18 - Overcurrent Settings
Diesel OC Settings, 200A, Merlin Gerin MV, Sepam S1000+
Group A Curve DT Curve DT Curve Curve
Is 150.0 Is 150.0 Is Is
T 10.00 T 10.00 T T

CB 48 Incomer HVSB13XX03, 200A, Merlin Gerin MV, Sepam S1000+


Group A Curve DT Curve DT Curve Curve
Is 150.0 Is 999000 Is Is
T 3.10 T 9.73 T T

CB 50 Feeder HVSB13XX03, 800A, Merlin Gerin MV, Sepam S1000+


Group A Curve DT Curve DT Curve Curve
Is 780.0 Is 999000 Is Is
T 2.00 T 1.05 T T

CB 9 Incomer HVSB-1XX01, 1250A, Merlin Gerin MV, Sepam S1000+


Group A Curve DT Curve DT Curve Curve
Is 780.0 Is 999000 Is Is
T 2.00 T 1.05 T T

CB 20 Bus Link, 800A, Merlin Gerin MV, Sepam S1000+


Group A Curve DT Curve IEC SIT Curve Curve
Is 780.0 Is 999000 Is Is
T 1.75 T 0.42 T T

CB 36 Ring Feed, 800A, Merlin Gerin MV, Sepam S1000+


Group A Curve RI Curve IEC SIT Curve Curve
Is 700.0 Is 999000 Is Is
T 0.60 T 0.19 T T

CB 47 Incomer HVSB13XX02, 800A, Merlin Gerin MV, Sepam S1000+


Group A Curve RI Curve DT Curve Curve
Is 700.0 Is 999000 Is Is
T 0.60 T 1.05 T T

CB 45 Feeder TX13XX04, 300A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve DT Curve Curve
Is 125.0 Is 3000.0 Is Is
T 0.12 T 0.05 T T

LVSB13XX04, 3200A, Schneider, Masterpact NW32 H1 Micrologic 5.0A standard


Ir 1.00 Isd 3.00 Iinst OFF
tr 1.0 tsd 0.1

04/02/2016 16:43:42 Amtech Protect HV Version 2015.0.0 Page 1 of 3


2No. OC DIESEL Mode 5 Broadgate_H19_H3_H6_H18.prs17
Overcurrent-Time/Current Analysis, Voltage Base: 11000V, 04/02/2016 16:43:45
10000s
Pscc 3ph
800.0A 2099A

1 hour

1000s
Diesel OC Settings
CB 48 Incomer HVSB13XX03
CB 50 Feeder HVSB13XX03
CB 9 Incomer HVSB-1XX01
CB 20 Bus Link
CB 36 Ring Feed
CB 47 Incomer HVSB13XX02
CB 45 Feeder TX13XX04
LVSB13XX04
100s

1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

04/02/2016 16:43:42 Amtech Protect HV Version 2015.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
2No. OC DIESEL Mode 5 Broadgate_H19_H3_H6_H18 - Overcurrent Analysis

2No. DIESEL - 11000V, Pscc is 0.8kA


~

Diesel OC Settings - 200A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.8kA, Icu is Unknown

CB 48 Incomer HVSB13XX03 - 200A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.8kA, Icu is Unknown

CB 50 Feeder HVSB13XX03 - 800A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.8kA, Icu is Unknown

CB 9 Incomer HVSB-1XX01 - 1250A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.8kA, Icu is Unknown

CB 20 Bus Link - 800A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.8kA, Icu is Unknown

CB 36 Ring Feed - 800A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.8kA, Icu is Unknown

CB 47 Incomer HVSB13XX02 - 800A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.8kA, Icu is Unknown

CB 45 Feeder TX13XX04 - 300A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.8kA, Icu is Unknown

TX13XX04 - 11000V/400V, 2000kVA

LVSB13XX04 - 3200A@400V
Schneider - Masterpact NW32 H1 Micrologic 5.0A standard
Pscc is 36kA, Icu is 65kA

Pscc Exceeds Fault Capacity.

04/02/2016 16:43:42 Amtech Protect HV Version 2015.0.0 Page 3 of 3


COMMISSIONING REPORT
AMTECH Protect - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision Created 26/01/2016 18:23:16
Job ID Last Saved 19/02/2016 16:04:30
Engineer
2No. OC DIESEL Mode 5 Broadgate_H19_H7 - Overcurrent Settings
Diesel OC Settings, 200A, Merlin Gerin MV, Sepam S1000+
Group A Curve DT Curve DT Curve Curve
Is 150.0 Is 150.0 Is Is
T 10.00 T 10.00 T T

CB 48 Incomer HVSB13XX03, 200A, Merlin Gerin MV, Sepam S1000+


Group A Curve DT Curve DT Curve Curve
Is 150.0 Is 999000 Is Is
T 3.10 T 9.73 T T

CB 50 Feeder HVSB13XX03, 800A, Merlin Gerin MV, Sepam S1000+


Group A Curve DT Curve DT Curve Curve
Is 780.0 Is 999000 Is Is
T 2.00 T 1.05 T T

CB 9 Incomer HVSB-1XX01, 1250A, Merlin Gerin MV, Sepam S1000+


Group A Curve DT Curve DT Curve Curve
Is 780.0 Is 999000 Is Is
T 2.00 T 1.05 T T

CB 15 Feeder TX-2XX01, 300A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve DT Curve Curve
Is 250.0 Is 4200.0 Is Is
T 0.12 T 0.05 T T

LVSB-2XX01, 6300A, Schneider, Masterpact NW63 H1 Micrologic 5.0A standard


Ir 1.00 Isd 5.00 Iinst OFF
tr 1.0 tsd 0.1

19/02/2016 16:04:35 Amtech Protect HV Version 2013.0.0 Page 1 of 3


2No. OC DIESEL Mode 5 Broadgate_H19_H7 .prs17
Overcurrent-Time/Current Analysis, Voltage Base: 11000V, 19/02/2016 16:04:39
10000s
Pscc 3ph
800.0A 2999A

1 hour

1000s
Diesel OC Settings
CB 48 Incomer HVSB13XX03
CB 50 Feeder HVSB13XX03
CB 9 Incomer HVSB-1XX01
CB 15 Feeder TX-2XX01
LVSB-2XX01

100s

1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

19/02/2016 16:04:35 Amtech Protect HV Version 2013.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
2No. OC DIESEL Mode 5 Broadgate_H19_H7 - Overcurrent Analysis

2No. DIESEL - 11000V, Pscc is 0.8kA


~

Diesel OC Settings - 200A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.8kA, Icu is Unknown

CB 48 Incomer HVSB13XX03 - 200A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.8kA, Icu is Unknown

CB 50 Feeder HVSB13XX03 - 800A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.8kA, Icu is Unknown

CB 9 Incomer HVSB-1XX01 - 1250A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.8kA, Icu is Unknown

CB 15 Feeder TX-2XX01 - 300A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.8kA, Icu is Unknown

TX-2XX01 - 11000V/400V, 4000kVA

LVSB-2XX01 - 6300A@400V
Schneider - Masterpact NW63 H1 Micrologic 5.0A standard
Pscc is 42kA, Icu is 100kA

Pscc Exceeds Fault Capacity.

19/02/2016 16:04:35 Amtech Protect HV Version 2013.0.0 Page 3 of 3


COMMISSIONING REPORT
AMTECH Protect - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision Created 26/01/2016 18:23:16
Job ID Last Saved 19/02/2016 17:00:04
Engineer
2No. OC DIESEL Mode 5 Broadgate_H19_H8 - Overcurrent Settings
Diesel OC Settings, 200A, Merlin Gerin MV, Sepam S1000+
Group A Curve DT Curve DT Curve Curve
Is 150.0 Is 150.0 Is Is
T 10.00 T 10.00 T T

CB 48 Incomer HVSB13XX03, 200A, Merlin Gerin MV, Sepam S1000+


Group A Curve RI Curve DT Curve Curve
Is 150.0 Is 999000 Is Is
T 3.10 T 9.73 T T

CB 50 Feeder HVSB13XX03, 800A, Merlin Gerin MV, Sepam S1000+


Group A Curve DT Curve DT Curve Curve
Is 780.0 Is 999000 Is Is
T 2.00 T 1.05 T T

CB 9 Incomer HVSB-1XX01, 1250A, Merlin Gerin MV, Sepam S1000+


Group A Curve DT Curve DT Curve Curve
Is 780.0 Is 999000 Is Is
T 2.00 T 1.05 T T

CB17 Feeder TX-2XX02, 200A, Merlin Gerin MV, Sepam S1000+


Group A + B Curve IEC SIT Curve DT Curve IEC SIT Curve DT
Is 60.0 Is 2000.0 Is 60.0 Is 2000.0
T 0.40 T 1.05 T 1.40 T 0.05

LVSB-2XX02, 1600A, Schneider, Masterpact NW16 H1 Micrologic 5.0A standard


Ir 1.00 Isd 3.00 Iinst OFF
tr 1.0 tsd 0.1

19/02/2016 17:03:49 Amtech Protect HV Version 2013.0.0 Page 1 of 3


2No. OC DIESEL Mode 5 Broadgate_H19_H8 .prs17
Overcurrent-Time/Current Analysis, Voltage Base: 11000V, 19/02/2016 17:03:54
10000s
3ph
1050A
Pscc
1 hour 800.0A

1000s
Diesel OC Settings
CB 48 Incomer HVSB13XX03
CB 50 Feeder HVSB13XX03
CB 9 Incomer HVSB-1XX01
CB17 Feeder TX-2XX02
LVSB-2XX02

100s

1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

19/02/2016 17:03:49 Amtech Protect HV Version 2013.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
2No. OC DIESEL Mode 5 Broadgate_H19_H8 - Overcurrent Analysis

2No. DIESEL - 11000V, Pscc is 0.8kA


~

Diesel OC Settings - 200A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.8kA, Icu is Unknown

CB 48 Incomer HVSB13XX03 - 200A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.8kA, Icu is Unknown

CB 50 Feeder HVSB13XX03 - 800A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.8kA, Icu is Unknown

CB 9 Incomer HVSB-1XX01 - 1250A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.8kA, Icu is Unknown

CB17 Feeder TX-2XX02 - 200A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0kA, Icu is Unknown

TX-2XX02 - 11000V/400V, 1000kVA

LVSB-2XX02 - 1600A@400V
Schneider - Masterpact NW16 H1 Micrologic 5.0A standard
Pscc is 42kA, Icu is 65kA

Pscc Exceeds Fault Capacity.

19/02/2016 17:03:49 Amtech Protect HV Version 2013.0.0 Page 3 of 3


COMMISSIONING REPORT
AMTECH Protect - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision Created 26/01/2016 18:23:16
Job ID Last Saved 19/02/2016 16:37:14
Engineer
2No. OC DIESEL Mode 5 Broadgate_H19_H9 - Overcurrent Settings
Diesel OC Settings, 200A, Merlin Gerin MV, Sepam S1000+
Group A Curve DT Curve DT Curve Curve
Is 150.0 Is 150.0 Is Is
T 10.00 T 10.00 T T

CB 48 Incomer HVSB13XX03, 200A, Merlin Gerin MV, Sepam S1000+


Group A Curve RI Curve DT Curve Curve
Is 150.0 Is 999000 Is Is
T 3.10 T 9.73 T T

CB 50 Feeder HVSB13XX03, 800A, Merlin Gerin MV, Sepam S1000+


Group A Curve DT Curve DT Curve Curve
Is 780.0 Is 999000 Is Is
T 2.00 T 1.05 T T

CB 9 Incomer HVSB-1XX01, 1250A, Merlin Gerin MV, Sepam S1000+


Group A Curve DT Curve DT Curve Curve
Is 780.0 Is 999000 Is Is
T 2.00 T 1.05 T T

CB 18 Feeder TX-2XX03, 300A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve DT Curve Curve
Is 200.0 Is 3800.0 Is Is
T 0.14 T 0.05 T T

LVSB -2XX03, 5000A, Schneider, Masterpact NW50 H1 Micrologic 5.0A standard


Ir 1.00 Isd 5.00 Iinst OFF
tr 1.0 tsd 0.1

19/02/2016 16:37:18 Amtech Protect HV Version 2013.0.0 Page 1 of 3


2No. OC DIESEL Mode 5 Broadgate_H19_H9 .prs17
Overcurrent-Time/Current Analysis, Voltage Base: 11000V, 19/02/2016 16:37:23
10000s
Pscc 3ph
800.0A 2756A

1 hour

1000s
Diesel OC Settings
CB 48 Incomer HVSB13XX03
CB 50 Feeder HVSB13XX03
CB 9 Incomer HVSB-1XX01
CB 18 Feeder TX-2XX03
LVSB -2XX03

100s

1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

19/02/2016 16:37:18 Amtech Protect HV Version 2013.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
2No. OC DIESEL Mode 5 Broadgate_H19_H9 - Overcurrent Analysis

2No. DIESEL - 11000V, Pscc is 0.8kA


~

Diesel OC Settings - 200A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.8kA, Icu is Unknown

CB 48 Incomer HVSB13XX03 - 200A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.8kA, Icu is Unknown

CB 50 Feeder HVSB13XX03 - 800A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.8kA, Icu is Unknown

CB 9 Incomer HVSB-1XX01 - 1250A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.8kA, Icu is Unknown

CB 18 Feeder TX-2XX03 - 300A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.8kA, Icu is Unknown

TX-2XX03 - 11000V/400V, 3150kVA

LVSB -2XX03 - 5000A@400V


Schneider - Masterpact NW50 H1 Micrologic 5.0A standard
Pscc is 0kA, Icu is 100kA

Pscc Exceeds Fault Capacity.

19/02/2016 16:37:18 Amtech Protect HV Version 2013.0.0 Page 3 of 3


COMMISSIONING REPORT
AMTECH Protect - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision Created 26/01/2016 18:23:16
Job ID Last Saved 31/01/2016 11:48:12
Engineer
2No. OC DIESEL Mode 5 Broadgate_H21_H3_H4_H15 - Overcurrent Settings
Diesel OC Settings, 200A, Merlin Gerin MV, Sepam S1000+
Group A Curve DT Curve DT Curve Curve
Is 20.0 Is 150.0 Is Is
T 9.50 T 9.50 T T

CB 64 Incomer HVSB13XX05, 200A, Merlin Gerin MV, Sepam S1000+


Group A Curve RI Curve DT Curve Curve
Is 150.0 Is 999000 Is Is
T 1.95 T 9.73 T T

CB 62 Feeder HVSB13XX05, 800A, Merlin Gerin MV, Sepam S1000+


Group A Curve RI Curve DT Curve Curve
Is 780.0 Is 999000 Is Is
T 0.56 T 1.05 T T

CB 29 Incomer HVSB-1XX02, 1250A, Merlin Gerin MV, Sepam S1000+


Group A Curve RI Curve DT Curve Curve
Is 780.0 Is 999000 Is Is
T 0.56 T 1.05 T T

CB 21 Bus Link, 800A, Merlin Gerin MV, Sepam S1000+


Group A Curve RI Curve IEC SIT Curve Curve
Is 780.0 Is 999000 Is Is
T 0.56 T 0.42 T T

CB 5 Ring Feed, 800A, Merlin Gerin MV, Sepam S1000+


Group A Curve RI Curve IEC SIT Curve Curve
Is 700.0 Is 999000 Is Is
T 0.31 T 0.19 T T

CB 38 Incomer HVSB13XX01, 800A, Merlin Gerin MV, Sepam S1000+


Group A Curve RI Curve DT Curve Curve
Is 700.0 Is 999000 Is Is
T 0.31 T 1.05 T T

CB 39 Feeder TX13XX01, 300A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve EIT Curve Curve
Is 125.0 Is 999000 Is Is
T 0.13 T 0.10 T T

LVSB13XX01, 3200A, Schneider, Masterpact NW32 H2 Micrologic 5.0A standard


Ir 1.00 Isd 3.00 Iinst OFF
tr 4.0 tsd 0.1

04/02/2016 16:48:59 Amtech Protect HV Version 2015.0.0 Page 1 of 3


2No. OC DIESEL Mode 5 Broadgate_H21_H3_H4_H15.prs17
Overcurrent-Time/Current Analysis, Voltage Base: 11000V, 04/02/2016 16:49:03
10000s
Pscc 3ph
800.0A 2099A

1 hour

1000s LVSB13XX01 - 3200A@0V Diesel OC Settings


Schneider CB 64 Incomer HVSB13XX05
Masterpact NW32 H2 Micrologic 5.0A standard CB 62 Feeder HVSB13XX05
CB 29 Incomer HVSB-1XX02
CB 21 Bus Link
CB 5 Ring Feed
CB 38 Incomer HVSB13XX01
CB 39 Feeder TX13XX01
LVSB13XX01
100s

1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

04/02/2016 16:48:59 Amtech Protect HV Version 2015.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
2No. OC DIESEL Mode 5 Broadgate_H21_H3_H4_H15 - Overcurrent Analysis

2No. DIESEL - 11000V, Pscc is 0.8kA


~

Diesel OC Settings - 200A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.8kA, Icu is Unknown

CB 64 Incomer HVSB13XX05 - 200A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.8kA, Icu is Unknown

CB 62 Feeder HVSB13XX05 - 800A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.8kA, Icu is Unknown

CB 29 Incomer HVSB-1XX02 - 1250A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.8kA, Icu is Unknown

CB 21 Bus Link - 800A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.8kA, Icu is Unknown

CB 5 Ring Feed - 800A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.8kA, Icu is Unknown

CB 38 Incomer HVSB13XX01 - 800A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.8kA, Icu is Unknown

CB 39 Feeder TX13XX01 - 300A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.8kA, Icu is Unknown

TX13XX01 - 11000V/400V, 2000kVA

LVSB13XX01 - 3200A@400V
Schneider - Masterpact NW32 H2 Micrologic 5.0A standard
Pscc is 34kA, Icu is 100kA

Pscc Exceeds Fault Capacity.

04/02/2016 16:48:59 Amtech Protect HV Version 2015.0.0 Page 3 of 3


COMMISSIONING REPORT
AMTECH Protect - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision Created 26/01/2016 18:23:16
Job ID Last Saved 18/02/2016 11:46:22
Engineer
2No. OC DIESEL Mode 5 Broadgate_H21_H3_H4_H5_H17 - Overcurrent Settings
Diesel OC Settings, 200A, Merlin Gerin MV, Sepam S1000+
Group A Curve DT Curve DT Curve Curve
Is 150.0 Is 150.0 Is Is
T 10.00 T 10.00 T T

CB 60 Incomer HVSB13XX05, 200A, Merlin Gerin MV, Sepam S1000+


Group A Curve DT Curve DT Curve Curve
Is 150.0 Is 999000 Is Is
T 3.10 T 9.73 T T

CB 62 Feeder HVSB13XX05, 800A, Merlin Gerin MV, Sepam S1000+


Group A Curve DT Curve DT Curve Curve
Is 780.0 Is 999000 Is Is
T 2.00 T 1.05 T T

CB 29 Incomer HVSB-1XX02, 1250A, Merlin Gerin MV, Sepam S1000+


Group A Curve DT Curve DT Curve Curve
Is 780.0 Is 999000 Is Is
T 2.00 T 1.05 T T

CB 21 Bus Link, 800A, Merlin Gerin MV, Sepam S1000+


Group A Curve DT Curve IEC SIT Curve Curve
Is 780.0 Is 999000 Is Is
T 1.75 T 0.42 T T

CB 5 Ring Feed, 800A, Merlin Gerin MV, Sepam S1000+


Group A Curve RI Curve IEC SIT Curve Curve
Is 700.0 Is 999000 Is Is
T 0.60 T 0.19 T T

CB 38 Incomer HVSB13XX01, 800A, Merlin Gerin MV, Sepam S1000+


Group A Curve RI Curve DT Curve Curve
Is 700.0 Is 999000 Is Is
T 0.60 T 1.05 T T

CB 42 Bus Link, 800A, Merlin Gerin MV, Sepam S1000+


Group A Curve RI Curve DT Curve Curve
Is 700.0 Is 999000 Is Is
T 0.33 T 1.05 T T

CB 40 Feeder TX13XX02, 300A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve DT Curve Curve
Is 250.0 Is 4200.0 Is Is
T 0.12 T 0.05 T T

LVSB13XX02, 6300A, Schneider, Masterpact NW63 H1 Micrologic 5.0A standard


Ir 1.00 Isd 5.00 Iinst OFF
tr 1.0 tsd 0.1

19/02/2016 16:14:13 Amtech Protect HV Version 2013.0.0 Page 1 of 3


2No. OC DIESEL Mode 5 Broadgate_H21_H3_H4_H5_H17 .prs17
Overcurrent-Time/Current Analysis, Voltage Base: 11000V, 19/02/2016 16:14:22
10000s
Pscc 3ph
800.0A 2999A

1 hour

1000s
Diesel OC Settings
CB 60 Incomer HVSB13XX05
CB 62 Feeder HVSB13XX05
CB 29 Incomer HVSB-1XX02
CB 21 Bus Link
CB 5 Ring Feed
CB 38 Incomer HVSB13XX01
CB 42 Bus Link
CB 40 Feeder TX13XX02
LVSB13XX02
100s

1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

19/02/2016 16:14:13 Amtech Protect HV Version 2013.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
2No. OC DIESEL Mode 5 Broadgate_H21_H3_H4_H5_H17 - Overcurrent Analysis

2No. DIESEL - 11000V, Pscc is 0.8kA


~

Diesel OC Settings - 200A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.8kA, Icu is Unknown

CB 60 Incomer HVSB13XX05 - 200A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.8kA, Icu is Unknown

CB 62 Feeder HVSB13XX05 - 800A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.8kA, Icu is Unknown

CB 29 Incomer HVSB-1XX02 - 1250A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.8kA, Icu is Unknown

CB 21 Bus Link - 800A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.8kA, Icu is Unknown

CB 5 Ring Feed - 800A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.8kA, Icu is Unknown

CB 38 Incomer HVSB13XX01 - 800A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.8kA, Icu is Unknown

CB 42 Bus Link - 800A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.8kA, Icu is Unknown

CB 40 Feeder TX13XX02 - 300A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.8kA, Icu is Unknown

TX13XX02 - 11000V/400V, 4000kVA

LVSB13XX02 - 6300A@400V
Schneider - Masterpact NW63 H1 Micrologic 5.0A standard
Pscc is 42kA, Icu is 100kA

Pscc Exceeds Fault Capacity.

19/02/2016 16:14:13 Amtech Protect HV Version 2013.0.0 Page 3 of 3


COMMISSIONING REPORT
AMTECH Protect - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision Created 26/01/2016 18:23:16
Job ID Last Saved 03/02/2016 23:18:21
Engineer
2No. OC DIESEL Mode 5 Broadgate_Reverse Current - Overcurrent Settings
Diesel OC Settings, 200A, Merlin Gerin MV, Sepam S1000+
Group A Curve DT Curve DT Curve Curve
Is 150.0 Is 150.0 Is Is
T 10.00 T 10.00 T T

CB 48 Incomer HVSB13XX03, 200A, Merlin Gerin MV, Sepam S1000+


Group A Curve DT Curve DT Curve Curve
Is 150.0 Is 999000 Is Is
T 3.10 T 9.73 T T

Reverse Current, 200A, Merlin Gerin MV, Sepam S1000+


Group A Curve DT Curve DT Curve Curve
Is 75.0 Is 999000 Is Is
T 0.10 T 1.05 T T

CB 50 Feeder HVSB13XX03, 800A, Merlin Gerin MV, Sepam S1000+


Group A Curve DT Curve DT Curve Curve
Is 780.0 Is 999000 Is Is
T 2.00 T 1.05 T T

04/02/2016 16:46:34 Amtech Protect HV Version 2015.0.0 Page 1 of 3


2No. OC DIESEL Mode 5 Broadgate_Reverse Current.prs17
Overcurrent-Time/Current Analysis, Voltage Base: 11000V, 04/02/2016 16:46:39
10000s
Pscc
800.0A

1 hour

1000s
Diesel OC Settings
CB 48 Incomer HVSB13XX03
Reverse Current
CB 50 Feeder HVSB13XX03

100s

1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

04/02/2016 16:46:34 Amtech Protect HV Version 2015.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
2No. OC DIESEL Mode 5 Broadgate_Reverse Current - Overcurrent Analysis

2No. DIESEL - 11000V, Pscc is 0.8kA


~

Diesel OC Settings - 200A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.8kA, Icu is Unknown

CB 48 Incomer HVSB13XX03 - 200A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.8kA, Icu is Unknown

Reverse Current - 200A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.8kA, Icu is Unknown

CB 50 Feeder HVSB13XX03 - 800A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.8kA, Icu is Unknown

Pscc Exceeds Fault Capacity.

04/02/2016 16:46:34 Amtech Protect HV Version 2015.0.0 Page 3 of 3


COMMISSIONING REPORT
AMTECH Protect - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision Created 26/01/2016 18:23:16
Job ID Last Saved 19/02/2016 15:59:00
Engineer
2No. OC DIESEL Mode 5 Broadgate_H19_H3_H6_H17 - Overcurrent Settings
Diesel OC Settings, 200A, Merlin Gerin MV, Sepam S1000+
Group A Curve DT Curve DT Curve Curve
Is 150.0 Is 150.0 Is Is
T 10.00 T 10.00 T T

CB 48 Incomer HVSB13XX03, 200A, Merlin Gerin MV, Sepam S1000+


Group A Curve RI Curve DT Curve Curve
Is 150.0 Is 999000 Is Is
T 3.10 T 9.73 T T

CB 50 Feeder HVSB13XX03, 800A, Merlin Gerin MV, Sepam S1000+


Group A Curve DT Curve DT Curve Curve
Is 780.0 Is 999000 Is Is
T 2.00 T 1.05 T T

CB 9 Incomer HVSB-1XX01, 1250A, Merlin Gerin MV, Sepam S1000+


Group A Curve DT Curve DT Curve Curve
Is 780.0 Is 999000 Is Is
T 2.00 T 1.05 T T

CB 20 Bus Link, 800A, Merlin Gerin MV, Sepam S1000+


Group A Curve DT Curve IEC SIT Curve Curve
Is 780.0 Is 999000 Is Is
T 1.75 T 0.42 T T

CB 36 Ring Feed, 800A, Merlin Gerin MV, Sepam S1000+


Group A Curve RI Curve IEC SIT Curve Curve
Is 700.0 Is 999000 Is Is
T 0.60 T 0.19 T T

CB 47 Incomer HVSB13XX02, 800A, Merlin Gerin MV, Sepam S1000+


Group A Curve RI Curve DT Curve Curve
Is 700.0 Is 999000 Is Is
T 0.33 T 1.05 T T

CB 44 Feeder TX13XX03, 300A, Merlin Gerin MV, Sepam S1000+


Group A Curve IEC SIT Curve DT Curve Curve
Is 250.0 Is 2750.0 Is Is
T 0.12 T 0.05 T T

LVSB13XX03, 6300A, Schneider, Masterpact NW63 H1 Micrologic 5.0A standard


Ir 1.00 Isd 5.00 Iinst OFF
tr 1.0 tsd 0.1

19/02/2016 15:59:04 Amtech Protect HV Version 2013.0.0 Page 1 of 3


2No. OC DIESEL Mode 5 Broadgate_H19_H3_H6_H17 .prs17
Overcurrent-Time/Current Analysis, Voltage Base: 11000V, 19/02/2016 15:59:08
10000s
3ph
Src Pscc
2999A
4.2kA
Pscc
1 hour 780.0A

1000s
Diesel OC Settings
CB 48 Incomer HVSB13XX03
CB 50 Feeder HVSB13XX03
CB 9 Incomer HVSB-1XX01
CB 20 Bus Link
CB 36 Ring Feed
CB 47 Incomer HVSB13XX02
CB 44 Feeder TX13XX03
LVSB13XX03
100s

1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

19/02/2016 15:59:04 Amtech Protect HV Version 2013.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
2No. OC DIESEL Mode 5 Broadgate_H19_H3_H6_H17 - Overcurrent Analysis

2No. DIESEL - 11000V, Pscc is 4.2kA


~

Diesel OC Settings - 200A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.78kA, Icu is Unknown

CB 48 Incomer HVSB13XX03 - 200A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.78kA, Icu is Unknown

CB 50 Feeder HVSB13XX03 - 800A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.78kA, Icu is Unknown

CB 9 Incomer HVSB-1XX01 - 1250A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.78kA, Icu is Unknown

CB 20 Bus Link - 800A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.78kA, Icu is Unknown

CB 36 Ring Feed - 800A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.78kA, Icu is Unknown

CB 47 Incomer HVSB13XX02 - 800A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.78kA, Icu is Unknown

CB 44 Feeder TX13XX03 - 300A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 0.78kA, Icu is Unknown

TX13XX03 - 11000V/400V, 4000kVA

LVSB13XX03 - 6300A@400V
Schneider - Masterpact NW63 H1 Micrologic 5.0A standard
Pscc is 42kA, Icu is 100kA

Pscc Exceeds Fault Capacity.

19/02/2016 15:59:04 Amtech Protect HV Version 2013.0.0 Page 3 of 3


COMMISSIONING REPORT
AMTECH Protect - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision Created 26/01/2016 18:23:16
Job ID Last Saved 03/02/2016 23:58:39
Engineer
EF DIESEL Mode 5 Broadgate_H16_H4_H3_H2 - Earth Fault Settings
Diesel EF Settings, 160A, Merlin Gerin MV, Sepam S1000+
Group A Curve DT Curve DT Curve Curve
Iso 119.0 Iso 999000 Iso Iso
T 1.00 T 1.05 T T

CB 64 Incomer HVSB13XX05, 120A, Merlin Gerin MV, Sepam S1000+


Group A Curve DT Curve DT Curve Curve
Iso 105.0 Iso 999000 Iso Iso
T 0.87 T 1.05 T T

CB 62 Feeder HVSB13XX05, 100A, Merlin Gerin MV, Sepam S1000+


Group A Curve DT Curve DT Curve Curve
Iso 95.0 Iso 999000 Iso Iso
T 0.62 T 1.05 T T

CB 29 Incomer HVSB-1XX02, 100A, Merlin Gerin MV, Sepam S1000+


Group A Curve DT Curve DT Curve Curve
Iso 95.0 Iso 999000 Iso Iso
T 0.62 T 1.05 T T

CB 21 Bus Link, 100A, Merlin Gerin MV, Sepam S1000+


Group A Curve DT Curve DT Curve Curve
Iso 95.0 Iso 999000 Iso Iso
T 0.62 T 1.05 T T

CB 5 Ring Feed, 100A, Merlin Gerin MV, Sepam S1000+


Group A Curve DT Curve DT Curve Curve
Iso 80.0 Iso 999000 Iso Iso
T 0.37 T 1.05 T T

CB 38 Incomer HVSB13XX01, 100A, Merlin Gerin MV, Sepam S1000+


Group A Curve DT Curve DT Curve Curve
Iso 80.0 Iso 999000 Iso Iso
T 0.37 T 1.05 T T

CB 40 Feeder TX13XX02, 100A, Merlin Gerin MV, Sepam S1000+


Group A Curve DT Curve DT Curve Curve
Iso 30.0 Iso 999000 Iso Iso
T 0.10 T 1.05 T T

04/02/2016 16:41:50 Amtech Protect HV Version 2015.0.0 Page 1 of 3


EF DIESEL Mode 5 Broadgate_H16_H4_H3_H2.prs17
Earth Fault-Time/Current Analysis, Voltage Base: 11000V, 04/02/2016 16:41:59
10000s
Ief 1ph EF
120.0A 1154A

1 hour

1000s
Diesel EF Settings
CB 64 Incomer HVSB13XX05
CB 62 Feeder HVSB13XX05
CB 29 Incomer HVSB-1XX02
CB 21 Bus Link
CB 5 Ring Feed
CB 38 Incomer HVSB13XX01
CB 40 Feeder TX13XX02

100s

1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
10mA 100mA 1A 10A 100A 1kA 10kA 100kA 1MA

04/02/2016 16:41:50 Amtech Protect HV Version 2015.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
EF DIESEL Mode 5 Broadgate_H16_H4_H3_H2 - Earth Fault Analysis

DIESEL EARTH - 11000V


~

Diesel EF Settings - 160A@11000V


Merlin Gerin MV - Sepam S1000+
Ief is 0.12kA, Icu is Unknown

CB 64 Incomer HVSB13XX05 - 120A@11000V


Merlin Gerin MV - Sepam S1000+
Ief is 0.12kA, Icu is Unknown

CB 62 Feeder HVSB13XX05 - 100A@11000V


Merlin Gerin MV - Sepam S1000+
Ief is 0.12kA, Icu is Unknown

CB 29 Incomer HVSB-1XX02 - 100A@11000V


Merlin Gerin MV - Sepam S1000+
Ief is 0.12kA, Icu is Unknown

CB 21 Bus Link - 100A@11000V


Merlin Gerin MV - Sepam S1000+
Ief is 0.12kA, Icu is Unknown

CB 5 Ring Feed - 100A@11000V


Merlin Gerin MV - Sepam S1000+
Ief is 0.12kA, Icu is Unknown

CB 38 Incomer HVSB13XX01 - 100A@11000V


Merlin Gerin MV - Sepam S1000+
Ief is 0.12kA, Icu is Unknown

CB 40 Feeder TX13XX02 - 100A@11000V


Merlin Gerin MV - Sepam S1000+
Ief is 0.12kA, Icu is Unknown

TX13XX02 - 11000V/400V, 4000kVA

Ief Exceeds Fault Capacity.

04/02/2016 16:41:50 Amtech Protect HV Version 2015.0.0 Page 3 of 3


COMMISSIONING REPORT
AMTECH Protect - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision Created 26/01/2016 18:23:16
Job ID Last Saved 19/02/2016 16:20:52
Engineer
8No. OC DIESEL Mode 5 Broadgate_HVSB14XX01 - Overcurrent Settings
Diesel OC Settings, 200A, Merlin Gerin MV, Sepam S1000+
Group A Curve DT Curve DT Curve Curve
Is 150.0 Is 150.0 Is Is
T 10.00 T 10.00 T T

CB 48 Incomer HVSB13XX03, 200A, Merlin Gerin MV, Sepam S1000+


Group A Curve DT Curve DT Curve Curve
Is 150.0 Is 999000 Is Is
T 3.10 T 9.73 T T

CB 51 Feeder HVSB14XX01, 160A, Merlin Gerin MV, Sepam S1000+


Group A Curve RI Curve DT Curve Curve
Is 140.0 Is 999000 Is Is
T 1.05 T 1.05 T T

CB 76 Incomer, Areva, MiCOM P122 - Version 6


ICT 200 Therm? No I> ? Yes I>> ? No I>>> ? Yes
Ith N/A Type IDMT Type I>>> 16.00
Te Curve MI Curve tl>>> 0.00
k N/A TMS 0.1250 TMS
Teta % I> 0.63 I>> N/A
tl> tl>>
K N/A K N/A

CB 77 Feeder TX13XX03, Areva, MiCOM P122 - Version 6


ICT 200 Therm? No I> ? Yes I>> ? No I>>> ? Yes
Ith N/A Type IDMT Type I>>> 16.00
Te Curve MI Curve tl>>> 0.00
k N/A TMS 0.1250 TMS
Teta % I> 0.63 I>> N/A
tl> tl>>
K N/A K N/A

LVSB 14XX01, 4000A, Schneider, Masterpact NW40b H1 Micrologic 5.0A standard


Ir 1.00 Isd 5.00 Iinst OFF
tr 1.0 tsd 0.1

19/02/2016 16:20:58 Amtech Protect HV Version 2013.0.0 Page 1 of 3


8No. OC DIESEL Mode 5 Broadgate_HVSB14XX01 .prs17
Overcurrent-Time/Current Analysis, Voltage Base: 11000V, 19/02/2016 16:21:02
10000s
3ph Pscc
2187A 4.200kA

1 hour

1000s
Diesel OC Settings
CB 48 Incomer HVSB13XX03
CB 51 Feeder HVSB14XX01
CB 76 Incomer
CB 77 Feeder TX13XX03
LVSB 14XX01

100s

1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

19/02/2016 16:20:58 Amtech Protect HV Version 2013.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
8No. OC DIESEL Mode 5 Broadgate_HVSB14XX01 - Overcurrent Analysis

8No. DIESEL - 11000V, Pscc is 4.2kA


~

Diesel OC Settings - 200A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 4.2kA, Icu is Unknown

CB 48 Incomer HVSB13XX03 - 200A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 4.2kA, Icu is Unknown

CB 51 Feeder HVSB14XX01 - 160A@11000V


Merlin Gerin MV - Sepam S1000+
Pscc is 4.2kA, Icu is Unknown

CB 76 Incomer - 11000V
Areva - MiCOM P122 - Version 6
Pscc is 4.2kA, Icu is Unknown

CB 77 Feeder TX13XX03 - 11000V


Areva - MiCOM P122 - Version 6
Pscc is 4.2kA, Icu is Unknown

TX-14XX01 - 11000V/400V, 2500kVA

LVSB 14XX01 - 4000A@400V


Schneider - Masterpact NW40b H1 Micrologic 5.0A standard
Pscc is 42kA, Icu is 100kA

Pscc Exceeds Fault Capacity.

19/02/2016 16:20:58 Amtech Protect HV Version 2013.0.0 Page 3 of 3


Electrical Discrimination Study
5 Broadgate

8.0 400 V Network Analysis

The following section contains comprehensive schedules detailing devices and their respective settings throughout the
LV network distribution.

A comprehensive set of LV curves generated using Amtech and Schneider ‘Curve Direct’ software packages are
included to demonstrate discrimination between the various combinations of the different types of individual devices
within the network.

It is to be noted that due to the software configuration and logic within Amtech, Schneider Curve Direct comparisons of
selected identical devices have been added to show that full discrimination is achieved within the network at LV level.

Long and Partners Ltd


Rev 11 QA-R06-1 14 of 14
LV Protective Devices Setting Schedule - Index

Page

LVSB -1XX01...............................................................................................................................................................................
1

LVSB -1XX02................................................................................................................................................................................
3

LVSB -1XX03................................................................................................................................................................................
4

LVSB -1XX04................................................................................................................................................................................
5

LVSB -1XX05................................................................................................................................................................................
6

LVSB -1XX06................................................................................................................................................................................
7

LVSB -1XX07................................................................................................................................................................................
8

LVSB -2XX01................................................................................................................................................................................
9

LVSB -2XX02...............................................................................................................................................................................
11

LVSB -2XX03................................................................................................................................................................................
12

LVSB -2XX04................................................................................................................................................................................
13

LVSB 06SE01................................................................................................................................................................................
14

LVSB 13XX01..............................................................................................................................................................................
15

LVSB 13XX02..............................................................................................................................................................................
17

LVSB 13XX03..............................................................................................................................................................................
18

LVSB 13XX04..............................................................................................................................................................................
19

LVSB 13XX05..............................................................................................................................................................................
20

LVSB 13XX06..............................................................................................................................................................................
21

LVSB 14XX01................................................................................................................................................................................
22
LV Protective Device Settings - LVSB -1XX01

Note The Schedule settings provide both Over Current and


Earth Fault protection for each Breaker

LV Thermal - Magnetic Settings


Overload Selective Short Circuit

Device Type Long Time Long Time Short Circuit Neutral Protection
Long Time Short Time Short time Instantaneous Short
Dial Setting Current Relay Trip
Delay (s) Current Delay Circuit
(Coarse) Multiplier setting
Board Name Device No. Trip ITEM Circuit Description

Breaker / Relay Set Current


Make/Brand Current Rating Rating Icu kA Io Ir tr Im Isd tsd Iinst (3D, 3D+N/2, 4D)
(Amperes) (Amperes)

A1 MICROLOGIC 5.0A AUTO ACB Mains Incoming Supply SCHNEIDER NW63H1 6300 6300 100 N/A 1.0 1.0 N/A 5.0 0.1 OFF N/A

A2 TM200D AUTO MCCB Supply to ESP SCHNEIDER NSX250N 250 200 50 N/A 200.0 N/A 2500.0 N/A N/A N/A N/A

A3 BS88 Fused Switch Supply to Sprinkler Pump 1 SOCOMEC 315 315 80 N/A N/A N/A N/A N/A N/A N/A N/A

A4 BS88 Fused Switch Supply to Sprinkler Pump 2 SOCOMEC 315 315 80 N/A N/A N/A N/A N/A N/A N/A N/A

A5 BS88 Fused Switch Supply to Wet Riser Pump 1 SOCOMEC 315 315 80 N/A N/A N/A N/A N/A N/A N/A N/A

A6 BS88 Fused Switch Supply to Wet Riser Pump 2 SOCOMEC 315 315 80 N/A N/A N/A N/A N/A N/A N/A N/A

A7 MICROLOGIC 5.0E NON-AUTO ACB Bus Coupler to LVSB-2 XX01 SCHNEIDER NW32H2 3200 3200 85 N/A 1.0 1.0 N/A 3.0 0.1 OFF N/A

A8 MICROLOGIC 2.0A AUTO MCCB Supply to 400KVAR PFC SCHNEIDER NS800L 800 800 150 N/A 1.0 16.0 N/A 10.0 N/A N/A N/A

A9 MICROLOGIC 2.2 AUTO MCCB Drinking water booster pump SCHNEIDER NSX100S 100 100 100 100 1.0 N/A N/A 5.0 N/A N/A N/A

A10 MICROLOGIC 2.2 AUTO MCCB Harvested rainwater booster set HRBS-1 SCHNEIDER NSX160S 160 100 100 100 1.0 N/A N/A 5.0 N/A N/A N/A

A11 MICROLOGIC 2.2 AUTO MCCB Spare SCHNEIDER NSX160S 160 160 100 160 1.0 N/A N/A 5.0 N/A N/A N/A

A12 MICROLOGIC 2.3 AUTO MCCB Supply to RBXXNW01 SCHNEIDER NSX630S 630 630 100 630 1.0 N/A N/A 5.0 N/A N/A N/A

A13 MICROLOGIC 2.3 AUTO MCCB Supply to RB XXNE01 SCHNEIDER NSX630S 630 630 100 630 1.0 N/A N/A 5.0 N/A N/A N/A

A14 MICROLOGIC 2.3 AUTO MCCB Supply to MCC-2XX06 SCHNEIDER NSX630S 630 630 100 630 1.0 N/A N/A 5.0 N/A N/A N/A

A15 MICROLOGIC 2.2 AUTO MCCB Supply to MCC-1XX03 SCHNEIDER NSX160S 160 100 100 100 1.0 N/A N/A 5.0 N/A N/A N/A

A16 MICROLOGIC 2.2 AUTO MCCB Spare SCHNEIDER NSX100S 160 100 100 100 1.0 N/A N/A 5.0 N/A N/A N/A

A17 MICROLOGIC 2.2 AUTO MCCB Spare SCHNEIDER NSX100S 100 100 100 100 1.0 N/A N/A 5.0 N/A N/A N/A

A18 MICROLOGIC 2.3 AUTO MCCB Supply to MCC-2 XX04 SCHNEIDER NSX400S 400 400 100 400 1.0 N/A N/A 5.0 N/A N/A N/A

A19 MICROLOGIC 2.3 AUTO MCCB Supply to MCC-2 XX 02 SCHNEIDER NSX400S 400 400 100 400 1.0 N/A N/A 5.0 N/A N/A N/A

A20 MICROLOGIC 2.3 AUTO MCCB Spare SCHNEIDER NSX400S 400 400 100 400 1.0 N/A N/A 5.0 N/A N/A N/A

A21 MICROLOGIC 2.2 AUTO MCCB Supply to MCC-1XX04 SCHNEIDER NSX160S 160 100 100 100 1.0 N/A N/A 5.0 N/A N/A N/A

A22 MICROLOGIC 2.2 AUTO MCCB Supply to MCC-1XX05 SCHNEIDER NSX160S 160 100 100 100 1.0 N/A N/A 5.0 N/A N/A N/A

A23 MICROLOGIC 2.2 AUTO MCCB Supply to Rain Water Booster Pump HRBS-1xx01 SCHNEIDER NSX160S 160 160 100 160 1.0 N/A N/A 5.0 N/A N/A N/A

A24 MICROLOGIC 2.2 AUTO MCCB Supply to MCC-1XX07 SCHNEIDER NSX160S 160 160 100 160 1.0 N/A N/A 5.0 N/A N/A N/A

A25 MICROLOGIC 2.2 AUTO MCCB Spare SCHNEIDER NSX250S 250 200 100 200 1.0 N/A N/A 5.0 N/A N/A N/A

A26 MICROLOGIC 2.2 AUTO MCCB Spare SCHNEIDER NSX250S 250 200 100 200 1.0 N/A N/A 5.0 N/A N/A N/A

A27 MICROLOGIC 2.2 AUTO MCCB Spare SCHNEIDER NSX250S 250 200 100 200 1.0 N/A N/A 5.0 N/A N/A N/A

A28 MICROLOGIC 2.2 AUTO MCCB Spare SCHNEIDER NSX160S 160 160 100 160 1.0 N/A N/A 5.0 N/A N/A N/A

A29 MICROLOGIC 2.2 AUTO MCCB Supply to MCC-1XX02 SCHNEIDER NSX160S 160 100 100 100 1.0 N/A N/A 5.0 N/A N/A N/A

A30 MICROLOGIC 2.2 AUTO MCCB Supply to DB-1 XX08 SCHNEIDER NSX160S 160 100 100 100 1.0 N/A N/A 5.0 N/A N/A N/A

A31 MICROLOGIC 2.2 AUTO MCCB Supply to DB-1 XX01 SCHNEIDER NSX160S 160 100 100 100 1.0 N/A N/A 5.0 N/A N/A N/A
LVSB -1XX01
A32 MICROLOGIC 2.2 AUTO MCCB Supply to DB-1 XX09 SCHNEIDER NSX160S 160 100 100 100 1.0 N/A N/A 5.0 N/A N/A N/A

A33 MICROLOGIC 2.2 AUTO MCCB Supply to DB-1 XX02 SCHNEIDER NSX160S 160 100 100 100 1.0 N/A N/A 5.0 N/A N/A N/A

A34 MICROLOGIC 2.2 AUTO MCCB Supply to DB-1 XX10 SCHNEIDER NSX160S 160 100 100 100 1.0 N/A N/A 5.0 N/A N/A N/A

A35 MICROLOGIC 2.2 AUTO MCCB Supply to DB-1 XX06 SCHNEIDER NSX160S 160 100 100 100 1.0 N/A N/A 5.0 N/A N/A N/A
LV Protective Device Settings - LVSB -1XX01

Note The Schedule settings provide both Over Current and


Earth Fault protection for each Breaker

LV Thermal - Magnetic Settings


Overload Selective Short Circuit

Device Type Long Time Long Time Short Circuit Neutral Protection
Long Time Short Time Short time Instantaneous Short
Dial Setting Current Relay Trip
Delay (s) Current Delay Circuit
(Coarse) Multiplier setting
Board Name Device No. Trip ITEM Circuit Description

Breaker / Relay Set Current


Make/Brand Current Rating Rating Icu kA Io Ir tr Im Isd tsd Iinst (3D, 3D+N/2, 4D)
(Amperes) (Amperes)

A36 MICROLOGIC 2.2 AUTO MCCB Spare SCHNEIDER NSX160S 160 160 100 160 1.0 N/A N/A 5.0 N/A N/A N/A

A37 MICROLOGIC 2.2 AUTO MCCB Supply to DB 00NE 05 SCHNEIDER NSX160S 160 100 100 100 1.0 N/A N/A 5.0 N/A N/A N/A

A38 MICROLOGIC 2.2 AUTO MCCB Spare SCHNEIDER NSX160S 160 160 100 160 1.0 N/A N/A 5.0 N/A N/A N/A

A39 MICROLOGIC 2.2 AUTO MCCB Supply to Fire Command Room DB00NE05 ACO SCHNEIDER NSX160S 160 160 100 160 1.0 N/A N/A 5.0 N/A N/A N/A

A40 MICROLOGIC 2.2 AUTO MCCB Supply to DB-1 XX 05 SCHNEIDER NSX160S 160 100 100 100 1.0 N/A N/A 5.0 N/A N/A N/A

A41 MICROLOGIC 2.2 AUTO MCCB Supply to MCB-1 XX 01 ACO SCHNEIDER NSX160S 160 160 100 160 1.0 N/A N/A 5.0 N/A N/A N/A

A42 MICROLOGIC 2.2 AUTO MCCB Supply to DB-1 XX 04 ACO SCHNEIDER NSX160S 160 100 100 100 1.0 N/A N/A 5.0 N/A N/A N/A

A43 MICROLOGIC 2.2 AUTO MCCB Supply to BD-1 XX 07 SCHNEIDER NSX160S 160 100 100 100 1.0 N/A N/A 5.0 N/A N/A N/A

A44 MICROLOGIC 2.2 AUTO MCCB Supply to DB-2 XX 05 ACO SCHNEIDER NSX160S 160 100 100 100 1.0 N/A N/A 5.0 N/A N/A N/A

A45 MICROLOGIC 2.2 AUTO MCCB Supply to DB-7 XX 06 ACO SCHNEIDER NSX160S 160 100 100 100 1.0 N/A N/A 5.0 N/A N/A N/A

A46 MICROLOGIC 2.2 AUTO MCCB Supply to DB-2 XX 12 SCHNEIDER NSX160S 160 100 100 100 1.0 N/A N/A 5.0 N/A N/A N/A

A47 MICROLOGIC 2.2 AUTO MCCB Supply to DB UKPN SCHNEIDER NSX160S 160 100 100 100 1.0 N/A N/A 5.0 N/A N/A N/A

A48 MICROLOGIC 2.2 AUTO MCCB Spare SCHNEIDER NSX100S 100 100 100 100 1.0 N/A N/A 5.0 N/A N/A N/A

A49 MICROLOGIC 2.2 AUTO MCCB Spare SCHNEIDER NSX100S 100 100 100 100 1.0 N/A N/A 5.0 N/A N/A N/A

A50 MICROLOGIC 2.2 AUTO MCCB Spare SCHNEIDER NSX100S 100 100 100 100 1.0 N/A N/A 5.0 N/A N/A N/A

A51 MICROLOGIC 2.2 AUTO MCCB Spare SCHNEIDER NSX100S 100 100 100 100 1.0 N/A N/A 5.0 N/A N/A N/A

A52 MICROLOGIC 2.2 AUTO MCCB Spare SCHNEIDER NSX100S 100 100 100 100 1.0 N/A N/A 5.0 N/A N/A N/A

A53 MICROLOGIC 2.2 AUTO MCCB Spare SCHNEIDER NSX100S 100 100 100 100 1.0 N/A N/A 5.0 N/A N/A N/A

A54 MICROLOGIC 2.2 AUTO MCCB Supply to remote AHF1 SCHNEIDER NSX160S 160 160 100 160 1.0 N/A N/A 5.0 N/A N/A N/A

A55 MICROLOGIC 2.2 AUTO MCCB Supply to remote AHF2 SCHNEIDER NSX160S 160 160 100 160 1.0 N/A N/A 5.0 N/A N/A N/A

A56 MICROLOGIC 2.2 AUTO MCCB Supply to remote AHF3 SCHNEIDER NSX160S 160 160 100 160 1.0 N/A N/A 5.0 N/A N/A N/A

A57 MICROLOGIC 2.2 AUTO MCCB Supply to remote AHF4 SCHNEIDER NSX160S 160 160 100 160 1.0 N/A N/A 5.0 N/A N/A N/A

A58 MICROLOGIC 2.0A AUTO MCCB Supply to LVSB-1 XX 06 ACO SCHNEIDER NS800L 800 800 150 N/A 1.0 16.0 N/A 10.0 N/A N/A N/A

A59 MICROLOGIC 2.0A AUTO MCCB Supply to CH-2 XX 07 SCHNEIDER NS800L 800 800 150 N/A 1.0 16.0 N/A 10.0 N/A N/A N/A

A60 MICROLOGIC 2.0A AUTO MCCB Supply to CH-2 XX 05 SCHNEIDER NS800L 800 800 150 N/A 1.0 16.0 N/A 10.0 N/A N/A N/A

A61 MICROLOGIC 2.0A AUTO MCCB Supply to CH-2 XX 08 SCHNEIDER NS800L 800 800 150 N/A 1.0 16.0 N/A 10.0 N/A N/A N/A

A62 MICROLOGIC 2.0A AUTO MCCB Supply to CH-2 XX 06 SCHNEIDER NS800L 800 800 150 N/A 1.0 16.0 N/A 10.0 N/A N/A N/A
LV Protective Device Settings - LVSB-1XX02

Note The Schedule settings provide both Over Current and


Earth Fault protection for each Breaker

LV Thermal - Magnetic Settings

Overload Selective Short Circuit

Long Time Long Time Short Circuit Neutral Protection


Device Type Long Time Short Time Short time Instantaneous Short
Dial Setting Current Relay Trip
Delay (s) Current Delay Circuit
(Coarse) Multiplier setting
Board Name Device No. Trip ITEM Circuit Description

Full Breaker / Relay Breaker / Relay


Icu
Make/Brand Current Rating Current Rating SET Io Ir tr lm Isd tsd Iinst (3D, 3D+N/2, 4D)
(KA)
(Amperes) @ (Amperes)

A1 Micrologic 5.0A AUTO ACB Main Incoming Supply SCHNEIDER NW16H1 1600 1600 65 N/A 1.0 1.0 N/A 3.0 0.1 Off N/A

A2 TM200D AUTO MCCB Supply to ESP SCHNEIDER NSX250N 250 200 50 N/A 200.0 N/A 2500.0 N/A N/A N/A N/A

A3 Micrologic 2.3 AUTO MCCB Supply to PFC SCHNEIDER NSX400N 400 400 50 400 1.0 N/A N/A 5.0 N/A N/A N/A

A4 Micrologic 2.2 AUTO MCCB AHF 3 Supply SCHNEIDER NSX160N 160 160 50 160 1.0 N/A N/A 5.0 N/A N/A N/A

A5 Micrologic 2.2 AUTO MCCB AHF 4 Supply SCHNEIDER NSX160N 160 160 50 160 1.0 N/A N/A 5.0 N/A N/A N/A

A6 Micrologic 2.3 AUTO MCCB Supply to RB XXNW05 SCHNEIDER NSX400N 400 400 50 400 1.0 N/A N/A 5.0 N/A N/A N/A

LVSB -1XX02 A7 Micrologic 2.3 AUTO MCCB Supply to RB XXSW02 SCHNEIDER NSX400N 400 400 50 400 1.0 N/A N/A 5.0 N/A N/A N/A

A8 Micrologic 2.3 AUTO MCCB SPARE SCHNEIDER NSX400N 400 400 50 400 1.0 N/A N/A 5.0 N/A N/A N/A

A9 Micrologic 2.3 AUTO MCCB AHF 1 Supply SCHNEIDER NSX160N 160 160 50 160 1.0 N/A N/A 5.0 N/A N/A N/A

A10 Micrologic 2.3 AUTO MCCB AHF 2 Supply SCHNEIDER NSX160N 160 160 50 160 1.0 N/A N/A 5.0 N/A N/A N/A

A11 Micrologic 2.3 AUTO MCCB Supply to RB XXNE05 SCHNEIDER NSX400N 400 400 50 400 1.0 N/A N/A 5.0 N/A N/A N/A

A12 Micrologic 2.3 AUTO MCCB Supply to RB XXSE02 SCHNEIDER NSX400N 400 400 50 400 1.0 N/A N/A 5.0 N/A N/A N/A

A13 Micrologic 2.3 AUTO MCCB Spare SCHNEIDER NSX400N 400 400 50 400 1.0 N/A N/A 5.0 N/A N/A N/A
LV Protective Device Settings - LVSB-1XX03

Note The Schedule settings provide both Over Current and


Earth Fault protection for each Breaker

LV Thermal - Magnetic Settings


Overload Selective Short Circuit

Device Type Long Time Long Time Short Circuit Neutral Protection
Long Time Short Time Short time Instantaneous Short
Dial Setting Current Relay Trip
Delay (s) Current Delay Circuit
(Coarse) Multiplier setting
Board Name Device No. Trip ITEM Circuit Description

Breaker / Relay
Set Current Rating
Make/Brand Current Rating Icu kA Io Ir tr Im Isd tsd Iinst (3D, 3D+N/2, 4D)
(Amperes)
(Amperes)

A1 Micrologic 5.0A AUTO ACB Main Incoming Supply SCHNEIDER NW50H1 5000 5000 100 N/A 1.0 1.0 N/A 5.0 0.1 Off N/A

A2 TM200D AUTO MCCB Supply to ESP SCHNEIDER NSX250N 250 200 50 N/A 200.0 N/A 2500.0 N/A N/A N/A N/A

A3 Micrologic 2.3 AUTO MCCB PFC Supply SCHNEIDER NSX400S 400 400 100 400 1.0 N/A N/A 5.0 N/A N/A N/A

A4 Micrologic 2.2 AUTO MCCB AHF 3 Supply SCHNEIDER NSX160S 160 160 100 160 1.0 N/A N/A 5.0 N/A N/A N/A

A5 Micrologic 2.2 AUTO MCCB AHF 4 Supply SCHNEIDER NSX160S 160 160 100 160 1.0 N/A N/A 5.0 N/A N/A N/A

A6 Micrologic 2.2 AUTO MCCB AHF 1 Supply SCHNEIDER NSX160S 160 160 100 160 1.0 N/A N/A 5.0 N/A N/A N/A

A7 Micrologic 2.2 AUTO MCCB AHF 2 Supply SCHNEIDER NSX160S 160 160 100 160 1.0 N/A N/A 5.0 N/A N/A N/A

A8 Micrologic 2.3 AUTO MCCB Spare SCHNEIDER NSX400S 400 400 100 400 1.0 N/A N/A 5.0 N/A N/A N/A

A9 Micrologic 2.0A AUTO MCCB Supply to RBXXSW04 SCHNEIDER NS800L 800 800 150 N/A 1.0 16.0 N/A 10.0 N/A N/A N/A
LVSB -1XX03
A10 Micrologic 2.0A AUTO MCCB Supply to RBXXSW06 SCHNEIDER NS800L 800 800 150 N/A 1.0 16.0 N/A 10.0 N/A N/A N/A

A11 Micrologic 2.0A AUTO MCCB Supply to RBXXNW07 SCHNEIDER NS800L 800 800 150 N/A 1.0 16.0 N/A 10.0 N/A N/A N/A

A12 Micrologic 2.0A AUTO MCCB Supply to RBXXNW10 SCHNEIDER NS800L 800 800 150 N/A 1.0 16.0 N/A 10.0 N/A N/A N/A

A13 Micrologic 2.0A AUTO MCCB Supply to RBXXNE08 SCHNEIDER NS800L 800 800 150 N/A 1.0 16.0 N/A 10.0 N/A N/A N/A

A14 Micrologic 2.0A AUTO MCCB Supply to RBXXNE10 SCHNEIDER NS800L 800 800 150 N/A 1.0 16.0 N/A 10.0 N/A N/A N/A

A15 Micrologic 2.0A AUTO MCCB Supply to RBXXSE06 SCHNEIDER NS800L 800 800 150 N/A 1.0 16.0 N/A 10.0 N/A N/A N/A

A16 Micrologic 2.0A AUTO MCCB Supply to SEXXSE03 SCHNEIDER NS800L 800 800 150 N/A 1.0 16.0 N/A 10.0 N/A N/A N/A

A17 Micrologic 2.0A AUTO MCCB Spare SCHNEIDER NS800L 800 800 150 N/A 1.0 16.0 N/A 10.0 N/A N/A N/A

A18 Micrologic 2.0A AUTO MCCB MCC-1XX01 SCHNEIDER NS800L 800 800 150 N/A 1.0 16.0 N/A 10.0 N/A N/A N/A
LV Protective Device Settings - LVSB-1XX04

Note The Schedule settings provide both Over Current and


Earth Fault protection for each Breaker

LV Thermal - Magnetic Settings


Overload Selective Short Circuit

Device Type Long Time Long Time Short Circuit Neutral Protection
Long Time Short Time Short time Instantaneous Short
Dial Setting Current Relay Trip
Delay (s) Current Delay Circuit
(Coarse) Multiplier setting
Board Name Device No. Trip ITEM Circuit Description

Breaker / Relay
Set Current Rating
Make/Brand Current Rating Icu kA Io Ir tr Im Isd tsd Iinst (3D, 3D+N/2, 4D)
(Amperes)
(Amperes)

A1 MICROLOGIC 5.0A AUTO ACB Main Incoming Supply SCHNEIDER NW32H1 3200 3200 65 N/A 1.0 1.0 N/A 3.0 0.1 Off N/A

A2 TM200D AUTO MCCB Supply to ESP SCHNEIDER NSX250N 250 200 50 N/A 200.0 N/A 2500.0 N/A N/A N/A N/A

A3 MICROLOGIC 5.0E NON-AUTO MCCB Bus coupler to LVSB - 2XX04 SCHNEIDER NS800N 800 800 50 N/A 1.0 8.0 N/A 3.0 0.1 Off N/A

A4 MICROLOGIC 2.0A AUTO MCCB Spare SCHNEIDER NS800N 800 800 50 N/A 1.0 8.0 N/A 3.0 N/A N/A N/A

A5 MICROLOGIC 2.2 AUTO MCCB Spare SCHNEIDER NSX250N 250 200 50 200 1.0 N/A N/A 5.0 N/A N/A N/A

A6 MICROLOGIC 2.2 AUTO MCCB Spare SCHNEIDER NSX250N 250 200 50 200 1.0 N/A N/A 5.0 N/A N/A N/A

A7 MICROLOGIC 2.3 AUTO MCCB Spare SCHNEIDER NSX400N 400 400 50 400 1.0 N/A N/A 5.0 N/A N/A N/A
LVSB -1XX04
A8 MICROLOGIC 2.3 AUTO MCCB Spare SCHNEIDER NSX400N 400 400 50 400 1.0 N/A N/A 5.0 N/A N/A N/A

A9 MICROLOGIC 2.3 AUTO MCCB Spare SCHNEIDER NSX400N 400 400 50 400 1.0 N/A N/A 5.0 N/A N/A N/A

A10 MICROLOGIC 2.2 AUTO MCCB Spare SCHNEIDER NSX250N 250 200 50 200 1.0 N/A N/A 5.0 N/A N/A N/A

A11 MICROLOGIC 2.2 AUTO MCCB Spare SCHNEIDER NSX250N 250 200 50 200 1.0 N/A N/A 5.0 N/A N/A N/A

A12 MICROLOGIC 2.3 AUTO MCCB Spare SCHNEIDER NSX400N 400 400 50 400 1.0 N/A N/A 5.0 N/A N/A N/A

A13 MICROLOGIC 2.3 AUTO MCCB Spare SCHNEIDER NSX400N 400 400 50 400 1.0 N/A N/A 5.0 N/A N/A N/A

A14 MICROLOGIC 2.3 AUTO MCCB Spare SCHNEIDER NSX400N 400 400 50 400 1.0 N/A N/A 5.0 N/A N/A N/A
LV Protective Device Settings - LVSB-1XX05

Note The Schedule settings provide both Over Current and


Earth Fault protection for each Breaker

LV Thermal - Magnetic Settings


Overload Selective Short Circuit

Device Type Long Time Long Time Short Circuit Neutral Protection
Long Time Short Time Short time Instantaneous Short
Dial Setting Current Relay Trip
Delay (s) Current Delay Circuit
(Coarse) Multiplier setting
Board Name Device No. TRIP ITEM Circuit Description

Full Current Rating Set Current Rating


Make/Brand Icu kA Io Ir tr Im Isd tsd Iinst (3D, 3D+N/2, 4D)
(Amperes) (Amperes)

A1 MICROLOGIC 2.3 AUTO MCCB Supply to Fire-Fighting Shaft - RB XX SW01 SCHENIDER NSX400N 400 200 50 200 1.0 N/A N/A 5.0 N/A N/A N/A

A2 MICROLOGIC 2.3 AUTO MCCB Supply to LVSB-1 XX 07 SCHENIDER NSX400N 400 400 50 400 1.0 N/A N/A 5.0 N/A N/A N/A

A3 MICROLOGIC 2.3 AUTO MCCB Supply to Fire Fighting Shaft - RB XX NE03 SCHENIDER NSX400N 400 200 50 200 1.0 N/A N/A 5.0 N/A N/A N/A

A4 MICROLOGIC 2.3 AUTO MCCB Supply to Fire Fighting Shaft - RB XX NW04 SCHENIDER NSX400N 400 200 50 200 1.0 N/A N/A 5.0 N/A N/A N/A

A5 MICROLOGIC 2.3 AUTO MCCB Supply to Fire Fighting Shaft - RB XX NW03 SCHENIDER NSX400N 400 200 50 200 1.0 N/A N/A 5.0 N/A N/A N/A

A6 MICROLOGIC 2.3 AUTO MCCB Supply to LVSB 06 SE 01 SCHENIDER NSX400N 400 400 50 400 1.0 N/A N/A 5.0 N/A N/A N/A

A7 MICROLOGIC 2.3 AUTO MCCB Supply to LVSB -1 XX 06 SCHENIDER NSX400N 400 400 50 400 1.0 N/A N/A 5.0 N/A N/A N/A

A8 N/A NON-AUTO ACB Generator Incoming Supply from LVSB 13 XX 05 SCHNEIDER NW12HF 1250 1250 85 N/A 1.0 8.0 N/A 6.0 0.1 off N/A

A9 BS88 FUSED SWITCH Supply to Wet Riser Pump 1 SOCOMEC 315 315 80 N/A N/A N/A N/A N/A N/A N/A N/A

A10 BS88 FUSED SWITCH Supply to Wet Riser Pump 2 SOCOMEC 315 315 80 N/A N/A N/A N/A N/A N/A N/A N/A

A11 BS88 FUSED SWITCH Supply to Sprinkler Pump 2 SOCOMEC 315 315 80 N/A N/A N/A N/A N/A N/A N/A N/A

A12 BS88 FUSED SWITCH Supply to Sprinkler Pump 1 SOCOMEC 315 315 80 N/A N/A N/A N/A N/A N/A N/A N/A

A13 MICROLOGIC 2.2 AUTO MCCB Spare SCHNEIDER NSX250N 250 200 50 200 1.0 N/A N/A 5.0 N/A N/A N/A

LVSB -1XX05 A14 MICROLOGIC 2.2 AUTO MCCB Spare SCHENIDER NSX250N 250 200 50 200 1.0 N/A N/A 5.0 N/A N/A N/A

A15 MICROLOGIC 2.2 AUTO MCCB Supply to DB-2 XX 03 ACO SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A16 MICROLOGIC 2.2 AUTO MCCB Supply to MCC -2 XX 10 ACO SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A17 MICROLOGIC 2.2 AUTO MCCB Suppy to MCC -2 XX 09 ACO SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A18 MICROLOGIC 2.2 AUTO MCCB Supply to DB -1 XX 04 ACO SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A19 MICROLOGIC 2.2 AUTO MCCB Supply to DB -1 XX 01 ACO SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A20 MICROLOGIC 2.2 AUTO MCCB Spare SCHNEIDER NSX160N 160 160 50 160 1.0 N/A N/A 5.0 N/A N/A N/A

A21 MICROLOGIC 2.2 AUTO MCCB Supply to Fire Command Control Room DB 00 XX 05 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A22 MICROLOGIC 2.2 AUTO MCCB Supply to MCC -2 XX 07 ACO SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A23 MICROLOGIC 2.2 AUTO MCCB Supply to DB -2 XX 04 ACO SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A24 MICROLOGIC 2.2 AUTO MCCB Spare SCHNEIDER NSX100N 100 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A25 MICROLOGIC 2.2 AUTO MCCB Spare SCHNEIDER NSX100N 100 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A26 MICROLOGIC 2.2 AUTO MCCB Spare SCHNEIDER NSX100N 100 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A27 MICROLOGIC 2.2 AUTO MCCB Spare SCHNEIDER NSX100N 100 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A
LV Protective Device Settings - LVSB-1XX06
Note The Schedule settings provide both Over Current and
Earth Fault protection for each Breaker

LV Thermal - Magnetic Settings

Overload Selective Short Circuit

Long Time Long Time Short Circuit Neutral Protection


Device Type Long Time Short Time Short time Instantaneous Short
Dial Setting Current relay trip
Delay (s) Current Delay Circuit
(Coarse) Multiplier setting
Board Name Device No. Trip ITEM Circuit Description

Full Breaker / Relay Breaker / Relay


Icu
Make/Brand Current Rating Current Rating SET Io Ir tr Im Isd tsd Iinst (3D, 3D+N/2, 4D)
(KA)
(Amperes) @ (Amperes)

A1 N/A NON-AUTO MCCB Changeover bypass SCHNEIDER NS800NA 800 800 50 N/A N/A N/A N/A N/A N/A N/A N/A

A2 N/A NON-AUTO MCCB Life Safert Incoming Supply SCHNEIDER NS800NA 800 800 50 N/A N/A N/A N/A N/A N/A N/A N/A

A3 MICROLOGIC 5.0A AUTO MCCB Mains Incoming supply SCHNEIDER NS800N 800 800 50 N/A 1.0 8.0 N/A 4.0 0.1 OFF N/A

A4 MICROLOGIC 2.2 AUTO MCCB Supply to office lift 9 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A5 MICROLOGIC 2.2 AUTO MCCB Supply to office lift 10 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A6 MICROLOGIC 2.2 AUTO MCCB Supply to office lift 11 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A7 MICROLOGIC 2.2 AUTO MCCB Supply to office lift 12 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A8 MICROLOGIC 2.2 AUTO MCCB Supply to office lift 13 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A
LVSB -1XX06
A9 MICROLOGIC 2.2 AUTO MCCB Supply to office lift 14 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A10 MICROLOGIC 2.2 AUTO MCCB Supply to office lift 15 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A11 MICROLOGIC 2.2 AUTO MCCB Supply to office lift 16 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A12 MICROLOGIC 2.2 AUTO MCCB Supply to goods lift 2 SCHNEIDER NSX160N 160 160 50 160 1.0 N/A N/A 5.0 N/A N/A N/A

A13 MICROLOGIC 2.2 AUTO MCCB Supply to office1 lift core DB-1 XX 11 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A14 MICROLOGIC 2.2 AUTO MCCB Supply to Car park lift 2 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A15 MICROLOGIC 2.2 AUTO MCCB Spare SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A16 MICROLOGIC 2.2 AUTO MCCB Spare SCHNEIDER NSX100N 100 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A
LV Protective Device Settings - LVSB-1XX07
Note The Schedule settings provide both Over Current and
Earth Fault protection for each Breaker

LV Thermal - Magnetic Settings

Overload Selective Short Circuit

Long Time Long Time Short Circuit Neutral Protection


Device Type Long Time Short Time Short time Instantaneous Short
Dial Setting Current relay trip
Delay (s) Current Delay Circuit
(Coarse) Multiplier setting
Board Name Device No. Trip ITEM Circuit Description

Full Breaker / Relay Breaker / Relay


Icu
Make/Brand Current Rating Current Rating SET Io Ir tr Im Isd tsd Iinst (3D, 3D+N/2, 4D)
(KA)
(Amperes) @ (Amperes)

A1 N/A NON-AUTO MCCB Changeover bypass SCHNEIDER NS800NA 800 800 50 N/A N/A N/A N/A N/A N/A N/A N/A

A2 N/A NON-AUTO MCCB Life Safety Incoming Supply SCHNEIDER NS800NA 800 800 50 N/A N/A N/A N/A N/A N/A N/A N/A

A3 MICROLOGIC 5.0A AUTO MCCB Mains incoming supply SCHNEIDER NS800N 800 800 50 N/A 1.0 8.0 N/A 4.0 0.1 OFF N/A

A4 MICROLOGIC 2.2 AUTO MCCB Supply to office lift 7 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A5 MICROLOGIC 2.2 AUTO MCCB Supply to office lift 6 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A6 MICROLOGIC 2.2 AUTO MCCB Supply to office lift 5 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A7 MICROLOGIC 2.2 AUTO MCCB Supply to office lift 4 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A8 MICROLOGIC 2.2 AUTO MCCB Supply to office lift 3 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

LVSB -1XX07 A9 MICROLOGIC 2.2 AUTO MCCB Supply to office lift 2 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A10 MICROLOGIC 2.2 AUTO MCCB Supply to office lift 1 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A11 MICROLOGIC 2.2 AUTO MCCB Supply to office lift 8 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A12 MICROLOGIC 2.2 AUTO MCCB Supply to Goods Lift SCHNEIDER NSX160N 160 160 50 160 1.0 N/A N/A 5.0 N/A N/A N/A

A13 MICROLOGIC 2.2 AUTO MCCB Supply to office1 lift core DB-1XX03 SCHNEIDER NSX160N 160 160 50 160 1.0 N/A N/A 5.0 N/A N/A N/A

A14 MICROLOGIC 2.2 AUTO MCCB Supply to Car park lift 1 SCHNEIDER NSX100N 100 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A15 MICROLOGIC 2.2 AUTO MCCB Spare SCHNEIDER NSX100N 100 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A16 MICROLOGIC 2.2 AUTO MCCB Spare SCHNEIDER NSX100N 100 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A17 MICROLOGIC 2.2 AUTO MCCB Spare SCHNEIDER NSX100N 100 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A
LV Protective Device Settings - LVSB-2XX01

Note The Schedule settings provide both Over Current and


Earth Fault protection for each Breaker

LV Thermal - Magnetic Settings


Overload Selective Short Circuit

Device Type Long Time Long Time Short Circuit Neutral Protection
Long Time Short Time Short time Instantaneous Short
Dial Setting Current Relay Trip
Delay (s) Current Delay Circuit
(Coarse) Multiplier setting
Board Name Device No. Trip ITEM Circuit Description

Breaker / Relay
Set Current Rating
Make/Brand Current Rating Icu kA Io Ir tr Im Isd tsd Iinst (3D, 3D+N/2, 4D)
(Amperes)
(Amperes)

A1 MICROLOGIC 5.0A ACB Main Incoming SCHNEIDER NW63H1 6300 6300 100 N/A 1.0 1.0 N/A 5.0 0.1 OFF N/A

A2 TM200D MCCB Supply ESP SCHNEIDER NSX250N 250 200 50 N/A 200.0 N/A 2500.0 N/A N/A N/A N/A

A3 BS 88 Fused Switch Supply Sprinkler Pump 1 SOCOMEC 315 315 80 N/A N/A N/A N/A N/A N/A N/A N/A

A4 BS 88 Fused Switch Supply Sprinkler Pump 2 SOCOMEC 315 315 80 N/A N/A N/A N/A N/A N/A N/A N/A

A5 BS 88 Fused Switch Supply Wet Pump 1 SOCOMEC 315 315 80 N/A N/A N/A N/A N/A N/A N/A N/A

A6 BS 88 Fused Switch Supply Wet Pump 2 SOCOMEC 315 315 80 N/A N/A N/A N/A N/A N/A N/A N/A

A7 MICROLOGIC 5.0E NON-AUTO ACB Bus Coupler to LVSB-1XX01 SCHNEIDER NW32H2 3200 3200 85 N/A 1.0 1.0 N/A 3.0 0.1 OFF N/A

A8 MICROLOGIC 2.0A AUTO MCCB Supply to 400 KVAR PFC SCHNEIDER NS800L 800 800 150 N/A 1.0 16.0 N/A 10.0 N/A N/A N/A

A9 MICROLOGIC 2.2 AUTO MCCB SPARE SCHNEIDER NSX100S 100 100 100 100 1.0 N/A N/A 5.0 N/A N/A N/A

A10 MICROLOGIC 2.2 AUTO MCCB SPARE SCHNEIDER NSX100S 100 100 100 100 1.0 N/A N/A 5.0 N/A N/A N/A

A11 MICROLOGIC 2.3 AUTO MCCB Supply to RBXXNW02 SCHNEIDER NSX630S 630 630 100 630 1.0 N/A N/A 5.0 N/A N/A N/A

A12 MICROLOGIC 2.3 AUTO MCCB Supply to RBXXNE02 SCHNEIDER NSX630S 630 630 100 630 1.0 N/A N/A 5.0 N/A N/A N/A

A13 MICROLOGIC 2.3 AUTO MCCB Supply to MCC-2XX01 SCHNEIDER NSX400S 400 400 100 400 1.0 N/A N/A 5.0 N/A N/A N/A

A14 MICROLOGIC 2.2 AUTO MCCB SPARE SCHNEIDER NSX100S 100 100 100 100 1.0 N/A N/A 5.0 N/A N/A N/A

A15 MICROLOGIC 2.2 AUTO MCCB SPARE SCHNEIDER NSX100S 100 100 100 100 1.0 N/A N/A 5.0 N/A N/A N/A

A16 MICROLOGIC 2.3 AUTO MCCB Supply to MCC-2XX03 SCHNEIDER NSX400S 400 400 100 400 1.0 N/A N/A 5.0 N/A N/A N/A

A17 MICROLOGIC 2.3 AUTO MCCB SPARE SCHNEIDER NSX400S 400 400 100 400 1.0 N/A N/A 5.0 N/A N/A N/A

A18 MICROLOGIC 2.3 AUTO MCCB SPARE SCHNEIDER NSX400S 400 400 100 400 1.0 N/A N/A 5.0 N/A N/A N/A

A19 MICROLOGIC 2.2 AUTO MCCB SPARE SCHNEIDER NSX250S 250 200 100 200 1.0 N/A N/A 5.0 N/A N/A N/A

A20 MICROLOGIC 2.2 AUTO MCCB SPARE SCHNEIDER NSX250S 250 200 100 200 1.0 N/A N/A 5.0 N/A N/A N/A

A21 MICROLOGIC 2.2 AUTO MCCB SUPPLY TO LANDLORDS UPS DB-2XX11 SCHNEIDER NSX250S 250 160 100 160 1.0 N/A N/A 5.0 N/A N/A N/A

A22 MICROLOGIC 2.2 AUTO MCCB SPARE SCHNEIDER NSX250S 250 200 100 200 1.0 N/A N/A 5.0 N/A N/A N/A

A23 MICROLOGIC 2.2 AUTO MCCB SUPPLY TO RBXXNW03 ACO SCHNEIDER NSX250S 250 200 100 200 1.0 N/A N/A 5.0 N/A N/A N/A

A24 MICROLOGIC 2.2 AUTO MCCB SUPPLY TO RBXXNW04 ACO SCHNEIDER NSX250S 250 200 100 200 1.0 N/A N/A 5.0 N/A N/A N/A

A25 MICROLOGIC 2.2 AUTO MCCB SUPPLY TO RBXXNE03 ACO SCHNEIDER NSX250S 250 200 100 200 1.0 N/A N/A 5.0 N/A N/A N/A

A26 MICROLOGIC 2.2 AUTO MCCB SUPPLY TO RBXXSW01 ACO SCHNEIDER NSX250S 250 200 100 200 1.0 N/A N/A 5.0 N/A N/A N/A

A27 MICROLOGIC 2.2 AUTO MCCB Mezzanie East Landlords DB-1XX12 SCHNEIDER NSX160S 160 100 100 100 1.0 N/A N/A 5.0 N/A N/A N/A

A28 MICROLOGIC 2.2 AUTO MCCB Ground WEST Landlords DB00NW01 SCHNEIDER NSX160S 160 100 100 100 1.0 N/A N/A 5.0 N/A N/A N/A

A29 MICROLOGIC 2.2 AUTO MCCB SUPPLY TO DB UKPN SCHNEIDER NSX160S 160 100 100 100 1.0 N/A N/A 5.0 N/A N/A N/A
SUPPLY TO RAIN WATER HARVESTING BOOSTER PUMP
A30 MICROLOGIC 2.2 AUTO MCCB SCHNEIDER NSX160S 160 160 100 160 1.0 N/A N/A 5.0 N/A N/A N/A
HRBS01XX01 ACO
A31 MICROLOGIC 2.2 AUTO MCCB Supply to DB-2 XX08 SCHNEIDER NSX160S 160 100 100 100 1.0 N/A N/A 5.0 N/A N/A N/A

LVSB -2XX01 A32 MICROLOGIC 2.2 AUTO MCCB Supply to DB-2 XX07 SCHNEIDER NSX160S 160 100 100 100 1.0 N/A N/A 5.0 N/A N/A N/A

A33 MICROLOGIC 2.2 AUTO MCCB Supply to DB-2 XX01 SCHNEIDER NSX160S 160 100 100 100 1.0 N/A N/A 5.0 N/A N/A N/A

A34 MICROLOGIC 2.2 AUTO MCCB Supply to DB-2 XX02 SCHNEIDER NSX160S 160 100 100 100 1.0 N/A N/A 5.0 N/A N/A N/A

A35 MICROLOGIC 2.2 AUTO MCCB Supply to DB-2 XX09 SCHNEIDER NSX160S 160 100 100 100 1.0 N/A N/A 5.0 N/A N/A N/A
LV Protective Device Settings - LVSB-2XX01

Note The Schedule settings provide both Over Current and


Earth Fault protection for each Breaker

LV Thermal - Magnetic Settings


Overload Selective Short Circuit

Device Type Long Time Long Time Short Circuit Neutral Protection
Long Time Short Time Short time Instantaneous Short
Dial Setting Current Relay Trip
Delay (s) Current Delay Circuit
(Coarse) Multiplier setting
Board Name Device No. Trip ITEM Circuit Description

Breaker / Relay
Set Current Rating
Make/Brand Current Rating Icu kA Io Ir tr Im Isd tsd Iinst (3D, 3D+N/2, 4D)
(Amperes)
(Amperes)

A36 MICROLOGIC 2.2 AUTO MCCB Supply to 33KV Room MCC 1 -XX06 SCHNEIDER NSX160S 160 100 100 100 1.0 N/A N/A 5.0 N/A N/A N/A

A37 MICROLOGIC 2.2 AUTO MCCB SPARE SCHNEIDER NSX160S 160 160 100 160 1.0 N/A N/A 5.0 N/A N/A N/A

A38 MICROLOGIC 2.2 AUTO MCCB Supply to MCC-2 XX08 SCHNEIDER NSX160S 160 100 100 100 1.0 N/A N/A 5.0 N/A N/A N/A

A39 MICROLOGIC 2.2 AUTO MCCB Supply to DB-2 XX03 ACO SCHNEIDER NSX160S 160 100 100 100 1.0 N/A N/A 5.0 N/A N/A N/A

A40 MICROLOGIC 2.2 AUTO MCCB Supply to DB-2 XX10 SCHNEIDER NSX160S 160 100 100 100 1.0 N/A N/A 5.0 N/A N/A N/A

A41 MICROLOGIC 2.2 AUTO MCCB Supply to MCC-2 XX09 ACO SCHNEIDER NSX160S 160 100 100 100 1.0 N/A N/A 5.0 N/A N/A N/A

A42 MICROLOGIC 2.2 AUTO MCCB Supply to DB-2 XX06 ACO SCHNEIDER NSX160S 160 100 100 100 1.0 N/A N/A 5.0 N/A N/A N/A

A43 MICROLOGIC 2.2 AUTO MCCB Supply to MCC-2 XX10 SCHNEIDER NSX160S 160 100 100 100 1.0 N/A N/A 5.0 N/A N/A N/A

A44 MICROLOGIC 2.2 AUTO MCCB Supply to DB-2 XX05 ACO SCHNEIDER NSX160S 160 100 100 100 1.0 N/A N/A 5.0 N/A N/A N/A

A45 MICROLOGIC 2.2 AUTO MCCB Supply to MCC-2 XX07 ACO SCHNEIDER NSX160S 160 100 100 100 1.0 N/A N/A 5.0 N/A N/A N/A

A46 MICROLOGIC 2.2 AUTO MCCB Supply to DB-2 XX04 ACO SCHNEIDER NSX160S 160 100 100 100 1.0 N/A N/A 5.0 N/A N/A N/A

A47 MICROLOGIC 2.2 AUTO MCCB Supply to CW Booster Set BS-2XX01 SCHNEIDER NSX160S 160 100 100 100 1.0 N/A N/A 5.0 N/A N/A N/A

A48 MICROLOGIC 2.2 AUTO MCCB Supply to MCC-2 XX13 SCHNEIDER NSX160S 160 100 100 100 1.0 N/A N/A 5.0 N/A N/A N/A

A49 MICROLOGIC 2.2 AUTO MCCB SPARE SCHNEIDER NSX100S 100 100 100 100 1.0 N/A N/A 5.0 N/A N/A N/A

A50 MICROLOGIC 2.2 AUTO MCCB SPARE SCHNEIDER NSX100S 100 100 100 100 1.0 N/A N/A 5.0 N/A N/A N/A

A51 MICROLOGIC 2.2 AUTO MCCB SPARE SCHNEIDER NSX100S 100 100 100 100 1.0 N/A N/A 5.0 N/A N/A N/A

A52 MICROLOGIC 2.2 AUTO MCCB Supply to Remote AHF 4 SCHNEIDER NSX160S 160 160 100 160 1.0 N/A N/A 5.0 N/A N/A N/A

A53 MICROLOGIC 2.2 AUTO MCCB Supply to Remote AHF 3 SCHNEIDER NSX160S 160 160 100 160 1.0 N/A N/A 5.0 N/A N/A N/A

A54 MICROLOGIC 2.2 AUTO MCCB Supply to Remote AHF 2 SCHNEIDER NSX160S 160 160 100 160 1.0 N/A N/A 5.0 N/A N/A N/A

A55 MICROLOGIC 2.2 AUTO MCCB Supply to Remote AHF 1 SCHNEIDER NSX160S 160 160 100 160 1.0 N/A N/A 5.0 N/A N/A N/A

A56 MICROLOGIC 2.3 AUTO MCCB Supply to MCC-2 XX 05 SCHNEIDER NSX630S 630 630 100 630 1.0 N/A N/A 5.0 N/A N/A N/A

A57 MICROLOGIC 2.0A AUTO MCCB Supply to LVSB 06 SE01 ACO SCHNEIDER NS800L 800 800 150 N/A 1.0 16.0 N/A 10.0 N/A N/A N/A

A58 MICROLOGIC 2.0A AUTO MCCB Supply to CH-2 XX04 SCHNEIDER NS800L 800 800 150 N/A 1.0 16.0 N/A 10.0 N/A N/A N/A

A59 MICROLOGIC 2.0A AUTO MCCB Supply to CH-2 XX02 SCHNEIDER NS800L 800 800 150 N/A 1.0 16.0 N/A 10.0 N/A N/A N/A

A60 MICROLOGIC 2.0A AUTO MCCB Supply to CH-2 XX03 SCHNEIDER NS800L 800 800 150 N/A 1.0 16.0 N/A 10.0 N/A N/A N/A

A61 MICROLOGIC 2.0A AUTO MCCB Supply to CH-2 XX01 SCHNEIDER NS800L 800 800 150 N/A 1.0 16.0 N/A 10.0 N/A N/A N/A

A62 MICROLOGIC 2.0A AUTO MCCB Supply to LVSB-1XX07 ACO SCHNEIDER NS800L 800 800 150 N/A 1.0 16.0 N/A 10.0 N/A N/A N/A

A63 MICROLOGIC 2.0A AUTO MCCB SPARE SCHNEIDER NS800L 800 800 150 N/A 1.0 16.0 N/A 10.0 N/A N/A N/A
LV Protective Device Settings - LVSB -2XX02

Note The Schedule settings provide both Over Current and


Earth Fault protection for each Breaker

LV Thermal - Magnetic Settings


Overload Selective Short Circuit

Long Time Long Time Short Circuit Neutral Protection


Device Type Long Time Short Time Short time Instantaneous Short
Dial Setting Current Relay Trip
Delay (s) Current Delay Circuit
(Coarse) Multiplier setting
Board Name Device No. Trip ITEM Circuit Description

Full Breaker / Relay Breaker / Relay


Icu
Make/Brand Current Rating Current Rating SET Io Ir tr lm Isd tsd Iinst (3D, 3D+N/2, 4D)
(KA)
(Amperes) @ (Amperes)

A1 Micrologic 5.0A AUTO ACB Main Incoming Supply SCHNEIDER NW16H1 1600 1600 65 N/A 1.0 1.0 N/A 3.0 0.1 Off N/A

A2 TM200D AUTO MCCB Supply to ESP SCHNEIDER NSX250N 250 200 50 N/A 200.0 N/A 2500.0 N/A N/A N/A N/A

A3 Micrologic 2.3 AUTO MCCB Supply to PFC SCHNEIDER NSX400N 400 400 50 400 1.0 N/A N/A 5.0 N/A N/A N/A

A4 Micrologic 2.2 AUTO MCCB AHF 4 Supply SCHNEIDER NSX160N 160 160 50 160 1.0 N/A N/A 5.0 N/A N/A N/A

A5 Micrologic 2.2 AUTO MCCB AHF 3 Supply SCHNEIDER NSX160N 160 160 50 160 1.0 N/A N/A 5.0 N/A N/A N/A

A6 Micrologic 2.3 AUTO MCCB Supply to RBXXNW06 SCHNEIDER NSX400N 400 400 50 400 1.0 N/A N/A 5.0 N/A N/A N/A

LVSB -2 XX02 A7 Micrologic 2.3 AUTO MCCB Supply to RBXXSW03 SCHNEIDER NSX400N 400 400 50 400 1.0 N/A N/A 5.0 N/A N/A N/A

A8 Micrologic 2.3 AUTO MCCB SPARE SCHNEIDER NSX400N 400 400 50 400 1.0 N/A N/A 5.0 N/A N/A N/A

A9 Micrologic 2.2 AUTO MCCB AHF 1 Supply SCHNEIDER NSX160N 160 160 50 160 1.0 N/A N/A 5.0 N/A N/A N/A

A10 Micrologic 2.2 AUTO MCCB AHF 2 Supply SCHNEIDER NSX160N 160 160 50 160 1.0 N/A N/A 5.0 N/A N/A N/A

A11 Micrologic 2.3 AUTO MCCB Supply to RBXXNE04 SCHNEIDER NSX400N 400 400 50 400 1.0 N/A N/A 5.0 N/A N/A N/A

A12 Micrologic 2.3 AUTO MCCB Supply to RBXXSE01 SCHNEIDER NSX400N 400 400 50 400 1.0 N/A N/A 5.0 N/A N/A N/A

A13 Micrologic 2.3 AUTO MCCB Spare SCHNEIDER NSX400N 400 400 50 400 1.0 N/A N/A 5.0 N/A N/A N/A
LV Protective Device Settings - LVSB -2XX03

Note The Schedule settings provide both Over Current and


Earth Fault protection for each Breaker

LV Thermal - Magnetic Settings


Overload Selective Short Circuit

Device Type Long Time Long Time Short Circuit Neutral Protection
Long Time Short Time Short time Instantaneous Short
Dial Setting Current Relay Trip
Delay (s) Current Delay Circuit
(Coarse) Multiplier setting
Board Name Device No. Trip ITEM Circuit Description

Breaker / Relay
Set Current Rating
Make/Brand Current Rating Icu kA Io Ir tr Im Isd tsd Iinst (3D, 3D+N/2, 4D)
(Amperes)
(Amperes)

A1 Micrologic 5.0A AUTO-ACB Main Incoming Supply SCHNEIDER NW50H1 5000 5000 100 N/A 1.0 1.0 N/A 5.0 0.1 Off N/A

A2 TM200D AUTO MCCB Supply to ESP SCHNEIDER NSX250N 250 200 50 200.0 1.0 N/A N/A 5.0 N/A N/A N/A

A3 Micrologic 2.3 AUTO MCCB PFC Supply SCHNEIDER NSX400S 400 400 100 400 1.0 N/A N/A 5.0 N/A N/A N/A

A4 Micrologic 2.2 AUTO MCCB AHF 3 Supply SCHNEIDER NSX160S 160 160 100 160 1.0 N/A N/A 5.0 N/A N/A N/A

A5 Micrologic 2.2 AUTO MCCB AHF 4 Supply SCHNEIDER NSX160S 160 160 100 160 1.0 N/A N/A 5.0 N/A N/A N/A

A6 Micrologic 2.2 AUTO MCCB AHF 1 Supply SCHNEIDER NSX160S 160 160 100 160 1.0 N/A N/A 5.0 N/A N/A N/A

A7 Micrologic 2.2 AUTO MCCB AHF 2 Supply SCHNEIDER NSX160S 160 160 100 160 1.0 N/A N/A 5.0 N/A N/A N/A

A8 Micrologic 2.0A AUTO MCCB SPARE SCHNEIDER NSX400S 400 400 100 400 1.0 N/A N/A 5.0 N/A N/A N/A

A9 Micrologic 2.0A AUTO MCCB Supply to RBXXSW05 SCHNEIDER NS800L 800 800 150 N/A 1.0 16.0 N/A 10.0 N/A N/A N/A
LVSB -2XX03
A10 Micrologic 2.0A AUTO MCCB Supply to RBXXSW07 SCHNEIDER NS800L 800 800 150 N/A 1.0 16.0 N/A 10.0 N/A N/A N/A

A11 Micrologic 2.0A AUTO MCCB Supply to RBXXSE04 SCHNEIDER NS800L 800 800 150 N/A 1.0 16.0 N/A 10.0 N/A N/A N/A

A12 Micrologic 2.0A AUTO MCCB Supply to RB XXSE05 SCHNEIDER NS800L 800 800 150 N/A 1.0 16.0 N/A 10.0 N/A N/A N/A

A13 Micrologic 2.0A AUTO MCCB Supply to RB XXNE07 SCHNEIDER NS800L 800 800 150 N/A 1.0 16.0 N/A 10.0 N/A N/A N/A

A14 Micrologic 2.0A AUTO MCCB Supply to RBXXNE09 SCHNEIDER NS800L 800 800 150 N/A 1.0 16.0 N/A 10.0 N/A N/A N/A

A15 Micrologic 2.0A AUTO MCCB Supply to RBXXNW09 SCHNEIDER NS800L 800 800 150 N/A 1.0 16.0 N/A 10.0 N/A N/A N/A

A16 Micrologic 2.0A AUTO MCCB Supply to RBXXNW08 SCHNEIDER NS800L 800 800 150 N/A 1.0 16.0 N/A 10.0 N/A N/A N/A

A17 Micrologic 2.0A AUTO MCCB SPARE SCHNEIDER NS800L 800 800 150 N/A 1.0 16.0 N/A 10.0 N/A N/A N/A

A18 Micrologic 2.0A AUTO MCCB SPARE SCHNEIDER NS800L 800 800 150 N/A 1.0 16.0 N/A 10.0 N/A N/A N/A
LV Protective Device Settings - LVSB-2XX04

Note The Schedule settings provide both Over Current and


Earth Fault protection for each Breaker

LV Thermal - Magnetic Settings


Overload Selective Short Circuit

Long Time Long Time Short Circuit Neutral Protection


Device Type Long Time Short Time Short time Instantaneous Short
Dial Setting Current relay trip
Delay (s) Current Delay Circuit
(Coarse) Multiplier setting
Board Name Device No. Trip ITEM Circuit Description

Full Breaker / Relay Breaker / Relay


Icu
Make/Brand Current Rating Current Rating SET Io Ir tr Im Isd tsd Iinst (3D, 3D+N/2, 4D)
(KA)
(Amperes) @ (Amperes)

A1 MICROLOGIC 5.0A AUTO ACB Main Incoming Supply SCHNEIDER NW32H1 3200 3200 65 N/A 1.0 1.0 N/A 3.0 0.1 Off N/A

A2 TM200D AUTO MCCB Supply to ESP SCHNEIDER NSX250N 250 200 50 N/A 200.0 N/A 2500.0 N/A N/A N/A N/A

A3 MICROLOGIC 5.0E NON-AUTO MCCB Bus Coupler to LVSB-1XX04 SCHNEIDER NS800N 800 800 50 N/A 1.0 1.0 N/A 3.0 0.1 off N/A

A4 MICROLOGIC 2.0A AUTO MCCB Spare SCHNEIDER NS800N 800 800 50 N/A 1.0 8.0 N/A 3.0 N/A N/A N/A

A5 MICROLOGIC 2.2 AUTO MCCB Spare SCHNEIDER NSX250N 250 200 50 200 1.0 N/A N/A 5.0 N/A N/A N/A

A6 MICROLOGIC 2.2 AUTO MCCB Spare SCHNEIDER NSX250N 250 200 50 200 1.0 N/A N/A 5.0 N/A N/A N/A

A7 MICROLOGIC 2.3 AUTO MCCB Spare SCHNEIDER NSX400N 400 400 50 400 1.0 N/A N/A 5.0 N/A N/A N/A

LVSB -2XX04 A8 MICROLOGIC 2.3 AUTO MCCB Spare SCHNEIDER NSX400N 400 400 50 400 1.0 N/A N/A 5.0 N/A N/A N/A

A9 MICROLOGIC 2.3 AUTO MCCB Spare SCHNEIDER NSX400N 400 400 50 400 1.0 N/A N/A 5.0 N/A N/A N/A

A10 MICROLOGIC 2.2 AUTO MCCB Spare SCHNEIDER NSX250N 250 200 50 200 1.0 N/A N/A 5.0 N/A N/A N/A

A11 MICROLOGIC 2.2 AUTO MCCB Spare SCHNEIDER NSX250N 250 200 50 200 1.0 N/A N/A 5.0 N/A N/A N/A

A12 MICROLOGIC 2.2 AUTO MCCB Spare SCHNEIDER NSX250N 250 200 50 200 1.0 N/A N/A 5.0 N/A N/A N/A

A13 MICROLOGIC 2.3 AUTO MCCB Spare SCHNEIDER NSX400N 400 400 50 400 1.0 N/A N/A 5.0 N/A N/A N/A

A14 MICROLOGIC 2.3 AUTO MCCB Spare SCHNEIDER NSX400N 400 400 50 400 1.0 N/A N/A 5.0 N/A N/A N/A

A15 MICROLOGIC 2.3 AUTO MCCB Spare SCHNEIDER NSX400N 400 400 50 400 1.0 N/A N/A 5.0 N/A N/A N/A
LV Protective Device Settings - LVSB06SE01

Note The Schedule settings provide both Over Current and


Earth Fault protection for each Breaker

LV Thermal - Magnetic Settings


Overload Selective Short Circuit

Device Type Long Time Long Time Short Circuit Neutral Protection
Long Time Short Time Short time Instantaneous Short
Dial Setting Current Relay Trip
Delay (s) Current Delay Circuit
(Coarse) Multiplier setting
Board Name Device No. TRIP ITEM Circuit Description

Breaker / Relay
Set Current Rating
Make/Brand Current Rating Icu kA Io Ir tr Im Isd tsd Iinst (3D, 3D+N/2, 4D)
(Amperes)
(Amperes)

A1 N/A NON-AUTO MCCB CHANGEOVER BYPASS SCHNEIDER NS800NA 800 800 50 N/A N/A N/A N/A N/A N/A N/A N/A

A2 N/A NON-AUTO MCCB LIFE SAFETY INCOMING SUPPLY SCHNEIDER NS800NA 800 800 50 N/A N/A N/A N/A N/A N/A N/A N/A

A3 MICROLOGIC 5.0A AUTO MCCB MAIN INCOMING SUPPLY SCHNEIDER NS800N 800 800 50 N/A 1.0 8.0 N/A 4.0 0.1 OFF N/A

A4 MICROLOGIC 2.2 AUTO MCCB SUPPLY TO TRADING LIFT 1 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A5 MICROLOGIC 2.2 AUTO MCCB SUPPLY TO TRADING LIFT 2 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A6 MICROLOGIC 2.2 AUTO MCCB SUPPLY TO TRADING LIFT 3 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A7 MICROLOGIC 2.2 AUTO MCCB SUPPLY TO TRADING LIFT 4 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A
LVSB06SE01
A8 MICROLOGIC 2.2 AUTO MCCB SUPPLY TO TRADING LIFT 5 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A9 MICROLOGIC 2.2 AUTO MCCB SUPPLY TO TRADING LIFT 6 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A10 MICROLOGIC 2.2 AUTO MCCB SUPPLY TO TRADING LIFT 7 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A11 MICROLOGIC 2.2 AUTO MCCB SUPPLY TO TRADING LIFT 8 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A12 MICROLOGIC 2.2 AUTO MCCB SUPPLY TO TRADING LIFT MOTOR ROOM DB 06 SE01 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A13 MICROLOGIC 2.2 AUTO MCCB SUPPLY TO MCC SE 01 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A14 MICROLOGIC 2.2 AUTO MCCB SPARE SCHNEIDER NSX100N 100 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A
LV Protective Device Settings - LVSB 13XX01

Note The Schedule settings provide both Over Current and


Earth Fault protection for each Breaker

LV Thermal - Magnetic Settings


Overload Selective Short Circuit

Device Type Long Time Long Time Short Circuit Neutral Protection
Long Time Short Time Short time Instantaneous Short
Dial Setting Current Relay Trip
Delay (s) Current Delay Circuit
(Coarse) Multiplier setting
Board Name Device No. Trip ITEM Circuit Description

Full Current Rating Set Current Rating


Make/Brand Icu kA Io Ir tr Im Isd tsd Iinst (3D, 3D+N/2, 4D)
(Amperes) (Amperes)

A1 MICROLOGIC 5.0A AUTO ACB Main Incoming Supply SCHNEIDER NW32H1 3200 3200 65 N/A 1.0 1.0 N/A 3.0 0.1 Off N/A

A2 TM200D AUTO MCCB Supply to ESP SCHNEIDER NSX250N 250 200 50 N/A 200.0 N/A 2500.0 N/A N/A N/A N/A

A3 MICROLOGIC 2.3 AUTO MCCB Supply to KVAR PFC SCHNEIDER NSX630N 630 630 50 630 1.0 N/A N/A 5.0 N/A N/A N/A

A4 MICROLOGIC 5.0E NON AUTO-ACB Bus coupler to LVSB -13 XX04 SCHNEIDER NW12H1 1250 1250 85 N/A 1.0 8.0 N/A 6.0 0.1 off N/A

A5 MICROLOGIC 2.2 AUTO MCCB Spare SCHNEIDER NSX250N 250 200 50 200 1.0 N/A N/A 5.0 N/A N/A N/A

A6 MICROLOGIC 2.2 AUTO MCCB Supply to MCC 13 XX 05 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A7 MICROLOGIC 2.2 AUTO MCCB Spare SCHNEIDER NSX160N 160 160 50 160 1.0 N/A N/A 5.0 N/A N/A N/A

A8 MICROLOGIC 2.2 AUTO MCCB Supply to MCC 13 XX 13 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A9 MICROLOGIC 2.2 AUTO MCCB Supply to MCC 13 XX 14 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A10 MICROLOGIC 2.2 AUTO MCCB Spare SCHNEIDER NSX100N 100 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A11 MICROLOGIC 2.2 AUTO MCCB Spare SCHNEIDER NSX100N 100 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A12 MICROLOGIC 2.2 AUTO MCCB Spare SCHNEIDER NSX100N 100 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A13 MICROLOGIC 2.2 AUTO MCCB Spare SCHNEIDER NSX250N 250 200 50 200 1.0 N/A N/A 5.0 N/A N/A N/A

A14 MICROLOGIC 2.2 AUTO MCCB Supply to MCC 13 XX 03 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A15 MICROLOGIC 2.2 AUTO MCCB Supply to MCC 13 XX 04 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A16 MICROLOGIC 2.2 AUTO MCCB Supply to MCC 13 XX 09 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A17 MICROLOGIC 2.2 AUTO MCCB Supply to MCC 13 XX 10 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A18 MICROLOGIC 2.2 AUTO MCCB Spare SCHNEIDER NSX100N 100 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A19 MICROLOGIC 2.2 AUTO MCCB Spare SCHNEIDER NSX100N 100 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A20 MICROLOGIC 2.2 AUTO MCCB Spare SCHNEIDER NSX100N 100 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

LVSB 13XX01 A21 TM63D AUTO MCCB Supply to FFS 13 XX 01 ACO SCHNEIDER NSX100N 100 63 50 N/A 63.0 N/A N/A N/A N/A N/A N/A

A22 MICROLOGIC 2.2 AUTO MCCB Supply to MCC 14 XX 01 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A23 MICROLOGIC 2.2 AUTO MCCB Supply to MCC 14 XX 02 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A24 MICROLOGIC 2.2 AUTO MCCB Supply to MCC 14 XX 03 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A25 MICROLOGIC 2.2 AUTO MCCB Supply to MCC 14 XX 04 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A26 TM63D AUTO MCCB Supply to Fire Lift Core 1 ACO SCHNEIDER NSX100N 100 63 50 N/A 63.0 N/A N/A N/A N/A N/A N/A

A27 TM63D AUTO MCCB Supply to Fire Lift Core 2 ACO SCHNEIDER NSX100N 100 63 50 N/A 63.0 N/A N/A N/A N/A N/A N/A

A28 TM63D AUTO MCCB Supply to FFS 13 XX 02 ACO SCHNEIDER NSX100N 100 63 50 N/A 63.0 N/A N/A N/A N/A N/A N/A

A29 MICROLOGIC 2.2 AUTO MCCB Supply to DB 13 XX 03 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A30 MICROLOGIC 2.2 AUTO MCCB Supply to DB 13 XX 04 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A31 MICROLOGIC 2.2 AUTO MCCB Supply to MCC 6 NE 01 Core 2 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A32 MICROLOGIC 2.2 AUTO MCCB Supply to Landlords Core 4 DB 06 SW01 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A33 MICROLOGIC 2.2 AUTO MCCB Spare SCHNEIDER NSX160N 160 160 50 160 1.0 N/A N/A 5.0 N/A N/A N/A

A34 MICROLOGIC 2.2 AUTO MCCB Supply to LVSB 13 XX 06 SCHNEIDER NSX400N 400 320 50 320 1.0 N/A N/A 5.0 N/A N/A N/A

A35 MICROLOGIC 2.2 AUTO MCCB Spare SCHNEIDER NSX400N 400 400 50 400 1.0 N/A N/A 5.0 N/A N/A N/A
LV Protective Device Settings - LVSB 13XX01

Note The Schedule settings provide both Over Current and


Earth Fault protection for each Breaker

LV Thermal - Magnetic Settings


Overload Selective Short Circuit

Device Type Long Time Long Time Short Circuit Neutral Protection
Long Time Short Time Short time Instantaneous Short
Dial Setting Current Relay Trip
Delay (s) Current Delay Circuit
(Coarse) Multiplier setting
Board Name Device No. Trip ITEM Circuit Description

Full Current Rating Set Current Rating


Make/Brand Icu kA Io Ir tr Im Isd tsd Iinst (3D, 3D+N/2, 4D)
(Amperes) (Amperes)

A36 MICROLOGIC 2.2 AUTO MCCB Supply to PV Panels SCHNEIDER NSX400N 400 400 50 400 1.0 N/A N/A 5.0 N/A N/A N/A

A37 MICROLOGIC 2.2 AUTO MCCB Supply to DB 13 XX 07 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A38 MICROLOGIC 2.2 AUTO MCCB Supply to Gen 13 XX 01 SCHNEIDER NSX160N 160 160 50 160 1.0 N/A N/A 5.0 N/A N/A N/A

A39 MICROLOGIC 2.2 AUTO MCCB Supply to Gen 13 XX 02 SCHNEIDER NSX160N 160 160 50 160 1.0 N/A N/A 5.0 N/A N/A N/A

A40 MICROLOGIC 2.2 AUTO MCCB Supply to Gen 12 XX 01 SCHNEIDER NSX160N 160 160 50 160 1.0 N/A N/A 5.0 N/A N/A N/A

A41 MICROLOGIC 2.2 AUTO MCCB Supply to Gen 12 XX 02 SCHNEIDER NSX160N 160 160 50 160 1.0 N/A N/A 5.0 N/A N/A N/A
LV Protective Device Settings - LVSB 13XX02

Note The Schedule settings provide both Over Current and


Earth Fault protection for each Breaker

LV Thermal - Magnetic Settings


Overload Selective Short Circuit

Device Type Long Time Long Time Short Circuit Neutral Protection
Long Time Short Time Short time Instantaneous Short
Dial Setting Current Relay Trip
Delay (s) Current Delay Circuit
(Coarse) Multiplier setting
Board Name Device No. Trip ITEM Circuit Description

Full Current Rating Set Current Rating


Make/Brand Icu kA Io Ir tr lm Isd tsd Iinst (3D, 3D+N/2, 4D)
(Amperes) (Amperes)

A1 MICROLOGIC 5.0A AUTO ACB Main Incoming Suppy SCHNEIDER NW63H1 6300 6300 100 N/A 1.0 1.0 N/A 5.0 0.1 OFF N/A

A2 TM200D AUTO MCCB Supply to ESP SCHNEIDER NSX250S 250 200 100 N/A 200.0 N/A 2500.0 N/A N/A N/A N/A

A3 MICROLOGIC 2.3 AUTO MCCB Supply to 200KVAR PFC SCHNEIDER NSX400S 400 400 100 400 1.0 N/A N/A 5.0 N/A N/A N/A

A4 MICROLOGIC 2.3 AUTO MCCB Spare SCHNEIDER NSX400S 400 400 100 400 1.0 N/A N/A 5.0 N/A N/A N/A

A5 MICROLOGIC 2.0A AUTO MCCB Spare SCHNEIDER NS800L 800 800 150 N/A 1.0 16.0 N/A 10.0 N/A N/A N/A
LVSB 13XX02
A6 MICROLOGIC 2.0A AUTO MCCB Spare SCHNEIDER NS800L 800 800 150 N/A 1.0 16.0 N/A 10.0 N/A N/A N/A

A7 MICROLOGIC 2.0A AUTO MCCB Spare SCHNEIDER NS800L 800 800 150 N/A 1.0 16.0 N/A 10.0 N/A N/A N/A

A8 MICROLOGIC 2.0A AUTO MCCB Spare SCHNEIDER NS800L 800 800 150 N/A 1.0 16.0 N/A 10.0 N/A N/A N/A

A9 MICROLOGIC 2.0A AUTO MCCB Spare SCHNEIDER NS800L 800 800 150 N/A 1.0 16.0 N/A 10.0 N/A N/A N/A

A10 MICROLOGIC 5.0E NON AUTO-ACB Bus coupler to LVSB -13 XX03 SCHNEIDER NW32H2 3200 3200 85 N/A 1.0 1.0 N/A 3.0 0.1 off N/A
LV Protective Device Settings - LVSB 13XX03

Note The Schedule settings provide both Over Current and


Earth Fault protection for each Breaker

LV Thermal - Magnetic Settings


Overload Selective Short Circuit

Device Type Long Time Long Time Short Circuit Neutral Protection
Long Time Short Time Short time Instantaneous Short
Dial Setting Current Relay Trip
Delay (s) Current Delay Circuit
(Coarse) Multiplier setting
Board Name Device No. Trip ITEM Circuit Description

Full Current Rating Set Current Rating


Make/Brand Icu kA Io Ir tr lm Isd tsd Iinst (3D, 3D+N/2, 4D)
(Amperes) (Amperes)

A1 MICROLOGIC 5.0 NON AUTO-ACB Main Incoming Suppy SCHNEIDER NW63H1 6300 6300 100 N/A 1.0 1.0 N/A 5.0 0.1 OFF N/A

A2 TM200D MCCB Supply to ESP SCHNEIDER NSX250S 250 200 100 N/A 200.0 N/A 2500.0 N/A N/A N/A N/A

A3 MICROLOGIC 2.3 MCCB Supply to 200KV PFC SCHNEIDER NSX400S 400 400 100 400 1.0 N/A N/A 5.0 N/A N/A N/A

A4 MICROLOGIC 2.0A MCCB SPARE SCHNEIDER NS800L 800 800 150 N/A 1.0 16.0 N/A 10.0 N/A N/A N/A

A5 MICROLOGIC 2.0A MCCB SPARE SCHNEIDER NS800L 800 800 150 N/A 1.0 16.0 N/A 10.0 N/A N/A N/A
LVSB 13XX03
A6 MICROLOGIC 2.0A MCCB SPARE SCHNEIDER NS800L 800 800 150 N/A 1.0 16.0 N/A 10.0 N/A N/A N/A

A7 MICROLOGIC 2.0A MCCB SPARE SCHNEIDER NS800L 800 800 150 N/A 1.0 16.0 N/A 10.0 N/A N/A N/A

A8 MICROLOGIC 2.3 MCCB SPARE SCHNEIDER NSX400S 400 400 100 400 1.0 N/A N/A 5.0 N/A N/A N/A

A9 MICROLOGIC 2.3 MCCB SPARE SCHNEIDER NSX400S 400 400 100 400 1.0 N/A N/A 5.0 N/A N/A N/A

A10 MICROLOGIC 5.0E NON AUTO-ACB Bus coupler to LVSB -13 XX02 SCHNEIDER NW32H2 3200 3200 85 N/A 1.0 1.0 N/A 3.0 0.1 off N/A
LV Protective Device Settings LVSB 13XX04

Note The Schedule settings provide both Over Current and


Earth Fault protection for each Breaker

LV Thermal - Magnetic Settings


Overload Selective Short Circuit

Device Type Long Time Long Time Short Circuit Neutral Protection
Long Time Short Time Short time Instantaneous Short
Dial Setting Current Relay Trip
Delay (s) Current Delay Circuit
(Coarse) Multiplier setting
Board Name Device No. Trip ITEM Circuit Description

Full Current Rating Set Current Rating


Make/Brand Icu kA Io Ir tr Im Isd tsd Iinst (3D, 3D+N/2, 4D)
(Amperes) (Amperes)

A1 MICROLOGIC 5.0A AUTO ACB Main Incoming Supply SCHNEIDER NW32H1 3200 3200 65 N/A 1.0 1.0 N/A 3.0 0.1 Off N/A

A2 TM200D AUTO MCCB Supply to ESP SCHNEIDER NSX250N 250 200 50 N/A 200.0 N/A 2500.0 N/A N/A N/A N/A

A3 MICROLOGIC 2.3 AUTO MCCB Supply to KVAR PFC SCHNEIDER NSX630N 630 630 50 630 1.0 N/A N/A 5.0 N/A N/A N/A

A4 MICROLOGIC 5.0E NON-AUTO ACB Bus coupler to LVSB-13XX01 SCHNEIDER NW12H1 1250 1250 85 N/A 1.0 8.0 N/A 6.0 0.1 Off N/A

A5 MICROLOGIC 2.2 AUTO MCCB SPARE SCHNEIDER NSX250N 250 200 50 200 1.0 N/A N/A 5.0 N/A N/A N/A

A6 MICROLOGIC 2.2 AUTO MCCB Supply to MCB 13XX02 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A7 MICROLOGIC 2.2 AUTO MCCB Supply to MCC 13XX11 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A8 MICROLOGIC 2.2 AUTO MCCB Supply to MCC 13XX15 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A9 MICROLOGIC 2.2 AUTO MCCB Supply to MCC 13XX16 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A10 MICROLOGIC 2.2 AUTO MCCB SPARE SCHNEIDER NSX100N 100 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A11 MICROLOGIC 2.2 AUTO MCCB SPARE SCHNEIDER NSX100N 100 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A12 MICROLOGIC 2.2 AUTO MCCB SPARE SCHNEIDER NSX100N 100 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A13 MICROLOGIC 2.2 AUTO MCCB SPARE SCHNEIDER NSX100N 100 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A14 MICROLOGIC 2.2 AUTO MCCB Supply to MCC 14XX05 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A15 MICROLOGIC 2.2 AUTO MCCB Supply to MCC 14XX06 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A16 MICROLOGIC 2.2 AUTO MCCB Supply to MCC 14XX07 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A17 MICROLOGIC 2.2 AUTO MCCB Supply to MCC 14XX08 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A18 MICROLOGIC 2.2 AUTO MCCB SPARE SCHNEIDER NSX100N 100 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A19 MICROLOGIC 2.2 AUTO MCCB SPARE SCHNEIDER NSX100N 100 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

LVSB 13XX04 A20 MICROLOGIC 2.2 AUTO MCCB SPARE SCHNEIDER NSX100N 100 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A21 MICROLOGIC 2.2 AUTO MCCB SUPPLY TO DB13XX01 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A22 MICROLOGIC 2.2 AUTO MCCB Supply to MCC 13XX12 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A23 MICROLOGIC 2.2 AUTO MCCB SPARE SCHNEIDER NSX160N 160 160 50 160 1.0 N/A N/A 5.0 N/A N/A N/A

A24 MICROLOGIC 2.2 AUTO MCCB Supply to MCC 13XX04 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A25 TM63D AUTO MCCB Supply to MCC 13XX01 SCHNEIDER NSX100N 100 63 50 N/A 63.0 N/A N/A N/A N/A N/A N/A

A26 MICROLOGIC 2.2 AUTO MCCB SPARE SCHNEIDER NSX100N 100 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A27 MICROLOGIC 2.2 AUTO MCCB SPARE SCHNEIDER NSX100N 100 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A28 MICROLOGIC 2.3 AUTO MCCB Supply to PV Panels SCHNEIDER NSX400N 400 400 50 400 1.0 N/A N/A 5.0 N/A N/A N/A

A29 TM63D AUTO MCCB Supply to fire fighting lift core 3 SCHNEIDER NSX100N 100 63 50 N/A 63.0 N/A N/A N/A N/A N/A N/A

A30 MICROLOGIC 2.2 AUTO MCCB Supply to MCC 14XX09 SCHNEIDER NSX160N 160 160 50 160 1.0 N/A N/A 5.0 N/A N/A N/A

A31 MICROLOGIC 2.2 AUTO MCCB Supply to Core 4 DB 13XX02 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A32 MICROLOGIC 2.2 AUTO MCCB Supply to Core 4 DB 13XX04 SCHNEIDER NSX160N 160 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A33 MICROLOGIC 2.2 AUTO MCCB Supply to FFS 13XX04 ACO SCHNEIDER NSX160N 160 160 50 160 1.0 N/A N/A 5.0 N/A N/A N/A

A34 TM63D AUTO MCCB Supply to FFS 13XX03 ACO SCHNEIDER NSX100N 100 63 50 N/A 63.0 N/A N/A N/A N/A N/A N/A

A35 MICROLOGIC 2.3 AUTO MCCB SPARE SCHNEIDER NSX400N 400 400 50 400 1.0 N/A N/A 5.0 N/A N/A N/A
LV Protective Device Settings LVSB 13XX04

Note The Schedule settings provide both Over Current and


Earth Fault protection for each Breaker

LV Thermal - Magnetic Settings


Overload Selective Short Circuit

Device Type Long Time Long Time Short Circuit Neutral Protection
Long Time Short Time Short time Instantaneous Short
Dial Setting Current Relay Trip
Delay (s) Current Delay Circuit
(Coarse) Multiplier setting
Board Name Device No. Trip ITEM Circuit Description

Full Current Rating Set Current Rating


Make/Brand Icu kA Io Ir tr Im Isd tsd Iinst (3D, 3D+N/2, 4D)
(Amperes) (Amperes)

A36 MICROLOGIC 2.2 AUTO MCCB SUPPLY TO GEN 12XX03 SCHNEIDER NSX160N 160 160 50 160 1.0 N/A N/A 5.0 N/A N/A N/A

A37 MICROLOGIC 2.2 AUTO MCCB SUPPLY TO GEN 12XX04 SCHNEIDER NSX160N 160 160 50 160 1.0 N/A N/A 5.0 N/A N/A N/A

A38 MICROLOGIC 2.2 AUTO MCCB SUPPLY TO GEN 12XX05 SCHNEIDER NSX160N 160 160 50 160 1.0 N/A N/A 5.0 N/A N/A N/A

A39 MICROLOGIC 2.2 AUTO MCCB SUPPLY TO GEN 12XX06 SCHNEIDER NSX160N 160 160 50 160 1.0 N/A N/A 5.0 N/A N/A N/A
LV Protective Device Settings LVSB 13XX05

Note The Schedule settings provide both Over Current and


Earth Fault protection for each Breaker

LV Thermal - Magnetic Settings


Overload Selective Short Circuit

Device Type Long Time Long Time Short Circuit Neutral Protection
Long Time Short Time Short time Instantaneous Short
Dial Setting Current Relay Trip
Delay (s) Current Delay Circuit
(Coarse) Multiplier setting
Board Name Device No. Trip ITEM Circuit Description

Breaker / Relay
Set Current Rating
Make/Brand Current Rating Icu kA Io Ir tr Im Isd tsd Iinst (3D, 3D+N/2, 4D)
(Amperes)
(Amperes)

A1 MICROLOGIC 5.0 AUTO ACB Generator Incoming Supply SCHNEIDER NW32H1 1600 1600 65 N/A 1.0 1.0 N/A 3.0 0.1 Off N/A

A2 MICROLOGIC 5.0 AUTO ACB Bus Bar to LVSB - 1XX05 SCHNEIDER NW12H1 1250 1250 85 N/A 1.0 8.0 N/A 6.0 0.1 off N/A

A3 MICROLOGIC 2.2 AUTO MCCB SPARE SCHNEIDER NSX250N 250 200 50 200 1.0 N/A N/A 5.0 N/A N/A N/A

A4 MICROLOGIC 2.2 AUTO MCCB SPARE SCHNEIDER NSX160N 160 160 85 160 1.0 N/A N/A 5.0 N/A N/A N/A

A5 TM63D AUTO MCCB Supply to FFS 13XX01 ACO SCHNEIDER NSX100N 100 63 50 N/A 63.0 N/A N/A N/A N/A N/A N/A

A6 TM63D AUTO MCCB Supply to FFS 13XX02 ACO SCHNEIDER NSX100N 100 63 50 N/A 63.0 N/A N/A N/A N/A N/A N/A

A7 MICROLOGIC 2.2 AUTO MCCB SPARE SCHNEIDER NSX160N 160 160 50 160 1.0 N/A N/A 5.0 N/A N/A N/A

A8 TM63D AUTO MCCB Supply to FFS 13XX04 ACO SCHNEIDER NSX100N 100 63 50 N/A 63.0 N/A N/A N/A N/A N/A N/A
LVSB 13XX05
A9 TM63D AUTO MCCB Supply to FFS 13XX03 ACO SCHNEIDER NSX100N 100 63 50 N/A 63.0 N/A N/A N/A N/A N/A N/A

A10 MICROLOGIC 2.2 AUTO MCCB SPARE SCHNEIDER NSX100N 100 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A11 MICROLOGIC 2.2 AUTO MCCB SPARE SCHNEIDER NSX100N 100 100 50 100 1.0 N/A N/A 5.0 N/A N/A N/A

A12 TM63D AUTO MCCB Supply to fire fighting lift core 3 SCHNEIDER NSX100N 100 63 50 N/A 63.0 N/A N/A N/A N/A N/A N/A

A13 TM63D AUTO MCCB SPARE SCHNEIDER NSX100N 100 63 50 N/A 63.0 N/A N/A N/A N/A N/A N/A

A14 TM63D AUTO MCCB Supply to fire fighting lift core 2 SCHNEIDER NSX100N 100 63 50 N/A 63.0 N/A N/A N/A N/A N/A N/A

A15 TM63D AUTO MCCB Supply to fire fighting lift core 1 SCHNEIDER NSX100N 100 63 50 N/A 63.0 N/A N/A N/A N/A N/A N/A

A16 MICROLOGIC 2.3 AUTO MCCB Supply to LVSB 13XX06 ACO SCHNEIDER NSX400N 400 400 50 400 1.0 N/A N/A 5.0 N/A N/A N/A
LV Protective Device Settings LVSB 13XX06

Note The Schedule settings provide both Over Current and


Earth Fault protection for each Breaker

LV Thermal - Magnetic Settings


Overload Selective Short Circuit

Device Type Long Time Long Time Short Circuit Neutral Protection
Long Time Short Time Short time Instantaneous Short
Dial Setting Current Relay Trip
Delay (s) Current Delay Circuit
(Coarse) Multiplier setting
Board Name Device No. Trip ITEM Circuit Description

Breaker / Relay
Set Current Rating
Make/Brand Current Rating Icu kA Io Ir tr Im Isd tsd Iinst (3D, 3D+N/2, 4D)
(Amperes)
(Amperes)

A1 N/A NON- AUTO MCCB Supply from LVSB13XX01 SCHNEIDER NSX400NA 400 400 50 N/A N/A N/A N/A N/A N/A N/A N/A

A2 N/A NON- AUTO MCCB Supply from LVSB13XX05 SCHNEIDER NSX400NA 400 400 50 N/A N/A N/A N/A N/A N/A N/A N/A

A3 N/A NON- AUTO MCCB Bypass SCHNEIDER NSX400NA 400 400 50 N/A N/A N/A N/A N/A N/A N/A N/A

LVSB 13XX06 A4 TM63D AUTO MCCB Supply to ESP SCHNEIDER NSX100N 100 63 50 N/A 63.0 N/A N/A N/A N/A N/A N/A

A5 MICROLOGIC 2.2 AUTO MCCB Supply to DB13XX05 SCHNEIDER NSX160N 160 160 50 160 1.0 N/A N/A 5.0 N/A N/A N/A

A6 MICROLOGIC 2.3 AUTO MCCB Supply to DB13XX06 SCHNEIDER NSX160N 160 160 50 160 1.0 N/A N/A 5.0 N/A N/A N/A

A7 TM63D AUTO MCCB SPARE SCHNEIDER NSX100N 100 63 50 N/A 63.0 N/A N/A N/A N/A N/A N/A
LV Protective Device Settings - LVSB 14XX01
Note The Schedule settings provide both Over Current and
Earth Fault protection for each Breaker

LV Thermal - Magnetic Settings

Overload Selective Short Circuit

Device Type Long Time Long Time Short Circuit Neutral Protection
Long Time Short Time Short time Instantaneous Short
Dial Setting Current Relay Trip
Delay (s) Current Delay Circuit
(Coarse) Multiplier setting
Board Name Device No. TRIP ITEM Circuit Description

Full Current Rating Set Current Rating


Make/Brand Icu kA Io Ir tr Im Isd tsd Iinst (3D, 3D+N/2, 4D)
(Amperes) (Amperes)

A1 MICROLOGIC 5.0A AUTO ACB Load Bank Transformer SCHNEIDER NW40H1 4000 4000 65 N/A 1.0 1.0 N/A 5.0 0.1 Off N/A

LVSB 14XX01 A2 MICROLOGIC 5.0A AUTO ACB Tenant FUTURE UPS Supply SCHNEIDER NW40H1 4000 4000 65 N/A 1.0 1.0 N/A 5.0 0.1 Off N/A

A3 MICROLOGIC 5.0A AUTO ACB Load Bank Suppy SCHNEIDER NW40H1 4000 4000 65 N/A 1.0 1.0 N/A 5.0 0.1 Off N/A
COMMISSIONING REPORT
5 Broadgate LVSB - 1 XX01 Study - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision rev 2 Created 28/06/2013 19:52:22
Job ID Last Saved 24/02/2016 17:32:09
Engineer K Lewis
6300-3200 - Overcurrent Settings
Device 1, 6300A, Schneider, Masterpact NW63 H1 Micrologic 5.0A standard
Ir 1.00 Isd 5.00 Iinst OFF
tr 1.0 tsd 0.1

Device 2, 3200A, Schneider, Masterpact NW32 H2 Micrologic 5.0A standard


Ir 1.00 Isd 3.00 Iinst OFF
tr 1.0 tsd 0.1

24/02/2016 19:01:14 Amtech Protect HV Version 2015.0.0 Page 1 of 3


6300-3200.prs17
Overcurrent-Time/Current Analysis, Voltage Base: 400V, 24/02/2016 19:01:26
10000s
Device 2 - 3200A@400V Src Pscc
Schneider 56.7kA
Masterpact NW32 H2 Micrologic 5.0A standard

1 hour

Device 1 - 6300A@400V
Schneider
Masterpact NW63 H1 Micrologic 5.0A standard
1000s
Device 1
Device 2

100s

1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

24/02/2016 19:01:14 Amtech Protect HV Version 2015.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
6300-3200 - Overcurrent Analysis

Source - 400V, Pscc is 56.7kA


~

Device 1 - 6300A@400V
Schneider - Masterpact NW63 H1 Micrologic 5.0A standard
Pscc is 0kA, Icu is 100kA

Device 2 - 3200A@400V
Schneider - Masterpact NW32 H2 Micrologic 5.0A standard
Pscc is 0kA, Icu is 100kA

24/02/2016 19:01:14 Amtech Protect HV Version 2015.0.0 Page 3 of 3


COMMISSIONING REPORT
5 Broadgate LVSB - 1 XX01 Study - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision rev 2 Created 28/06/2013 19:52:22
Job ID Last Saved 17/02/2016 18:21:14
Engineer K Lewis
6300-800-160-32 - Overcurrent Settings
Device 1, 6300A, Schneider, Masterpact NW63 H1 Micrologic 5.0A standard
Ir 1.00 Isd 5.00 Iinst OFF
tr 1.0 tsd 0.1

Device 2, 800A, Schneider, Compact NS800 L Micrologic 2.0A standard


Ir 1.00 Isd 10.0
tr 16.0

Device 4, 160A, Schneider, Compact NSX160N Micrologic 2.2


Io 100 Isd 5.0
Ir 1.00

Device 5, 32A, Schneider, Multi9 C60H Type C Th-Mag

24/02/2016 19:02:38 Amtech Protect HV Version 2015.0.0 Page 1 of 3


6300-800-160-32.prs17
Overcurrent-Time/Current Analysis, Voltage Base: 400V, 24/02/2016 19:02:43
10000s
Src Pscc
56.7kA

Device 1 - 6300A@400V
1 hour Schneider
Masterpact NW63 H1 Micrologic 5.0A standard

1000s
Device 1
Device 2
Device 2 - 800A@400V
Device 4
Schneider
Device 5
Compact NS800 L Micrologic 2.0A standard

100s Device 5 - 32A@400V


Schneider
Multi9 C60H Type C Th-Mag
1 min

Device 4 - 160A@400V
Schneider
Compact NSX160N Micrologic 2.2
10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

24/02/2016 19:02:38 Amtech Protect HV Version 2015.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
6300-800-160-32 - Overcurrent Analysis

Source - 400V, Pscc is 56.7kA


~

Device 1 - 6300A@400V
Schneider - Masterpact NW63 H1 Micrologic 5.0A standard
Pscc is 0kA, Icu is 100kA

Device 2 - 800A@400V
Schneider - Compact NS800 L Micrologic 2.0A standard
Pscc is 0kA, Icu is 150kA

Device 4 - 160A@400V
Schneider - Compact NSX160N Micrologic 2.2
Pscc is 0kA, Icu is 50kA

Device 5 - 32A@400V
Schneider - Multi9 C60H Type C Th-Mag
Pscc is 0kA, Icu is 15kA

24/02/2016 19:02:38 Amtech Protect HV Version 2015.0.0 Page 3 of 3


COMMISSIONING REPORT
5 Broadgate LVSB - 1 XX01 Study - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision rev 2 Created 28/06/2013 19:52:22
Job ID Last Saved 24/02/2016 19:03:46
Engineer K Lewis
6300-800-160 - Overcurrent Settings
Device 1, 6300A, Schneider, Masterpact NW63 H1 Micrologic 5.0A standard
Ir 1.00 Isd 3.00 Iinst OFF
tr 2.0 tsd 0.1

Device 2, 800A, Schneider, Compact NS800 L Micrologic 2.0A standard


Ir 1.00 Isd 10.0
tr 16.0

Device 3, 160A, Schneider, Compact NSX160S Micrologic 2.2


Io 160 Isd 5.0
Ir 1.00

24/02/2016 19:03:52 Amtech Protect HV Version 2015.0.0 Page 1 of 3


6300-800-160.prs17
Overcurrent-Time/Current Analysis, Voltage Base: 400V, 24/02/2016 19:03:56
10000s
Src Pscc
56.7kA

1 hour

1000s Device 3 - 160A@400V Device 1


Schneider Device 2
Compact NSX160S Micrologic 2.2 Device 3

Device 2 - 800A@400V
Schneider
Compact NS800 L Micrologic 2.0A standard

100s

1 min Device 1 - 6300A@400V


Schneider
Masterpact NW63 H1 Micrologic 5.0A standard

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

24/02/2016 19:03:52 Amtech Protect HV Version 2015.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
6300-800-160 - Overcurrent Analysis

Source - 400V, Pscc is 56.7kA


~

Device 1 - 6300A@400V
Schneider - Masterpact NW63 H1 Micrologic 5.0A standard
Pscc is 0kA, Icu is 100kA

Device 2 - 800A@400V
Schneider - Compact NS800 L Micrologic 2.0A standard
Pscc is 0kA, Icu is 150kA

Device 3 - 160A@400V
Schneider - Compact NSX160S Micrologic 2.2
Pscc is 0kA, Icu is 100kA

24/02/2016 19:03:52 Amtech Protect HV Version 2015.0.0 Page 3 of 3


COMMISSIONING REPORT
5 Broadgate LVSB - 1 XX01 Study - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision rev 2 Created 28/06/2013 19:52:22
Job ID Last Saved 17/02/2016 18:03:47
Engineer K Lewis
6300-800 - Overcurrent Settings
Device 1, 6300A, Schneider, Masterpact NW63 H1 Micrologic 5.0A standard
Ir 1.00 Isd 5.00 Iinst OFF
tr 1.0 tsd 0.1

Device 2, 800A, Schneider, Compact NS800 L Micrologic 2.0A standard


Ir 1.00 Isd 10.0
tr 16.0

24/02/2016 19:09:05 Amtech Protect HV Version 2015.0.0 Page 1 of 3


6300-800.prs17
Overcurrent-Time/Current Analysis, Voltage Base: 400V, 24/02/2016 19:09:19
10000s
Src Pscc
56.7kA

1 hour

1000s
Device 1
Device 2
Device 2 - 800A@400V
Schneider
Compact NS800 L Micrologic 2.0A standard

Device 1 - 6300A@400V
100s
Schneider
Masterpact NW63 H1 Micrologic 5.0A standard
1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

24/02/2016 19:09:05 Amtech Protect HV Version 2015.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
6300-800 - Overcurrent Analysis

Source - 400V, Pscc is 56.7kA


~

Device 1 - 6300A@400V
Schneider - Masterpact NW63 H1 Micrologic 5.0A standard
Pscc is 0kA, Icu is 100kA

Device 2 - 800A@400V
Schneider - Compact NS800 L Micrologic 2.0A standard
Pscc is 0kA, Icu is 150kA

24/02/2016 19:09:05 Amtech Protect HV Version 2015.0.0 Page 3 of 3


COMMISSIONING REPORT
5 Broadgate LVSB - 1 XX01 Study - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision rev 2 Created 28/06/2013 19:52:22
Job ID Last Saved 17/02/2016 18:00:34
Engineer K Lewis
6300-630-160-32 - Overcurrent Settings
Device 1, 6300A, Schneider, Masterpact NW63 H1 Micrologic 5.0A standard
Ir 1.00 Isd 5.00 Iinst OFF
tr 1.0 tsd 0.1

Device 2, 630A, Schneider, Compact NSX630S Micrologic 2.3


Io 630 Isd 5.0
Ir 1.00

Device 5, 160A, Schneider, Compact NSX160S Micrologic 2.2


Io 100 Isd 5.0
Ir 1.00

Device 4, 32A, Schneider, Multi9 C60H Type C Th-Mag

17/02/2016 18:00:41 Amtech Protect HV Version 2015.0.0 Page 1 of 3


6300-630-160-32.prs17
Overcurrent-Time/Current Analysis, Voltage Base: 400V, 17/02/2016 18:00:54
10000s
Src Pscc
56.7kA

1 hour

1000s
Device 1
Device 2
Device 5
Device 4

Device 4 - 32A@400V
Schneider
100s Multi9 C60H Type C Th-Mag

1 min Device 5 - 160A@400V


Schneider
Compact NSX160S Micrologic 2.2

Device 2 - 630A@400V
10s Schneider
Compact NSX630S Micrologic 2.3
Device 1 - 6300A@400V
5 sec Schneider
Masterpact NW63 H1 Micrologic 5.0A standard

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

17/02/2016 18:00:41 Amtech Protect HV Version 2015.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
6300-630-160-32 - Overcurrent Analysis

Source - 400V, Pscc is 56.7kA


~

Device 1 - 6300A@400V
Schneider - Masterpact NW63 H1 Micrologic 5.0A standard
Pscc is 0kA, Icu is 100kA

Device 2 - 630A@400V
Schneider - Compact NSX630S Micrologic 2.3
Pscc is 0kA, Icu is 100kA

Device 5 - 160A@400V
Schneider - Compact NSX160S Micrologic 2.2
Pscc is 0kA, Icu is 100kA

Device 4 - 32A@400V
Schneider - Multi9 C60H Type C Th-Mag
Pscc is 0kA, Icu is 15kA

17/02/2016 18:00:41 Amtech Protect HV Version 2015.0.0 Page 3 of 3


COMMISSIONING REPORT
5 Broadgate LVSB - 1 XX01 Study - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision rev2 Created 28/06/2013 19:52:22
Job ID Last Saved 17/02/2016 17:58:13
Engineer K Lewis
6300-400 - Overcurrent Settings
Device 1, 6300A, Schneider, Masterpact NW63 H1 Micrologic 5.0A standard
Ir 1.00 Isd 5.00 Iinst OFF
tr 1.0 tsd 0.1

Device 2, 400A, Schneider, Compact NSX400S Micrologic 2.3


Io 400 Isd 5.0
Ir 1.00

17/02/2016 17:58:19 Amtech Protect HV Version 2015.0.0 Page 1 of 3


6300-400.prs17
Overcurrent-Time/Current Analysis, Voltage Base: 400V, 17/02/2016 17:58:23
10000s
Src Pscc
56.7kA

1 hour

Device 1 - 6300A@400V
Schneider
1000s Masterpact NW63 H1 Micrologic 5.0A standard
Device 2 - 400A@400V Device 1
Schneider Device 2
Compact NSX400S Micrologic 2.3

100s

1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

17/02/2016 17:58:19 Amtech Protect HV Version 2015.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
6300-400 - Overcurrent Analysis

Source - 400V, Pscc is 56.7kA


~

Device 1 - 6300A@400V
Schneider - Masterpact NW63 H1 Micrologic 5.0A standard
Pscc is 0kA, Icu is 100kA

Device 2 - 400A@400V
Schneider - Compact NSX400S Micrologic 2.3
Pscc is 0kA, Icu is 100kA

17/02/2016 17:58:19 Amtech Protect HV Version 2015.0.0 Page 3 of 3


COMMISSIONING REPORT
5 Broadgate LVSB - 1 XX01 Study - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision rev 2 Created 28/06/2013 19:52:22
Job ID Last Saved 17/02/2016 17:57:25
Engineer K Lewis
6300-315 - Overcurrent Settings
Device 1, 6300A, Schneider, Masterpact NW63 H1 Micrologic 5.0A standard
Ir 1.00 Isd 5.00 Iinst OFF
tr 1.0 tsd 0.1

Device 2, 315A, Generic, BS88-2 Fuse System E

17/02/2016 17:57:29 Amtech Protect HV Version 2015.0.0 Page 1 of 3


6300-315.prs17
Overcurrent-Time/Current Analysis, Voltage Base: 400V, 17/02/2016 17:57:33
10000s
Src Pscc
56.7kA

1 hour Device 2 - 315A@400V


Generic
BS88-2 Fuse System E

1000s
Device 1
Device 2

Device 1 - 6300A@400V
Schneider
Masterpact NW63 H1 Micrologic 5.0A standard
100s

1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

17/02/2016 17:57:29 Amtech Protect HV Version 2015.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
6300-315 - Overcurrent Analysis

Source - 400V, Pscc is 56.7kA


~

Device 1 - 6300A@400V
Schneider - Masterpact NW63 H1 Micrologic 5.0A standard
Pscc is 0kA, Icu is 100kA

Device 2 - 315A@400V
Generic - BS88-2 Fuse System E
Pscc is 0kA, Icu is 80kA

17/02/2016 17:57:29 Amtech Protect HV Version 2015.0.0 Page 3 of 3


COMMISSIONING REPORT
5 Broadgate LVSB - 1 XX01 Study - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision Created 28/06/2013 19:52:22
Job ID Last Saved 17/02/2016 17:56:26
Engineer K Lewis
6300-250 - Overcurrent Settings
Device 1, 6300A, Schneider, Masterpact NW63 H1 Micrologic 5.0A standard
Ir 1.00 Isd 5.00 Iinst OFF
tr 1.0 tsd 0.1

Device 2, 250A, Schneider, Compact NSX250S Micrologic 2.2


Io 250 Isd 5.0
Ir 1.00

17/02/2016 17:56:35 Amtech Protect HV Version 2015.0.0 Page 1 of 3


6300-250.prs17
Overcurrent-Time/Current Analysis, Voltage Base: 400V, 17/02/2016 17:56:41
10000s
Src Pscc
56.7kA

1 hour

Device 1 - 6300A@400V
Schneider
Masterpact NW63 H1 Micrologic 5.0A standard
1000s
Device 1
Device 2

Device 2 - 250A@400V
Schneider
Compact NSX250S Micrologic 2.2

100s

1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

17/02/2016 17:56:35 Amtech Protect HV Version 2015.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
6300-250 - Overcurrent Analysis

Source - 400V, Pscc is 56.7kA


~

Device 1 - 6300A@400V
Schneider - Masterpact NW63 H1 Micrologic 5.0A standard
Pscc is 0kA, Icu is 100kA

Device 2 - 250A@400V
Schneider - Compact NSX250S Micrologic 2.2
Pscc is 0kA, Icu is 100kA

17/02/2016 17:56:35 Amtech Protect HV Version 2015.0.0 Page 3 of 3


COMMISSIONING REPORT
5 Broadgate LVSB - 1 XX01 Study - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision rev 2 Created 28/06/2013 19:52:22
Job ID Last Saved 17/02/2016 17:54:03
Engineer K Lewis
6300-200- - Overcurrent Settings
Device 1, 6300A, Schneider, Masterpact NW63 H1 Micrologic 5.0A standard
Ir 1.00 Isd 5.00 Iinst OFF
tr 1.0 tsd 0.1

Device 2, 250A, Schneider, Compact NSX250S Micrologic 2.2


Io 200 Isd 5.0
Ir 1.00

17/02/2016 17:54:15 Amtech Protect HV Version 2015.0.0 Page 1 of 3


6300-200-.prs17
Overcurrent-Time/Current Analysis, Voltage Base: 400V, 17/02/2016 17:54:20
10000s
Src Pscc
56.7kA

1 hour

Device 1 - 6300A@400V
Schneider
Masterpact NW63 H1 Micrologic 5.0A standard
1000s
Device 1
Device 2 - 250A@400V Device 2
Schneider
Compact NSX250S Micrologic 2.2

100s

1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

17/02/2016 17:54:15 Amtech Protect HV Version 2015.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
6300-200- - Overcurrent Analysis

Source - 400V, Pscc is 56.7kA


~

Device 1 - 6300A@400V
Schneider - Masterpact NW63 H1 Micrologic 5.0A standard
Pscc is 0kA, Icu is 100kA

Device 2 - 250A@400V
Schneider - Compact NSX250S Micrologic 2.2
Pscc is 0kA, Icu is 100kA

17/02/2016 17:54:15 Amtech Protect HV Version 2015.0.0 Page 3 of 3


COMMISSIONING REPORT
5 Broadgate LVSB - 1 XX01 Study - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision rev 2 Created 28/06/2013 19:52:22
Job ID Last Saved 15/02/2016 22:56:11
Engineer K Lewis
6300-160 - Overcurrent Settings
Device 1, 6300A, Schneider, Masterpact NW63 H1 Micrologic 5.0A standard
Ir 1.00 Isd 5.00 Iinst OFF
tr 1.0 tsd 0.1

Device 3, 160A, Schneider, Compact NSX160S Micrologic 2.2


Io 160 Isd 5.0
Ir 1.00

17/02/2016 17:48:24 Amtech Protect HV Version 2015.0.0 Page 1 of 3


6300-160.prs17
Overcurrent-Time/Current Analysis, Voltage Base: 400V, 17/02/2016 17:48:28
10000s
Src Pscc
56.7kA

1 hour

Device 1 - 6300A@400V
Schneider
1000s Masterpact NW63 H1 Micrologic 5.0A standard
Device 3 - 160A@400V Device 1
Schneider Device 3
Compact NSX160S Micrologic 2.2

100s

1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

17/02/2016 17:48:24 Amtech Protect HV Version 2015.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
6300-160 - Overcurrent Analysis

Source - 400V, Pscc is 56.7kA


~

Device 1 - 6300A@400V
Schneider - Masterpact NW63 H1 Micrologic 5.0A standard
Pscc is 0kA, Icu is 100kA

Device 3 - 160A@400V
Schneider - Compact NSX160S Micrologic 2.2
Pscc is 0kA, Icu is 100kA

17/02/2016 17:48:24 Amtech Protect HV Version 2015.0.0 Page 3 of 3


COMMISSIONING REPORT
5 Broadgate LVSB -1 XX01 Study - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision rev 2 Created 28/06/2013 19:52:22
Job ID Last Saved 15/02/2016 22:54:52
Engineer K Lewis
6300-100 - - Overcurrent Settings
Device 1, 6300A, Schneider, Masterpact NW63 H1 Micrologic 5.0A standard
Ir 1.00 Isd 5.00 Iinst OFF
tr 1.0 tsd 0.1

Device 3, 100A, Schneider, Compact NSX100S Micrologic 2.2


Io 100 Isd 5.0
Ir 1.00

17/02/2016 17:45:23 Amtech Protect HV Version 2015.0.0 Page 1 of 3


6300-100 - .prs17
Overcurrent-Time/Current Analysis, Voltage Base: 400V, 17/02/2016 17:46:09
10000s
Src Pscc
56.7kA

1 hour
Device 1 - 6300A@400V
Schneider
Masterpact NW63 H1 Micrologic 5.0A standard

1000s
Device 1
Device 3

100s

1 min
Device 3 - 100A@400V
Schneider
Compact NSX100S Micrologic 2.2

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

17/02/2016 17:45:23 Amtech Protect HV Version 2015.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
6300-100 - - Overcurrent Analysis

Source - 400V, Pscc is 56.7kA


~

Device 1 - 6300A@400V
Schneider - Masterpact NW63 H1 Micrologic 5.0A standard
Pscc is 0kA, Icu is 100kA

Device 3 - 100A@400V
Schneider - Compact NSX100S Micrologic 2.2
Pscc is 0kA, Icu is 100kA

17/02/2016 17:45:23 Amtech Protect HV Version 2015.0.0 Page 3 of 3


COMMISSIONING REPORT
5 Broadgate LVSB - 13 XX02 Study - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision rev 2 Created 28/06/2013 19:52:22
Job ID Last Saved 17/02/2016 19:47:50
Engineer K Lewis
6300-32 - Overcurrent Settings
Device 1, 6300A, Schneider, Masterpact NW63 H1 Micrologic 5.0A standard
Ir 1.00 Isd 5.00 Iinst OFF
tr 1.0 tsd 0.1

Device 2, 32A, Schneider, Multi9 C60H Type C Th-Mag

17/02/2016 19:47:57 Amtech Protect HV Version 2015.0.0 Page 1 of 3


6300-32.prs17
Overcurrent-Time/Current Analysis, Voltage Base: 400V, 17/02/2016 19:48:01
10000s
Src Pscc
53.5kA

1 hour

1000s
Device 1
Device 2

Device 1 - 6300A@400V
Schneider
Masterpact NW63 H1 Micrologic 5.0A standard

100s Device 2 - 32A@400V


Schneider
1 min Multi9 C60H Type C Th-Mag

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

17/02/2016 19:47:57 Amtech Protect HV Version 2015.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
6300-32 - Overcurrent Analysis

Source - 400V, Pscc is 53.5kA


~

Device 1 - 6300A@400V
Schneider - Masterpact NW63 H1 Micrologic 5.0A standard
Pscc is 0kA, Icu is 100kA

Device 2 - 32A@400V
Schneider - Multi9 C60H Type C Th-Mag
Pscc is 0kA, Icu is 15kA

17/02/2016 19:47:57 Amtech Protect HV Version 2015.0.0 Page 3 of 3


COMMISSIONING REPORT
5 Broadgate LVSB - 1 XX03 Study - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision rev 2 Created 28/06/2013 19:52:22
Job ID Last Saved 24/02/2016 19:12:27
Engineer K Lewis
5000-800-200-32 - Overcurrent Settings
Device 1, 5000A, Schneider, Masterpact NW50 H1 Micrologic 5.0A standard
Ir 1.00 Isd 5.00 Iinst OFF
tr 1.0 tsd 0.1

Device 2, 800A, Schneider, Compact NS800 L Micrologic 2.0A standard


Ir 1.00 Isd 10.0
tr 16.0

Device 3, 250A, Schneider, Compact NSX250S Micrologic 2.2


Io 200 Isd 5.0
Ir 1.00

Device 6, 32A, Schneider, Multi9 C60H Type C Th-Mag

24/02/2016 19:12:32 Amtech Protect HV Version 2015.0.0 Page 1 of 3


5000-800-200-32.prs17
Overcurrent-Time/Current Analysis, Voltage Base: 400V, 24/02/2016 19:12:37
10000s
Src Pscc
51.2kA

1 hour

1000s
Device 1
Device 2
Device 3
Device 6 - 32A@400V Device 6
Schneider
Multi9 C60H Type C Th-Mag

Device 3 - 250A@400V
Schneider
100s Compact NSX250S Micrologic 2.2

1 min Device 2 - 800A@400V


Schneider
Compact NS800 L Micrologic 2.0A standard

Device 1 - 5000A@400V
Schneider
Masterpact NW50 H1 Micrologic 5.0A standard
10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

24/02/2016 19:12:32 Amtech Protect HV Version 2015.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
5000-800-200-32 - Overcurrent Analysis

Source - 400V, Pscc is 51.2kA


~

Device 1 - 5000A@400V
Schneider - Masterpact NW50 H1 Micrologic 5.0A standard
Pscc is 0kA, Icu is 100kA

Device 2 - 800A@400V
Schneider - Compact NS800 L Micrologic 2.0A standard
Pscc is 0kA, Icu is 150kA

Device 3 - 250A@400V
Schneider - Compact NSX250S Micrologic 2.2
Pscc is 0kA, Icu is 100kA

Device 6 - 32A@400V
Schneider - Multi9 C60H Type C Th-Mag
Pscc is 0kA, Icu is 15kA

24/02/2016 19:12:32 Amtech Protect HV Version 2015.0.0 Page 3 of 3


COMMISSIONING REPORT
5 Broadgate LVSB - 1 XX03 Study - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision rev 2 Created 28/06/2013 19:52:22
Job ID Last Saved 17/02/2016 18:45:53
Engineer K Lewis
5000-400 - Overcurrent Settings
Device 1, 5000A, Schneider, Masterpact NW50 H1 Micrologic 5.0A standard
Ir 1.00 Isd 5.00 Iinst OFF
tr 1.0 tsd 0.1

Device 2, 400A, Schneider, Compact NSX400S Micrologic 2.3


Io 400 Isd 5.0
Ir 1.00

17/02/2016 18:46:32 Amtech Protect HV Version 2015.0.0 Page 1 of 3


5000-400.prs17
Overcurrent-Time/Current Analysis, Voltage Base: 400V, 17/02/2016 18:46:36
10000s
Src Pscc
51.2kA

1 hour Device 2 - 400A@400V


Schneider
Compact NSX400S Micrologic 2.3

1000s
Device 1
Device 2

Device 1 - 5000A@400V
Schneider
Masterpact NW50 H1 Micrologic 5.0A standard
100s

1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

17/02/2016 18:46:32 Amtech Protect HV Version 2015.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
5000-400 - Overcurrent Analysis

Source - 400V, Pscc is 51.2kA


~

Device 1 - 5000A@400V
Schneider - Masterpact NW50 H1 Micrologic 5.0A standard
Pscc is 0kA, Icu is 100kA

Device 2 - 400A@400V
Schneider - Compact NSX400S Micrologic 2.3
Pscc is 0kA, Icu is 100kA

17/02/2016 18:46:32 Amtech Protect HV Version 2015.0.0 Page 3 of 3


COMMISSIONING REPORT
5 Broadgate LVSB - 1 XX03 Study - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision rev 2 Created 28/06/2013 19:52:22
Job ID Last Saved 17/02/2016 18:55:33
Engineer K Lewis
5000-250 - Overcurrent Settings
Device 1, 5000A, Schneider, Masterpact NW50 H1 Micrologic 5.0A standard
Ir 1.00 Isd 5.00 Iinst OFF
tr 1.0 tsd 0.1

Device 2, 250A, Schneider, Compact NSX250N TM D


Ir 200 Im 2500

17/02/2016 18:55:39 Amtech Protect HV Version 2015.0.0 Page 1 of 3


5000-250 .prs17
Overcurrent-Time/Current Analysis, Voltage Base: 400V, 17/02/2016 18:55:44
10000s
Src Pscc
51.2kA

1 hour

1000s
Device 1
Device 2 - 250A@400V Device 2
Schneider
Compact NSX250N TM D

Device 1 - 5000A@400V
Schneider
Masterpact NW50 H1 Micrologic 5.0A standard
100s

1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

17/02/2016 18:55:39 Amtech Protect HV Version 2015.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
5000-250 - Overcurrent Analysis

Source - 400V, Pscc is 51.2kA


~

Device 1 - 5000A@400V
Schneider - Masterpact NW50 H1 Micrologic 5.0A standard
Pscc is 0kA, Icu is 100kA

Device 2 - 250A@400V
Schneider - Compact NSX250N TM D
Pscc is 0kA, Icu is 50kA

17/02/2016 18:55:39 Amtech Protect HV Version 2015.0.0 Page 3 of 3


COMMISSIONING REPORT
5 Broadgate LVSB - 1 XX03 Study - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision rev 2 Created 28/06/2013 19:52:22
Job ID Last Saved 17/02/2016 18:59:00
Engineer K Lewis
5000-160 - Overcurrent Settings
Device 1, 5000A, Schneider, Masterpact NW50 H1 Micrologic 5.0A standard
Ir 1.00 Isd 5.00 Iinst OFF
tr 1.0 tsd 0.1

Device 2, 160A, Schneider, Compact NSX160S Micrologic 2.2


Io 160 Isd 5.0
Ir 1.00

17/02/2016 18:59:05 Amtech Protect HV Version 2015.0.0 Page 1 of 3


5000-160.prs17
Overcurrent-Time/Current Analysis, Voltage Base: 400V, 17/02/2016 18:59:11
10000s
Src Pscc
51.2kA

1 hour

1000s Device 1 - 5000A@400V


Schneider Device 1
Masterpact NW50 H1 Micrologic 5.0A standard Device 2

Device 2 - 160A@400V
Schneider
Compact NSX160S Micrologic 2.2

100s

1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

17/02/2016 18:59:05 Amtech Protect HV Version 2015.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
5000-160 - Overcurrent Analysis

Source - 400V, Pscc is 51.2kA


~

Device 1 - 5000A@400V
Schneider - Masterpact NW50 H1 Micrologic 5.0A standard
Pscc is 0kA, Icu is 100kA

Device 2 - 160A@400V
Schneider - Compact NSX160S Micrologic 2.2
Pscc is 0kA, Icu is 100kA

17/02/2016 18:59:05 Amtech Protect HV Version 2015.0.0 Page 3 of 3


COMMISSIONING REPORT
5 Broadgate LVSB - 1 XX04 Study - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision rev 2 Created 28/06/2013 19:52:22
Job ID Last Saved 24/02/2016 17:42:00
Engineer K Lewis
3200-800 - bus coupler - Overcurrent Settings
Device 1 incomer, 3200A, Schneider, Masterpact NW32 H1 Micrologic 5.0A standard
Ir 1.00 Isd 3.00 Iinst OFF
tr 1.0 tsd 0.1

Device 2 bus coupler, 800A, Schneider, Compact NS800 N Micrologic 5.0A standard
Ir 1.00 Isd 3.00 Iinst OFF
tr 8.0 tsd 0.1

24/02/2016 19:13:43 Amtech Protect HV Version 2015.0.0 Page 1 of 3


3200-800 - bus coupler.prs17
Overcurrent-Time/Current Analysis, Voltage Base: 400V, 24/02/2016 19:14:01
10000s
Device 2 bus coupler - 800A@400V Src Pscc
Schneider 37.4kA
Compact NS800 N Micrologic 5.0A standard

1 hour
Device 1 incomer - 3200A@400V
Schneider
Masterpact NW32 H1 Micrologic 5.0A standard

1000s
Device 1 incomer
Device 2 bus coupler

100s

1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

24/02/2016 19:13:43 Amtech Protect HV Version 2015.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
3200-800 - bus coupler - Overcurrent Analysis

Source - 400V, Pscc is 37.4kA


~

Device 1 incomer - 3200A@400V


Schneider - Masterpact NW32 H1 Micrologic 5.0A standard
Pscc is 0kA, Icu is 65kA

Device 2 bus coupler - 800A@400V


Schneider - Compact NS800 N Micrologic 5.0A standard
Pscc is 0kA, Icu is 50kA

24/02/2016 19:13:43 Amtech Protect HV Version 2015.0.0 Page 3 of 3


COMMISSIONING REPORT
5 Broadgate LVSB - 1 XX04 Study - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision rev 2 Created 28/06/2013 19:52:22
Job ID Last Saved 17/02/2016 19:30:51
Engineer K Lewis
3200-800 - Overcurrent Settings
Device 1, 3200A, Schneider, Masterpact NW32 H1 Micrologic 5.0A standard
Ir 1.00 Isd 3.00 Iinst OFF
tr 1.0 tsd 0.1

Device 2, 800A, Schneider, Compact NS800 N Micrologic 2.0A standard


Ir 0.40 Isd 10.0
tr 16.0

17/02/2016 19:30:57 Amtech Protect HV Version 2015.0.0 Page 1 of 3


3200-800.prs17
Overcurrent-Time/Current Analysis, Voltage Base: 400V, 17/02/2016 19:31:01
10000s
Src Pscc
37.4kA

1 hour

1000s
Device 1
Device 2

Device 2 - 800A@400V
Schneider
Compact NS800 N Micrologic 2.0A standard

100s

1 min
Device 1 - 3200A@400V
Schneider
Masterpact NW32 H1 Micrologic 5.0A standard

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

17/02/2016 19:30:57 Amtech Protect HV Version 2015.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
3200-800 - Overcurrent Analysis

Source - 400V, Pscc is 37.4kA


~

Device 1 - 3200A@400V
Schneider - Masterpact NW32 H1 Micrologic 5.0A standard
Pscc is 0kA, Icu is 65kA

Device 2 - 800A@400V
Schneider - Compact NS800 N Micrologic 2.0A standard
Pscc is 0kA, Icu is 50kA

17/02/2016 19:30:57 Amtech Protect HV Version 2015.0.0 Page 3 of 3


COMMISSIONING REPORT
5 Broadgate LVSB - 13 XX04 Study - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision rev 1 Created 28/06/2013 19:52:22
Job ID Last Saved 17/02/2016 19:45:44
Engineer K Lewis
3200-630 - Overcurrent Settings
Device 1, 3200A, Schneider, Masterpact NW32 H1 Micrologic 5.0A standard
Ir 1.00 Isd 3.00 Iinst OFF
tr 1.0 tsd 0.1

Device 2, 630A, Schneider, Compact NSX630N Micrologic 2.3


Io 630 Isd 5.0
Ir 1.00

17/02/2016 19:45:56 Amtech Protect HV Version 2015.0.0 Page 1 of 3


3200-630.prs17
Overcurrent-Time/Current Analysis, Voltage Base: 400V, 17/02/2016 19:46:00
10000s
Src Pscc
37.3kA

1 hour

Device 2 - 630A@400V
Schneider
Compact NSX630N Micrologic 2.3
1000s
Device 1
Device 2

Device 1 - 3200A@400V
100s Schneider
Masterpact NW32 H1 Micrologic 5.0A standard
1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

17/02/2016 19:45:56 Amtech Protect HV Version 2015.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
3200-630 - Overcurrent Analysis

Source - 400V, Pscc is 37.3kA


~

Device 1 - 3200A@400V
Schneider - Masterpact NW32 H1 Micrologic 5.0A standard
Pscc is 0kA, Icu is 65kA

Device 2 - 630A@400V
Schneider - Compact NSX630N Micrologic 2.3
Pscc is 0kA, Icu is 50kA

17/02/2016 19:45:56 Amtech Protect HV Version 2015.0.0 Page 3 of 3


COMMISSIONING REPORT
5 Broadgate LVSB - 1 XX04 Study - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision rev 2 Created 28/06/2013 19:52:22
Job ID Last Saved 15/02/2016 23:08:15
Engineer K Lewis
3200-400 - Overcurrent Settings
Device 1, 3200A, Schneider, Masterpact NW32 H1 Micrologic 5.0A standard
Ir 1.00 Isd 3.00 Iinst OFF
tr 1.0 tsd 0.1

Device 2, 400A, Schneider, Compact NSX400N Micrologic 2.3


Io 400 Isd 5.0
Ir 1.00

17/02/2016 19:32:25 Amtech Protect HV Version 2015.0.0 Page 1 of 3


3200-400.prs17
Overcurrent-Time/Current Analysis, Voltage Base: 400V, 17/02/2016 19:32:29
10000s
Src Pscc
37.4kA

1 hour

1000s
Device 1
Device 2
Device 2 - 400A@400V
Schneider
Compact NSX400N Micrologic 2.3

Device 1 - 3200A@400V
100s
Schneider
Masterpact NW32 H1 Micrologic 5.0A standard
1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

17/02/2016 19:32:25 Amtech Protect HV Version 2015.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
3200-400 - Overcurrent Analysis

Source - 400V, Pscc is 37.4kA


~

Device 1 - 3200A@400V
Schneider - Masterpact NW32 H1 Micrologic 5.0A standard
Pscc is 0kA, Icu is 65kA

Device 2 - 400A@400V
Schneider - Compact NSX400N Micrologic 2.3
Pscc is 0kA, Icu is 50kA

17/02/2016 19:32:25 Amtech Protect HV Version 2015.0.0 Page 3 of 3


COMMISSIONING REPORT
5 Broadgate LVSB - 1 XX04 Study - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision rev 2 Created 28/06/2013 19:52:22
Job ID Last Saved 17/02/2016 19:33:50
Engineer K Lewis
3200-250 - Overcurrent Settings
Device 1, 3200A, Schneider, Masterpact NW32 H1 Micrologic 5.0A standard
Ir 1.00 Isd 3.00 Iinst OFF
tr 1.0 tsd 0.1

Device 2, 250A, Schneider, Compact NSX250N Micrologic 2.2


Io 200 Isd 5.0
Ir 1.00

17/02/2016 19:33:56 Amtech Protect HV Version 2015.0.0 Page 1 of 3


3200-250.prs17
Overcurrent-Time/Current Analysis, Voltage Base: 400V, 17/02/2016 19:34:00
10000s
Src Pscc
37.4kA

1 hour

1000s
Device 1
Device 2

Device 2 - 250A@400V
Schneider
Compact NSX250N Micrologic 2.2
100s

1 min Device 1 - 3200A@400V


Schneider
Masterpact NW32 H1 Micrologic 5.0A standard

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

17/02/2016 19:33:56 Amtech Protect HV Version 2015.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
3200-250 - Overcurrent Analysis

Source - 400V, Pscc is 37.4kA


~

Device 1 - 3200A@400V
Schneider - Masterpact NW32 H1 Micrologic 5.0A standard
Pscc is 0kA, Icu is 65kA

Device 2 - 250A@400V
Schneider - Compact NSX250N Micrologic 2.2
Pscc is 0kA, Icu is 50kA

17/02/2016 19:33:56 Amtech Protect HV Version 2015.0.0 Page 3 of 3


COMMISSIONING REPORT
5 Broadgate LVSB - 1 XX04 Study - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision rev 2 Created 28/06/2013 19:52:22
Job ID Last Saved 17/02/2016 19:35:31
Engineer K Lewis
3200-200 - Overcurrent Settings
Device 1, 3200A, Schneider, Masterpact NW32 H1 Micrologic 5.0A standard
Ir 1.00 Isd 3.00 Iinst OFF
tr 1.0 tsd 0.1

Device 2, 250A, Schneider, Compact NSX250N Micrologic 2.2


Io 200 Isd 5.0
Ir 1.00

17/02/2016 19:35:35 Amtech Protect HV Version 2015.0.0 Page 1 of 3


3200-200.prs17
Overcurrent-Time/Current Analysis, Voltage Base: 400V, 17/02/2016 19:35:39
10000s
Src Pscc
37.4kA

1 hour

1000s
Device 1
Device 2

Device 2 - 250A@400V
Schneider
Compact NSX250N Micrologic 2.2

100s

1 min
Device 1 - 3200A@400V
Schneider
Masterpact NW32 H1 Micrologic 5.0A standard

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

17/02/2016 19:35:35 Amtech Protect HV Version 2015.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
3200-200 - Overcurrent Analysis

Source - 400V, Pscc is 37.4kA


~

Device 1 - 3200A@400V
Schneider - Masterpact NW32 H1 Micrologic 5.0A standard
Pscc is 0kA, Icu is 65kA

Device 2 - 250A@400V
Schneider - Compact NSX250N Micrologic 2.2
Pscc is 0kA, Icu is 50kA

17/02/2016 19:35:35 Amtech Protect HV Version 2015.0.0 Page 3 of 3


COMMISSIONING REPORT
5 Broadgate LVSB - 13 XX04 Study - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision rev 1 Created 28/06/2013 19:52:22
Job ID Last Saved 17/02/2016 19:44:35
Engineer K Lewis
3200-160-10 - Overcurrent Settings
Device 1, 3200A, Schneider, Masterpact NW32 H1 Micrologic 5.0A standard
Ir 1.00 Isd 3.00 Iinst OFF
tr 1.0 tsd 0.1

Device 2, 160A, Schneider, Compact NSX160N Micrologic 2.2


Io 160 Isd 5.0
Ir 1.00

Device 3, 10A, Schneider, Multi9 C60H Type C Th-Mag

17/02/2016 19:44:41 Amtech Protect HV Version 2015.0.0 Page 1 of 3


3200-160-10.prs17
Overcurrent-Time/Current Analysis, Voltage Base: 400V, 17/02/2016 19:44:45
10000s
Src Pscc
37.3kA

1 hour

1000s
Device 1
Device 2
Device 3

Device 3 - 10A@400V
Schneider
Multi9 C60H Type C Th-Mag

100s Device 2 - 160A@400V


Schneider
1 min Compact NSX160N Micrologic 2.2

Device 1 - 3200A@400V
Schneider
Masterpact NW32 H1 Micrologic 5.0A standard

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

17/02/2016 19:44:41 Amtech Protect HV Version 2015.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
3200-160-10 - Overcurrent Analysis

Source - 400V, Pscc is 37.3kA


~

Device 1 - 3200A@400V
Schneider - Masterpact NW32 H1 Micrologic 5.0A standard
Pscc is 0kA, Icu is 65kA

Device 2 - 160A@400V
Schneider - Compact NSX160N Micrologic 2.2
Pscc is 0kA, Icu is 50kA

Device 3 - 10A@400V
Schneider - Multi9 C60H Type C Th-Mag
Pscc is 0kA, Icu is 15kA

17/02/2016 19:44:41 Amtech Protect HV Version 2015.0.0 Page 3 of 3


COMMISSIONING REPORT
5 Broadgate LVSB - 13 XX04 Study - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision rev 1 Created 28/06/2013 19:52:22
Job ID Last Saved 17/02/2016 19:41:06
Engineer K Lewis
3200-100-10 - - Overcurrent Settings
Device 1, 3200A, Schneider, Masterpact NW32 H1 Micrologic 5.0A standard
Ir 1.00 Isd 3.00 Iinst OFF
tr 1.0 tsd 0.1

Device 2, 100A, Schneider, Compact NSX100N Micrologic 2.2


Io 100 Isd 5.0
Ir 1.00

Device 3, 10A, Schneider, Multi9 C60H Type C Th-Mag

17/02/2016 19:41:20 Amtech Protect HV Version 2015.0.0 Page 1 of 3


3200-100-10 - .prs17
Overcurrent-Time/Current Analysis, Voltage Base: 400V, 17/02/2016 19:41:26
10000s
Src Pscc
37.3kA

1 hour

Device 2 - 100A@400V
Schneider
Compact NSX100N Micrologic 2.2
1000s
Device 1
Device 2
Device 3
Device 3 - 10A@400V
Schneider
Multi9 C60H Type C Th-Mag

100s Device 1 - 3200A@400V


Schneider
1 min Masterpact NW32 H1 Micrologic 5.0A standard

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

17/02/2016 19:41:20 Amtech Protect HV Version 2015.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
3200-100-10 - - Overcurrent Analysis

Source - 400V, Pscc is 37.3kA


~

Device 1 - 3200A@400V
Schneider - Masterpact NW32 H1 Micrologic 5.0A standard
Pscc is 0kA, Icu is 65kA

Device 2 - 100A@400V
Schneider - Compact NSX100N Micrologic 2.2
Pscc is 0kA, Icu is 50kA

Device 3 - 10A@400V
Schneider - Multi9 C60H Type C Th-Mag
Pscc is 0kA, Icu is 15kA

17/02/2016 19:41:20 Amtech Protect HV Version 2015.0.0 Page 3 of 3


COMMISSIONING REPORT
5 Broadgate LVSB - 13 XX04 Study - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision rev 1 Created 28/06/2013 19:52:22
Job ID Last Saved 17/02/2016 19:39:37
Engineer K Lewis
3200-63 - Overcurrent Settings
Device 1, 3200A, Schneider, Masterpact NW32 H1 Micrologic 5.0A standard
Ir 1.00 Isd 3.00 Iinst OFF
tr 1.0 tsd 0.1

Device 2, 63A, Schneider, Compact NSX100N TM D


Ir 63.0

17/02/2016 19:39:42 Amtech Protect HV Version 2015.0.0 Page 1 of 3


3200-63.prs17
Overcurrent-Time/Current Analysis, Voltage Base: 400V, 17/02/2016 19:39:47
10000s
Src Pscc
37.3kA

1 hour

Device 2 - 63A@400V
Schneider
Compact NSX100N TM D

1000s
Device 1
Device 1 - 3200A@400V Device 2
Schneider
Masterpact NW32 H1 Micrologic 5.0A standard

100s

1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

17/02/2016 19:39:42 Amtech Protect HV Version 2015.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
3200-63 - Overcurrent Analysis

Source - 400V, Pscc is 37.3kA


~

Device 1 - 3200A@400V
Schneider - Masterpact NW32 H1 Micrologic 5.0A standard
Pscc is 0kA, Icu is 65kA

Device 2 - 63A@400V
Schneider - Compact NSX100N TM D
Pscc is 0kA, Icu is 50kA

17/02/2016 19:39:42 Amtech Protect HV Version 2015.0.0 Page 3 of 3


COMMISSIONING REPORT
5 Broadgate LVSB - 2 XX02 Study - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision rev 3 Created 28/06/2013 19:52:22
Job ID Last Saved 17/02/2016 19:59:15
Engineer K Lewis
1600-400-160-32 - Overcurrent Settings
Device 1, 1600A, Schneider, Masterpact NW16 H1 Micrologic 5.0A standard
Ir 1.00 Isd 3.00 Iinst OFF
tr 1.0 tsd 0.1

Device 2, 400A, Schneider, Compact NSX400N Micrologic 2.3


Io 400 Isd 5.0
Ir 1.00

Device 5, 160A, Schneider, Compact NSX160S Micrologic 2.2


Io 160 Isd 5.0
Ir 1.00

Device 4, 32A, Schneider, Multi9 C60H Type C Th-Mag

17/02/2016 19:59:23 Amtech Protect HV Version 2015.0.0 Page 1 of 3


1600-400-160-32.prs17
Overcurrent-Time/Current Analysis, Voltage Base: 400V, 17/02/2016 19:59:29
10000s
Src Pscc
24.3kA

1 hour

1000s Device 4 - 32A@400V


Schneider Device 1
Multi9 C60H Type C Th-Mag Device 5 - 160A@400V Device 2
Schneider Device 5
Compact NSX160S Micrologic 2.2 Device 4

Device 2 - 400A@400V
Schneider
Compact NSX400N Micrologic 2.3

Device 1 - 1600A@400V
100s
Schneider
Masterpact NW16 H1 Micrologic 5.0A standard
1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

17/02/2016 19:59:23 Amtech Protect HV Version 2015.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
1600-400-160-32 - Overcurrent Analysis

Source - 400V, Pscc is 24.3kA


~

Device 1 - 1600A@400V
Schneider - Masterpact NW16 H1 Micrologic 5.0A standard
Pscc is 0kA, Icu is 65kA

Device 2 - 400A@400V
Schneider - Compact NSX400N Micrologic 2.3
Pscc is 0kA, Icu is 50kA

Device 5 - 160A@400V
Schneider - Compact NSX160S Micrologic 2.2
Pscc is 0kA, Icu is 100kA

Device 4 - 32A@400V
Schneider - Multi9 C60H Type C Th-Mag
Pscc is 0kA, Icu is 15kA

17/02/2016 19:59:23 Amtech Protect HV Version 2015.0.0 Page 3 of 3


COMMISSIONING REPORT
5 Broadgate LVSB - 13 XX05 Study - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision rev 2 Created 28/06/2013 19:52:22
Job ID Last Saved 17/02/2016 20:26:45
Engineer K Lewis
1600-400 - Overcurrent Settings
Device 2, 1600A, Schneider, Masterpact NW16 H1 Micrologic 5.0A standard
Ir 1.00 Isd 3.00 Iinst OFF
tr 1.0 tsd 0.1

Device 1, 400A, Schneider, Compact NSX400N Micrologic 2.3


Io 400 Isd 5.0
Ir 1.00

17/02/2016 20:26:53 Amtech Protect HV Version 2015.0.0 Page 1 of 3


1600-400.prs17
Overcurrent-Time/Current Analysis, Voltage Base: 400V, 17/02/2016 20:26:57
10000s
Src Pscc
4.2kA

1 hour

Device 1 - 400A@400V
Schneider
1000s Compact NSX400N Micrologic 2.3
Device 2
Device 1

Device 2 - 1600A@400V
Schneider
Masterpact NW16 H1 Micrologic 5.0A standard

100s

1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

17/02/2016 20:26:53 Amtech Protect HV Version 2015.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
1600-400 - Overcurrent Analysis

Generator - 400V, Pscc is 4.2kA


~

Device 2 - 1600A@400V
Schneider - Masterpact NW16 H1 Micrologic 5.0A standard
Pscc is 0kA, Icu is 65kA

Device 1 - 400A@400V
Schneider - Compact NSX400N Micrologic 2.3
Pscc is 0kA, Icu is 50kA

17/02/2016 20:26:53 Amtech Protect HV Version 2015.0.0 Page 3 of 3


COMMISSIONING REPORT
5 Broadgate LVSB - 2 XX02 Study - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision rev 3 Created 28/06/2013 19:52:22
Job ID Last Saved 17/02/2016 20:20:29
Engineer K Lewis
1600-200 - Overcurrent Settings
Device 1, 1600A, Schneider, Masterpact NW16 H1 Micrologic 5.0A standard
Ir 1.00 Isd 3.00 Iinst OFF
tr 1.0 tsd 0.1

Device 2, 250A, Schneider, Compact NSX250N TM D


Ir 200 Im 2500

17/02/2016 20:20:34 Amtech Protect HV Version 2015.0.0 Page 1 of 3


1600-200.prs17
Overcurrent-Time/Current Analysis, Voltage Base: 400V, 17/02/2016 20:20:40
10000s
Src Pscc
24.3kA

1 hour

Device 2 - 250A@400V
1000s Schneider Device 1
Compact NSX250N TM D Device 2

100s

1 min
Device 1 - 1600A@400V
Schneider
Masterpact NW16 H1 Micrologic 5.0A standard

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

17/02/2016 20:20:34 Amtech Protect HV Version 2015.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
1600-200 - Overcurrent Analysis

Source - 400V, Pscc is 24.3kA


~

Device 1 - 1600A@400V
Schneider - Masterpact NW16 H1 Micrologic 5.0A standard
Pscc is 0kA, Icu is 65kA

Device 2 - 250A@400V
Schneider - Compact NSX250N TM D
Pscc is 0kA, Icu is 50kA

17/02/2016 20:20:34 Amtech Protect HV Version 2015.0.0 Page 3 of 3


COMMISSIONING REPORT
5 Broadgate LVSB - 2 XX02 Study - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision rev 3 Created 28/06/2013 19:52:22
Job ID Last Saved 17/02/2016 20:22:07
Engineer K Lewis
1600-160 - Overcurrent Settings
Device 1, 1600A, Schneider, Masterpact NW16 H1 Micrologic 5.0A standard
Ir 1.00 Isd 3.00 Iinst OFF
tr 1.0 tsd 0.1

Device 3, 160A, Schneider, Compact NSX160N Micrologic 2.2


Io 160 Isd 5.0
Ir 1.00

17/02/2016 20:22:13 Amtech Protect HV Version 2015.0.0 Page 1 of 3


1600-160.prs17
Overcurrent-Time/Current Analysis, Voltage Base: 400V, 17/02/2016 20:22:17
10000s
Src Pscc
24.3kA

1 hour

1000s
Device 1
Device 3

Device 3 - 160A@400V
Schneider
Compact NSX160N Micrologic 2.2

Device 1 - 1600A@400V
Schneider
Masterpact NW16 H1 Micrologic 5.0A standard
100s

1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

17/02/2016 20:22:13 Amtech Protect HV Version 2015.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
1600-160 - Overcurrent Analysis

Source - 400V, Pscc is 24.3kA


~

Device 1 - 1600A@400V
Schneider - Masterpact NW16 H1 Micrologic 5.0A standard
Pscc is 0kA, Icu is 65kA

Device 3 - 160A@400V
Schneider - Compact NSX160N Micrologic 2.2
Pscc is 0kA, Icu is 50kA

17/02/2016 20:22:13 Amtech Protect HV Version 2015.0.0 Page 3 of 3


COMMISSIONING REPORT
5 Broadgate LVSB - 13 XX05 Study - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision rev 2 Created 28/06/2013 19:52:22
Job ID Last Saved 17/02/2016 20:27:34
Engineer K Lewis
1600-63 - Overcurrent Settings
Device 2, 1600A, Schneider, Masterpact NW16 H1 Micrologic 5.0A standard
Ir 1.00 Isd 3.00 Iinst OFF
tr 1.0 tsd 0.1

Device 1, 63A, Schneider, Compact NSX100N TM D


Ir 63.0

17/02/2016 20:27:39 Amtech Protect HV Version 2015.0.0 Page 1 of 3


1600-63.prs17
Overcurrent-Time/Current Analysis, Voltage Base: 400V, 17/02/2016 20:27:43
10000s
Src Pscc
4.2kA

1 hour

Device 1 - 63A@400V
Schneider
Compact NSX100N TM D

1000s
Device 2
Device 1

100s

1 min Device 2 - 1600A@400V


Schneider
Masterpact NW16 H1 Micrologic 5.0A standard

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

17/02/2016 20:27:39 Amtech Protect HV Version 2015.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
1600-63 - Overcurrent Analysis

Generator - 400V, Pscc is 4.2kA


~

Device 2 - 1600A@400V
Schneider - Masterpact NW16 H1 Micrologic 5.0A standard
Pscc is 0kA, Icu is 65kA

Device 1 - 63A@400V
Schneider - Compact NSX100N TM D
Pscc is 0kA, Icu is 50kA

17/02/2016 20:27:39 Amtech Protect HV Version 2015.0.0 Page 3 of 3


COMMISSIONING REPORT
5 Broadgate LVSB - 1 XX05 Study - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision rev 1 Created 28/06/2013 19:52:22
Job ID Last Saved 17/02/2016 21:09:26
Engineer K Lewis
1250 - 400 - Overcurrent Settings
Device 1, 1250A, Schneider, Masterpact NW12 H1 Micrologic 5.0A standard
Ir 1.00 Isd 6.00 Iinst OFF
tr 8.0 tsd 0.1

Device 2, 400A, Schneider, Compact NSX400N Micrologic 2.3


Io 400 Isd 5.0
Ir 1.00

17/02/2016 21:09:34 Amtech Protect HV Version 2015.0.0 Page 1 of 3


1250 - 400.prs17
Overcurrent-Time/Current Analysis, Voltage Base: 400V, 17/02/2016 21:09:39
10000s
Src Pscc
37.3kA

1 hour

Device 2 - 400A@400V
Schneider
Compact NSX400N Micrologic 2.3
1000s
Device 1
Device 2

Device 1 - 1250A@400V
Schneider
Masterpact NW12 H1 Micrologic 5.0A standard
100s

1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

17/02/2016 21:09:34 Amtech Protect HV Version 2015.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
1250 - 400 - Overcurrent Analysis

Source - 400V, Pscc is 37.3kA


~

Device 1 - 1250A@400V
Schneider - Masterpact NW12 H1 Micrologic 5.0A standard
Pscc is 0kA, Icu is 65kA

Device 2 - 400A@400V
Schneider - Compact NSX400N Micrologic 2.3
Pscc is 0kA, Icu is 50kA

17/02/2016 21:09:34 Amtech Protect HV Version 2015.0.0 Page 3 of 3


COMMISSIONING REPORT
5 Broadgate LVSB - 1 XX05 Study - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision rev 1 Created 28/06/2013 19:52:22
Job ID Last Saved 17/02/2016 21:09:26
Engineer K Lewis
1250 - 400 - set 200 - Overcurrent Settings
Device 1, 1250A, Schneider, Masterpact NW12 H1 Micrologic 5.0A standard
Ir 1.00 Isd 6.00 Iinst OFF
tr 8.0 tsd 0.1

Device 2, 400A, Schneider, Compact NSX400N Micrologic 2.3


Io 200 Isd 5.0
Ir 1.00

24/02/2016 17:45:23 Amtech Protect HV Version 2015.0.0 Page 1 of 3


1250 - 400 - set 200.prs17
Overcurrent-Time/Current Analysis, Voltage Base: 400V, 24/02/2016 17:45:28
10000s
Src Pscc
37.3kA

1 hour

Device 2 - 400A@400V Device 1 - 1250A@400V


Schneider Schneider
Compact NSX400N Micrologic 2.3 Masterpact NW12 H1 Micrologic 5.0A standard
1000s
Device 1
Device 2

100s

1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

24/02/2016 17:45:23 Amtech Protect HV Version 2015.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
1250 - 400 - set 200 - Overcurrent Analysis

Source - 400V, Pscc is 37.3kA


~

Device 1 - 1250A@400V
Schneider - Masterpact NW12 H1 Micrologic 5.0A standard
Pscc is 0kA, Icu is 65kA

Device 2 - 400A@400V
Schneider - Compact NSX400N Micrologic 2.3
Pscc is 0kA, Icu is 50kA

24/02/2016 17:45:23 Amtech Protect HV Version 2015.0.0 Page 3 of 3


COMMISSIONING REPORT
5 Broadgate LVSB - 1 XX05 Study - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision rev 1 Created 28/06/2013 19:52:22
Job ID Last Saved 17/02/2016 21:05:56
Engineer K Lewis
1250 - 315 - Overcurrent Settings
Device 3, 1250A, Schneider, Masterpact NW12 H1 Micrologic 5.0A standard
Ir 1.00 Isd 6.00 Iinst OFF
tr 8.0 tsd 0.1

Device 2, 315A, Generic, BS88-2 Fuse System E

17/02/2016 21:06:02 Amtech Protect HV Version 2015.0.0 Page 1 of 3


1250 - 315.prs17
Overcurrent-Time/Current Analysis, Voltage Base: 400V, 17/02/2016 21:06:06
10000s
Src Pscc
37.3kA

1 hour
Device 2 - 315A@400V
Generic
BS88-2 Fuse System E

Device 3 - 1250A@400V
1000s Schneider
Device 3
Masterpact NW12 H1 Micrologic 5.0A standard
Device 2

100s

1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

17/02/2016 21:06:02 Amtech Protect HV Version 2015.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
1250 - 315 - Overcurrent Analysis

Source - 400V, Pscc is 37.3kA


~

Device 3 - 1250A@400V
Schneider - Masterpact NW12 H1 Micrologic 5.0A standard
Pscc is 0kA, Icu is 65kA

Device 2 - 315A@400V
Generic - BS88-2 Fuse System E
Pscc is 0kA, Icu is 80kA

17/02/2016 21:06:02 Amtech Protect HV Version 2015.0.0 Page 3 of 3


COMMISSIONING REPORT
5 Broadgate LVSB - 1 XX05 Study - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision rev 1 Created 28/06/2013 19:52:22
Job ID Last Saved 17/02/2016 21:17:00
Engineer K Lewis
1250 - 200 - Overcurrent Settings
Device 1, 1250A, Schneider, Masterpact NW12 H1 Micrologic 5.0A standard
Ir 1.00 Isd 6.00 Iinst OFF
tr 8.0 tsd 0.1

Device 3, 250A, Schneider, Compact NSX250N Micrologic 2.2


Io 200 Isd 5.0
Ir 1.00

17/02/2016 21:17:05 Amtech Protect HV Version 2015.0.0 Page 1 of 3


1250 - 200.prs17
Overcurrent-Time/Current Analysis, Voltage Base: 400V, 17/02/2016 21:17:10
10000s
Src Pscc
37.3kA

1 hour

1000s
Device 1
Device 3

Device 3 - 250A@400V
Schneider
Compact NSX250N Micrologic 2.2

100s

1 min

Device 1 - 1250A@400V
Schneider
Masterpact NW12 H1 Micrologic 5.0A standard

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

17/02/2016 21:17:05 Amtech Protect HV Version 2015.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
1250 - 200 - Overcurrent Analysis

Source - 400V, Pscc is 37.3kA


~

Device 1 - 1250A@400V
Schneider - Masterpact NW12 H1 Micrologic 5.0A standard
Pscc is 0kA, Icu is 65kA

Device 3 - 250A@400V
Schneider - Compact NSX250N Micrologic 2.2
Pscc is 0kA, Icu is 50kA

17/02/2016 21:17:05 Amtech Protect HV Version 2015.0.0 Page 3 of 3


COMMISSIONING REPORT
5 Broadgate LVSB - 1 XX05 Study - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision rev 1 Created 28/06/2013 19:52:22
Job ID Last Saved 17/02/2016 21:12:12
Engineer K Lewis
1250 - 1600 - - Overcurrent Settings
Device 2, 1250A, Schneider, Masterpact NW12 H1 Micrologic 5.0A standard
Ir 1.00 Isd 6.00 Iinst OFF
tr 8.0 tsd 0.1

Device 1, 1600A, Schneider, Masterpact NW16 H1 Micrologic 5.0A standard


Ir 1.00 Isd 3.00 Iinst OFF
tr 1.0 tsd 0.1

17/02/2016 21:12:18 Amtech Protect HV Version 2015.0.0 Page 1 of 3


1250 - 1600 -.prs17
Overcurrent-Time/Current Analysis, Voltage Base: 400V, 17/02/2016 21:12:24
10000s
Src Pscc
37.3kA

1 hour

1000s
Device 2
Device 2 - 1250A@400V Device 1
Schneider
Masterpact NW12 H1 Micrologic 5.0A standard

100s

1 min

Device 1 - 1600A@400V
Schneider
Masterpact NW16 H1 Micrologic 5.0A standard

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

17/02/2016 21:12:18 Amtech Protect HV Version 2015.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
1250 - 1600 - - Overcurrent Analysis

Source - 400V, Pscc is 37.3kA


~

Device 2 - 1250A@400V
Schneider - Masterpact NW12 H1 Micrologic 5.0A standard
Pscc is 0kA, Icu is 65kA

Device 1 - 1600A@400V
Schneider - Masterpact NW16 H1 Micrologic 5.0A standard
Pscc is 0kA, Icu is 65kA

17/02/2016 21:12:18 Amtech Protect HV Version 2015.0.0 Page 3 of 3


COMMISSIONING REPORT
5 Broadgate LVSB - 1 XX05 Study - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision rev 1 Created 28/06/2013 19:52:22
Job ID Last Saved 17/02/2016 21:13:51
Engineer K Lewis
1250 - 160 - Overcurrent Settings
Device 3, 1250A, Schneider, Masterpact NW12 H1 Micrologic 5.0A standard
Ir 1.00 Isd 5.00 Iinst OFF
tr 8.0 tsd 0.1

Device 2, 160A, Schneider, Compact NSX160N Micrologic 2.2


Io 160 Isd 5.0
Ir 1.00

17/02/2016 21:13:55 Amtech Protect HV Version 2015.0.0 Page 1 of 3


1250 - 160.prs17
Overcurrent-Time/Current Analysis, Voltage Base: 400V, 17/02/2016 21:13:59
10000s
Src Pscc
37.3kA

1 hour

1000s
Device 3
Device 2

Device 2 - 160A@400V
Schneider
Compact NSX160N Micrologic 2.2

100s

1 min

Device 3 - 1250A@400V
Schneider
Masterpact NW12 H1 Micrologic 5.0A standard
10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

17/02/2016 21:13:55 Amtech Protect HV Version 2015.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
1250 - 160 - Overcurrent Analysis

Source - 400V, Pscc is 37.3kA


~

Device 3 - 1250A@400V
Schneider - Masterpact NW12 H1 Micrologic 5.0A standard
Pscc is 0kA, Icu is 65kA

Device 2 - 160A@400V
Schneider - Compact NSX160N Micrologic 2.2
Pscc is 0kA, Icu is 50kA

17/02/2016 21:13:55 Amtech Protect HV Version 2015.0.0 Page 3 of 3


COMMISSIONING REPORT
5 Broadgate LVSB - 1 XX05 Study - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision rev 1 Created 28/06/2013 19:52:22
Job ID Last Saved 17/02/2016 21:15:31
Engineer K Lewis
1250 - 100 - Overcurrent Settings
Device 3, 1250A, Schneider, Masterpact NW12 H1 Micrologic 5.0A standard
Ir 1.00 Isd 6.00 Iinst OFF
tr 8.0 tsd 0.1

Device 2, 100A, Schneider, Compact NSX100N Micrologic 2.2


Io 100 Isd 5.0
Ir 1.00

17/02/2016 21:15:36 Amtech Protect HV Version 2015.0.0 Page 1 of 3


1250 - 100.prs17
Overcurrent-Time/Current Analysis, Voltage Base: 400V, 17/02/2016 21:15:40
10000s
Src Pscc
37.3kA

1 hour

1000s
Device 3
Device 2

100s

1 min
Device 2 - 100A@400V
Schneider
Compact NSX100N Micrologic 2.2

Device 3 - 1250A@400V
Schneider
10s
Masterpact NW12 H1 Micrologic 5.0A standard

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

17/02/2016 21:15:36 Amtech Protect HV Version 2015.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
1250 - 100 - Overcurrent Analysis

Source - 400V, Pscc is 37.3kA


~

Device 3 - 1250A@400V
Schneider - Masterpact NW12 H1 Micrologic 5.0A standard
Pscc is 0kA, Icu is 65kA

Device 2 - 100A@400V
Schneider - Compact NSX100N Micrologic 2.2
Pscc is 0kA, Icu is 50kA

17/02/2016 21:15:36 Amtech Protect HV Version 2015.0.0 Page 3 of 3


COMMISSIONING REPORT
5 Broadgate LVSB - 1 XX06 Study - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision rev 2 Created 28/06/2013 19:52:22
Job ID Last Saved 24/02/2016 18:14:17
Engineer K Lewis
800-160 - Overcurrent Settings
Device 1 main incomer, 800A, Schneider, Compact NS800 N Micrologic 5.0A standard
Ir 1.00 Isd 4.00 Iinst OFF
tr 8.0 tsd 0.1

Device2, 160A, Schneider, Compact NSX160N Micrologic 2.2


Io 160 Isd 5.0
Ir 1.00

24/02/2016 18:14:22 Amtech Protect HV Version 2015.0.0 Page 1 of 3


800-160 .prs17
Overcurrent-Time/Current Analysis, Voltage Base: 400V, 24/02/2016 18:14:27
10000s
Device2 - 160A@400V Src Pscc
Schneider 56.7kA
Compact NSX160N Micrologic 2.2

1 hour
Device 1 main incomer - 800A@400V
Schneider
Compact NS800 N Micrologic 5.0A standard

1000s
Device 1 main incomer
Device2

100s

1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

24/02/2016 18:14:22 Amtech Protect HV Version 2015.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
800-160 - Overcurrent Analysis

Source - 400V, Pscc is 56.7kA


~

Device 1 main incomer - 800A@400V


Schneider - Compact NS800 N Micrologic 5.0A standard
Pscc is 0kA, Icu is 50kA

Device2 - 160A@400V
Schneider - Compact NSX160N Micrologic 2.2
Pscc is 0kA, Icu is 50kA

24/02/2016 18:14:22 Amtech Protect HV Version 2015.0.0 Page 3 of 3


COMMISSIONING REPORT
5 Broadgate LVSB - 1 XX06 Study - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision rev 2 Created 28/06/2013 19:52:22
Job ID Last Saved 17/02/2016 21:20:08
Engineer K Lewis
800-160 - Overcurrent Settings
Device 2, 800A, Schneider, Compact NS800 L Micrologic 2.0A standard
Ir 0.40 Isd 10.0
tr 16.0

Device 3, 160A, Schneider, Compact NSX160S Micrologic 2.2


Io 160 Isd 5.0
Ir 1.00

17/02/2016 21:20:15 Amtech Protect HV Version 2015.0.0 Page 1 of 3


800-160.prs17
Overcurrent-Time/Current Analysis, Voltage Base: 400V, 17/02/2016 21:20:20
10000s
Src Pscc
56.7kA

1 hour

Device 2 - 800A@400V
1000s Schneider
Compact NS800 L Micrologic 2.0A standard Device 2
Device 3

Device 3 - 160A@400V
Schneider
100s Compact NSX160S Micrologic 2.2

1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

17/02/2016 21:20:15 Amtech Protect HV Version 2015.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
800-160 - Overcurrent Analysis

Source - 400V, Pscc is 56.7kA


~

Device 2 - 800A@400V
Schneider - Compact NS800 L Micrologic 2.0A standard
Pscc is 0kA, Icu is 150kA

Device 3 - 160A@400V
Schneider - Compact NSX160S Micrologic 2.2
Pscc is 0kA, Icu is 100kA

17/02/2016 21:20:15 Amtech Protect HV Version 2015.0.0 Page 3 of 3


COMMISSIONING REPORT
5 Broadgate LVSB - 1 XX06 Study - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision rev 2 Created 28/06/2013 19:52:22
Job ID Last Saved 17/02/2016 21:20:08
Engineer K Lewis
800-160 - set at 100 - Overcurrent Settings
Device 1 main incomer, 800A, Schneider, Compact NS800 N Micrologic 5.0A standard
Ir 1.00 Isd 4.00 Iinst OFF
tr 8.0 tsd 0.1

Device2, 160A, Schneider, Compact NSX160N Micrologic 2.2


Io 100 Isd 5.0
Ir 1.00

24/02/2016 18:05:32 Amtech Protect HV Version 2015.0.0 Page 1 of 3


800-160 - set at 100.prs17
Overcurrent-Time/Current Analysis, Voltage Base: 400V, 24/02/2016 18:05:38
10000s
Device2 - 160A@400V Src Pscc
Schneider 56.7kA
Compact NSX160N Micrologic 2.2

1 hour Device 1 main incomer - 800A@400V


Schneider
Compact NS800 N Micrologic 5.0A standard

1000s
Device 1 main incomer
Device2

100s

1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

24/02/2016 18:05:32 Amtech Protect HV Version 2015.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
800-160 - set at 100 - Overcurrent Analysis

Source - 400V, Pscc is 56.7kA


~

Device 1 main incomer - 800A@400V


Schneider - Compact NS800 N Micrologic 5.0A standard
Pscc is 0kA, Icu is 50kA

Device2 - 160A@400V
Schneider - Compact NSX160N Micrologic 2.2
Pscc is 0kA, Icu is 50kA

24/02/2016 18:05:32 Amtech Protect HV Version 2015.0.0 Page 3 of 3


COMMISSIONING REPORT
5 Broadgate LVSB - 1 XX06 Study - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision rev 2 Created 28/06/2013 19:52:22
Job ID Last Saved 24/02/2016 18:11:14
Engineer K Lewis
800-100 - Overcurrent Settings
Device 1 incomer, 800A, Schneider, Compact NS800 N Micrologic 5.0A standard
Ir 1.00 Isd 4.00 Iinst OFF
tr 8.0 tsd 0.1

Device 1, 100A, Schneider, Compact NSX100N Micrologic 2.2


Io 100 Isd 5.0
Ir 1.00

24/02/2016 18:11:26 Amtech Protect HV Version 2015.0.0 Page 1 of 3


800-100.prs17
Overcurrent-Time/Current Analysis, Voltage Base: 400V, 24/02/2016 18:11:32
10000s
Src Pscc
56.7kA

1 hour Device 1 incomer - 800A@400V


Device 1 - 100A@400V
Schneider
Schneider
Compact NS800 N Micrologic 5.0A standard
Compact NSX100N Micrologic 2.2

1000s
Device 1 incomer
Device 1

100s

1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

24/02/2016 18:11:26 Amtech Protect HV Version 2015.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
800-100 - Overcurrent Analysis

Source - 400V, Pscc is 56.7kA


~

Device 1 incomer - 800A@400V


Schneider - Compact NS800 N Micrologic 5.0A standard
Pscc is 0kA, Icu is 50kA

Device 1 - 100A@400V
Schneider - Compact NSX100N Micrologic 2.2
Pscc is 0kA, Icu is 50kA

24/02/2016 18:11:26 Amtech Protect HV Version 2015.0.0 Page 3 of 3


COMMISSIONING REPORT
5 Broadgate LVSB - 1 XX05 Study - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision rev 1 Created 28/06/2013 19:52:22
Job ID Last Saved 17/02/2016 21:30:21
Engineer K Lewis
400- 250 - Copy - Overcurrent Settings
Device 2, 400A, Schneider, Compact NSX400N Micrologic 2.3
Io 400 Isd 5.0
Ir 1.00

Device 1, 250A, Schneider, Compact NSX250S Micrologic 2.2


Io 250 Isd 5.0
Ir 1.00

17/02/2016 21:30:27 Amtech Protect HV Version 2015.0.0 Page 1 of 3


400- 250 - Copy.prs17
Overcurrent-Time/Current Analysis, Voltage Base: 400V, 17/02/2016 21:30:38
10000s
Src Pscc
37.3kA

1 hour Device 2 - 400A@400V


Schneider
Compact NSX400N Micrologic 2.3
Device 1 - 250A@400V
Schneider
1000s Compact NSX250S Micrologic 2.2
Device 2
Device 1

100s

1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

17/02/2016 21:30:27 Amtech Protect HV Version 2015.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
400- 250 - Copy - Overcurrent Analysis

Source - 400V, Pscc is 37.3kA


~

Device 2 - 400A@400V
Schneider - Compact NSX400N Micrologic 2.3
Pscc is 0kA, Icu is 50kA

Device 1 - 250A@400V
Schneider - Compact NSX250S Micrologic 2.2
Pscc is 0kA, Icu is 100kA

17/02/2016 21:30:27 Amtech Protect HV Version 2015.0.0 Page 3 of 3


COMMISSIONING REPORT
5 Broadgate LVSB - 13 XX06 Study - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision rev 1 Created 28/06/2013 19:52:22
Job ID Last Saved 17/02/2016 21:24:39
Engineer K Lewis
400-160-63 - Overcurrent Settings
Device 1, 400A, Schneider, Compact NSX400N Micrologic 2.3
Io 400 Isd 5.0
Ir 1.00

Device 3, 160A, Schneider, Compact NSX160N Micrologic 2.2


Io 160 Isd 5.0
Ir 1.00

Device 2, 63A, Schneider, Compact NSX100N TM D


Ir 63.0

17/02/2016 21:24:44 Amtech Protect HV Version 2015.0.0 Page 1 of 3


400-160-63.prs17
Overcurrent-Time/Current Analysis, Voltage Base: 400V, 17/02/2016 21:24:48
10000s
Src Pscc
Device 1 - 400A@400V
37.3kA
Schneider
Compact NSX400N Micrologic 2.3
1 hour
Device 2 - 63A@400V
Schneider
Device 3 - 160A@400V
Compact NSX100N TM D
Schneider
Compact NSX160N Micrologic 2.2
1000s
Device 1
Device 3
Device 2

100s

1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

17/02/2016 21:24:44 Amtech Protect HV Version 2015.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
400-160-63 - Overcurrent Analysis

Source - 400V, Pscc is 37.3kA


~

Device 1 - 400A@400V
Schneider - Compact NSX400N Micrologic 2.3
Pscc is 0kA, Icu is 50kA

Device 3 - 160A@400V
Schneider - Compact NSX160N Micrologic 2.2
Pscc is 0kA, Icu is 50kA

Device 2 - 63A@400V
Schneider - Compact NSX100N TM D
Pscc is 0kA, Icu is 50kA

17/02/2016 21:24:44 Amtech Protect HV Version 2015.0.0 Page 3 of 3


COMMISSIONING REPORT
5 Broadgate LVSB - 13 XX05 Study - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision rev 2 Created 28/06/2013 19:52:22
Job ID Last Saved 17/02/2016 21:26:36
Engineer K Lewis
400-160-40 - Overcurrent Settings
Device 1, 400A, Schneider, Compact NSX400N Micrologic 2.3
Io 400 Isd 10.0
Ir 1.00

Device 3, 160A, Schneider, Compact NSX160N Micrologic 2.2


Io 160 Isd 5.0
Ir 1.00

Device 2, 40A, Schneider, Multi9 C60H Type C Th-Mag

17/02/2016 21:26:40 Amtech Protect HV Version 2015.0.0 Page 1 of 3


400-160-40.prs17
Overcurrent-Time/Current Analysis, Voltage Base: 400V, 17/02/2016 21:26:44
10000s
Src Pscc
37.3kA

1 hour Device 1 - 400A@400V


Schneider
Compact NSX400N Micrologic 2.3

1000s
Device 1
Device 3
Device 3 - 160A@400V Device 2
Schneider
Compact NSX160N Micrologic 2.2

100s

1 min

Device 2 - 40A@400V
Schneider
Multi9 C60H Type C Th-Mag

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

17/02/2016 21:26:40 Amtech Protect HV Version 2015.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
400-160-40 - Overcurrent Analysis

Source - 400V, Pscc is 37.3kA


~

Device 1 - 400A@400V
Schneider - Compact NSX400N Micrologic 2.3
Pscc is 0kA, Icu is 50kA

Device 3 - 160A@400V
Schneider - Compact NSX160N Micrologic 2.2
Pscc is 0kA, Icu is 50kA

Device 2 - 40A@400V
Schneider - Multi9 C60H Type C Th-Mag
Pscc is 0kA, Icu is 15kA

17/02/2016 21:26:40 Amtech Protect HV Version 2015.0.0 Page 3 of 3


COMMISSIONING REPORT
5 Broadgate LVSB - 13 XX05 Study - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision rev 1 Created 28/06/2013 19:52:22
Job ID Last Saved 17/02/2016 21:27:42
Engineer K Lewis
400-160 - Overcurrent Settings
Device 1, 400A, Schneider, Compact NSX400N Micrologic 2.3
Io 400 Isd 10.0
Ir 1.00

Device 2, 160A, Schneider, Compact NSX160N Micrologic 2.2


Io 160 Isd 5.0
Ir 1.00

17/02/2016 21:27:47 Amtech Protect HV Version 2015.0.0 Page 1 of 3


400-160.prs17
Overcurrent-Time/Current Analysis, Voltage Base: 400V, 17/02/2016 21:27:51
10000s
Src Pscc
37.3kA

1 hour

Device 1 - 400A@400V
Schneider
1000s Compact NSX400N Micrologic 2.3
Device 1
Device 2
Device 2 - 160A@400V
Schneider
Compact NSX160N Micrologic 2.2

100s

1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

17/02/2016 21:27:47 Amtech Protect HV Version 2015.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
400-160 - Overcurrent Analysis

Source - 400V, Pscc is 37.3kA


~

Device 1 - 400A@400V
Schneider - Compact NSX400N Micrologic 2.3
Pscc is 0kA, Icu is 50kA

Device 2 - 160A@400V
Schneider - Compact NSX160N Micrologic 2.2
Pscc is 0kA, Icu is 50kA

17/02/2016 21:27:47 Amtech Protect HV Version 2015.0.0 Page 3 of 3


COMMISSIONING REPORT
5 Broadgate LVSB - 1 XX05 Study - Licenced to Long & Partners Ltd

Project Reference Modified By


Revision rev 1 Created 28/06/2013 19:52:22
Job ID Last Saved 17/02/2016 21:31:40
Engineer K Lewis
400- 160 - Overcurrent Settings
Device 2, 400A, Schneider, Compact NSX400N Micrologic 2.3
Io 400 Isd 5.0
Ir 1.00

Device 1, 160A, Schneider, Compact NSX160S Micrologic 2.2


Io 160 Isd 5.0
Ir 1.00

17/02/2016 21:31:51 Amtech Protect HV Version 2015.0.0 Page 1 of 3


400- 160 .prs17
Overcurrent-Time/Current Analysis, Voltage Base: 400V, 17/02/2016 21:31:55
10000s
Src Pscc
37.3kA

1 hour

Device 1 - 160A@400V
Schneider
Compact NSX160S Micrologic 2.2
1000s
Device 2
Device 1
Device 2 - 400A@400V
Schneider
Compact NSX400N Micrologic 2.3

100s

1 min

10s

5 sec

1s

0.4 sec

0.1s

0.01s
1A 10A 100A 1kA 10kA 100kA 1MA

17/02/2016 21:31:51 Amtech Protect HV Version 2015.0.0 Page 2 of 3


SINGLE LINE DIAGRAM
400- 160 - Overcurrent Analysis

Source - 400V, Pscc is 37.3kA


~

Device 2 - 400A@400V
Schneider - Compact NSX400N Micrologic 2.3
Pscc is 0kA, Icu is 50kA

Device 1 - 160A@400V
Schneider - Compact NSX160S Micrologic 2.2
Pscc is 0kA, Icu is 100kA

17/02/2016 21:31:51 Amtech Protect HV Version 2015.0.0 Page 3 of 3


LVSB-13XX02 6300A_3200A 5 Broadgate

Discrimination report

Schneider
Page 2/4

Information

Name : LVSB-13XX02 6300A_3200A


First name : 5 Broadgate
Company : Long & Partners
Customer : Mace

Project: Schneider 02/24/2016 08:07:28 PM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.
Page 3/4

Discrimination diagram
Discrimination status :

Project: Schneider 02/24/2016 08:07:28 PM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.
Page 4/4

Range Masterpact NW Masterpact NW

Designation/Fuse NW63H1 NW32H1


technology
Rating (A) 6300 A 3200 A

Trip unit Micrologic 5.0 E Micrologic 5.0 E

Trip unit rating 6300 A 3200 A

Trip class

Long delay settings

Ir 6300 A 3200 A

Tr 1s 1s

Short delay settings

Isd 31500 A 9600 A

Tsd 0.1 s 0.1 s

Instantaneous
tripping
Ii

Discrimination Total
Upstream
Status discrimination

Project: Schneider 02/24/2016 08:07:28 PM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.
LVSB-13XX02 3200A_800A 5 Broadgate

Discrimination report

Schneider
Page 2/4

Information

Name : LVSB-13XX02 3200A_800A


First name : 5 Broadgate
Company : Long & Partners
Customer : Mace

Project: Schneider 02/24/2016 08:09:43 PM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.
Page 3/4

Discrimination diagram
Discrimination status :

Project: Schneider 02/24/2016 08:09:43 PM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.
Page 4/4

Range Masterpact NW Compact


NS630b-3200
Designation/Fuse NW32H1 NS800N
technology
Rating (A) 3200 A 800 A

Trip unit Micrologic 5.0 E Micrologic 2.0 A

Trip unit rating 3200 A 800 A

Trip class

Long delay settings

Ir 3200 A 800 A

Tr 1s 2s

Short delay settings

Isd 9600 A 4000 A

Tsd 0.1 s 0.05 s

Instantaneous
tripping
Ii NA

Discrimination Total
Upstream
Status discrimination

Project: Schneider 02/24/2016 08:09:43 PM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.
LVSB-13XX01 3200A_1250A 5 Broadgate

Discrimination report

Schneider
Page 2/4

Information

Name : LVSB-13XX01 3200A_1250A


First name : 5 Broadgate
Company : Long & Partners
Customer : Mace

Project: Schneider 02/24/2016 08:01:57 PM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.
Page 3/4

Discrimination diagram
Discrimination status :

Project: Schneider 02/24/2016 08:01:57 PM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.
Page 4/4

Range Masterpact NW Masterpact NW

Designation/Fuse NW32H1 NW12H1


technology
Rating (A) 3200 A 1250 A

Trip unit Micrologic 5.0 E Micrologic 5.0 E

Trip unit rating 3200 A 1250 A

Trip class

Long delay settings

Ir 3200 A 1250 A

Tr 1s 4s

Short delay settings

Isd 9600 A 6250 A

Tsd 0.1 s 0.1 s

Instantaneous
tripping
Ii

Discrimination Discrimination
Upstream
Status limit: 48000A

Project: Schneider 02/24/2016 08:01:57 PM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.
LVSB-13XX01 1250A_630A 5 Broadgate

Discrimination report

Schneider
Page 2/4

Information

Name : LVSB-13XX01 1250A_630A


First name : 5 Broadgate
Company : Long & Partners
Customer : Mace

Project: Schneider 02/24/2016 08:03:41 PM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.
Page 3/4

Discrimination diagram
Discrimination status :

Project: Schneider 02/24/2016 08:03:41 PM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.
Page 4/4

Range Masterpact NW Compact NSX

Designation/Fuse NW12H1 NSX630N


technology
Rating (A) 1250 A 630 A

Trip unit Micrologic 5.0 E Micrologic 2.3

Trip unit rating 1250 A 630 A

Trip class

Long delay settings

Ir 1250 A 630 A

Tr 4s 16 s

Short delay settings

Isd 6250 A 3150 A

Tsd 0.1 s 0.02 s

Instantaneous
tripping
Ii 6900 A

Discrimination Total
Upstream
Status discrimination

Project: Schneider 02/24/2016 08:03:41 PM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.
LVSB-2XX04 3200A_800A 5 Broadgate

Discrimination report

Schneider
Page 2/4

Information

Name : LVSB-2XX04 3200A_800A


First name : 5 Broadgate
Company : Long & Partners
Customer : Mace

Project: Schneider 02/24/2016 08:13:28 PM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.
Page 3/4

Discrimination diagram
Discrimination status :

Project: Schneider 02/24/2016 08:13:28 PM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.
Page 4/4

Range Masterpact NW Compact


NS630b-3200
Designation/Fuse NW32H1 NS800N
technology
Rating (A) 3200 A 800 A

Trip unit Micrologic 5.0 E Micrologic 2.0 A

Trip unit rating 3200 A 800 A

Trip class

Long delay settings

Ir 3200 A 800 A

Tr 1s 16 s

Short delay settings

Isd 9600 A 8000 A

Tsd 0.1 s 0.05 s

Instantaneous
tripping
Ii NA

Discrimination Total
Upstream
Status discrimination

Project: Schneider 02/24/2016 08:13:28 PM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.
LVSB-2XX04 800A_400A 5 Broadgate

Discrimination report

Schneider
Page 2/4

Information

Name : LVSB-2XX04 800A_400A


First name : 5 Broadgate
Company : Long & Partners
Customer : Mace

Project: Schneider 02/24/2016 08:14:57 PM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.
Page 3/4

Discrimination diagram
Discrimination status :

Project: Schneider 02/24/2016 08:14:57 PM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.
Page 4/4

Range Compact NS630b- Compact NSX


3200
Designation/Fuse NS800N NSX400N
technology
Rating (A) 800 A 400 A

Trip unit Micrologic 2.0 A Micrologic 2.3

Trip unit rating 800 A 400 A

Trip class

Long delay settings

Ir 800 A 400 A

Tr 16 s 16 s

Short delay settings

Isd 8000 A 2000 A

Tsd 0.05 s 0.02 s

Instantaneous
tripping
Ii NA 4800 A

Discrimination Total
Upstream
Status discrimination

Project: Schneider 02/24/2016 08:14:57 PM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.
LVSB-2XX01 3200A_800A 5 Broadgate

Discrimination report

Schneider
Page 2/4

Information

Name : LVSB-2XX01 3200A_800A


First name : 5 Broadgate
Company : Long & Partners
Customer : Mace

Project: Schneider 02/24/2016 08:12:10 PM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.
Page 3/4

Discrimination diagram
Discrimination status :

Project: Schneider 02/24/2016 08:12:10 PM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.
Page 4/4

Range Masterpact NW Compact


NS630b-3200
Designation/Fuse NW32H1 NS800N
technology
Rating (A) 3200 A 800 A

Trip unit Micrologic 5.0 E Micrologic 2.0 A

Trip unit rating 3200 A 800 A

Trip class

Long delay settings

Ir 3200 A 800 A

Tr 1s 16 s

Short delay settings

Isd 9600 A 8000 A

Tsd 0.1 s 0.05 s

Instantaneous
tripping
Ii NA

Discrimination Total
Upstream
Status discrimination

Project: Schneider 02/24/2016 08:12:10 PM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.

S-ar putea să vă placă și