Documente Academic
Documente Profesional
Documente Cultură
The 2 Door Module is an intelligent device used for access control of two single direction Card Reader:
doors, or one bi-directional door. It is used in conjunction with Delta’s new generation of
2 Wiegand Devices (card reader,
BACnet™ Controllers. When connected to an Access System Manager on the Delta LINKnet™ keypad, biometric device etc)
network, it provides programmable remote door access control and expanded I/O capabilities.
Inputs (External):
Application EOL Supervised Inputs (Types: 1, 2, 3, 4)
The 2 Door Module is designed for access 2 Door Contacts
control of 2 single direction doors or 2 Request-to-Exit Switches
1 bi-directional door. Up to twelve Door 2 Auxiliary (i.e. tamper from Card
Modules may be connected to an Access Reader, motion detector – used in
System Manager (ASM 24 / ASM24E) via access/ security, etc.)
LINKnet™. 1 Tamper Switch
Equipped with a built-in battery charging Outputs (External):
circuit to provide optional battery backup 2 Doorstrike/Maglocks, Form C Relay
for the Controller, all of it’s Peripheral 5A @ 24VDC/AC, MOV protection.
+12VDC @ 500mA available for
equipment and the Access System each lock. Lock power protected
Manager (i.e. Card Readers, Door strikes, ADM-2W704 Access 2 Door Module
and internally wired and monitored
and Maglocks) when the AC power fails. 4 LED driver, open-controller current
Features sink @ 50mA, 24VDC maximum,
All external inputs can be monitored
> Controls two single direction doors, Current limited, (LED or Buzzer driver)
for wiring status using EOL devices
(Types 1, 2, 3, 4).To give trouble indication or one bi-directional door 2 Auxiliary Relays, Form C Relay
5A @ 24 VDC/AC, MOV protection
as well as normal and alarm conditions. > Can operate under a degraded
mode of operation in the event Output Voltages:
of communication failures 2 Card Reader +5VDC @ 50 mA each,
(0.10A total) each individually fused
> Communicates on LINKnet™ with a resetable fuse
> Configurable Wiegand card format 2 Card Reader +12VDC @ 160mA
up to 64 bits each, (0.32A total) each individually
fused with a resetable fuse
> All external inputs can be
1 Auxiliary +12VDC @ 50mA, fused
monitored to give status of the with a resetable fuse
input wiring using EOL devices 1 DC Power out +10 to +15VDC @
(Types 1, 2, 3, 4) 0.25A fused with a resetable fuse
> Easy-to-mount Enclosure Device Type:
> Designed for easy field wiring LINKnet™ device only
> Equiped with battery Communications Ports:
charging circut Delta LINKnet™ @ 76,800 bps
(maximum of 12 Door Modules) >>